MYOUNG IN Standard of Cables
Myoung In

1. Scope

This specification covers 0.6/ 1KV grade, Ethylene propylene (EP) rubber insulated,

Polychloroprene (PCP) sheathed flexible cables used for industrial purpose.

2. Reference Standard

KS C IEC 60228 : Conductors of insulated cables.

KS C IEC 60502- 1 : Power cables with extruded insulation and their accessories for rated voltages from 1

kV(Um 1.2 kV) up to 30 kV(Um 36 kV)=
Part 1 :Cables for rated voltages of 1 kV(Um =1.2 kV) and 3 kV(Um =3.6 kV)

KS C IEC 60811- 1- 1 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 1 : Measurement of thickness and overall dimension.

KS C IEC 60811- 1- 2 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 2 : Thermal ageing methods.

KS C IEC 60811- 1- 3 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 3 : Methods for determining the density,Water absorption tests,Shrinkage test.

KS C IEC 60811- 2- 1 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 2 : Methodsspecific to elastomeric compounds.
Section 1 : Ozone resistance,hot set and mineral oil immersion tests.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
MYOUNG IN Standard of Cables
Myoung In

3. Class and Symbol of Cable

The class and symbol of cable are as shown in Table 1

〈Table 1.〉
Description Symbol

0.6/ 1kV EP rubber insulated and PCP sheathed flexible


cable 0.6/ 1kV PNCT

4. Construction and Material

4.1. Conductor
The conductor shall be bunched or multi- stranded with tinned annealed copper wires
specified in KS C IEC 60228, class 5.
A suitable tape shall be applied on the conductor.

4.2. Insulation

The insulation shall be applied concentrically to the conductor with Ethylene Propylene(EP) rubber
complying with characteristics specified in the attached table A.

The average thickness of insulation shall be not less than the value given in the attached table 1
and the minimum thickness at any point shall be not less than 90% of the specified value minus
0.1mm.

4.3. Identification of insulated cores

The core of cables shall be identified either by color or by numbers in accordance with the

following methods.

One core : Black


Two core : Black, White
Three core : Black, White, Red
Four core : Black, White, Red, Green
Five core and above : 1, 2, 3, ........., No. (No. : number of Core)
Any other colors of insulated core may be applicable when purchaser required.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
MYOUNG IN Standard of Cables
Myoung In

4.4. Cabling
The cores of a multicore cable shall be cabled with suitable lay length.
The interstices between the cores may be filled with suitable filler to form a compact circular
cross - section.
A suitable tape may be applied on the cabling

4.5 Sheath
sheath shall be applied concentrically to the core assembly with Black colored

Polychloroprene (PCP) compound complying with the characteristics specified in the

attached table A.

The average thickness of sheath shall be not less than the value given in the attached

table 1 and the minimum thickness at any point shall be not less than 85% of the

specified value minus 0.1mm.

5. Test

The test shall be carried out on the finished cable at our works in accordance with the

test method specified in the attached table A.

5.1 Routine tests

5.1.1 Conductor resistance test

5.1.2 Voltage test

5.2 Sample tests

5.2.1 Construction test

5.2.2 Thickness of insulation and sheath

5.2.3 Hot set test of insulation and sheath

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
MYOUNG IN Standard of Cables
Myoung In

<Table 2 : Number of sample for sample test>

Cable Length

Multicore cables Single core cables No. of sample

Above Up to and including Above Up to and including


(km) (km) (km) (km)

2 10 4 20 1

10 20 20 40 2

20 30 40 60 3

etc etc etc

5.2 Type tests

The type tests required by KS C IEC 60502- 1 standard for insulation and sheath.

6. Marking

6.1. Marking on the Cable

The cable shall be indelibly marked on its surface repeatedly by a suitable method with

following information ;

1) Type of cable (as 0.6/ 1KV PNCT- F)

2) Nominal sectional area & number of cores (as 4C x 16SQMM)

3) Manufacturer's name (as MYOUNG IN)

4) Year of manufacture

Note) Any other information marking may be applicable, when purchaser required.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
MYOUNG IN Standard of Cables
Myoung In

6.2. Marking on the Package

The drum shall be marked on the side face and the coil shall be affixed with a tag
marked with following particulars ;

1) Type of cable

2) Nominal sectional area & number of cores

3) Length(m)

4) Manufacturer's name or trade mark

5) Year of manufacture

6) Net & gross weight in case of drum (kg)

7. Packing

Customer and manufacturer will agree upon the lengths and packing by order.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
MYOUNG IN Standard of Cables
Myoung In

Attached table A

* Properties of Insulation and Sheath Compound

Kind of test
DESIGNATION PROPERTIES KS C IEC Clause
Routine Sample Type
* Electrical test
Conductor resistance ○ - ○ 15.2

Insulation resistance constant Ki (90 ) Min. 3.67 ㏁ㆍkm - - ○ 17.2
Voltage test for 4hours (4Uo at 4 h) - - ○ 17.3
Voltage test for (Attached table of dimension at 5 min.) - - ○ 15.3
* Construction and dimension of Cables
Conductor examination - ○ - 16.4
Measurement of thickness of insulation - ○ ○ 18.1
Measurement of thickness of sheath - ○ ○ 18.2
* Mechanical properties
Insulation Ethylene propylene (EP)

Without
Tensile strength Min. 4.2N/mm² - -○
ageing
Elongation at break Min. 200% - - ○
After ageing
Tensile
strength Variation ±30% - - ○ 18.3

in air oven Elongation Variation


at break ±30% - - ○
Hot set
Elongation under
load Max. 175% - ○ ○ KS C IEC

test Permanent elongation after Max. 15%


cooling - ○ ○ 16.9 60502- 1

Water absorption Max. 5mg/cm² - - ○ 18.13


Sheath Polychloroprene (PCP)

Without
Tensile strength Min. 10.0N/mm² - -○
ageing
Elongation at break Min. 300% 이상 - - ○

18.4
Minimum - - -
Tensile
After ageing
strength
Variation ±30% - - ○
in air oven
Elongation
Minimum 250% - - ○ 18.12
at break
Variation ±30% - - ○
After
Tensile
strength Variation ±40% - - ○
immersion in
hot oil Elongation
at break Variation ±40% - - ○ 16.9

Hot set
Elongation under load Max. 175% - ○ ○
○ ○
test
Permanent elongation after
cooling Max. 15% -

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
MYOUNG IN Standard of Cables
Myoung In

Attached table 1. 0.6/ 1kV PNCT

Conductor Thick Thick


-ness -ness Nominal dia. Conductor
No. Nominal No. & of of over sheath Resistance Test
sectional dia. of Dia. (20℃) Voltage
of (App.) insulation sheath (App.)
core area wire (Max.)
mm2 mm mm mm mm mm Ω/km V/5min
30 1.5 27/0.25 TA 1.5 1.0 2.9 30.6 13.53
3,500
4 35 7/37/0.4 TA 8.4 1.2 3.1 33.4 0.565
App. = approximate

* Construction

1. Conductor : Tinned annealed copper wires

2. Insulation : Ethylene propylene rubber (EPR)

3. Filler : Jute

4. Sheath : polychloroprene rubber (PCP)

1. Conductor : Tinned annealed copper wires

2. Insulation : Ethylene propylene rubber (EPR)

3. Filler : Jute

4. Sheath : polychloroprene rubber (PCP)

< NOT TO SCALE >