Job Name/Location: Tag #:

Date: For: File Resubmit


PO No.: Approval Other
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)

ARUN1Ϯ0BTE5
Multi V™ 5 - 220V
1ϮHP  Outdoor Unit for Heat Pump
Performance: Operating Range:
Cooling Mode: -15° ‐ 48°
Cooling (˚C DB)**
Nominal Capacity (Btu/h) 1ϭϰ,ϲ00 Heating (˚C WB) ‐25° ‐  18°
Power Input¹ (kW) ϴ͘ϭϲ

Heating Mode:
Nominal Capacity (Btu/h)  1Ϯϵ,Ϭ00 Unit Data:
Power Input¹ (kW) ϴ͘ϰϬ Refrigerant Type R410A
Refrigerant Control EEV
Nominal Capacity is outside the scope of AHRI Standard 1230 and based on the following conditions:
Indoor: 80°F DB / 67°F WB Indoor: 70°F DB Max Number of Indoor Units² 2Ϭ
Outdoor 95°F DB Outdoor 47°F DB / 43°F WB
: : Sound Pressure³ dB(A) 59.0
Electrical:
Power Supply  (V/Hz/Ø) 220/60/3 Net Unit Weight (Kg) 200

MFA (A) 40
Communication Cable⁴ (No x AWG) 2 x 18
MCA (A) 36.4
Heat Exchanger Coating Black Coated Fin™
Rated Amps (A) 23.2
Compressor A (A) 18.2 Compressor:
Compressor B (A) - Type HSS DC Scroll
Fan (A) 5 Quantity 1
Oil/Type PVE/FVC68D
Piping:
Fan:
Refrigerant Charge (Kg) 1Ϭ.0
Liquid Line (in, OD) 1/2 Braze Type Propeller
Vapor Line (in, OD) 1 1/8 Braze Quantity 1
Motor/Drive Brushless Digitally Controlled/Direc
Air Flow Rate (CFM)  8,476
Standard Features:
Notes:
•Advanced Smart Load Control •Fault Detec on and Diagnosis
•Intelligent Heating •Active Refrigerant Control 1.For AHRI ra ngs, refer to the AHRI website h p://www.ahridirectory.org.
2.For main pipe segment size, refer to the LATS Mul  V tree diagram.
•HiPOR (high pressure oil return) •Variable Path Heat Exchanger 3.The combina on ra o must be between 50‐130%.
•Smart Oil Control •Subcooling and Vapor Injection 4.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745 for the 
combination of outdoor units.
•Night Quiet Opera on Control 5.All communication cable to be minimum 18 American wire gage (AWG),  2‐conductor, 
•Liquid Cooled Inverter Controller stranded, shielded or unshielded wire and must comply with applicable local and national
Required Accessories: code. If shielded, the wire must be grounded to the chassis at the outdoor unit only.
6.Nominal data is rated 0   above sea level, with 25   of refrigerant line per indoor unit and 
ARCNB21 (frame connector Y‐branch) a 0 ft level difference between outdoor and indoor units.  All capacities are net with a 
combination ratio between 95‐105%.
ARCNB31 (frame connector Y‐branch) 7.Power wiring cable size must comply with the applicable local and na onal code. Cables
terminate at each frame.
Optional Accessories: 8.Acceptable operating voltage: 187V ‐ 253V.
9.The order of each of these units on the submittal (i.e., a+b+c) do not represent the 
Air Guide ‐ ZAGDKA52A (3 required) installation order. Highest capacity unit is used as the Master, followed by the next 
Hail Guard Kit ‐ ZHGDKA52A (3 Required) smaller size as Slave 1 and so on.

Low Ambient Baffle Kit ‐ ZLABKA52A (3), Control Kit ‐ PRVC2  (1 per 
system)
**(‐9.9°F achieved only when all IDU's are operating in cooling mode. 
Does not impact synchronous operating range.)
LG Electronics Perú S.A. www.lg.com.pe / www.lgaircon.com
© LG Electronics PERÚ S.A., Av. República de Colombia 791 Piso 12 San Isidro / Lima - Perú
SB_MultiV_5_ODU_ARUN120BTE5_02_18 Page 1 of 2
Job Name/Location:

ARUN120BTE5 Tag #:
Multi V™ 5 -  220V Date:
12HP Outdoor Unit for Heat Pump PO No.:

Ø 28.58 (1-1/8)
[mm(inch)]

Ø 22.2 (7/8)
Gas
pipe
Heat Pump

Ø 9.52 (3/8)

Ø 12.7 (1/2)
Liquid
pipe
High Pressure

Ø 19.05 (3/4)

Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 19.05 (3/4)


Gas pipe
Heat Recovery

Low Pressure

Ø 22.2 (7/8)
Gas pipe
Ø 9.52 (3/8)
Liquid
pipe
System

HP

10

12
Gravity point

LG Electronics USA, Inc. 1000 Sylvan Ave, Englewood Cliffs, NJ 07632/www.lg‐vrf.com