LM Battery Range
FIAMM.COM
T HE LM BATTERY SERIES IS AN OPZS VENTED RANGE
DESIGNED BY FIAMM TO MEET DIN 40736 SPECIFICATIONS.
M A I N A P P L I C AT I O N S :
RAI LWAY S
OIL & G AS
SPECIFICATIONS
The positive tubular grid is composed of a special alloy (Pb-Sb) which is die-cast to guarantee high corrosion resistance and low
water consumption (1 topping up in 3 years in float conditions)
Electrolyte: sulphuric acid electrolyte with specific gravity of 1.24kg/l at 20°C
Separators have high porosity and provide very low internal resistance
Robust design thanks to high mechanical polymers properties; box made of SAN and with an ABS lid
The vent plug is made of porous flameproof material for a superior safety
A long shelf life of up to six months is possible without recharge (<2% discharge per month)
The metallic threaded insert on terminals ensures the highest conductivity and provides maximum torque retention and easy installation
The connecting bolt is fully insulated but with probe hole on the top to grant electrical measurements
TECHNOLOGY
Separator
Positive
Tubular Plate
Gasket
Plastic Sleeve Epoxy Resin
Negative
Flat Plate
THE UNIQUE FIAMM TERMINAL DESIGN PERMITS THE LM RANGE HAS A DESIGN LIFE IS 20
PILLAR GROWTH DURING CELL LIFE WITHOUT YEARS DUE TO HIGH RELIABILITY AND
L E A K A G E . T H I S F E AT U R E S A V O I D M E C H A N I C A L C O M P O N E N T S M A N U FA C T U R E P R O C E S S .
STRESS ON THE LID OF THE CELL. A L L L M M O D E L S A R E AVA I L A B L E I N A D R Y
CHARGE VERSION.
FIAMM Energy Techology reserves the right to change or revise without notice any information or detail given in this publication LM Battery Range_2018_09
ELECTRICAL CHARACTERISTICS STANDARDS
Float Voltage: 2.23 V/cell at 20°C DIN 40736 – specification OPzS cell
Boost Voltage: 2.40 V/cell DIN 43539T5 – deep discharge
Float Voltage Compensation with Temperature: -2.5 mV/cell/°C DIN 40740 – electrolyte level indicator
Self-Discharge at 20°C: <2%/month IEC 60896 Part 11 – vented types requirements & tests
CERTIFICATIONS ACCESSORIES
ISO 9001 Recombination plug
Quality Management System Filtering plugs to DIN standard
ISO 14001 Racks for battery installation (standard and anti-seismic)
Environmental Management System Monitoring system
OHSAS 18001
Workplace Safety & Health
2.0
Battery Voltage (V/cell)
1.9
1.8
0.10 C
0.18 C
1.7
0.4 C
0.5 C
1.6
1C
1.5
1 10 100 1.000 10.000
The above discharge curves are typical. For more detailed information please see the specific product sheets. Discharge time (min)
Charging Voltage
2.2 100 90
Recharged Capacity
Refreshing charge at
2.4 Vpc for 24 hours
2.0 80 (at 20-25°C) must be
applied as soon as
possible
1.8 60 80
0.10 C10 5°C
Refreshing charge of
1.6 40 2.4 Vpc may be
insufficient to recover 20°C
0.05 C10 the battery capacity. 30°C
40°C
20 It is important to 70
avoid this area <80%
0 0 0
0 5 10 15 20 [hours] 0 2 4 6 8 10 12
Storage Time (months)
Voltage 100% Recharged 100% Current 100%
50% Capacity 50% 50%
Headquarters
FIAMM Energy Technology S.p.A.
Viale Europa, 75
36075 Montecchio Maggiore (VI) - Italy
Tel. +39 0444 709311
Fax +39 0444 694178
youtube.com/user/FIAMMvideo
A Hitachi Group Company