Sie sind auf Seite 1von 24

www.reinhausen.

com
TAPCON® XPA-I – External Paralleling Assistant
Operating Instructions BA 282/01
Contents

Contents

1 General ............................................................................................................................................................................................................... 4
1.1 External Paralleling Assistant .......................................................................................................................................................... 4

2 Safety ................................................................................................................................................................................................................ 6

3 Introduction .................................................................................................................................................................................................. 7
3.1 Paralleling ............................................................................................................................................................................................ 7
3.1.1 Paralleling with MR-Tap-changer Controls TAPCON 230 ......................................................................................... 7
3.1.2 Paralleling with a Mixture of Controls ........................................................................................................................... 7

4 Theory of Operation ..................................................................................................................................................................................... 8

5 Application .................................................................................................................................................................................................. 9
5.1 Terminal Connections ....................................................................................................................................................................... 10
Figure 1 Simplified Schematic of Current Circuit for Paralleling
Two Transformers using the Circulating Current Method ...................................................................................................... 10
Figure 2 Paralleling Scheme for Two Transformers using the Circulating Current Method .......................................... 11
Figure 3 Paralleling Scheme for Two Transformers for mixed controls using
the Circulating Current Method ..................................................................................................................................................... 12
Figure 4 Schematic for mixed controls
Three Transformers using the Circulating Current Method .................................................................................................... 13
Figure 5 Interconnection TAPCON® XPA-I – TAPCON® 230 .................................................................................................. 14

6 Test Procedures .............................................................................................................................................................................................. 15


6.1 Two Transformer Parallel Verification Test Procedure ............................................................................................................. 15
6.2 Three Transformer Parallel Verification Test Guide ................................................................................................................... 17

7 Effect of the TAPCON® XPA-I on Control Sensitivity ..................................................................................................................... 19


Table 1 Sensitivity Settings .......................................................................................................................................................................... 19
Figure 6 Vector Diagram .............................................................................................................................................................................. 20
Figure 7 TAPCON® XPA-I Outline and Mounting Dimension .............................................................................................................. 21
Figure 8 TAPCON® XPA-I Outline and Mounting Dimension .............................................................................................................. 22
Figure 9 TAPCON® XPA-I Block diagram .................................................................................................................................................. 23

282/01/01/0
3
1 General

1 General

1.1 External Paralleling Assistant

The mode of operation of TAPCON® XPA-I complies with the


method set forth in ANSI C57.12.10-1998, Paragraph 10.2.
TAPCON® XPA-I offers all the required components to place an
additional power transformer and on-load tap-changer
electrically in parallel with an existing transformer(s) using the
minimum circulating reactive current method. It provides the
parallel-independent control switch (43P), settable trip current
level to interrupt the motor operation and sensitivity adjust-
ment to balance tap-changer operations. The characteristics of
the present circulating reactive current is transferred via the
CAN-Bus to the TAPCON® AVR family (90 Relay) for proper
regulation and control.
By using a special current transformer switching system,
TAPCON® XPA-I registers the circulating reactive current
between parallel connected power transformers.
Since the sensitivity for the circulating reactive current can be
balanced directly at the TAPCON® XPA-I, problems such as
hunting of tap position between two voltage steps of the
transformer (sensitivity too high) or the passing over of several
voltage steps (sensitivity too low) can be effectively avoided.

Additionally, the motor-drive unit of the on-load tap-changer


can be stopped by a relay contact in case the circulating
reactive current exceeds an adjustable threshold value.
Your advantages:
• Three-in-one: Paralleling module, AC-current relay and
adaptable to replace existing equipment or install in
existing parallel provisions
• Prevents damage to LTC transformer’s switching mechanism
under excessive loads
• 50 % cost savings in wiring compared with
non-Reinhausen parallel regulated transformer
• Reduced electrical interference levels
• Compatible with all parallel working voltage controllers of
the Reinhausen TAPCON® series
• Flush panel mounting or DIN rail
• Robust aluminium housing
• Usable with numerous non-Reinhausen paralleling voltage
controller devices
• Easy one to one replaceable design

4 282/01/01/0
1 General

Current Inputs Mounting


Rated at 0.2 A, 10 VA, 50/60 Hz. Panel mounted using 8-1/2" x 6-1/8" cutout (21.59 cm x
15.56 cm). May be surface mounted using the M-0124
Current Ratings Surface Mounting Adapter.
Either winding K1, K2 from terminal 1 to 5 is rated for 0.2 A
continuous. Environmental
All windings will withstand the following: 0.4 A continuous, Temperature Range:
2.9 A for 5 sec; 3.3 A for 4 sec; 4.0 A for 3 sec; 5.0 A for 2 sec. Stated accuracies are maintained from –40 ° to +80 °C.
Cores are unsaturated at 10 VA burden. Humidity: Stated accuracies are maintained at up to 95 %
relative humidity (non-condensing).
Sensitivity Control
Sensitivity adjustment prevents LTC transformers from hunting Physical
or being several steps apart. Size: 10" high x 6-3/8" wide x 4-15/32" deep (25.40 cm x
Sensitivity is adjustable from two times normal to 0.5 times 16.19 cm x 11.35 cm). When using the M-0124 Surface
normal in nine steps. Mounting Adapter, maximum depth is 4-9/16" (11.59 cm).

Circulating Overcurrent-Relay Approximate Weight: 5 lb (2.3 kg)


Its range permits the maximum circulating current to be set
from 5 % to 50 % of the rated full load current. Approximate Shipping Weight: ……..

Parallel/Independent Switch
Mode of LTC control is switch selectable.

Transient Protection
Input and output circuits are protected against system
transients. The –XPA-I will exhibit no component failure or
false commands when subjected to the requirements of ANSI/
IEEE C37.90.1-1989, which defines oscillatory and fast
transient surge withstand capability. All inputs and outputs
will withstand 1500 V ac to chassis or instrument ground for
one minute. Voltage inputs are electrically isolated from each
other, from other circuits, and from ground.

282/01/01/0
5
2 Safety

2 Safety

WARNING Always Ground the Equipment

DANGEROUS VOLTAGES, capable of causing death or serious To avoid possible shock hazard, the chassis must be con-
injury, are present on the external terminals and inside the nected to an electrical ground. When servicing equipment
equipment. Use extreme caution and follow all safety rules in a test area, the Protective Earth Terminal must be attached
when handling, testing or adjusting the equipment. to a separate ground securely by use of a tool, since it is not
However, these internal voltage levels are no greater than grounded by external connectors.
the voltages applied to the external terminals.

CAUTION
DANGER! HIGH VOLTAGE!
Do NOT operate in an explosive environment
This sign warns that the area is connected to a dangerous Do not operate this equipment in the presence of flammable
high voltage, and you must never touch it. or explosive gases or fumes. To do so would risk a possible
fire or explosion.

Keep away from live circuits


PERSONNEL SAFETY PRECAUTIONS Operating personnel must not remove the cover or expose
the printed circuit board while power is applied. In no case
may components be replaced with power applied. In some
The following general rules and other specific warnings
instances, dangerous voltages may exist even when power is
throughout the manual must be followed during appli-
disconnected. To avoid electrical shock, always disconnect
cation, test or repair of this equipment. Failure to do so will
power and discharge circuits before working on the unit.
violate standards for safety in the design, manufacture, and
intended use of the product. Qualified personnel should be
Exercise care during installation, operation, and
the only ones who operate and maintain this equipment.
maintenance procedures
Beckwith Electric Co., Inc. assumes no liability for the
The equipment described in this manual contains voltages
customer’s failure to comply with these requirements.
high enough to cause serious injury or death. Only qualified
personnel should install, operate, test, and maintain this
equipment. Be sure that all personnel safety procedures are
carefully followed. Exercise due care when operating or
CAUTION servicing alone.

This sign means that you should refer to the corresponding Do not modify equipment
section of the operation manual for important information Do not perform any unauthorized modifications on this
before proceeding. instrument. Return of the unit to a MR Electric repair facility
is preferred. If authorized modifications are to be attempted,
be sure to follow replacement procedures carefully to assure
that safety features are maintained.

6 282/01/01/0
3 Introduction

3 Introduction

Background 3.1 Paralleling


When LTC transformers are connected in parallel, a control The TAPCON® XPA-I Parallel Balancing Module includes all the
scheme is necessary to assure that the tap positions of all compo-nents that must be added to LTC transformers to
paralleled transformers remain at or near the same tap posi- permit them to operate in parallel, using the circulating
tion. If tap positions are not maintained at or near the same current method. The transformer controls must have a 0.2 A
positions, reactive current will circulate between the transfor- input for load and circulating current.
mers, wasting energy and overheating the transformers,
possibly causing damage. The circulating current control is 3.1.1 Paralleling with MR On-Load Tap-Changer
the most common method for control of LTC transformers in Controls TAPCON® 230
parallel, being covered by ANSI C57.12.10-1998 paragraph
10.2, and has the following advantages: Excellent results are obtained using the MR On-Load Tap-
Changer Controls TAPCON® 230. The fast response to voltage
• Any transformer can be automatically or manually changes, the excellent phase accuracy of the line drop com-
switched-out for maintenance; the remaining units will pensator and the temperature stability of the MR On-Load
operate properly (in parallel, if more than two are being Tap-Changer Controls assures that the parallel combination
used). will maintain the same tap settings with changes in temper-
• Proper line drop compensator (LDC) action for each unit is ature and load, even when using low bandwidth settings.
provided at all times.
3.1.2 Paralleling with a Mixture of Controls
• Transformers from different manufacturers or vintages can
be easily paralleled if they meet certain performance A mixture of following Balancing-modules and controls is
criteria, even if they were not originally equipped for possible!
paralleling. TAPCON® XPA-I – SkB20 with Mk, Mk30 (MR)
TAPCON® XPA-I – M-0115A with M-0067E
M-2001B, M-2001C (Beckwith)
MR cannot assure maximum performance where a mixture of
equipment from various manufacturers exists.

282/01/01/0
7
4 Theory of Operation

4 Theory of Operation

The general paralleling schemes for two and three transformer The third and fourth path shown (Half Current and LDC Cur-
paralleling using the circulating current method are shown in rent), connecting the K2 auxiliary C.T. of the TAPCON® XPA-I
Figure 1 through. modules together, ensures proper operation of the Load Drop
Compensator circuit if one of the transformers is taken out of
Figure 1 shows the schematic of the current circuit only;
service by opening its breaker. For instance, if transformer #2
redrawn from the Paralleling Scheme figures to allow easier
is taken out of service by opening breaker 52-2, then half of
tracing of the load current (IL) and circulating current (IP)
transformer #1’s load current is forced to flow through the
paths.
half current loop. In this way, transformer #1’s voltage
A current, proportional to the transformer secondary current, regulating control sees the same load current as it did before,
is fed to the TAPCON® XPA-I unit. Because of the secondary and the proper amount of line drop compensation in the
parallel connection, however, this is actually the vector sum of transformer #1 control is maintained. This circuit configura-
the desired load current and any undesired circulating current. tion and grounding points must be maintained, if transformers
The TAPCON® XPA-I separates these currents, and sends them are to be successfully paralleled.
to the circulating current transformer K3 and to the proper
load (LDC) inputs of the associated control.
Two current loops are formed. One involves the K3 auxiliary
transformers in each of the TAPCON® XPA-I units. This loop
forms a measure of the transformer bank circulating current,
subtracted from the LDC control input and forced to flow into
the secondary winding of K3.
The second loop involves the K1 and K2 auxiliary transformers.
They force the load current to divide properly between the
various controls so that each senses its proper portion of the
total bank load. Thus, the LDC setting for each control may
properly be the same, regardless of whether or not the
associated transformer is being used in parallel.
The first current path shown (Circulating Current) has a current
analogous in angle and magnitude to the reactive current
circulating through the paralleled transformers (The current is
measured by amount and phase position. The difference is
calculated from this and transferred via CAN bus to the voltage
regulator). It also includes the overcurrent relay function,
which is used to detect excessive circulating current and block
the on-load tap-changer movement, if this occurs. Also, a LED
will alert the operator when excessive circulating current is
detected.
The second path shown (Balance Current), connecting the K1
auxiliary C.T. of the TAPCON® XPA-I modules together, has a
balance current which forces the two load currents of trans-
formers #1 and #2 to be identical. This means that any
difference in currents must flow in the circulating current
path.

8 282/01/01/0
5 Application

5 Application

The ..XP-I Parallel Balancing Module can be ordered with new • If paralleling and hand-operated load switches are used:
equipment from most transformer manufacturers or added to
existing transformers. If the Module is added to existing a. AUTO/MANUAL switches on the TAPCON® 230 should
equipment, the following factors should be considered: be placed in the MANUAL position.
• If the old control uses a 5 A input for the line drop b. Other controls should be placed in the MANUAL
compensator, a new control must be installed to provide position.
the required 0.2 A load and circulating current inputs.
A MR On-Load Tap-Changer Control is recommended for
this application. CAUTION
• If an existing 5/0.2 A auxiliary current transformer is not
Do not place the TAPCON® XPA-I PARALLEL/
available to provide the measure of secondary load
INDEPENDENT switch in the INDEPENDENT position if
current, one must be added.
the transformers are in parallel and under automatic control.
An Auxiliary Current Transformer is recommended for this
application (8,66 or 5/0,2 A).
c. The TAPCON® XP-I PARALLEL/INDEPENDENT (P/I)
• If phase-to-phase voltage is used, Figure 6 shows the
switchshould be placed in the INDEPENDENT position
application of two current transformers to derive a current
before the load switches are operated.
in phase with the voltage. Connection must be made to
Terminal of the 8,66A-range.
• If circuit breakers (52) exist, then the auxiliary breaker
contacts shown in the Paralleling Scheme figures are
required to automatically change from parallel to
independent operation should the breakers operate
automatically or by remote control.
If these breakers do not exist and, for example, only one
common load breaker is used, the circuit should be wired
to make a circuit where the normally closed contacts are
shown. No circuit should be made where the normally
open contacts are shown.

282/01/01/0
9
5 Application

5.1 Terminal connections

Notes:
52 and 24 contacts are shown in the breaker colsed positon; 43 P in the parallel position

Fig. 1 Simplified Schematic of Current Circuit for Paralleling – Two Transformers using the Circulating Current Method

10 282/01/01/0
5 Application

Fig. 2 Paralleling Scheme for Two Transformers using the Circulating Current Method

2
282/01/01/0
11
5 Application

Fig. 3 Paralleling Scheme for Two Transformers for mixed controls using the Circulating Current Method

12 282/01/01/0
5 Application

Fig. 4 Schematic for mixed controls – Three Transformers using the Circulating Current Method

4
282/01/01/0
13
5 Application

Fig. 5 Interconnection TAPCON® XPA-I-TAPCON® 230

14 282/01/01/0
6 Test Procedures

6 Test Procedures

Test procedures are provided for two and three transformer 11. Verify Transformer #1 voltage is within the band.
applications.
12. Manually raise Transformer #1 one to two taps (it could
6.1 Two Transformer Parallel Verification Test take three of four to obtain a response).
Procedure
13. Manually lower Transformer #2 one to two taps (could take
three or four to obtain a response).
NOTE
14. Verify that Transformer #2 calls for a Raise and Transformer
There must be a load on the transformer to perform this #1 calls for a Lower.
test.
15. Manually return Transformer #1 and Transformer #2 to the
same tap.
1. Place all transformer controls (adapter panels) in MANUAL Neither control should call for a Raise or Lower.
and parallel balancing modules (..XP-I) in the INDEPEN-
DENT switch position. 16. Manually raise Transformer #2 one or two taps (may take 3
Set the sensitivity to N. or 4 to obtain a response).
Set the "TRIP CIRCULATING CURRENT" to maximum
(100 mA) 17. Manually lower Transformer #1 one or two taps (may take 3
or 4 to obtain a response).
2. Set all the transformer controls to the same tap position
and the same bandwidth setting. 18. Verify that Transformer #1 calls for a raise and Transformer
Neither control should be calling for a raise or lower. #2 calls for a lower.

3. Close all transformer breakers and tie breakers. 19. Manually return Transformer #1 and Transformer #2 back
to the same tap.
4. Verify that the load current has the correct polarity. Neither control should call for a Raise or Lower.

5. On the control the CT/VT phasing must be set 0 degrees.


CAUTION
6. Set Transformer #1 R Line Drop Compensation to 24.
The control should call for a Raise. (If the control calls for a
If the loads are not evenly balanced between the two trans-
Lower, then the polarity of the line current coming into the
formers then the voltage on the transformer with the larger
control is reversed, and must be corrected before
load may drop and the control may call for a raise and the
continuing the test.)
transformer with the smaller load may rise and the control
may call for a lower.
7. Set Transformer #1 R Line Drop Compensation to 0.

8. Set Transformer #2 R Line Drop Compensation to 24. 20. Open the tie breaker between Transformer #1 and
The control should call for a Raise. (If the control calls for a Transformer #2 (24).
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before 21. Verify that the controls do not call for a Raise or Lower.
continuing the test.)
22. Manually raise Transformer #1 two or three taps (may take
4 or 5 to obtain a response).
9. Place the Transformer #1 ..XP-I Parallel/Independent
switch in the Parallel position.
23. Verify that Transformer #1 calls for a Lower, the circulating
current is zero on both controls and Transformer #2 is not
10. Place the Transformer #2 ..XP-I Parallel/Independent
affected.
switch in the Parallel position.

282/01/01/0
15
6 Test Procedures

24. Manually return Transformer #1 to the same tap. 41. Verify Transformer #2 is not affected.

25. Manually raise Transformer #2 two or three taps (may take


4 or 5 to obtain a response). CAUTION
26. Verify that Transformer #2 calls for a Lower, the circulating Transformer #2 is now supplying all the load, its voltage may
current is zero. Transformer #1 is not affected. drop.
27. Manually return Transformer #2 to the same tap.
42. Manually raise Transformer #2 two or three taps (may take
28. Close the tie breaker between Transformer #1 and 4 or 5 to obtain a response).
Transformer #2 (24).
43. Verify that Transformer #2 calls for a Lower and
29. Manually raise Transformer #1 two or three taps (may take Transformer #1 is not affected.
4 or 5 to obtain a response).
44. Manually return Transformer #2 to the same tap.
30. Verify that Transformer #1 calls for a Lower and
Transformer #2 calls for a Raise. 45. Close the Transformer #1 /52-1).
Test complete. Place the desired settings on the controls
31. Place both controls in AUTOMATIC at the same time. and set all controls to AUTOMATIC.
The controls should cause the on-load tap-changers to
return to the same tap or within 1-2 taps of each other. 46. Set circulating reactive current monitoring (TRIP-
CIRCULATING CURRENT). Circulating reactive current
monitoring is also set empirically. Prerequisite is that
32. Return both controls to MANUAL.
automatically-controlled parallel operation is working
correctly.
33. Manually place Transformer #1 and Transformer #2 on the
same tap and in the bandwidth.
47. Proceed as shown below:
Disconnect a voltage regulator from the motor-drive unit
34. Open the transformer breaker on Transformer #2 (52-2).
by changing the mode switch to MANUAL.
Manually raise this motor-drive unit by the maximum
permissible difference of the operating positions between
CAUTION parallel-operating units (e. g., 2 to 3 taps).

Transformer #1 is now supplying all the load, its voltage may 48. Starting with the scaling value 100, turn the „TRIP CIRCU-
drop. LATING CURRENT“ rotary button slowly to the left until the
LED shows „RELAY TRIPPED.“ The tripping value of
circulating reactive current monitoring has been reached
35. Verify that Transformer #1 is not affected.
when the lamp indicator lights up. It indicates the output
relay of circulating reactive current monitoring and breaks
36. Manually raise Transformer #1 two or three taps (may take
the contact between terminals 15, 16. The voltage regu-
4 or 5 to obtain a response).
lator then blocks.
37. Verify that Transformer #1 calls for a Lower and that
Transformer #2 is not affected.

38. Manually return Transformer #1 to the same tap.

39. Close the Transformer #2 breaker (52-2).

40. Open Transformer #1 breaker (52-1).

16 282/01/01/0
6 Test Procedures

6.2 Three Transformer Parallel Verification Test Guide 12. Set Transformer #3 R Line Drop Compensation to 0.

13. Set Transformer #1, #2 and #3 Parallel Balancing Modules


TAPCON® XPA-I to the PARALLEL position.
NOTE
14. Manually Raise Transformer #1 two or three taps (may take
There must be a load on the transformer to perform this 4 or 5 to obtain a response).
test.
15. Verify that Transformer #2 and Transformer #3 call for a
1. Set all transformer controls as follows: Raise and Transformer #1 calls for a Lower.
a. Adapter Panels to MANUAL
b. Parallel Balancing modules ..XP-I set to INDEPENDENT. 16. Return Transformer #1 back to the same tap. All controls
Set the sensitivity to N. should return to a state where no lower or raise is called
for.
c. Set the block level to maximum (100 mA).
17. Manually Raise Transformer #2 two or three taps (may take
2. Set all transformer controls to the same tap position and 4 or 5 to obtain a response).
the same bandwidth setting.
Neither control should be calling for a raise or lower. 18. Verify that Transformer #1 and Transformer #3 call for a
Raise and Transformer #2 calls for a Lower.
3. Close all transformer breakers and tie breakers.
19. Return Transformer #2 back to the same tap.
4. Verify that the load current has the correct polarity.
20. Manually Raise Transformer #3 two or three taps up (may
5. On the control the CT/VT phasing must be 0 degrees. take 4 or 5 to obtain a response).

6. Verify that the voltage and CT transformers are connected 21. Verify that Transformer #1 and Transformer #2 call for a
to the same phase. Raise and Transformer #3 calls for a Lower.

7. Set Transformer #1 R Line Drop Compensation to 24. 22. Return Transformer #3 back to the same tap.
The control should call for a Raise. If the control calls for a
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before CAUTION
continuing the test.
If the loads are not evenly balanced between the transfor-
8. Set Transformer #1 R Line Drop Compensation to 0. mers then the voltage on the transformer with the larger
load may decrease and the control may call for a Raise and
9. Set Transformer #2 R Line Drop Compensation to 24. the transformer with the smaller load may increase and the
control may call for a Lower.
The control should call for a Raise. If the control calls for a
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before 23. Open the tie breaker between Transformer #1 and
continuing the test. Transformer #2 (24-1), then verify that the controls are not
affected.
10. Set Transformer #2 R Line Drop Compensation to 0.
24. Manually Raise Transformer #1 two or three taps, then
11. Set Transformer #3 R Line Drop Compensation to 24. verify that Transformer #2 and #3 are not affected.
Transformer #1 should call for a Lower and have zero
The control should call for a Raise. If the control calls for a circulating current on it’s control.
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before 25. Return Transformer #1 back to the same tap.
continuing the test.

282/01/01/0
17
6 Test Procedures

26. Manually Raise Transformer #2 two or three taps, then


verify the following: NOTE
a. Transformer #2 calls for a Lower.
b. Transformer #3 calls for a Raise. Since Transformer #2 and #3 will be supplying all the load,
c. Transformer #1 is not affected. their voltage may decrease.

27. Place Transformer #2 and Transformer #3 Controls to AUTO 37. Open Transformer #1 breaker 52-1, then verify that
at the same time. Observe where the on-load tap-changer Transformer #2 and #3 are not affected.
positions settle, and adjust the sensitivity of the TAPCON®
XP-I needed. 38. Manually Raise Transformer #2 two or three taps, then
verify that Transformer #2 calls for a Lower and Transformer
28. Manually return Transformer #2 back to the same tap. #3 calls for a Raise.

39. Manually return Transformer #2 to the same tap.


CAUTION
40. Close Transformer #1 breaker 52-1.
If the loads are not evenly balanced between the transfor-
mers then the voltage on the transformer with the larger
load may decrease and the control may call for a Raise and NOTE
the transformer with the smaller load may increase and the
control may call for a Lower. Since Transformer #1 and #3 will be supplying all the load,
their voltage may decrease.

29. Close tie breaker 24-1 and open tie breaker 24-2 (between
Transformer #2 and Transformer #3) 41. Open Transformer #2 breaker 52-2, then verify Transformer
#1 and #3 are not affected.
30. Verify that the controls are not affected.
42. Manually Raise Transformer #1 two or three taps, then
31. Manually Raise Transformer #3 two or three taps, and then verify that Transformer #1 calls for a Lower and Transformer
verify that Transformer #1 and Transformer #2 are not #3 calls for a Raise.
affected. Transformer #3 should call for a Lower.
43. Manually return Transformer #1 back to the same tap.
32. Manually return Transformer #3 back to the same tap.
44. Close Transformer #2 breaker 52-2.
33. Manually Raise Transformer #1 two or three taps, then
verify the following: Note: Since Transformer #1 and #2 will be supplying all the
a. Transformer #1 calls for a Lower. load, their voltage may decrease.
b. Transformer #2 calls for a Raise.
45. Open Transformer #3 breaker 52-3, then verify that
c. Transformer #3 is not affected. Transformer #1 and #2 are not affected.

34. Place Transformer #1 and Transformer #2 Controls to AUTO 46. Manually Raise Transformer #1 two or three taps, then
at the same time. Observe where the on-load tap-changer verify that Transformer #1 calls for a Lower and Transformer
positions settle, and adjust the sensitivity of the TAPCON® #2 calls for a Raise.
XPA-I if needed.
47. Manually return Transformer #1 to the same tap.
35. Manually return Transformer #1 back to the same tap.
48. Close Transformer #3 breaker 52-3.
36. Close tie breaker 241 and 24-2.
Test complete. Place the desired settings on the controls and
set all controls to automatic.

18 282/01/01/0
7 Effect of the TAPCON® XPA-I on Control Sensitivity

7 Effect of the TAPCON® XPA-I on


Control Sensitivity

The sensitivity of the circulating current to the TAPCON® 230.


On-load tap-changer control is fixed at nominal 24 V at full
load current of 0.2 A.

The sensitivity of the on-load tap-changer controls is then


changed by the TAPCON® XP-I as shown in Table 1.

Tap Nominal Full-Scale Sensitivity for


TAPCON® 230

More 4 48 Vac
Sensitive 3 41 Vac
2 32 Vac
1 29 Vac
N 24 Vac
1 20 Vac
2 17 Vac
Less 3 14 Vac
Sensitive 4 12 Vac

Table 1 Sensitivity Settings

282/01/01/0
19
7 Effect of the TAPCON® XPA-I on Control Sensitivity

NOTE: Only needed if Phase-to Phase voltage is used.

Fig. 6 Vector Diagram

20 282/01/01/0
7 Effect of the TAPCON® XPA-I on Control Sensitivity

Fig. 7 TAPCON® XPA-I Outline and Mounting Dimension

7
282/01/01/0
21
7 Effect of the TAPCON® XPA-I on Control Sensitivity

Fig. 8 TAPCON® XPA-I Outline and Mounting Dimension

22 282/01/01/0
7 Effect of the TAPCON® XPA-I on Control Sensitivity

Fig. 9 TAPCON® XPA-I Block Diagram

9
282/01/01/0
23
© Maschinenfabrik Reinhausen GmbH Phone +49 (0)941 4090 0
www.reinhausen.com Falkensteinstrasse 8 Fax +49 (0)941 4090-6 00
93059 Regensburg, Germany E-Mail sales@reinhausen.com

BA 282/01 en • 0106/1000 • 282/01/01/0 • F0149700• Printed in Germany

Das könnte Ihnen auch gefallen