Beruflich Dokumente
Kultur Dokumente
com
TAPCON® XPA-I – External Paralleling Assistant
Operating Instructions BA 282/01
Contents
Contents
1 General ............................................................................................................................................................................................................... 4
1.1 External Paralleling Assistant .......................................................................................................................................................... 4
2 Safety ................................................................................................................................................................................................................ 6
3 Introduction .................................................................................................................................................................................................. 7
3.1 Paralleling ............................................................................................................................................................................................ 7
3.1.1 Paralleling with MR-Tap-changer Controls TAPCON 230 ......................................................................................... 7
3.1.2 Paralleling with a Mixture of Controls ........................................................................................................................... 7
5 Application .................................................................................................................................................................................................. 9
5.1 Terminal Connections ....................................................................................................................................................................... 10
Figure 1 Simplified Schematic of Current Circuit for Paralleling
Two Transformers using the Circulating Current Method ...................................................................................................... 10
Figure 2 Paralleling Scheme for Two Transformers using the Circulating Current Method .......................................... 11
Figure 3 Paralleling Scheme for Two Transformers for mixed controls using
the Circulating Current Method ..................................................................................................................................................... 12
Figure 4 Schematic for mixed controls
Three Transformers using the Circulating Current Method .................................................................................................... 13
Figure 5 Interconnection TAPCON® XPA-I – TAPCON® 230 .................................................................................................. 14
282/01/01/0
3
1 General
1 General
4 282/01/01/0
1 General
Parallel/Independent Switch
Mode of LTC control is switch selectable.
Transient Protection
Input and output circuits are protected against system
transients. The –XPA-I will exhibit no component failure or
false commands when subjected to the requirements of ANSI/
IEEE C37.90.1-1989, which defines oscillatory and fast
transient surge withstand capability. All inputs and outputs
will withstand 1500 V ac to chassis or instrument ground for
one minute. Voltage inputs are electrically isolated from each
other, from other circuits, and from ground.
282/01/01/0
5
2 Safety
2 Safety
DANGEROUS VOLTAGES, capable of causing death or serious To avoid possible shock hazard, the chassis must be con-
injury, are present on the external terminals and inside the nected to an electrical ground. When servicing equipment
equipment. Use extreme caution and follow all safety rules in a test area, the Protective Earth Terminal must be attached
when handling, testing or adjusting the equipment. to a separate ground securely by use of a tool, since it is not
However, these internal voltage levels are no greater than grounded by external connectors.
the voltages applied to the external terminals.
CAUTION
DANGER! HIGH VOLTAGE!
Do NOT operate in an explosive environment
This sign warns that the area is connected to a dangerous Do not operate this equipment in the presence of flammable
high voltage, and you must never touch it. or explosive gases or fumes. To do so would risk a possible
fire or explosion.
This sign means that you should refer to the corresponding Do not modify equipment
section of the operation manual for important information Do not perform any unauthorized modifications on this
before proceeding. instrument. Return of the unit to a MR Electric repair facility
is preferred. If authorized modifications are to be attempted,
be sure to follow replacement procedures carefully to assure
that safety features are maintained.
6 282/01/01/0
3 Introduction
3 Introduction
282/01/01/0
7
4 Theory of Operation
4 Theory of Operation
The general paralleling schemes for two and three transformer The third and fourth path shown (Half Current and LDC Cur-
paralleling using the circulating current method are shown in rent), connecting the K2 auxiliary C.T. of the TAPCON® XPA-I
Figure 1 through. modules together, ensures proper operation of the Load Drop
Compensator circuit if one of the transformers is taken out of
Figure 1 shows the schematic of the current circuit only;
service by opening its breaker. For instance, if transformer #2
redrawn from the Paralleling Scheme figures to allow easier
is taken out of service by opening breaker 52-2, then half of
tracing of the load current (IL) and circulating current (IP)
transformer #1’s load current is forced to flow through the
paths.
half current loop. In this way, transformer #1’s voltage
A current, proportional to the transformer secondary current, regulating control sees the same load current as it did before,
is fed to the TAPCON® XPA-I unit. Because of the secondary and the proper amount of line drop compensation in the
parallel connection, however, this is actually the vector sum of transformer #1 control is maintained. This circuit configura-
the desired load current and any undesired circulating current. tion and grounding points must be maintained, if transformers
The TAPCON® XPA-I separates these currents, and sends them are to be successfully paralleled.
to the circulating current transformer K3 and to the proper
load (LDC) inputs of the associated control.
Two current loops are formed. One involves the K3 auxiliary
transformers in each of the TAPCON® XPA-I units. This loop
forms a measure of the transformer bank circulating current,
subtracted from the LDC control input and forced to flow into
the secondary winding of K3.
The second loop involves the K1 and K2 auxiliary transformers.
They force the load current to divide properly between the
various controls so that each senses its proper portion of the
total bank load. Thus, the LDC setting for each control may
properly be the same, regardless of whether or not the
associated transformer is being used in parallel.
The first current path shown (Circulating Current) has a current
analogous in angle and magnitude to the reactive current
circulating through the paralleled transformers (The current is
measured by amount and phase position. The difference is
calculated from this and transferred via CAN bus to the voltage
regulator). It also includes the overcurrent relay function,
which is used to detect excessive circulating current and block
the on-load tap-changer movement, if this occurs. Also, a LED
will alert the operator when excessive circulating current is
detected.
The second path shown (Balance Current), connecting the K1
auxiliary C.T. of the TAPCON® XPA-I modules together, has a
balance current which forces the two load currents of trans-
formers #1 and #2 to be identical. This means that any
difference in currents must flow in the circulating current
path.
8 282/01/01/0
5 Application
5 Application
The ..XP-I Parallel Balancing Module can be ordered with new • If paralleling and hand-operated load switches are used:
equipment from most transformer manufacturers or added to
existing transformers. If the Module is added to existing a. AUTO/MANUAL switches on the TAPCON® 230 should
equipment, the following factors should be considered: be placed in the MANUAL position.
• If the old control uses a 5 A input for the line drop b. Other controls should be placed in the MANUAL
compensator, a new control must be installed to provide position.
the required 0.2 A load and circulating current inputs.
A MR On-Load Tap-Changer Control is recommended for
this application. CAUTION
• If an existing 5/0.2 A auxiliary current transformer is not
Do not place the TAPCON® XPA-I PARALLEL/
available to provide the measure of secondary load
INDEPENDENT switch in the INDEPENDENT position if
current, one must be added.
the transformers are in parallel and under automatic control.
An Auxiliary Current Transformer is recommended for this
application (8,66 or 5/0,2 A).
c. The TAPCON® XP-I PARALLEL/INDEPENDENT (P/I)
• If phase-to-phase voltage is used, Figure 6 shows the
switchshould be placed in the INDEPENDENT position
application of two current transformers to derive a current
before the load switches are operated.
in phase with the voltage. Connection must be made to
Terminal of the 8,66A-range.
• If circuit breakers (52) exist, then the auxiliary breaker
contacts shown in the Paralleling Scheme figures are
required to automatically change from parallel to
independent operation should the breakers operate
automatically or by remote control.
If these breakers do not exist and, for example, only one
common load breaker is used, the circuit should be wired
to make a circuit where the normally closed contacts are
shown. No circuit should be made where the normally
open contacts are shown.
282/01/01/0
9
5 Application
Notes:
52 and 24 contacts are shown in the breaker colsed positon; 43 P in the parallel position
Fig. 1 Simplified Schematic of Current Circuit for Paralleling – Two Transformers using the Circulating Current Method
10 282/01/01/0
5 Application
Fig. 2 Paralleling Scheme for Two Transformers using the Circulating Current Method
2
282/01/01/0
11
5 Application
Fig. 3 Paralleling Scheme for Two Transformers for mixed controls using the Circulating Current Method
12 282/01/01/0
5 Application
Fig. 4 Schematic for mixed controls – Three Transformers using the Circulating Current Method
4
282/01/01/0
13
5 Application
14 282/01/01/0
6 Test Procedures
6 Test Procedures
Test procedures are provided for two and three transformer 11. Verify Transformer #1 voltage is within the band.
applications.
12. Manually raise Transformer #1 one to two taps (it could
6.1 Two Transformer Parallel Verification Test take three of four to obtain a response).
Procedure
13. Manually lower Transformer #2 one to two taps (could take
three or four to obtain a response).
NOTE
14. Verify that Transformer #2 calls for a Raise and Transformer
There must be a load on the transformer to perform this #1 calls for a Lower.
test.
15. Manually return Transformer #1 and Transformer #2 to the
same tap.
1. Place all transformer controls (adapter panels) in MANUAL Neither control should call for a Raise or Lower.
and parallel balancing modules (..XP-I) in the INDEPEN-
DENT switch position. 16. Manually raise Transformer #2 one or two taps (may take 3
Set the sensitivity to N. or 4 to obtain a response).
Set the "TRIP CIRCULATING CURRENT" to maximum
(100 mA) 17. Manually lower Transformer #1 one or two taps (may take 3
or 4 to obtain a response).
2. Set all the transformer controls to the same tap position
and the same bandwidth setting. 18. Verify that Transformer #1 calls for a raise and Transformer
Neither control should be calling for a raise or lower. #2 calls for a lower.
3. Close all transformer breakers and tie breakers. 19. Manually return Transformer #1 and Transformer #2 back
to the same tap.
4. Verify that the load current has the correct polarity. Neither control should call for a Raise or Lower.
8. Set Transformer #2 R Line Drop Compensation to 24. 20. Open the tie breaker between Transformer #1 and
The control should call for a Raise. (If the control calls for a Transformer #2 (24).
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before 21. Verify that the controls do not call for a Raise or Lower.
continuing the test.)
22. Manually raise Transformer #1 two or three taps (may take
4 or 5 to obtain a response).
9. Place the Transformer #1 ..XP-I Parallel/Independent
switch in the Parallel position.
23. Verify that Transformer #1 calls for a Lower, the circulating
current is zero on both controls and Transformer #2 is not
10. Place the Transformer #2 ..XP-I Parallel/Independent
affected.
switch in the Parallel position.
282/01/01/0
15
6 Test Procedures
24. Manually return Transformer #1 to the same tap. 41. Verify Transformer #2 is not affected.
Transformer #1 is now supplying all the load, its voltage may 48. Starting with the scaling value 100, turn the „TRIP CIRCU-
drop. LATING CURRENT“ rotary button slowly to the left until the
LED shows „RELAY TRIPPED.“ The tripping value of
circulating reactive current monitoring has been reached
35. Verify that Transformer #1 is not affected.
when the lamp indicator lights up. It indicates the output
relay of circulating reactive current monitoring and breaks
36. Manually raise Transformer #1 two or three taps (may take
the contact between terminals 15, 16. The voltage regu-
4 or 5 to obtain a response).
lator then blocks.
37. Verify that Transformer #1 calls for a Lower and that
Transformer #2 is not affected.
16 282/01/01/0
6 Test Procedures
6.2 Three Transformer Parallel Verification Test Guide 12. Set Transformer #3 R Line Drop Compensation to 0.
6. Verify that the voltage and CT transformers are connected 21. Verify that Transformer #1 and Transformer #2 call for a
to the same phase. Raise and Transformer #3 calls for a Lower.
7. Set Transformer #1 R Line Drop Compensation to 24. 22. Return Transformer #3 back to the same tap.
The control should call for a Raise. If the control calls for a
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before CAUTION
continuing the test.
If the loads are not evenly balanced between the transfor-
8. Set Transformer #1 R Line Drop Compensation to 0. mers then the voltage on the transformer with the larger
load may decrease and the control may call for a Raise and
9. Set Transformer #2 R Line Drop Compensation to 24. the transformer with the smaller load may increase and the
control may call for a Lower.
The control should call for a Raise. If the control calls for a
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before 23. Open the tie breaker between Transformer #1 and
continuing the test. Transformer #2 (24-1), then verify that the controls are not
affected.
10. Set Transformer #2 R Line Drop Compensation to 0.
24. Manually Raise Transformer #1 two or three taps, then
11. Set Transformer #3 R Line Drop Compensation to 24. verify that Transformer #2 and #3 are not affected.
Transformer #1 should call for a Lower and have zero
The control should call for a Raise. If the control calls for a circulating current on it’s control.
Lower, then the polarity of the line current coming into the
control is reversed, and must be corrected before 25. Return Transformer #1 back to the same tap.
continuing the test.
282/01/01/0
17
6 Test Procedures
27. Place Transformer #2 and Transformer #3 Controls to AUTO 37. Open Transformer #1 breaker 52-1, then verify that
at the same time. Observe where the on-load tap-changer Transformer #2 and #3 are not affected.
positions settle, and adjust the sensitivity of the TAPCON®
XP-I needed. 38. Manually Raise Transformer #2 two or three taps, then
verify that Transformer #2 calls for a Lower and Transformer
28. Manually return Transformer #2 back to the same tap. #3 calls for a Raise.
29. Close tie breaker 24-1 and open tie breaker 24-2 (between
Transformer #2 and Transformer #3) 41. Open Transformer #2 breaker 52-2, then verify Transformer
#1 and #3 are not affected.
30. Verify that the controls are not affected.
42. Manually Raise Transformer #1 two or three taps, then
31. Manually Raise Transformer #3 two or three taps, and then verify that Transformer #1 calls for a Lower and Transformer
verify that Transformer #1 and Transformer #2 are not #3 calls for a Raise.
affected. Transformer #3 should call for a Lower.
43. Manually return Transformer #1 back to the same tap.
32. Manually return Transformer #3 back to the same tap.
44. Close Transformer #2 breaker 52-2.
33. Manually Raise Transformer #1 two or three taps, then
verify the following: Note: Since Transformer #1 and #2 will be supplying all the
a. Transformer #1 calls for a Lower. load, their voltage may decrease.
b. Transformer #2 calls for a Raise.
45. Open Transformer #3 breaker 52-3, then verify that
c. Transformer #3 is not affected. Transformer #1 and #2 are not affected.
34. Place Transformer #1 and Transformer #2 Controls to AUTO 46. Manually Raise Transformer #1 two or three taps, then
at the same time. Observe where the on-load tap-changer verify that Transformer #1 calls for a Lower and Transformer
positions settle, and adjust the sensitivity of the TAPCON® #2 calls for a Raise.
XPA-I if needed.
47. Manually return Transformer #1 to the same tap.
35. Manually return Transformer #1 back to the same tap.
48. Close Transformer #3 breaker 52-3.
36. Close tie breaker 241 and 24-2.
Test complete. Place the desired settings on the controls and
set all controls to automatic.
18 282/01/01/0
7 Effect of the TAPCON® XPA-I on Control Sensitivity
More 4 48 Vac
Sensitive 3 41 Vac
2 32 Vac
1 29 Vac
N 24 Vac
1 20 Vac
2 17 Vac
Less 3 14 Vac
Sensitive 4 12 Vac
282/01/01/0
19
7 Effect of the TAPCON® XPA-I on Control Sensitivity
20 282/01/01/0
7 Effect of the TAPCON® XPA-I on Control Sensitivity
7
282/01/01/0
21
7 Effect of the TAPCON® XPA-I on Control Sensitivity
22 282/01/01/0
7 Effect of the TAPCON® XPA-I on Control Sensitivity
9
282/01/01/0
23
© Maschinenfabrik Reinhausen GmbH Phone +49 (0)941 4090 0
www.reinhausen.com Falkensteinstrasse 8 Fax +49 (0)941 4090-6 00
93059 Regensburg, Germany E-Mail sales@reinhausen.com