Beruflich Dokumente
Kultur Dokumente
Discussion
The 3-phase electric power system is the common method of ac electric power transmission. In this
system three conductors carry three ac currents of the same frequency to a single target. The currents
have a phase difference of 120°, and it is this delay between "phases" that gives a constant power transfer
over each cycle of the current, “and also makes it possible to produce a rotating magnetic field in an electric
motor” (wikipedia).
The neutral wire allows the three phase system to provide a higher line-to-line voltage while still supporting
a lower line-to-neutral voltage. In high voltage distribution systems it is common not to have a neutral wire
while the loads can be simply connected between phases (line-to-line connection). Finally, three-phase
systems can produce a magnetic field that rotates in a specified direction, which simplifies the design of
electric motors.
A 3-phase source consists of three single-phase generators, all with equal voltage magnitudes but with a
120° phase difference.
Assuming that
Ean=V0° V, Ebn=V-120° V, Ecn=V-240° V
The return current In, in the neutral wire is the sum of the three currents ( In=Ian+Ibn+Icn). If the three loads
are equal and the voltages are equal in magnitude but have a 120° phase difference, the system is a
balanced 3-phase system, ( In such a case In=0A).
Phase sequence
The phase sequence of a system “is the order in which the voltages in the individual phases peak”
(Chapman, 2005). The voltages of figure(2-2) are said to have a positive phase sequence, since the
voltages peak in the order a,b,c . However, in the voltages peak in the order a,c,b, the system is said to
have a negative sequence.
IL=I
In case of the voltages however
VLL=3V
The line voltages are also shifted 30° with respect to the phase voltages. Figure(2-3) the phasor diagram
and the voltage triangle of the line and phase voltages of the Y-connection.
Delta ()-Connection
A -connected load and source is shown in figure(2-4) below. In this case the line and phase voltages are
equal, therefore,
VLL=V
The currents however,
IL=3I
Figure (2-6), Two-Watt-Meter Method, 3-phase measurement, Balanced or unbalanced connections (3, 3-conductors, or )
5. Return the voltage to zero and turn off the power supply.
VLL = 380V
5. Return the voltage to zero and turn off the power supply.
VLL = 220V
2) Use the results of the (R-L, 3-4, Y-connected) load in Table (2-4) to prove the relationship between the
phase and line voltages in the Y-connected circuit.
3) Use the values of Pt, IL and VL, of the (R-C, 4-3, -connected) load in Table (2-5) to
i) Calculate S and the pf.
ii) Compare the calculated values in (i) with the practical values (calculate % error).
4) A 3-phase motor draws a current of 10 Amperes on a 415 Volt line and p.f.=0.85 lagging.
i) Calculate the apparent power, S.
ii) Calculate the real power, P.
iii) Calculate the reactive power, Q.
References
1) Chapman, S.J., “Electric Machinery Fundamentals”, Third Edition, McGraw Hill, 1998.
2) Chapman, S.J., “Electric Machinery Fundamentals”, McGraw Hill, 2005.
3) Rayan, M., Al-Shaher, M., “Electric Machines Laboratory Manual”, Kuwait University, Summer
2000.
4) http://wikipedia.org/