Sie sind auf Seite 1von 1

Refrigerant Tray Sizing

Project No.: O M - 1 6 - 2 6 Reference: CT-01

Project Title: Date: 4-Dec-19 Rev.: 00

Area: Refrigerant Tray Calculation By:

Min Tray Requirement Calculator


Sr.No. Tonnage Index Capacity Refrigerent Pipe Size Gap Between Total Width
(kW) pipes mm mm
Gas Pipe Liquid Pipe Insulation mm

1 10 85.91 15.9 9.5 9 5 66.4


2 2.5 21.48 12.7 6.4 9 5 60.1
3 6 51.55 15.9 9.5 9 5 66.4
4 8 68.73 15.9 9.5 9 5 66.4
5
6
7
8
9
10
11
12
13
14
15
Total 259.3
MINIMUM SPARE CAPACITY REQ'MT:- 30.00%

A OVERALL LINEAR CONTAINMENT REQ'MT (Min):- 337.1mm

Min Tray Requirement Calculator


Standard Tray / Ladder Sizes Select No. to suit Min Cont'mt Total Linear Dim. Comment
Req'mt (if required)

50mm
75mm
100mm
150mm
225mm
300mm
450mm 1No. 450mm
600mm
750mm
900mm

B OVERALL TOTALS:- 1Nos. 450mm

0 50 13 6.4
51 125 16 9.5
126 200 19 9.5
201 250 22 9.5
251 400 29 13
401 530 29 16
531 590 35 16
591 840 35 19
841 ### 41 19