Print Date: 16/11/2019 12:57:09

Results Summary Log

Motor ID Time Temp Resist Megohm DA/PI DC Surge


OT 014 14/11/2019 10:53:11 -- -- -- -- PASS Tested

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 16/11/2019 12:57:09

Nameplate Information Motor ID OT 014


Location LA RINCONADA DEL SUR Building OT 014
Model Manufacturer
Serial Number HP/KW 45
Volts-Rating 440 Volts-Operating 0
Amps-Rating 74 A Amps-Operating 0
Insulation Enclosure
RPM 1780 Service Factor 0
Frame Freq-Hz 60
LR Code LR Amps 0
NEMA Design Max Amb °C 0
NEMA nom eff 0 Duty Cycle
Manuf's Type Manuf Dt Cd
Description M04

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 16/11/2019 12:57:09

Nameplate Information Motor ID OT 014


Location LA RINCONADA DEL SUR Building OT 014
Model Manufacturer
Serial Number HP/KW 45
Volts-Rating 440 Volts-Operating 0
Amps-Rating 74 A Amps-Operating 0
Insulation Enclosure
RPM 1780 Service Factor 0
Frame Freq-Hz 60
LR Code LR Amps 0
NEMA Design Max Amb °C 0
NEMA nom eff 0 Duty Cycle
Manuf's Type Manuf Dt Cd
Description M04

Application Information Test Date/Time 14/11/2019 10:53:11


Test ID Default Repair/Job #
Tested By Tested For
Room # MCC
Location LA RINCONADA DEL SUR Building OT 014
Use % Load
Vert/Horiz Starter
Starts/24Hrs Rewind Dt
Install Dt Basic Dt
Volts 1 0,0 Amps 1 0,0
Volts 2 0,0 Amps 2 0,0
Volts 3 0,0 Amps 3 0,0
Tester Type D12R Tester SN 0
Tester ID PP30 SN 0
Cal Date Next Cal Date

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 16/11/2019 12:57:09

Nameplate Information Motor ID OT 014


Location LA RINCONADA DEL SUR Building OT 014
Model Manufacturer
Serial Number HP/KW 45
Volts-Rating 440 Volts-Operating 0
Amps-Rating 74 A Amps-Operating 0
Insulation Enclosure
RPM 1780 Service Factor 0
Frame Freq-Hz 60
LR Code LR Amps 0
NEMA Design Max Amb °C 0
NEMA nom eff 0 Duty Cycle
Manuf's Type Manuf Dt Cd
Description M04

Results Summary Test Date/Time 14/11/2019 10:53:11


Test ID: Default Repair/Job #
Tested By Tested For
Room # MCC
Location LA RINCONADA DEL SUR Building OT 014
Temp Status No Test Performed PI Status No Test Performed
Temp Volts (V) 0
Resist Status No Test Performed DA Ratio 0,0
L1-L2 (Ohms) 0 PI Ratio 0,0
L2-L3 (Ohms) 0 HiPot PASS
L3-L1 (Ohms) 0 Volts (V) 500
Max Delta R % 0,000% Current(µA) 0,01
Coil 1 (Ohms) 0 Resist (Mohm) 37313
Coil 2 (Ohms) 0 Surge Status Tested
Coil 3 (Ohms) 0 Peak Volt(V) L1 1820
Megohm Status No Test Performed Peak Volt(V) L2 1840
Volts (V) 0 Peak Volt(V) L3 1840
Current(µA) 0 Max P-P EAR% --,--,--
Resist (Mohm) 0 EAR 1-2,2-3,3-1 6%,38%,42%

Tester Info: ; 0; Cal Dates: -

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 16/11/2019 12:57:09

Surge: Nested Waveforms Motor ID OT 014


Test Date/Time 14/11/2019 10:53:11 Surge Status Tested

Lead Surge Status Peak Voltage Max P-P EAR%


1 PASS 1820 ---
2 PASS 1840 ---
3 PASS 1840 ---

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 16/11/2019 12:57:09

Surge Phase-to-Phase Comparison Motor ID OT 014


Test Date/Time 14/11/2019 10:53:11 Surge Status Tested

Lead Surge Status Peak Voltage L-L EAR%


1 PASS 1820 6,0%
2 PASS 1840 38,0%
3 PASS 1840 42,0%

Tester Info: ; 0; Cal Dates: -


Report Generated by Baker Instrument Company, An SKF Group Company - MTA
Print Date: 16/11/2019 12:57:09

Tester Info: ; 0; Cal Dates: -

Report Generated by Baker Instrument Company, An SKF Group Company - MTA