Sie sind auf Seite 1von 6

AAA PROTECTION RELAY SETTING Contract No.

PGGA-2875 25 SYNCHRO CHECK FUNCTION Date


Prepared: PK 33/11kV SHAAB AL ASHKAR-B PRIMARY SUBSTATION Doc No.
Checked: TR 11kV K15-BUS SECTION-1 Rev No.

Function Parameter Paramete Paramete Paramete Paramete


S.No Parameter Description Proposed Setting Adopted Settings L&T SNC
Name Name r Unit r Min r Max r Step

1 Control: 0 Rated frequency Rated frequency of the network 50Hz 50Hz


2 Phase rotation Phase rotation order ABC ABC
3 Blocking mode Behaviour for function BLOCK inputs Freeze timer Freeze timer
4 Bay name Bay name in system K15_BS-1_F25 K15_BS-1_F25
5 IDMT Sat point Overcurrent IDMT saturation point I/I> 10 50 1 50 50
Voltage
6 Primary voltage Primary rated voltage kV 0.1 440 0.001 33 33
(3U,VT): 1
Secondary
7 Secondary rated voltage V 60 210 1 110 110
voltage
Voltage transducer measurement
8 VT connection Wye Wye
connection
Phase A Voltage phasor magnitude
9 Amplitude Corr A correction of an external voltage 0.9 1.1 0.0001 1 1
transformer
Phase B Voltage phasor magnitude
10 Amplitude Corr B correction of an external voltage 0.9 1.1 0.0001 1 1
transformer
Phase C Voltage phasor magnitude
11 Amplitude Corr C correction of an external voltage 0.9 1.1 0.0001 1 1
transformer
Voltage input
12 Type of the voltage input Voltage trafo Voltage trafo
type
Phase A Voltage phasor angle
13 Angle Corr A correction of an external voltage deg -20 20 0.0001 0 0
transformer
Phase B Voltage phasor angle
14 Angle Corr B correction of an external voltage deg -20 20 0.0001 0 0
transformer
Phase C Voltage phasor angle
15 Angle Corr C correction of an external voltage deg -20 20 0.0001 0 0
transformer
Voltage
16 Primary voltage Primary rated voltage kV 0.1 440 0.001 33 33
(3UB,VT): 2
Secondary
17 Secondary rated voltage V 60 210 1 110 110
voltage
Voltage transducer measurement
18 VT connection U12 U12
connection
Phase A Voltage phasor magnitude
19 Amplitude Corr A correction of an external voltage 0.9 1.1 0.0001 1 1
transformer
AAA PROTECTION RELAY SETTING Contract No.
PGGA-2875 25 SYNCHRO CHECK FUNCTION Date
Prepared: PK 33/11kV SHAAB AL ASHKAR-B PRIMARY SUBSTATION Doc No.
Checked: TR 11kV K15-BUS SECTION-1 Rev No.

Function Parameter Paramete Paramete Paramete Paramete


S.No Parameter Description Proposed Setting Adopted Settings L&T SNC
Name Name r Unit r Min r Max r Step

Voltage input
20 Type of the voltage input Voltage trafo Voltage trafo
type
Phase A Voltage phasor angle
21 Angle Corr A correction of an external voltage deg -20 20 0.0001 0 0
transformer
Voltage
22 Primary voltage Primary voltage kV 0.1 440 0.001 33 33
(Uo,VT): 1
Secondary
23 Secondary voltage V 60 210 1 110 110
voltage
24 Amplitude Corr Amplitude correction 0.9 1.1 0.0001 1 1
25 Angle correction Angle correction factor deg -20 20 0.0001 0 0

Product
26 Type IED type REU615 REU615
identifiers: 0
27 Product version Product version number 5.0 FP1 5.0 FP1
28 Serial number IED serial number 1VHR91389448 1VHR91389448
29 Order code IED order code HBUAEAADNEA1ANN11G HBUAEAADNEA1ANN11G
30 Production date IED production date 43080 2/21/2018
Configuration
31 IED configuration name UE01 UE01
name
32 SW version IED SW version 5.1.10 5.1.11
33 SW date IED SW date 42997.4131944444 2017-12-01 5:52PM
34 SW number IED SW number 2RCA035041L 2RCA035041L
35 HW revision IED HW revision G G
36 SECRSYN1: 1 Operation Operation Off / On on on

Synchro check
37 Synchro check operation mode Asynchronous Asynchronous
mode
Selection of synchro check
38 Control mode command or Continuous control Command Command
mode
Voltage low limit line for energizing
39 Dead line value xUn 0.1 0.8 0.1 0.1 0.1
check
Voltage high limit line for energizing
40 Live line value xUn 0.2 1 0.1 0.8 0.8
check
Voltage low limit bus for energizing
41 Dead bus value xUn 0.1 0.8 0.1 0.1 0.1
check
Voltage high limit bus for energizing
42 Live bus value xUn 0.2 1 0.1 0.8 0.8
check
43 Close pulse Breaker closing pulse duration ms 200 60000 10 200 200
AAA PROTECTION RELAY SETTING Contract No.
PGGA-2875 25 SYNCHRO CHECK FUNCTION Date
Prepared: PK 33/11kV SHAAB AL ASHKAR-B PRIMARY SUBSTATION Doc No.
Checked: TR 11kV K15-BUS SECTION-1 Rev No.

Function Parameter Paramete Paramete Paramete Paramete


S.No Parameter Description Proposed Setting Adopted Settings L&T SNC
Name Name r Unit r Min r Max r Step

44 Max energizing V Maximum voltage for energizing xUn 0.5 1.15 0.01 1.05 1.1

Correction of phase difference


45 Phase shift between measured U_BUS and deg -180 180 1 0 0
U_LINE
Minimum Syn Minimum time to accept
46 ms 0 60000 10 0 0
time synchronizing
Maximum Syn Maximum time to accept
47 ms 100 6000000 10 200 200
time synchronizing
48 Energizing time Time delay for energizing check ms 100 60000 10 100 100
Closing time of
49 Closing time of the breaker ms 40 250 10 60 60
CB
Voltage source
50 Voltage source switch 0 1
switch
51 Live dead mode Energizing check mode One Live, Dead One Live, Dead
Difference
52 Maximum voltage difference limit xUn 0.01 0.5 0.01 0.1 0.1
voltage
Difference
53 Maximum frequency difference limit xFn 0.001 0.1 0.001 0.1 0.1
frequency

54 Difference angle Maximum angle difference limit deg 5 90 1 10 10


A12829
7-Aug-19
C5C-8300-J-1033
B

AADC Remarks
A12829
7-Aug-19
C5C-8300-J-1033
B

AADC Remarks
A12829
7-Aug-19
C5C-8300-J-1033
B

AADC Remarks

Das könnte Ihnen auch gefallen