Equator Line
Java Island & Bali
SERPONG
Jakarta
serpong
Lightning Measurement Station
Mnt Tangkuban Perahu
• Ng is around =
• 15-40
strike/km2/yr
10
Monthly Variant of Lightning Activity in
Serpong Area
PROTECTION OF MV OVERHEAD
LINE
• 1 OHGW reduce
induction up to 33%.
• 2 OHGW reduce the
induction up to 66%
(Peek).
Multi Chamber System (MCS)
• The base of multi chamber arresters (MCA), shown
in next picture.
• It comprises a large number of electrodes mounted
in a length of silicon rubber.
• Holes drilled between the electrodes and going
through the length act as miniature gas discharge
chambers.
Fig. 1. Multichambersystem (MCS): (a) Diagram showing the discharge onset instant.
(b) Diagram showing the discharge end instant.
1) silicon rubber length, 2) electrodes, 3) arc quenching chamber, and 4) discharge channel.
Multi Chamber System (MCS)
• When a lightning overvoltage impulse is applied to
the arrester, it breaks down gaps between electrodes.
• Discharges between electrodes occur inside
chambers of a very small volume; the resulting high
pressure drives spark discharge channels between
electrodes to the surface of the insulating body and,
hence, outside into the air around the arrester.
Fig 2. Spark discharge occurs into the air around the Multichamber arresters
installation 20-kV lines.
SERPONG LINES CHARACTERISTICS
• A 20 kV feeder, called “Ruko” in Serpong region has been
chosen to be equipped with the multi-chamber arresters. The
choice is determined due to highest lightning outage of the
feeder.
• Outages have been recorded through this logger at
substation and reclosers as shown on table 1. It can be noted
that in total of 40 to 60 outages took place every year on
these lines.
• Average outages recorded per 100km per year at feeder
KDS4 and feeder SR20 is 120 outages.
Column1 2010 2011 2012 2013
Substation Trips 44 5 2 4
SR20 line Trips Recloser not installed Not available 27 21
KDS4 line Trips Recloser not installed Not available 18 32
Total number of trips 44 5 47 57
Substation
Parameter of Area Overall Area
Vicinity
Area Width in km 2,9 7,7
Area Length in km 3,4 10,9
Area in km2 10,0 84,1
Longitude min 106,589211 106,582423
Longitude max 106,614253 106,646372
Latitude min -6,306472 -6,285117
Latitude max -6,336874 -6,378302
24kV Circuit Length of line in Area in km 10 45
Surface sensitive to lightning in km2 4 20
Table 2. Data of the research location which are equipped by arrester on SR20 and KDS4 feeders.
Fig 3. 20kV lines of feeder SR20 and feeder KDS4.Orange Color is the vicinity area, and in
blue color is the whole research area.
Installation of Arresters
• On 20 October and 19 November 2013, a total of 44
arresters have been installed in the vicinity area.
• Installed arrester was shown in Fig 4, one arrester per
pole is installed on alternate phases.
• This arrester has been installed on poles that were not
equipped with gapped or gapless metal oxide arresters
(MOA).
• Arrester was simply mounted on the cross arm using
standard metal fitting.
Fig4. Multi-Chamber Arresters installed on alternate phases, one piece per pole
Research Result
Table 4. Lightning activity during 54 days from 27 Feb 2012 to 20 Oct 2013
32