Protections:
ZCS 4E from v 7.0
ZCR 4E from v 7.0
ZZN 4E/S from v 7.0
ZZN 4E/RP from v7.0
ZCS 5E from v 5.0
Trasnsmission speed could be programmed using device's keyboard – for this purpose: select
from device's menu option TRANSFER, press S – it appears menu with selection beetwen
C&C BUS and IEC BUS. Using arrows keys up/down it is possible to change required
transmission speed, and using key N to choose right protocol. Protocol's speed wchich is to be
changed will blink. Selected speed is confirmed with E key.
Link layer.
Special character <0x5e> is not used, negative acknowledgments are short frames (frames
without data).
Application layer.
There has been implemented following appilaction functions (acc. to IEC 870—5—103
norm):
time synchronisation;
command transmission;
general interrogation function;
station initialisation;
There is no generic service, compatibility level lies in mentioned above functions.
Cyclic data—measurements are available via link function nr 11 (request class 2 data), as
ASDU 9, without frequency measurement. For devices ZZN are valid only current
measurements.
Spontaneous data—Are available via setting bit ACD by protection device in field „Control”
protocol's frame in course of device's polling (reading cyclic data) via link function 10
(request class 1 data).
These data may be, as weell, read using only link function nr 10 (request class 1 data).
Spontaneous data are buffered, nevertheles, it can take place overriding data buffer, then is
information loss, so user appropriate care is read transmision buffer as quickly as it is
necessary.
Par example.
For voltage measuring tarnsformers with transformation 1100 and current measuring
tarnsformers with transformation 120, for obtaining identity ASDU=4, INF=73 with value
displayed by protection, it should be divided by number 9.17=1100/120.
are events about latest change, e.g. are not recorded in events log, and number of recorded
events for all previous mentioned INF–s amounts exactly 1 (one).
Function Type field—sort of protecion, fifth field in ASDU–s units, has got value:
Time synchronization—
in ZCR 4E, ZCS 4E, ZZN 4E refers to disturbance recorder, in ZCS 5E refers to protection:
time synchronization function is realised as broadcast or with confirmation with ASDU 6.
Station initialization—
refers to protection:
as confirmation of station initialization is returned ASDU 5
Command transmission.
refers to protection:
commands are executed sending ASDU 20 to the device.
ASDU INF ZCR ZCS ZZN/S ZZN/S ZZN/
STER. RP
20 19 LEDs reset x x x x x
20 31 manual circuit breaker control (on/off) x x x x x
20 53 events recorder reset x x x x x
20 60 connector number 1 control* x x x x x
20 61 connector number 2 control* x x x x x
20 62 connector number 3 control* x x x x x
20 63 connector number 4 control* x x x x x
20 64 connector number 5 control* x x x x x
20 65 connector number 6 control* x x x x x
20 66 connector number 7 control* x x x x x
20 67 connector number 8 control* x x x x x
20 68 connector number 9 control* x x x x x
20 69 connector number 10 control* x x x x x
20 70 connector number 11 control* x x x x x
20 71 connector number 12 control* x x x x x
20 72 connector number 13 control* x x x x x
20 73 connector number 14 control* x x x x x
20 74 connector number 15 control* x x x x x
20 82 PU 1 relay control x x x x x
20 83 PU 2 relay control x x x x x
20 84 PU 3 relay control x x x x x
20 85 PU 4 relay control x x x x x
20 86 PU 5 relay control x x x x x
20 87 PU 6 relay control x x x x x
20 88 PU 7 relay control x x x x x
20 89 PU 8 relay control x x x x x
20 90 PU 9 relay control x x x x x
20 91 PU 10 relay control x x x x x
20 92 PU 11 relay control x x x x x
20 93 PU 12 relay control x x x x x
20 94 PU 13 relay control x x x x x
20 95 PU 14 relay control x x x x x
20 96 PU 15 relay control x x x x x
20 97 PU 16 relay control x x x x x
20 98 PU 17 relay control x x x x x
20 99 PU 18 relay control x x x x x
20 108 function fxl_9 x x x x x
20 109 function fxl_10 x x x x x
20 110 function fxl_11 x x x x x
20 111 function fxl_12 x x x x x
20 112 function fxl_13 x x x x x
20 113 function fxl_14 x x x x x
20 114 function fxl_15 x x x x x
*—is
not present in GI
**—connector means: circuit breaker or recloser or earthing switch