GARDU INDUK PAOKMOTONG 150KV


TECHNICAL PARTICULAR AND GUARANTEE
150KV CURRENT TRANSFORMER

DRAWING BY : ESTABLISHED BY : CHECKED BY : APPROVED BY :

- FSR RY UA

DATE: 5-Dec-2017 DATE: 5-Dec-2017 DATE: 5-Dec-2017 DATE: 5-Dec-2017


DRAWING No :
SCALE : SIZE : PAGE :
1HID1-1-7030-E725 1 OF -

PLN DWG No. REVISION :


NTS A4 - A
Technical Particular and Guarantee

TPG HV CURRENT TRANSFORMER FOR TRAFO BAY 150 KV

NO DESCRIPTION UNIT PLN REQUIRED PROPOSED AND GUARANTEE

Manufacturer to be mentioned ABB


Origin of Manufacturer to be mentioned SWEDEN
Type to be mentioned IMB 170
1 Standard IEC 61869-1; IEC 61869-2 IEC 61869-1; IEC 61869-2
2 Type of designation - Post Type, single phase Post Type, single phase
3 Service condition Outdoor; Tropical Area Outdoor; Tropical Area
4 Highest voltage for equipment (Um) kV 170 170
5 Rated Frequency (Fr) Hz 50 50
Cantumkan dengan
6 Rated short time thermal current (Ith) kA 31.5 or 40 40 nilai
7 Rated duration of short circuit s ≥1 ≥1
8 Dynamic withstand current (Idyn) kA ≥ 2,5 x I th ≥ 2,5 x I th
9 Rated primary current (Ipr) A 300 or 4000 300
10 Rated continuous thermal current (Icth) A 1.2 x Ipr 300
11 Rated secondary current (Isr) A 1 1 1,2 x 300= 360
12 Insulation Medium Paper oil insulated Paper oil insulated
RATED INSULATION LEVEL
13 Rated Lightning impulse withstand voltage kVp 750 750
14 Rated Switching impulse withstand voltage kVp N.A N.A
15 Rated Power frequency withstand voltage kVrms 325 325
Technical Particular and Guarantee

TPG HV CURRENT TRANSFORMER FOR TRAFO BAY 150 KV

PROPOSED AND
NO DESCRIPTION UNIT PLN REQUIRED
GUARANTEE
GENERAL
16 Number of cores - 5 5
Tambahkan
17 Ratio
keterangan
Core-1 : Main protection A/A 150-300/1 150-300/1
Core-2 : Back up protection A/A 150-300/1 150-300/1
Core-3 : Busbar protection A/A 2000-4000/1 150-300/1
Core-4 : Checkzone buspro high impedance/centralized low A/A 2000-4000/1 2000-4000/1
impedance
Core-5 : Bidding meter A/A 150-300/1 2000-4000/1
18 Accuracy class :
Core-1 : Main protection - class PX class PX
Core-2 : Back up protection - 5P20 5P20
Core-3 : Busbar protection - class PX 0.2s
Core-4 : Checkzone buspro high impedance - class PX class PX
Core-5 : Bidding meter - 0.2s class PX
19 Secondary resistance (Rct) for protection purpose at 75OC :
Core-1 : Main protection Ohm to be mentioned 1
Core-2 : Back up protection Ohm to be mentioned N/A
Core-3 : Busbar protection Ohm to be mentioned N/A
Core-4 : Checkzone buspro high impedance Ohm to be mentioned 25
Core-5 : Bidding meter Ohm to be mentioned 25
20 Rated burden or Knee Point Voltage (on lowest ratio) :
(Rlead = 1.85 ohm for Isr = 1 A or Rlead = 1.16 ohm for Isr = 5 A)
Core-1 (I fault trafo = 1847.5 A) V Vk ≥ 2 x (Ifault/Ratio x (Rct + Rlead)) 70
Core-2 VA ≥ 40 (for Isr = 5) 20 ( Isr =1 A)
Core-3 (I fault = Ith) V Vk ≥ 2 x (Ifault/Ratio x (Rct + Rlead)) 15 (Isr = 1 A)
Core- 4 (I fault = Ith) V Vk ≥ 2 x (Ifault/Ratio x (Rct + Rlead)) 1074
Core-5 VA ≥ 35 (for Isr = 5) 1074
21 Instrument security factor at nominal burden (measuring cores) - ≤ FS 10 FS 10
Technical Particular and Guarantee

TPG HV CURRENT TRANSFORMER FOR TRAFO BAY 150 KV

PROPOSED AND
NO DESCRIPTION UNIT PLN REQUIRED
GUARANTEE
OTHERS
22 Insulator:
- Type Porcelain or Silicon Rubber Porcelain
- Creepage distance to earth mm/kV 25 or 31 31
23 CT head housing material Aluminium alloy / Die cast / Mild steel Aluminium alloy
24 CT base housing material - Aluminium alloy / Die cast / Mild steel Aluminium alloy
Flexible connection, suitable for
25 Primary terminal - Flexible connection, suitable for plate
plate
Made from corrosion resistant
Made from corrosion resistant die cast
die cast alluminium, min IP54,
26 Secondary terminal box - alluminium, min IP54, removable,
removable, undrilled, terminal
undrilled, terminal flange with drainage
flange with drainage
27 Earth terminal - one earth terminal one earth terminal
28 Oil level indicator - Indirect / Direct type Direct type
Corrosion-proof metallic bellow / Gas
29 Oil compensation - Gas Cushion
Cushion
30 Method of ratio changing - Secondary Secondary
Capacitance Tap for Measurements of Voltage or Tan
31 Yes Yes
Delta
32 Static withstand load class Load class II Load class II
33 Seismic condition (according to seismic map) g 0,3 0,3
CT shall be designed for transport and storage in
34 yes yes
either horizontal or vertical position