Beruflich Dokumente
Kultur Dokumente
Introduction
1.1 General
With the increasing dependence on electricity supplies, in both developing and
developed countries, the need to achieve an acceptable level of reliability, quality
and safety at an economic price becomes even more important to customers.
A further requirement is the safety of the electricity supply. A priority of any
supply system is that it has been well designed and properly maintained in order to
limit the number of faults that might occur.
Associated with the distribution networks themselves are a number of ancillary
systems to assist in meeting the requirements for safety, reliability and quality of
supply. The most important of these are the protection systems that are installed to
clear faults and limit any damage to distribution equipment. Among the principal
causes of faults are lightning discharges, the deterioration of insulation, vandalism,
and tree branches and animals contacting the electricity circuits. The majority of
faults are of a transient nature and can often be cleared with no loss of supply, or just
the shortest of interruptions, whereas permanent faults can result in longer outages.
To avoid damage, suitable and reliable protection should be installed on all circuits
and electrical equipment. Protective relays initiate the isolation of faulted sections of
the network in order to maintain supplies elsewhere on the system. This then leads to
an improved electricity service with better continuity and quality of supply.
A properly coordinated protection system is vital to ensure that an electricity
distribution network can operate within preset requirements for safety for indivi-
dual items of equipment, staff and public, and the network overall. Automatic
operation is necessary to isolate faults on the networks as quickly as possible in
order to minimise damage. The economic costs and the benefits of a protection
system must be considered in order to arrive at a suitable balance between the
requirements of the scheme and the available financial resources. In addition,
minimising the costs of non-distributed energy is receiving increasing attention.
When providing protective devices on any supply network, the following basic
principles must apply. On the occurrence of a fault or abnormal condition, the
protection system must be capable of detecting it immediately in order to isolate
the affected section, thus permitting the rest of the power system to remain in
service and limiting the possibility of damage to other equipment. Disconnection of
equipment must be restricted to the minimum amount necessary to isolate the fault
2 Protection of electricity distribution networks
from the system. The protection must be sensitive enough to operate when a fault
occurs under minimum fault conditions, yet be stable enough not to operate when
its associated equipment is carrying the maximum rated current, which may be a
short-time value. It must also be fast enough to operate in order to clear the fault
from the system quickly to minimise damage to system components and be reliable
in operation. Back-up protection to cover the possible failure of the main protection
is provided on most circuits in order to improve the reliability of the protection
system. While electromechanical relays can still be found in some utilities, the
tendency is to replace these by microprocessor and numerical relays, particularly in
the more complex protection arrangements.
The primary aim of any electricity supply system is to meet all customers’
demands for energy. Power generation is carried out wherever it achieves the
most economic selling cost overall. The transmission system is used to transfer
large amounts of energy to major load centres, while distribution systems carry
the energy to the furthest customer, using the most appropriate voltage level.
Where the transport of very large amounts of power over large distances is
involved, an extra high voltage (EHV) system, sometimes termed major or pri-
mary transmission, is required. Such systems operate in the >300-kV range,
typical values being 400, 500 and 765 kV.
High-voltage (HV) networks transport large amounts of power within a particular
region and are operated as either interconnected systems or discrete groups. Below the
transmission system, there can be two or three distribution voltage levels to cater for
the variety of customers and their demands. In general, the medium-voltage (MV)
networks and low-voltage (LV) networks are operated as radial systems.
Figure 1.1 illustrates the interrelation of the various networks. The HV
networks are supplied from EHV/HV substations that themselves are supplied by
inter-regional EHV lines. HV/MV transforming substations situated around each
HV network supply individual MV networks. The HV and MV networks provide
supplies direct to large customers, but the vast majority of customers are connected
at low voltage and supplied via MV/LV distribution substations and their asso-
ciated networks, as shown in Figure 1.2.
EHV
EHV/HV
Major HV
substation
HV/MV
HV network
HV/MV
MV
MV
overhead MV cable
network network
To adjacent
MV
network
Urban distribution
Rural MV/LV
distribution
LV board
LV network
Generation
EHV
Generation
EHV/HV
HV
HV/MV
MV
Consumption
MV/LV
LV
Consumption
M M
~ ~
Busbar protection
Line protection
protection, operate only for faults within their protection zone. Other relays are able
to detect faults both within a particular zone and outside of it, usually in adjacent
zones, and can be used to back up the primary protection as a second line of
defence. It is essential that any fault is isolated, even if the associated main pro-
tection does not operate. Therefore, wherever possible, every element in the power
system should be protected by both primary and back-up relays.
A B C
G2 G3 G4
2 5 9
G1
1 3 4 6 10
F1 F2 F3
7 8 11
F4
Table 1.1 shows the breakers that failed to open and those that were tripped by
the primary protection and by the back-up protection.
For fault F1, the protection correctly tripped breaker 4 to open one end of the
faulted feeder. With breaker 3 failing to open, breakers 1 and 2 were tripped by
back-up protection to stop fault current flowing into the fault from generators
8 Protection of electricity distribution networks
G1 and G2. With fault F2, when breaker 6 failed to operate, the directional pro-
tection on breakers 3 and 8 operated to open the incoming feeders from the adjacent
busbars, and the back-up protection on breaker 5 tripped to stop G3 feeding into
the fault.
Fault F3 was correctly cleared by the tripping of feeder breaker 10. Fault F4
was correctly cleared by the operation of breaker 11, so that the tripping of breaker
G1
1
Termoyumbo 115 kV
G2 2 3 4
F1 5 6 29
10
Bajo Anchicayá 115 kV Chipichape 115 kV San Luis 115 kV
9 28
11 12 13 14 7 8
15
20 27
Pailon 115 kV Chipichape 34.5 kV San Luis 34.5 kV
F3
16 21 22 26
17 18 23 24
19 25
G3
8 was incorrect. Any fault current flowing along inter-busbar feeder 7–8 before
breaker 11 opened would have been from 7 to 8. Relay 8 is directional, and
operation should not have been initiated for flows from 7 to 8. Thus, the first two
cases illustrate maloperation from a dependability point of view, with the last one
illustrating maloperation from a security standpoint.
Exercise 1.1
For the power system arrangement shown in Figure 1.6, complete Table 1.2, taking
into account the operation of the circuit breakers as shown for each fault case.
Please note that, as in Example 1.1, some of the circuit breakers that operated may
have done so unnecessarily.