Power

Generation

Cummins Natural Gas Generating Set


Range - 180 Kva
Options Technical Data
Gas Generating Set - Typical Maximum KWe Prime Power 144 - Heat
Engine Rating at 50 Hz (0.8 p.f.) Exchanger cooling
Gas Generating Set - Typical KWe Baseload Power Rating at 115- Heat
❑ Spark arrester silencer 50 Hz (0.8 p.f.) Exchanger cooling
❑ Heavy duty air cleaner Output Voltage and Frequency 415 Volts, 50 Hz
❑ Heaters Power Factor 0.8 ( lag )
No.of Phases 3 Phase
Alternator Overall Genset Dimensions (mm) Length 2560
Width 1223
❑ Thermister Height 1907
❑ PMG excitation Dry weight 2204
❑ Space heater Engine Model GTA - 855 - G
❑ 105 degree C temperature rise alternator No. of Cylinders 6
Aspiration Turbocharged Aftercooled
Control Panel Bore - mm 140
Stroke - mm 152
❑ AMF control panel
Displacement - liter 14.0
❑ KW and Power factor meters Engine Output Prime - KWm (maximum) 180.5
❑ Battery charger Engine Output Baseload - KWm (maximum) 152.9
❑ Remote and auto start panel Piston Speed - m / s 7.6
❑ Auto / Manual synchronising panel Break Mean Effective Pressure (BMEP) - kPa 1031
❑ Indicating lamps for engine faults Overall Engine Dimensions Length (Engine Only) 1810
/ Audio / Visual annunciation Width (Engine Only) 811
Height (Engine Only) 1200
Others Dry weight of engine 1386
without cooling system
❑ Acoustic enclosure Engine Rating at 1500 RPM (BHP) 12.0 : 1
❑ Weatherproof enclosure Piston Compression Ratio 10.0 : 1 242
❑ Mobile set with canopy 8.5 : 1 227
Compression Ratio ( for following data ) **** 10:1
Natural Gas Consumption for Gas Calorific Value 53
(970 BTU/CFT or 8632 KCal/SM3) SCM/Hr
Exhaust Temperature ( Stack ) Deg C 500
Energy Input - KW 528

Power Energy Output - KW


Heat Rejected to Jacket Water - KW
181
174
Generation Heat Rejected to Aftercooler LTA Circuit - KW 25
Heat Rejected to Exhaust - KW 116
Heat Rejected to Ambient + Unaccounted - KW 33
Air Flow (Lit/Sec) 189
Cummins India Limited Exhaust Gas Flow - Lit / Sec 475
Energy Solutions Business Unit Exhaust System Permissible Back Pressure - mm Hg 76.2
35 A/ 1/ 2, Erandwana, Pune- 411 038 Engine Water Flow - (Lit / min) 348
Phone: (020) 402 7525 Fax: (020) 402 8090 After Cooler Circulating Water Flow - (Lit/Min) 133
Website: www.cumminsindia.com Raw water flow for Engine side Heat Exchanger 511
( 92 deg F / 32 deg C water inlet temperature ) - Lit / min
Raw water flow for Aftercooler Heat Exchanger 151
( 92 deg F / 32 deg C water inlet temperature )
Recommended Cooling Tower Capacity (TR) 60
Cummins has always been a pioneer in product improvement. Main Line Pipe size (mm) 50
Thus specifications may change without notice.
Illustrations may include optional equipment. Main Line Gas Pressure (kg/cm2) 1.4
Data is indicative and could vary based on gas composition and site conditions.
Data is based on typical natural gas with 970 BTU / CFT heat valve.