The following calculations estimate the hot gas layer temperature and smoke layer height in enclosure fire.
Parameters in YELLOW CELLS are Entered by the User.
Parameters in GREEN CELLS are Automatically Selected from the DROP DOWN MENU for the Material Selected.
All subsequent output values are calculated by the spreadsheet and based on values specified in the input parameters. This spreadsheet is protected
and secure to avoid errors due to a wrong entry in a cell(s). The chapter in the NUREG should be read before an analysis is made.
Project / Inspection
Title:
INPUT PARAMETERS
Fuel Spill Volume (V) 5.00 gallons 0.0189 m3
Fuel Spill Area or Dike Area (Adike) 9.00 ft2 0.836 m2
Mass Burning Rate of Fuel (m") 0.078 kg/m2-sec
Effective Heat of Combustion of Fuel (DHc,eff) 45700 kJ/kg
Fuel Density (r) 573 kg/m3
Empirical Constant (kb) 2.7 m-1
Ambient Air Temperature (Ta) 77.00 °F 25.00 °C
298.00 K
Gravitational Acceleration (g) 9.81 m/sec2
Ambient Air Density (ra) 1.18 kg/m3
Calculate
Note: Air density will automatically correct with Ambient Air Temperature (Ta) Input
451594283.xls 1 of 5 12/11/201914:23:36
CHAPTER 3: ESTIMATING BURNING CHARACTERISTICS
OF LIQUID POOL FIRE, HEAT RELEASE RATE, Version 1805.1
BURNING DURATION, AND FLAME HEIGHT (English Units)
Adike = pD2/4
Where
Adike = surface area of pool fire (m2)
D = pool fire diameter (m)
D = √(4Adike/p)
D= 1.032 m
Heat Release Rate Calculation (Liquids with relatively high flash point, like transformer oil, require
localized heating to achieve ignition)
451594283.xls 2 of 5 12/11/201914:23:37
CHAPTER 3: ESTIMATING BURNING CHARACTERISTICS
OF LIQUID POOL FIRE, HEAT RELEASE RATE, Version 1805.1
BURNING DURATION, AND FLAME HEIGHT (English Units)
tb = 4V / pD2n
Where
tb = burning duration of pool fire (sec)
V = volume of liquid (m3)
D = pool diameter (m)
n = regression rate (m/sec)
n = m"/r
Where
n = regression rate (m/sec)
m" = mass burning rate of fuel (kg/m2-sec)
r = liquid fuel density (kg/m3)
n= 0.000136 m/sec
tb = 4V/pD2n
451594283.xls 3 of 5 12/11/201914:23:37
CHAPTER 3: ESTIMATING BURNING CHARACTERISTICS
OF LIQUID POOL FIRE, HEAT RELEASE RATE, Version 1805.1
BURNING DURATION, AND FLAME HEIGHT (English Units)
METHOD OF HESKESTAD
Reference: SFPE Handbook of Fire Protection Engineering, 2nd Edition, 1995, Page 2-10.
Where
Hf = pool fire flame height (m)
Q = pool fire heat release rate (kW)
D = pool fire diameter (m)
Hf = 14.98 ft 4.57 m
METHOD OF THOMAS
Reference: SFPE Handbook of Fire Protection Engineering, 2nd Edition, 1995, Page 3-204.
Where
Hf = pool fire flame height (m)
m" = mass burning rate of fuel per unit surface area (kg/m2-sec)
ra = ambient air density (kg/m3)
D = pool fire diameter (m)
g = gravitational acceleration (m/sec2)
Hf = 13.35 ft 4.07 m
451594283.xls 4 of 5 12/11/201914:23:37
CHAPTER 3: ESTIMATING BURNING CHARACTERISTICS
OF LIQUID POOL FIRE, HEAT RELEASE RATE, Version 1805.1
BURNING DURATION, AND FLAME HEIGHT (English Units)
Summary of Results
Heat Release Rate Calculation (Liquids with relatively high flash point, like transformer oil, require
localized heating to achieve ignition)
ESTIMATING POOL FIRE RESULTS FOR RANDOM SIZE SPILLS USING INPUT PARAMETERS
Area (ft2) Area (m2) Diameter (m) Q (kW) tb (sec) Hf (ft) (Heskestad) Hf (ft) (Thomas)
1 0.09 0.34 200.32 1496.46 5.27 6.22
2 0.19 0.49 484.20 748.23 7.51 7.92
Caution! The purpose of this
3 0.28 0.60 794.58 498.82 9.15 9.11 random spill size chart is to aid
4 0.37 0.69 1117.86 374.12 10.47 10.07 the user in evaluating the hazard
5 0.46 0.77 1448.21 299.29 11.60 10.88 of random sized spills. Please
6 0.56 0.84 1782.64 249.41 12.58 11.60 note that the calculation does
7 0.65 0.91 2119.47 213.78 13.46 12.23 not take into account the
8 0.74 0.97 2457.67 187.06 14.25 12.82 viscosity or volatility of the
9 0.84 1.03 2796.63 166.27 14.98 13.35 liquid, or the absorptivity of the
10 0.93 1.09 3135.94 149.65 15.66 13.85
11 1.02 1.14 3475.34 136.04 16.29 14.32
surface. The results generated
12 1.11 1.19 3814.66 124.71 16.89 14.76 for small volume spills over
13 1.21 1.24 4153.79 115.11 17.45 15.17 large areas should be used with
14 1.30 1.29 4492.66 106.89 17.98 15.57 extreme caution.
15 1.39 1.33 4831.23 99.76 18.49 15.94
20 1.86 1.54 6519.13 74.82 20.72 17.62
25 2.32 1.72 8199.34 59.86 22.60 19.04
50 4.65 2.43 16534.81 29.93 29.39 24.23
75 6.97 2.98 24829.17 19.95 34.19 27.89
100 9.29 3.44 33113.15 14.96 38.04 30.83
NOTE:
The above calculations are based on principles developed in the Structural Design for Fire Safety, 2001. Calculations are based on certain assumptions and have inherent
limitations. The results of such calculations may or may not have reasonable predictive capabilities for a given situation and should only be interpreted by an informed user.
Although each calculation in the spreadsheet has been verified with the results of hand calculation, there is no absolute guarantee of the accuracy of these calculations. Any
questions, comments, concerns and suggestions or to report an error(s) in the spreadsheet, please send an email to David.Stroup@nrc.gov or Naeem.Iqbal@nrc.gov.
Additional Information:
451594283.xls 5 of 5 12/11/201914:23:37