Sie sind auf Seite 1von 2

Project 132/11 kV Miracle Substation Designed SSP

Contractor L&T Checked ASV


Client DEWA Approved
Title First floor Date 11.12.19

DESIGN OF CHEQUERED PLATE

Length of the plate L = 2.25 m

Width of the plate b = 0.65 m

Thickness of the plate provided t = 8 mm

Yield strength of plate Py = 275 N/mm


2

2
Live Load LL = 5 kN/m
2
Dead Load (Self weight) DL = 0.628 kN/m

Loads:

Total factored load w = 1.2 DL + 1.6 LL

= 8.75 kN/m
2
Ultimate Design Moment Mu = WL /24

= 1.85 kN-m

fy =M/Z

Thickness of the plate required t = Sqrt (6 M / fy b)

= 7.87 mm

Provided Plate Thickness = 8 mm

Hence Safe

Check for deflection

Deflection δ = 5wl4 / 384EI

= 0.339 mm

Allowable deflection d = Span / 240

= 9.38 mm > 0.339 mm

Hence Safe
Project 132/11 kV Miracle Substation Designed SSP
Contractor L&T Checked ASV
Client DEWA Approved
Title First floor Date 11.12.19

DESIGN OF CHEQUERED PLATE

Length of the plate L = 2.25 m

Width of the plate b = 0.65 m

Thickness of the plate provided t = 10 mm

Yield strength of plate Py = 275 N/mm


2

2
Live Load LL = 5 kN/m
2
Dead Load (Self weight) DL = 0.785 kN/m

Loads:

Total factored load w = 1.2 DL + 1.6 LL

= 8.94 kN/m
2
Ultimate Design Moment Mu = WL /24

= 1.89 kN-m

fy = M/Z

Thickness of the plate required t = Sqrt (6 M / f y b)

= 7.96 mm

Provided Plate Thickness = 10 mm

Hence Safe

Check for deflection

Deflection δ = 5wl4 / 384EI

= 0.179 mm

Allowable deflection d = Span / 240

= 9.38 mm > 0.179 mm

Hence Safe