Beruflich Dokumente
Kultur Dokumente
Mekelle University
Acknowledgement..........................................................................................................- 2 -
Abstract...........................................................................................................................- 3 -
Objective.........................................................................................................................- 4 -
Limitation........................................................................................................................- 5 -
1. Literature review.........................................................................................................- 6 -
2. Introduction.................................................................................................................- 7 -
3. Design of components...............................................................................................- 12 -
3.1. Design inputs:....................................................................................................- 12 -
3.2. Design considerations:.......................................................................................- 13 -
3.3. Sizing the collector.............................................................................................- 13 -
3.4. Design of fin.......................................................................................................- 15 -
3.5. Calculation for losses and use full energy..........................................................- 19 -
3.5.1. Top loss.......................................................................................................- 19 -
3.5.2. Bottom loss.................................................................................................- 21 -
3.5.3. Edge loss ....................................................................................................- 22 -
3.5.4. The total loss coefficient.............................................................................- 22 -
3.6. Design of insulation...........................................................................................- 23 -
3.7. Summary of results............................................................................................- 25 -
4. Manufacturing process..............................................................................................- 26 -
5. Economic analysis.....................................................................................................- 28 -
Conclusion....................................................................................................................- 30 -
Recommendation..........................................................................................................- 31 -
Bibliography..................................................................................................................- 32 -
Appendix.......................................................................................................................- 33 -
Acknowledgement
We would like to acknowledge our advisor Dr. Mulu Bayray for his overall support and
advice throughout the project. We would also like to thank Ato Michael for his huge
cooperation. At last our appreciation goes to DIF for the financial support.
Bekri M.
Bruck A.
Abstract
This report contains mainly a design of flat plat collector for house hold uses. It contains
a literature review about the experience solar water heating in the world and in our
country. The introduction part tries to discus briefly about different kinds of solar water
heating systems. The main part of the report which is the design of flat plate collector for
water heating contains the design of the major parts of the collector that is the design of
collector area, the fin and the calculation for the different losses. The collector is
designed to heat 150 liters of water per day assuming that it is used around Mekelle. The
report also contains manufacturing process, taking that the collector is manufactured in
Mekelle University mechanical engineering department workshop. Economic analysis is
done to show the advantage of solar water heating over water heating using electricity.
The main components of the flat plat collector are clearly shown in the assembly and
detail drawings which are included in the report.
Objective
The objective of this project is to design, manufacture and test a flat plate collector (passive,
direct type).The collector is assumed to work around Mekelle. The basic things to consider are
the cost of the collector, which has to be minimum and able to be manufactured in Mekelle
University mechanical engineering workshop.
Limitation
The lack of reference materials on solar energy or solar heating systems was a
huge problem.
The unavailability and delaines of materials like insulation (urethane foam),
copper pipe etc.
The lack of cooperation from the workshop, like not willing to give required
tools.
At last due to the above reasons the manufacturing process was not completed
because of shortage of time.
1. Literature review
The most common use of the suns energy is to provide light and warmth. How ever, there is
significant potential for providing hot water as well. Solar water heating systems have many
benefits including providing reliable hot water in times of electricity shortage, lower electricity
costs and increasing awareness of a renewable energy resource.
Solar radiation is free, non-polluting and renewable; it has significant environmental benefits
like carbon dioxide emissions from electricity generation would be reduced and as well if we are
using a biomass fuel smoke emission would be reduced.
In developed countries like USA so many researches are conducted to increase the efficiency of
SWH and to minimize the cost. Countries like Israel produce and use SWH for domestic
applications.
In our country Ethiopia “thirteen months of sun shine” solar water heaters can function well all
around the country through out the year in which the country can save its biomass wastage in
great amount. How ever, due to lack of awareness and their high costs solar water heaters are not
widely in use; but in recent years different importers involved in the business(importing SWH)
are increasing in number.
In Mekelle University project works have been conducted on solar collectors especially on solar
water heaters. Two project works have been done on solar water heaters employing heat pipes in
the past two years (2005, 2006) by graduating students, in which the last one was manufactured
and tested but failed due to some manufacturing errors.
Open and closed loop systems (direct and indirect): In an ‘open loop’ system, water from the
storage cylinder is circulated through the collector panel and heated directly. In a ‘closed loop’
system, water from the storage cylinder is circulated through a heat exchanger and heated by a
primary heat transfer fluid, which has been heated in the collector panel.
Transfer mechanism: Water or transfer fluid is circulated through the collector panel by one of
two methods:
Natural circulation (passive system): by thermo siphon heated fluid in the collector creates a
natural convection. The cool water (or transfer fluid) moves down from the storage cylinder to
the panel and the more buoyant heated fluid moves up again. With a thermo siphon system, the
storage cylinder must be positioned higher than the collector panel with the connecting pipes
sloping at a specified angle to ensure proper performance. The cylinder is normally positioned
horizontally and immediately above the collector on the roof, or concealed within the roof space.
Using a pump (forced circulation or active system): to move the water or transfer fluid
through the collector panels to the cylinder. The main advantage of a pump is that the cylinder
can be below the collectors, which is suitable for a system where a storage cylinder already
exists at floor level. The pump is used in conjunction with a control unit which ensures that the
pump runs only when the water in the collector panel is hotter than in the cylinder.
The most common type of solar collector is the flat plate (fig. 1.1) panel. This consists of a flat
sheet absorber or envelope of specially blackened metal. It absorbs the sunlight and transfers the
heat produced into the water, or the transfer fluid, flowing through the collector. The absorber is
enclosed within an insulated housing with a transparent cover. The whole enclosure, or
‘collector’, acts as a greenhouse. It reduces heat loss, enabling the collector to work at elevated
temperatures and ensures that a high percentage of the solar energy goes into the water. Another
increasingly common collector is the type which can reach very high temperatures and works
well in colder and low-sun climates. This collector typically includes heat exchanger at its higher
end and a transfer fluid, which rises in the tubes and heats the water in the heat exchanger.
Ideally a solar collector should face true north and be tilted from the horizontal at an angle
greater than 10°(some times up to-60°) . An ideal angle is equal to the latitude of where the house
is located. The collector on typical domestic solar water heating systems is between 3 and 8
square meters the actual size is related to the size of the cylinder, working to a ratio of about one
square meter of collector per 40 - 70 (some times up to 90) litters of cylinder volume.
1
WWW.solarexpert.com
Temperature:
From the metrological data of Mekelle University of 2003, the following data are obtained.
Minimum mean monthly temperature
Jan Feb Mar Apr May June July Aug Sep Oct Nov Dec
10.3 12.5 14.5 14.97 14.9 14.75 14.35 13.6 12.9 12.36 12.3 9.65
Jan Feb Mar Apr May June July Aug Sep Oct Nov Dec
25.5 27.56 27.77 27.63 27.9 28.32 23.56 24.34 26.08 24.773 24.3 23.92
Wind speed
Monthly mean wind speed in m/sec
Jan Feb Mar Apr May June July Aug Sep Oct Nov Dec
3.27 4.59 4.29 4.94 3.45 2.56 1.83 1.47 1.88 3.63 4.38 4.59
Average wind speed equals 3.61 m/sec but for design purpose therefore we take
5m/sec.
Solar intensity
Since there is no data available about solar intensity of Mekelle University we have taken a
measurement by using a pyranometera on May 6/2007, we have found the average value to be
940 W/m². Note that the solar intensity is expected to be higher in May.
From the above data the following values are taken for the design purpose.
So as discussed above in the introduction part among the different solar water heating systems
the one chosen for this design is passive and direct system.
This is because:
Passive system is cheaper since it does not employ pumps.
Since the minimum ambient temperature of Mekelle is not less than 5°c, there is no
danger of freezing, so we can use direct system.
Note:-the very first thing that has to be considered through-out this design is the cost of the
collector which has to be as minimum as possible.
A) For determining the capacity of or the volume of the cold water cylinder, for a family of
five (taking average family number in Ethiopia) the following estimation is taken.
B) For determining the over all size of the collector different parameters are considered.
The collector is assumed to work around Mekelle zone and deferent input parameters are
considered from metrological data for Mekelle. i.e.
I=800W/m2
Ta=23°c
Assumptions:
Water inlet temperature, Twi =20°c.
Water outlet temperature, Twi =60°c.
Efficiency of the collector, =30%
In different literatures and manufacturers catalogue the efficiency of a flat plate collector
lies between 45 and 60% and considering the manufacturing ability of our workshop it is
assumed to be 30 %.
Solar availability=100%
Assuming that there is an 8 hour solar availability (in average per day) the solar insolation per
day is going to be:
I=7200W/m2
The equation for determining the collector area is:
A = (load \ .I ).(% solaravailability )
Where:
A=collector area in square feet
Load=the energy per day (in Btu/day) to heat needed water to the service temperature.
h=the measure of collector’s efficiency.
I=the average solar insolation in Btu/ft2/day.
In the design of the fin the main thing that is to be tackled on is the distance between the centers
of two tubes that is optimum for effective heat transfer. Normally in solar collectors fins are used
for transferring heat to the tube, but in our case we will consider the fin in the reverse way. That
is the heat is transferred from the tube to the fin.
Note: - to get sense of the proper length of a fin, we compare heat transferred from a fin of finite
length to heat transfer from an infinitely long fin under the same conditions. The ratio of this heat
transfer is:-
.
Q fin hpkAc Tb T tanh al
= = tanh al 2 …………………… (1)
hpkAc Tb T
.
Qlongfin
Where:
hp
a=
kAc
l = length
t b = temprature of fin
t = temprature of surroundin g
h = heat transfer coeficient
Ac = area of collector
p = perimeter
k = conductivity of fin
4T 3
hr =
A) 1 1 ……. Radiative heat transfer coefficient
1
1 2
B) Since it is difficult to determine the convective heat transfer coefficient ( hc ), we have taken a
recommended value i.e. for free convection it is recommended to take in the range of 2-
25W/m²◦c and for convection of hot surface it is desirable to take hc =10W/m²◦c.Thus-
2
YUNUS A. CENGLE, “Heat Transfer a Practical Approach”, Tata McGraw-Hill Edition, NEWDELHI,
2002
hcombined =hr+hc7.2+10=17.2≈18W/m²◦c
hp
Where, a=
kAc
K= 211W/m²◦c h=18W/m²◦c
a=13.1/m
Using some calculations, the values of tanh al are evaluated for some values of l and the
results are given in the table bellow. We observed from the table that heat transfer from the fin
increases with l almost linearly first but the transfer rate starts to be constant (very small
increase) after some value of l .
L(m) tanh al
0.01 0.129
0.02 0.254
0.03 0.372
0.04 0.478
0.05 0.572
0.06 0.653
0.07 0.722
0.08 0.788
0.09 0.824
0.10 0.862
0.11 0.892
The heat transfer rate after l =0.1m is almost constant and small. Therefore we can take 0.1m as
the appropriate fin length. That is in our case the heat transfer from fin to the tube will be small
after 0.1m.
From this we can conclude that for our collector which is with an area of 3.25m², the number of
pipes needed will be 8.
C = 520 1 0.000051 2
3 4
. JOHN A.DUFFIE&WILLIAM A.BECK MAN” Solar engineering of thermal processes”, 2nd edition,
Wiley-inter science publication, USA, 1991
C p =emitance of plate=0.97
T pm
=mean plate temperature (K)
hw =wind heat transfer coefficient (W/m2°c)
And hw =5.7+3.8Vw=24.7W/m2°c
Thus f=0.437
c=515 (no unit)
In order to find the top losses and the overall lose coefficient it is necessary first to find T pm
and:-
QU
A
T pm = T fi C 1 FR
FRU L
m C p T fo T fi
.
And FR =
Ac S U L T fi Ta
Where
Assuming:-
= Effective transmittance absorbance=0.9.
F ' =0.93
.
Flow rate ( m )
. U L F ' AC
m=
U L To Ti
5
C P ln 1
S U L Ti Ta
Where
S=absorbed solar radiation per unit area. = I
The only way to find T pm is first to take a reasonable assumption and to iterate until we find a
refined value and to use this value to calculate the losses.
For the first assumption or iteration the most reasonable value of Tpm is given as
T pm
=Tfi+10, which is 30°c [2]
So, e=.288
5 6
. JOHN A.DUFFIE&WILLIAM A.BECK MAN” Solar engineering of thermal processes”, 2nd edition,
Wiley-inter science publication, USA, 1991
Ub = K / L 6
6
7 89
. JOHN A.DUFFIE&WILLIAM A.BECK MAN” Solar engineering of thermal processes”, 2nd edition,
Wiley-inter science publication, USA, 1991
8
From the second iteration, since the value of T pm is closer to the first iteration there is no need
U L =13w/m2°c.
As mentioned above the hot water tanker has six faces with capacity of 75 liters. The dimensions
of the tanker are as given below in the fig.
Material for the tanker is steel, to be painted with an antirust paint, with conductivity,
k=54W/m°c.
The minimum ambient temperature is taken to be 10°c.
Insulation thickness, L, is assumed to be 50mm.
Convictive heat transfer to the environment; hw =24.7W/m2°c.
Surface temperature of the tanker is assumed to be 60°c.
Now let’s calculate the heat loss, Eloss for 24 hour storage which is given by:-
AT
E loss = t
L 1
k hw
Where, m= w volume
= 985 .075
= 73.875kg
T =50.5°c
From this result we can see that the insulation is enough to keep the water hot with an acceptable
temperature decrease. Thus the insulation thickness assumed is acceptable, which is 50 mm.
4. Manufacturing process
The fin
The fin is produced using aluminum sheet by cutting it into the required dimensions and pressing
it along the length so that the copper tubes will fit in, to increase the heat transfer. Due to the lack
of different diameter dies we have to use the only available die, which is 10mm diameter (the out
The width of the fin (the collector) is 1.6m that is the pressed fin width. The overall width of the
fin (aluminum sheet) required is 1.65m considering the perimeter of the pressed fin. Since the
standard width of aluminum sheet is 1m, two sheet metals are used and 0.825m is used from
each sheet, this is done to increase the heat transfer as much as possible. (I.e. since the number of
tubes are eight four tubes will be in each part).The different parts of the fin are connected using
rivets which will of course reduce the efficiency of the collector in a great amount. After
assembling the parts the fin painted black to increase absorbivity of the fin (aluminum sheet).
The stand
The stands are made up of angle iron. Since the inclination of the collector is 14°, and choosing
the height in the shorter side to be 50cm, the height in the longer side will be 102cm. There is a
requirement of short support and cross support to give it strength to the stand. The frame holding
the casing is made also from angle iron. The stand is connected with the frame by simple
welding. Every connection in this part is made by welding.
Note: - the cold water tanker is assumed to be normal plastic tanker available in the market
(e.g.roto). The cold water passes from the container through the PVC pipe connected to it, which
is directly connected to the eight copper tubes. And the hot water from the copper tubes inters
into another PVC pipe which is connected to the hot water tanker. This pipe has to be properly
insulated or covered with insulation (urethane foam).
5. Economic analysis
To analyze the economic feasibility of this project we need to compare the overall cost of water
heating using electricity and flat plat collector.
Using electricity:
Energy needed to heat water from 20 o c to 60 o c can be found using the formula:
Q = mc p T
Q = 150 1478.4 20
Q = 4435200 J
When we come to the case of water heating using flat plate collector the only major cost is the
initial cost which is the cost of the flat plat collector. The table below shows the cost of the flat
plate collector according to our project.
Material Size Quantity Unit cost (birr) Total cost (birr)
Copper pipe 10mm(inside diameter) 8 30 (per meter) 510
Aluminum sheet 2m² (1mm thickness) 2 185 (2m*1m) 370
Wood 4m*.25m 1 104 104
Glass 3.65m² 2 70 (per m²) 255.5
Angle iron 0.04m*0.04m 2 100 200
Rivet 4mm diameter ½ pack 70 70
Sheet metal 2m² 1 195 (2m*1m) 195
RHS .04m 1 120 120
PVC pipe ½ inch 1 10 10
Plastic tanker 150 liter 1 150 150
Insulation 4.4m² 10 10
Black paint 400ml 5 16 80
Anti rust 1 liter 1 23 23
Cheep wood 2.5m*1.5m 2 120 240
nail ½ kg 13/kg 6.50
Total 2344
Note: - the above cost will reduce during mass production that is this cost is done for a unit
production.
From this we can see that there is at least 3000birr profit gain per year using solar water heating
(flat plat collector) over water heating using electricity, considering only electric cost.
Conclusion
These designed flat plate collectors have a capacity of heating 150 liters of water in the interval
of 8 hours. The area of the collector is found to be 3.25m2 (2m*1.6m) assuming a theoretical
efficiency of 30%. The orientation of the collector is to the true south. According to the previous
plan of this project, the aim was to design and manufacture the collector but due to lack and
delaines of materials like insulation and copper pipe the manufacturing process was not
completed thus no test is conducted. Even though there was no test conducted on the actual
efficiency of the collector, as seen from the economic analysis using flat plat collector for water
heating is very much advantageous.
Recommendations
To increase the efficiency of the collector that is to increase conduction there should be a
complete contact (should be welded) between the different parts of the fin and the copper
tube which was not achieved in the department workshop.
There must be a filter at the interns of the cold water to the collector to avoid the effect of
dust particles that could reduce the life of the collector.
The cold water tanker is preferred to be a normal plastic tanker due to ease of
manufacturing, availability and durability.
In the future the department must make sure the availability of materials and required
working tools before starting any manufacturing process.
Also an intensive test and research must be conducted in this area so as our country can
utilize its surplus solar energy.
Bibliography
2. Frank P.Incropera; David P. DeWitt, “Fundamentals of Heat and Mass Transfer”, 3rd
Ed, John Wiley and Sons, (1990)
5. J.P. HOLMAN,” Heat transfer” 8th edition, Mc graw-hill, INC., New York, 1997
7. www.amazon.com
Appendix