INSTRUCTION MANUAL
Low Noise Multi-Function High performance
Current Dynamic torque-Vector control
HiTAKE INVERTERS
HiTAKE
220V Class 2.2Kw TO 110Kw
WWW.hitake.com.tw 44 0V Cl as s 2. 2K w TO 30 0K w
CONTENT
1. RECEIVING ................................................................................................................................ 2
1.1 INSPECTION CHECKPOINTS .......................................................................................................................2
2. INSTALLATION ......................................................................................................................... 3
2.1 CHOOSING A LOCATION TO MOUNT THE INVERTER ...........................................................................3
2.2 CLEARANCES.................................................................................................................................................4
3 WIRING......................................................................................................................................... 5
3.1 CONNECTION DIAGRAM .............................................................................................................................5
3.2 WIRING THE MAIN CIRCUIT .......................................................................................................................7
3.3 WIRING THE CONTROL CIRCUIT .............................................................................................................10
3.4 WIRING INSPECTION .................................................................................................................................. 11
4 OPERATION............................................................................................................................... 12
4.1 OPERATION MODE SELECTION................................................................................................................13
4.2 TEST RUN CHECKPOINTS..........................................................................................................................13
4.3 TEST RUN ......................................................................................................................................................14
5 SETTING OPERATION CONDTIONS................................................................................... 15
5.1 DIGITAL OPERATOR KEY DESCRIPTION ................................................................................................15
5.2 DIGITAL OPERATOR COMPONENT NAMES AND FUNCTIONS...........................................................16
5.3 DIGITAL OPERATOR MODE SELECTION.................................................................................................17
5.4 CHANGING CONTROL METHOD ..............................................................................................................18
5.5 INITIATLIZE MODE .....................................................................................................................................19
5.6 PROGRAMMING MODE ..............................................................................................................................20
6 MAINTENANCE AND INSPECTION..................................................................................... 21
6.1 PERIODIC INSPECTION ..............................................................................................................................22
6.2 PARTS REPLACEMENT SCHDULE (GUIDELINES).................................................................................23
7 TROBLESHOOTING ................................................................................................................ 24
7.1 FAULT DIAGNOSIS AND CORRECTIVE ACTIONS .................................................................................24
7.2 MOTOR FAULTS AND CORRECTIVE ACTIONS ......................................................................................29
8 SPECIFICATIONS..................................................................................................................... 30
8.1 220V CLASS SPECIFICATIONS..................................................................................................................30
8.2 440V CLASS SPECIFICATIONS..................................................................................................................31
8.3 DIMENSTIONS (mm) ...................................................................................................................................32
9 CONSTANTS LIST .................................................................................................................... 33
9.1 CONSTANTS LIST .......................................................................................................................................35
1
1 RECEIVING
CAUTION
.Do not install or operate any inverter which is damaged or has
missing parts.
Failure to observe this caution may result in personal injury or
equipment damage.
This chapter describes how to verify the inverter after delivery to the user.
If any of the above checkpoints are not satisfactory, contact your HiTAKE
representative.
(2) Checking the Nameplate Data
(a) Nameplate Data
An example for types of 3-phase, A220V、L15HP、11KW 49A)
MODEL : VFC-3600-G2011
(AC220V / L15HP) F2011→ L:220V Level
SOURCE : 3PH AC220V 50/60HZ F4011→ H:440V Level
OUTPUT : 3PH AC0~230V 11KW 49A
SER.NO :
www.hitake.com.tw
2
2 INSTALLATION
CAUTION
.Lift the cabinet by the base. When moving the unit, never lift by the
front cover.
Otherwise, the main unit may be dropped causing damage to the unit.
.Mount the inverter on nonflammable material (i.e. metal).
Failure to observe this caution can result in a fire.
.When mounting units in an enclosure, install a fan or other cooling device
to keep the intake air temperature below 45℃.
Overheating may cause a fire or damage to the unit.
This chapter describes the configuration, location and space when mounting the VFC-3600.
when choosing a location for installing the VFC-3600. Make sure the inverter is protected
1.Extreme cold and heat. Use only within ambient temperature range: -10℃ to +45℃.
10.High humidity.
11.Radioactive materials.
3
2.2 CLEARANCES
Install the VFC-3600 vertically and allow sufficient clearances for effective cooling as
shown in
1. The clearances required at top/bottom and both sides are common in open chassis and
enclosed wall-mounted.
3. Ensure sufficient space for the sections at the upper and lower parts marked with * in
order to permit the flow of intake/exhaust air to/ from the inverter.
4
3 WIRING
WARNING
.Only commence wiring after verifying that the power supply is turned OFF.
Failure to observe this warning can result in an electrical shock or a fire.
.Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in an electrical shock or a fire.
.When wiring the emergency stop circuit, check the wiring thoroughly before
operation.
Failure to observe this warning can result in personal injury.
CAUTION
.Verify that the inverter rated voltage coincides with the AC power supply
voltage.
Failure to observe this caution can result in personal injury or a fire.
.Do not perform a withstand voltage test of the inverter.
It may cause semi-conductor elements to be damaged.
.To connect a braking resistor, braking resistor unit or braking unit.
Improper connection may cause a fire.
.Tighten terminal screws to the specified tightening torque.
Failure to observe this caution can result in a fire.
This chapter describes the main circuit wiring and the control circuit wiring of the VFC-3600.
5
6
3.2 WIRING THE MAIN CIRCUIT
WARNING
.Make sure to ground the ground terminal.
(Ground resistance 220V class: 100 or less, 440V Class: 10 or less)
Failure to observe this warning can result in an electrical shock or a fire.
CAUTION
.Never connect the AC main circuit power supply to output terminals
U,V and W
The inverter will be damaged and invalidate the guarantee.
(R)L1, (S)L2 and (T)L3, select one that is not affected by high frequency.
supply side. When the main circuit power supply is shut OFF in the sequence, a
side, regenerative braking does not function and the motor coasts to a stop.
.The load can be operated/stopped by opening/closing the magnetic contactor at the
primary side. However, frequent switching may cause the inverter to
malfunction.
.When using a braking resistor unit, use a sequencer to break power supply side on
overload relay trip contact. If the inverter malfunctions, the braking resistor unit
may be burned out.
7
(d) Terminal block Connection Sequence
Input power supply phases can be connected to any terminal regardless of the
order of (R)L1, (S)L2 and (T)L3 on the terminal block.
8
(d) Prohibition of Connection of Phase Advancing Capacitor or LC/RC Noise Filter
Never connect a phase advancing capacitor or LC/RC noise filter to the output
circuit.
(3) Grounding
z Ground resistance
220V class: 100Ω or less, 440V class: 10Ω or less.
z Never ground VFC-3600 in common with welding machines, motors, or other
large-current electrical equipment. Run all the ground wires in a conduit
separate from wires for large-current electrical equipment.
9
3.3 WIRING THE CONTROL CIRCUIT
The following table outlines the functions of the control circuit terminals.
Wire according to each terminal function.
(1) Functions of Control Circuit Terminals
Classifi-
cation
Terminal Signal Function Description Signal Level
FWD Forward run/stop Forward run when closed, stop when open
Sequence control
CM input common -
terminal
+15V For analog command +15 V power supply +15 V
+15 (Allowable current 20mA max.)
power supply output
-15V For analog command -15 V power supply -15 V
-15 (Allowable current 20mA max.)
Power supply output
Analog Input Signal
30VDC 5A or less
Multi-function contact output
Y1 Zero speed detection Makes at min. freq. (51-09) or less Open collector output
48V 50mA or less
Speed agree detection Makes when the freq reaches to±1Hz
Y2
fo set freq.
Open collector output common
YC -
Dry contact
EA
Contact capacity:
Fault contact output Fault when closed between terminals 18 and 20 250 VAC 5A or less
EB
(NO/NC contact) Fault when open between terminals 19 and 20 30 VDC 5A or less
EC
Frequency meter
Analog Output
MV+
output Multi-function analog monitor 1
0 to +10V/100% freq.
Signal
10
3.4 WIRING INSPECTION
After completing of installation and wiring, check for the following items. Never use
control circuit buzzer check.
Wiring is proper.
Wire clippings or screws are not left in the unit.
Screws are securely tightened.
Bare wire in the terminal does not contact other terminals.
11
4 OPERATION
WARNING
z Only turn ON the input power supply after replacing the front cover.
Do not remove the cover while current is flowing.
Failure to observe this warning can result in an electrical shock.
z When the retry function (P5-02) is selected, do not approach the inverter
or the load, since it may restart suddenly after being stopped.
(Construct machine system, so as to assure safety for personnel, even
if the inverter should restart.) Failure to observe this warning can
result in personal injury.
z Since the stop button can be disabled by a function setting, install a
separate emergency stop switch.
Failure to observe this warning can result in personal injury.
z If an alarm is reset with the operation signal ON, the inverter restarts
automatically.
Only reset the alarm after verifying that the operation signal is OFF.
Failure to observe this warning can result in personal injury.
CAUTION
z Never touch the heat sink or discharging resistor since the temperature
is very high.
Failure to observe this caution can result in harmful burns to the body.
z Since it is easy to change operation speed from low to high speed,
verify the safe working range of the motor and machine before
operation.
Failure to observe this caution can result in personal injury and
machine damage.
z Install a holding brake separately if necessary.
Failure to observe this caution can result in personal injury.
z Do not change signals during operation.
The machine or the inverter may be damaged.
z All the constants of the inverter have been preset at the factory. Do
not change the settings unnecessarily.
The inverter may be damaged. For supply voltage, follow Par. 4.3.
13
4.3 TEST RUN
(1) Digital operator Display at Power-up
When the system is ready for operation, turn ON the power supply. Verify that the
inverter power up properly. If any problems are found, turn OFF the power supply
immediately. The digital operator display illuminates as shown below when turning
The diagram below shows a typical operation pattern using the digital operator .
5 6 7
1 2 3 4 forward
15Hz
ON Reverse
Forward Jog Run Frequency Set Frequency Reference Change
60Hz
14
5 SETING OPERATION CONDITIONS
5.1 DIGITAL OPERATOR KEY DESCRIPTION
FREQ COMMAND
M1-01= 000.00 HZ Dispiay Section﹕ Frequency reference
VFC-3600 CONTROL PANEL corresponding to anaiog reference value
RESET
PRG PANEL
ESC REMOTE
REV-FWD
RUN STOP
JOG
Output frequency
RUN
STOP STOP
Frequency set
JOG
JOG Not Lit Lit Not Lit Not Lit Not Lit
15
5.2 DIGITAL OPERATOR COMPONENT NAMES AND FUNCTIONS
PRG PRG=Prgram key。 * HITAKE MENU * displays the menu for mode
FUNCTION:PUSE PANEL<->REMOTE。
REMOTE.
JOG JOG JOG :Jog run is enabled while depressing this key、JOG Lit
16
5.3 DIGITAL OPERATOR MODE SELECTION
The digital operator of the VFC-3600 has the following four modes.
Mode Description
Inverter operation is enabled. Display monitor value,
RUN/STATUS
fault trace or faults that occurred previously.
Sets and reads language displayed on the digital
INIT-SET operator, level to set/ read constants and control
method.
PROGRAM-SET Sets/reads constants.
Sets/reads constants changed from the values preset at
SET--LIST
the factory.
Depressing the [MENU] key displays “Operation.” Change the mode display by
using [UP] or [DOW] key and select a mode by the [DATA/ENTER] key. The
【HITAKE MENU】→【RUN/STATUS】→【INIT-SET】→【PROGRAM-SET】
→【EASY-TUNING】→【SET-LIST】→【HITAKE MENU】。
The mode can be changed even during operation. Even if the mode is changed to the
operation. The inverter does not operate even if the run command is input, when the
17
5.4 Changing Control Method:
The control method is changed from OPEN LOOP VECTOR to FLUX VECTOR。
Description Key Sequence Digital Operator Display
FREQ COMMAND
.Display Frequency reference
M1-01=60.00HZ
PRG
.Display Operation
* HITAKE MENU *
RUN/STATUS
.Select Initialize
FACTORY ID:1234567
VFC1604-0K-05-G19
ADVANCED LEVEL
FLUX VECTOR
Puse『PRG』2Sec
* HITAKE MENU * Enter
FREQ COMMAND
18
5.5 INITIALIZE MODE
As described below, the language displayed on the digital operator, the access level to
set/read constants or control method (V/f control, vector control) can be selected.
Make sure to set this mode before use of the VFC-3600. the following table shows
Initialize Mode
Digital Operator
Constant No. Name Description
Display
11-00 FACTORY ID:
0: Exclusive for monitoring
1: Constants for user selection
(constants to be Set/read can be programmed by
operator)
Access level 2: QUICK-START
11-01 ACCESS LEVEL (change enable during run) (Constants required for test run are set/read.)
3: BASIC
(Normally-used constants are set/read.)
4: ADVANCED
(All constants are set/read.)
0: V/f control
1: V/f control with PG feedback
11-02 CONTROL METHOD Control method selection 2: Open loop vector
3: Flux vector
0 : No Initialization
1110 : Initialization of user setting
11-03 INIT PARAMETERS Reset to factory defaults. 2220 : 2-wire initialization
3330 : 3-wire initialization
11-04 ENTER PASSWORD Password Password setting
19
5.6 PROGRAMMING MODE
The constants of the VFC-3600 are composed of group symbols, function Nos. and
serial Nos. for each function item as shown below. Use UP or DOWN key to change
the group, function or name display and select one by [ENTER] key. For details of
Constant NO.
2-Application-related constants
Function No.
3-Accel/decel time setting constants
Group symbol
4-Frequency reference-related constants
5-Motor-related constants
6-Option-related constants
T-Control circuit terminal-related
constants
P-Protection-related constants
O-Operator-related constants
According to access level (11-01) setting, there are four ways to set and read constants
as described below.
Constant Access Level
20
6 MAINTENANCE AND INSPECTION
WARNING
z Never touch high-voltage terminals in the inverter.
Failure to observe this warning can result in an electrical shock.
z Replace all protective covers before powering up the inverter. To remove
the cover, make sure to shut OFF the molded-case circuit breaker.
Failure to observe this warning can result in an electrical shock.
z Perform maintenance or inspection only after verifying that the CHARGE
LED goes OFF, after the main circuit power supply is turned OFF.
The capacitors are still charged and can be dangerous.
z Only authorized personnel should be permitted to perform maintenance,
inspections or parts replacement.
[Remove all metal objects (watches, bracelets, etc.) before operation.]
(Use tools which are insulated against electrical shock.)
Failure to observe this warning can result in an electrical shock.
CAUTION
z The control PC board employs CMOS ICs. Do not touch the CMOS
elements.
They are easily damaged by static electricity.
z Do not connect or disconnect wires or connectors while power is applied to
the circuit.
Failure to observe this caution can result in personal injury.
This chapter describes basic maintenance and inspection procedures for the VFC-3600.
21
6.1 PRIODIC INSPECTION
The VFC-3600 will function longer if it is kept clean, cool and dry, while observing
the precautions listed in Par. 2.3. Check for tightness of electrical connections,
discoloration or other signs of overheating or aging. Use Table 20 as your inspection
guide. Before servicing, turn OFF AC main circuit power and be sure that the
CHAARGE LED is OFF.
Periodic Inspection
Component Check Corrective Action
External Terminals, Unit Loose screws Tighten.
Mounting Bolts, Connectors, etc. Loose connectors Tighten.
Blow with dry compressed air of
4 4
Heatsink Build-up of dust and dirt 39.2×10 to 58.8×10 Pa (4 to
2
6kg.com ) pressure.
Blow with dry compressed air of
4 4
Accumulation of conductive dust or 39.2×10 to 58.8×10 Pa (4 to
Printed Circuit Board oil
2
6kg.com ) pressure. If dust and oil
cannot be removed, replace the board.
For abnormal noise and vibration.
Cooling Fan Whether the cumulative operation Replace the cooling fan.
time exceeds 20,000 hours or not.
Blow with dry compressed air of
Power Elements Accumulation of dust and dirt 39.2×104 to 58.8×104 Pa (4 to
6kg.com2) pressure.
Smoothing capacitor Discoloration or odor Replace the capacitor or inverter unit.
22
6.2 PARTS REPLACEMENT SCHEDULE (GUIDELINES)
Replace the following parts periodically, for a long, safe, trouble free working life of
VFC-3600.
23
7 TROUBLESHOOTING
This chapter describes the inverter fault display and the fault contents caused by motor/
machine malfunctions and the corrective actions to be taken.
operator and activates the fault contact output and the motor coasts to a stop. Check
the cause in the table below and take the corrective actions.
(2) If the inspections or corrective actions described cannot solve the problem,
(3) To restart, turn ON the reset input signal or depress [>] [RESET] key or shut OFF
the main circuit power supply once, to reset the stop status.
24
Fault Diagnosis and Corrective Actions
Rank*
Fault Display Description Details Corrective Action (Standard
Value)
Undervoltage in the direct current main circuit
during running.
UV1 Main circuit
Detection level A
DC Bus Undervolt undervoltage (PUV)
220V class: Approx. 190V or less z Check the power supply
440V class: Approx. 380V or less wiring.
UV2 Control circuit z Correct the line voltage .
Undervoltage in the control circuit during running. A
DC Bus Undervolt Undervoltage (CUV)
UV3
MC fault The pre-charge contactor opened during running. A
DC Bus Undervolt
z The main circuit direct current voltage fell below
the PUV level.
UV
Momentary power loss z The control power source fell below the CUV - B
Under Voltage level.
z The pre-charge contactor opened.
z Check the motor coil
resistance.
OC
Overcurrent (OC) The inverter output current exceeded the OC level z Extend the accel/decel time. A
Overcurrent z Check the motor insulation.
z Multi-meter check
z Check that motor insulation
has not deteriorated.
GF Grounding (GF) Inverter output grouding current exceeded 50% of
z Check that connection A
Ground Fault (Earth fault) inverter rated current.
between inverter and motor is
not damaged.
The main circuit direct current voltage exceeded
the OV level.
OV Extend the deceleration time,
Overvoltage (OV) Detection level A
Overvoltage 220V class: Approx. 440V
add braking circuit.
440V class: Approx. 880V
z Check the motor coil
SC
Load short-circuit (SC) Inverter output (load) is short-circuited. resistance. A
Short Circuit z Check the motor insulation.
Check for damaged transistor,
PUF z The direct current circuit fuse is blown.
Fuse blown (FU) load side short circuit, A
DC Bus Fuse Open z The output transistors were damaged.
grounding, etc.
OH Heatsink overheat The transistor heatsink temperature exceeded the Check the fan an ambient
A
Heatsink Over tmp (OH1) allowable value. temperature.
O L1
Motor overload (OL1) Inverter output exceeded the motor overload level. Reduce the load. A
Motor overloaded
O L2 Inverter output exceeded the inverter overload Reduce the load, extend the
Inverter overload(OL2) A
Inv Overloaded level. acceleration time.
z Check the line voltage.
PF z Inverter input power supply has open-phase.
Input open-phase z Re-tighten the input terminal A
Input Pha Loss z Large unbalance in input voltage.
screws.
z Check the output wiring.
LF z Check the motor impedance.
Output open-phase z Inverter output has open-phase. A
Output Pha Loss z Re-tighten the output
terminal screws.
25
Fault Diagnosis and Corrective Actions (Cont’d)
Rank*
Fault Display Description Details Corrective Action (Standard
Value)
RR Braking transistor Replace the inverter
failure The braking transistor has failed A
Dyn Brk Transistor
The braking resistor unit temperature has Reduce the regenerative load.
RH Braking resistor unit
exceeded the allowable value. (Protects only A
Dyn Brk Resistor overheat
inverter built-in type)
OS
Overspeed (OS) The motor speed exceeded the overspeed _ A
Overspeed
z Check the PG line.
PGO
PG open circuit (PGO) The PG line is broken. Check the condition of the A
PG Open motor lock or the load.
DEV The deviation of the speed reference and speed
Speed deviation (DEV) Check the load. B
Speed Deviation feedback exceeded the regulation level..
EF Operation reference Both FWD and REV run commands were closed
Check sequence circuit. B
External Fault fault (External) for 500ms or more.
EF3 External fault at
A
External Fault 3 terminal EF
EF4 External fault at
B
External Fault 4 terminal RST
EF5 External fault at Check the condition of the input
terminal . B
External Fault 5 terminal MS1
Fault occurred in the external control circuit. If the LED lights when terminal
EF6 External fault at is not connected, replace the B
External Fault 6 terminal MS2 inverter.
EF7 External fault at
B
External Fault 7 terminal JOG
EF8 External fault at
B
External Fault 8 terminal BX
OPE01
kVA selection fault kVA selection fault Check and set the constant data. C
kVA Selection
OPE02 Constant setting range
Constant data is out of range. Check the constant data settings. C
Limit fault (OPE02)
z In T1-01 to T1-06 settings:
zThe same values are set except for F, FF
and 20 to 2F.
zBoth UP/DOWN and HOLD commands
are set.
zUP and DOWN commands are not set at
the same time.
zTwo or more HOLD,UP/DOWN,
Multi-function contact
O P E 03 sample/hold commands are set.
input selection fault Check the constants. C
Terminal zTwo or more external baseblock and
(OPE03)
speed search FWD REV EF commands
are set.
zIn 25-01 setting, both PID control and
UP/DOWN commands are set.
zIn T3-09 setting terminal FIV/FIC
selection and the value other than “Not
used” are set at the same time.
26
Fault diagnosis and Corrective Actins (Cont’d)
Rank*
Fault Display Description Details Corrective Action (Standard
Value)
z In 21-01 setting, C-option is not
connected although frequency
Option reference
OPE05 reference from C-option is selected.
Selection fault Check the constants C
Sequence Select z In 21-02 setting, C-option is not
(OPE05)
connected although run command from
C-option is selected.
In 11-02 setting,
Control method z Pg is not connected although V/f
OPE06
selection fault control with PG feedback is selected. Check the constants. C
PG Opt Missing
(OPE06) is not connected although flux
vector control is selected.
z In T3-05 and T3-09 setting, the same
Multi-function
values are set except for 0 and 1F.
OPE07 analog
z While is connected, “0” is set in Check the constants. C
Analog Selection input selection fault
and option/inverter selection is set in
(OPE07)
multi-function contact input.
When the settings of E1-04 to E1-10 do not
satisfy the following conditions:
OPE10 V/f data setting fault
z F Max.≧FA>FB≧F Min. Check the constants. C
V/f (51-04 to 51-10)
(51-04)(51-07)(51-09)
27
Fault diagnosis and corrective actions (Cont’d)
Rank*
Fault Display Description Details Corrective Action (Standard
Value)
C PF02 Baseblock circuit fault
A
BB Circuit Err (CPF02)
Rank A: Major fault (Motor coasts to a stop, operator indication lights, and FAULT
contact is output.)
Rank B: Fault [Operation continues, operator indication blinks, no FAULT contact is
output, and minor fault contact is output (when multi-function output is
selected.)
Rank C: Warning (Operation cannot be performed, operator indication lights, no
FAULT contact is output, no minor fault contact is output.)
28
7.2 MOTOR FAULTS AND CORRECTIVE ACTIONS
(1) If any of the following faults occurs in the motor, check the cause and provide the
relevant corrective action.
(2) If these inspections and corrective actions cannot solve the problem, contact your
RICH ELECTRIC representative immediately.
29
8 SPECIFICATIONS
8.1 220V Class Specifications
SERIAL VFC-3600
Inverter Model HP L003 L005 L07.5 L010 L015 L020 L025 L030 L040 L050 L060 L075 L100 L120 L150
Max. Applicable
KW 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110
Characteristic
Motor output
Output
Allowable Voltage
+10~-15﹪
Fluctuation
Allowable Frequency
±5﹪
Fluctuation
Control Method PWM, Electric Current Torque Vector Control,V/F Control,PG etc Control Mode
Speed Control Accuracy ±0.2 ﹪, 【±0.01﹪=PG】
Speed Control Range 1:100 , 【1:1000 =PG】
Speed Response 5Hz, 【30Hz =PG】
Starting Torque 150﹪/0.3HZ-200﹪/0.5Hz, 【200﹪/0Hz =PG】
Torque Response 20Hz,50ms, 【40Hz,25ms =PG】
Torque Limit control mode set
Control Characteristics
Overload Motor coasts to a stop after 1 minute at 150﹪of rated output current.
Overload Voltage Motor coasts to a stop if converter output voltage exceeds DC 410V
Under Voltage Motor coasts to a stop if converter output voltage drop to DC 190V
Heatsink Overheat Protected by thermistor
Immediately stop by 15ms and above momentary power loss. (Factory setting)
Momentary Power Loss
Continuous operation during power loss less than 2secis equipped as standard.
Stall Prevention Stall prevention during accel/decel and constant speed operation
Ground Fault Protected by electronic circuit (Overcurrent level)
Power Charge Indication Charge LED stays ON Until bus voltage drops below 50V.
Ambient Temperature -10℃~+50℃
Environment
30
8.2 440V Class Specifications
SERIAL VFC-3600
Inverter Model HP H3 H5 H7.5 H10 H15 H20 H25 H30 H40 H50 H60 H75 H100 H150 H200 H250 H300 H400
Max. Applicable
KW 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 110 160 185 220 300
Characteristics
Motor output
Output
Inverter Capacity KVA 4.7 6.1 11 14 21 26 31 37 50 61 73 98 130 170 230 260 340 460
Rated output Current A 6.2 8 14 18 27 34 41 48 65 80 96 128 165 224 302 340 450 605
Max. Output Voltage V 3-Phase, 380/415/440/460V/480V(Proportional to input voltage)
Rated Output Frequency Up to 400Hz available by programming
Rated Input Voltage and
3-Phase 380~480V、50Hz/60Hz
Frequency
Supply
Power
Allowable Voltage
+10~-15﹪
Fluctuation
Allowable Frequency
±5﹪
Fluctuation
Control Method PWM, Electric Current Torque Vector Control,V/F Control,PG etc Control Mode
Speed Control Accuracy ±0.2 ﹪, 【±0.01﹪=PG】
Speed Control Range 1:100 , 【1:1000 =PG】
Speed Response 5Hz,0.2s, 【30Hz,33ms =PG】
Starting Torque 200﹪/0.5Hz, 【200﹪/0Hz =PG】
Torque Response 20Hz,50ms, 【40Hz,25ms =PG】
Torque Limit control mode set
Control Characteristics
Overload Motor coasts to a stop after 1 minute at 150﹪of rated output current.
Overload Voltage Motor coasts to a stop if converter output voltage exceeds DC 820V
Under Voltage Motor coasts to a stop if converter output voltage drop to DC 380V
Heatsink Overheat Protected by thermistor
Immediately stop by 15ms and above momentary power loss. (Factory setting)
Momentary Power Loss
Continuous operation during power loss less than 2secis equipped as standard.
Stall Prevention Stall prevention during accel/decel and constant speed operation
Ground Fault Protected by electronic circuit (Overcurrent level)
Power Charge Indication Charge LED stays ON Until bus voltage drops below 50V.
Ambient Temperature -10℃~+50℃
Environment
31
32
9. CONSTANTS LIST
Monitor Constants List
Digital
Operator Constant Digital Operator Out signal
Constant Name Unit Data Selection
Function No. Display Levels
Display
Frequency 10V/ Max
M1-01 FREQ COMMAND
reference
0.01HZ frequency
10V/ Max
M1-02 OUTPUT FREQ Output frequency 0.01HZ frequency
10V/
M1-03 OUTPUT CURRENT Output current 0.1A Rated current
1:Terminal FWD〝ON〞
1:Terminal REV〝ON〞
1:Terminal EF〝ON〞
M1-10 -- 1:Terminal RST〝ON〞 --
INPUT TERM STS Input terminal 1:Terminal MS1〝ON〞
status 1:Terminal MS2〝ON〞
1:Terminal JOG〝ON〞
1:Terminal BX〝ON〞
0 0 0 0 0 0 0 0
1:Terminal RA-RC〝ON〞
1:Terminal Y1〝ON〞
1:Terminal Y2〝ON〞
0:Not used
M1-11 -- 0:Not used --
OUTPUT TERM STS Output terminal 0:Not used
status 0:Not used
1:Terminal RC-RB-RA
0 0 0 0 0 0 0 0
1:Running
1:Zero-speed level
1:reverse
M1-12 -- 1:Reset input ON --
INT CT1 STS 1 Internal control 1:F./out agree
status 1:Inverter ready
1:Minor fault detected
1:Major fault detected
Cumulative
M1-13 ELAPSED TIME
operation time
1hour --
M1-14 SOFT VER: SOFT VER -- --
33
Monitor Constants List
Digital
Operator Digital Operator Out signal
Constant No. Constant Name Unit Data Selection
Function Display Levels
Display
Terminal FIV
TERM FIV LEVEL 0.1﹪ 10V/100﹪
voltage level
Terminal FIC
M1-16 TERM FIC LEVEL 0.1﹪ 10V/100﹪
voltage level
Terminal MFI
M1-17 TERM MFI LEVEL 0.1﹪ 10V/100﹪
voltage level
Motor secondary 10V/
M1-18 MOT SEC CURRENT 0.1﹪
Current Rated current
Motor exciting 10V/
M1-19 MOT EXC CURRENT 0.1﹪ Rated current
current
Output frequency 10V/ Max
M1-20 SFS OUTPUT
after soft-start
0.01HZ frequency
10V/ Max
M1-21 ASR INPUT ASR input 0.01﹪ frequency
10V/ Rated
M1-22 ASR OUTPUT ASR output 0.01﹪ frequency
10V/ Max
M1-23 SPEED DEVIATION Speed deviation 0.01﹪ frequency
PID feedback
M1-24 PID FEEDBACK 0.01﹪ --
value
DI-16H input
M1-25 DI-16 REFERENCE
status
-- --
DC bus voltage at
M2-08 DC BUS VOLTAGE
fault
1V --
Output power at
M2-09 OUTPUT KWATTS
fault
0.1KW --
34
Monitor constants List
Digital
Constant Digital Operator Out signal
Operator No. Display
Constant Name Unit Data Selection
Levels
Display
Input terminal --
M2-11 INPUT TERM STS
status
-- M1-10
Output terminal --
M2-12 OUTPUT TERM STS
status at fault
-- M1-11
Operation status at --
M2-13 INVERTER STATUS
fault
-- M1-12
Cumulative --
M2-14 ELAPSED TIME operation time at 1hour
fault
M3-01 LAST FAULT Last fault -- --
Second most
M3-02 FAULT MESSAGE 2
recent fault
-- --
Fault Third most recent --
M3-03 FAULT MESSAGE 3
fault
--
History
M3-04 FAULT MESSAGE 4 Fourth/Oldest fault -- --
Cumulative --
M3-05 ELAPSED TIME 1 operation time at 1hour
fault
Accumulated time --
M3-06 ELAPSED TIME 2
of second fault
1hour
Accumulated time --
M3-07 ELAPSED TIME 3
of third fault
1hour
Accumulated time --
M3-08 ELAPSED TIME 4 of fourth/oldest 1hour
fault
35
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
22-01 DCLNJ START FREQ DCinj Zero speed 0.0~10.0 0.1HZ 0.5 Dcinj Zero speed level Cannot
DC injection
22-02 DCLNJ CURRENT DCinj current 0~100 1﹪ 50 DCinj braking current Cannot
22-03 DCLNJ TIME @START DCinj time Start 0.00~10.0 0.01sec 0.00 DCinj braking T-Start Cannot
22-04 DCLNJ TIME @STOP DCinj time Stop 0.00~10.0 0.01sec 0.50 DCinj braking T-Stop Cannot
36
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
23-01 SPDSRCH AT START Speed search 0,1 1 0 0:Start speed Disabled Cannot
Speed search
23-02 SPDSRCH CURRENT search Current 0~200 1﹪ 150 Speed search Current Cannot
23-03 SPDSRCH DEC TIME Deceleration timer 0.1~10.0 0.1sec 2.0 Speed Search Cannot
deceleration time
24-01 DELAY-ON TIMER ON DELAY timer 0.0~300.0 0.1sec 0.0 Timer Function On delay Cannot
Timer
24-02 DELAY-OFF TIMER OFF DELAY timer 0.0~300.0 0.1sec 0.0 Timer Function OFF delay Cannot
25-01 PID MODE PID control mode 0,1,2 1 0 0:PID Disabled Cannot
1:PID Enabled
selection 2:PID Enabled
25-02 PID GAIN Proportional gain (P) 0.00~10.00 0.01 1.00 Proportional gain (P) Can
25-03 PID I TIME Integral (I) time 0.0~360.0 0.1sec 1.0 Can
PID Control
25-04 PID I LIMIT Integral (I) limit 0.0~100.0 0.1﹪ 100.0 Can
25-05 PID D TIME Differential (D) 0.00~10.0 0.01sec 0.00 Differential (D) time Can
adjustment 100.0
25-08 PID DELAY TIME PID primary delay 0.00~-100.0 0.01sec 0.00 Can
time constant
26-01 DWELL REF @ START Dwell frequency at 0.0~400.0 0.1HZ 0.0 Cannot
start
Dwell Functions
26-02 DWELL TIME @ STOP Dwell time at 0.0~10.0 0.1sec 0.0 Cannot
start
26-03 DWELL REF @ STOP Dwell frequency at 0.0~400.0 0.1HZ 0.0 Cannot
stop
26-04 DWELL TIME @ STOP Dwell time at 0.0~400.0 0.1sec 0.0 Cannot
stop
27-01 DROOP QUANTITY Droop control gain 0.00~100.0 0.01 0.0 Can
Droop Control
27-02 DROOP DELAY TIME Droop control 0.03~2.00 0.03sec 0.05 Can
Delay time
gain
28-02 ENERGY SAVE FREQ Energy saving 0.0~400.0 0.1HZ 0.0 Cannot
frequency
37
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
completion width
31-09 FAST STOP TIME Emergency stop 0.0~6000.0 0.1sec 10.0 Emergency stop time Cannot
31-11 ACC/DEC SW FREQ Accel/Decel time 0.0~400.0 0.1HZ 0.0 Accel/Decel time Cannot
32-01 SCRV ACC @ START S-curve charac 0.00~2.50 0.01sec 0.20 Cannot
Autotuning
32-02 SCRV ACC @ END S-curve charac 0.00~2.50 0.01sec 0.20 Cannot
32-03 SCRV EDC @ START S-curve charac 0.00~2.50 0.01sec 0.20 Cannot
32-04 SCRV EDC @ END S-curve charac 0.00~2.50 0.01sec 0.20 Cannot
33-01 SLIP COMP GAIN Slip comp gain 0.00~2.50 0.01 1.0 Slip compensation gain Can
Motor Slip Compensation
33-02 SLIP COMP TIME Slip compensation 0~1000 1ms 200 Cannot
33-03 SLIP COMP LIMIT Slip comp limit 0~250 1﹪ 200 Slip compensation limit Cannot
34-01 TORQ COMP GAIN Torque gain 0.00~2.5 0.01 1.00 Can
Torque
38
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
35-01 ASR P GAIN 1 ASR gain 1 0.00~300.0 0.01 20.00 ASR proportional gain Can
35-02 ASR I TIME 1 ASR integral time 0.000~ 0.001 0.500 Can
1 10.000 sec
Speed Control ASR
35-03 ASR P GAIN 2 ASR gain 2 0.00~300.0 0.01 20.00 ASR proportional gain Can
35-04 ASR I TIME 2 ASR integral time 0.000~ 0.001 0.500 Can
2 10.000 sec
35-05 ASR LIMIT ASR limit 0.0~20.0 0.1﹪ 5.0 Cannot
35-06 ASR DELAY TIME ASR primary 0.000~0.500 0.001 0.004 Cannot
dealy time sec
35-07 ASR GAIN SW FREQ ASR switching 0.0~400.0 0.01HZ 0.0 ASR switching freq Cannot
Autotuning
36-01 CARRIER FREQ MAX Carrier up limit 0.4~15.0 0.1KHZ 15.0 FIXED Cannot
Carrier Freq
36-01~02 setting
36-02 CARRIER FREQ MIN Carrier lower limit 0.4~15.0 0.1KHZ 15.0 2.0~15.0 Cannot
selection 1:Enabled
37-02 HNUT PREV GAIN Hunting gain 0.00~2.50 0.01 1.00 Cannot
38-30 CURRIER IN TUNE Carrier freq selection 0,1,2 0 2 0:Carrier set 2.0kHZ Can
1:Carrier 36-01 setting
during autotuing 2:Carrier set 5.0kHZ
41-01 REFERENCE 1 Freq reference 1 0.0~400.00 0.1HZ 0.00 Frequency reference 1 Can
41-02 REFERENCE 2 Freq reference 2 0.0~400.00 0.1HZ 0.00 Frequency reference 2 Can
41-03 REFERENCE 3 Freq reference 3 0.0~400.00 0.1HZ 0.00 Frequency reference 3 Can
Preset Reference
41-04 REFERENCE 4 Freq reference 4 0.0~400.00 0.1HZ 0.00 Frequency reference 4 Can
41-05 REFERENCE 5 Freq reference 5 0.0~400.00 0.1HZ 0.00 Frequency reference 5 Can
41-06 REFERENCE 6 Freq reference 6 0.0~400.00 0.1HZ 0.00 Frequency reference 6 Can
41-07 REFERENCE 7 Freq reference 7 0.0~400.00 0.1HZ 0.00 Frequency reference 7 Can
Reference Constants
41-08 REFERENCE 8 Freq reference 8 0.0~400.00 0.1HZ 0.00 Frequency reference 8 Can
41-09 JOG REFERENCE Jog reference 0.0~400.00 0.1HZ 6.00 Jog Frequency reference Can
42-01 REF UPPER LIMIT Reference upper limit 0.0~110.0 0.1﹪ 100﹪ Cannot
Reference
Limits
42-02 REF LOWER LIMIT Reference lower limit 0.0~110.0 0.1﹪ 0.0﹪ Cannot
43-04 JUMP BANDWIDTH Jump freq width 0.0~20.0 0.1HZ 1.0 Cannot
39
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
45-01 TORQ CONTROL SEL Torque selection 0,.1 1 0 0:Speed control 35-01~07 Cannot
1:Torque control
45-02 TORQUE REF FILTER Torque reference 0~1000 1msec 0 Cannot
Torque Control
delay time
45-03 SPEED LIMIT SEL Speed limit selection 1,.2 1 1 1:Anaiog input Cannot
2:Limited 45-04 constant
45-04 SPEED LMT VALUE Speed limit -120~+120 0﹪ 0 Cannot
51-07 MID FREQUENCY A Mid output freq A 0.0~400.0 0.1HZ 3.0 Cannot
51-08 MID VOLTAGE A Mid output freq 0.0~255.0 0.1V 11.0 Cnanot
voltage A
51-09 MIN FREQUENCY Min. output freq 0.0~400.0 0.1HZ 0.5 Cannot
51-10 MIN VOLTAGE Min. output freq 0.0~255.0 0.1V 2.0 Cannit
voltage
51-11 MIN FREQUENCY B Mid output freq B 0.0~400.0 0.1HE 0.0 Cannot
51-12 MID VOLTAGE B Mid output freq 0.0~255.0 0.1V 0.0 Cannot
voltage B
51-13 BASE VOLTAGE Base voltage 0.01~255.0 0.1V 0.0 Cannot
52-01 MOTOR RATED FLA Motor rated current 0.01~1500.0 0.1A 1.90 Cannot
52-02 MOTOR RATED SLIP Motor rated slip 0.00~20.00 0.01HZ 2.9 Cannot
52-05 TERM RESISTANCE Line resistance 0.00~65.000 0.001Ω 9.842 Motor line-to line resistance Cannot
0:V/F CONTROL
Motor 2 control 1:V/F WITH PG
2Method
Motor
40
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
54-01 V/F2 MAX FREQ Max. output 50.0~ 0.1HZ 60.0 Cannot
frequency 2 400.0
54-02 V/F2 MAX VOLTAGE Max. voltage 2 0.0~255.0 0.1V 200.0 Cannot
54-03 V/F2 BASE FREQ Max. viltage 0.0~400.0 0.1HZ 60.0 Cannot
V/F Pattern 2
frequency 2
5404 V/F2 MID FREQ Max. mid 0.0~400.0 0.1HZ 3.0 11-03 Cannot
frequency 2
Motor Constant Constants
5405 V/F2 MIN VOLTAGE Max. mid 0.0~255.0 0.1V 10.0 11-03 Cannot
frequency voltage2
5406 V/F2 MID FREQ Max. min 0.0~400.0 0.1HZ 0.5 11-03 Cannot
frequency 2
54-07 V/F2 MIN VOLTAGE Max. min 0.0~255.0 0.1V 1.7 11-03 Cannot
frequency voltage2
55-01 MOTOR 2 RATED FLA 2 rated current 0.00~ 0.1A 1.90 Cannot
1500.0
55-02 MOTOR 2 SLIP FREQ 2 rated slip 0.00~ 0.01HZ 2.90 Cannot
Motor 2 Setup
20.00
55-03 MOTOR 2 NO-LOAD 1 2 no-load current 0.00~ 0.01A 1.20 Cannot
1500.0
55-04 MOTOR 2 # POLES 2 number of poles 2~48 1pole 4 Cannot
61-14 PGO DETECTION PGO oper circuit 0.0~10.0 0.1 2.0 Cannot
Detection time
41
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
MS2
T3-01 TERM FIV SIGNAL Signal level FIV 0,1 0 0 0:0~+10V Input Cannot
1:-10V~+10V Input
T3-02 TERMINAL FIV GAIN Gain FIV 0.0~ 0.1﹪ 100.0 Can
1000.0
T3-03 TERMINAL FIV BIAS Bias FIV -100.0~ 0.1﹪ 0.0 Can
+100.0
T3-04 TERM MFI SEL Signal level MFI 0,1 1 0 0:0~+10V Input Cannot
1:-10V~+10V Input
T3-05 TERMINAL MFI SEL Mulit-function 0~1F 1 0 Cannot
analog input MFI
T3-06 TERMINAL MFI GAIN Gain MFI 0.0~ 0.1﹪ 100.0 Can
1000.0
T3-07 TERMINAL MFI BIAS Bias MFI -100.0~ 0.1﹪ 0.0 Can
+100.0
T3-08 TERM FIC SIGNAL Signal level FIC 0,1,2 1 2 0:0~+10V Cannot
1:-10V~+10V
2:4~20mA
T3-09 TERMINAL FIC SEL Mulit-function 0~1F 1 1F Cannot
analog input FIC
T3-10 TERMINAL FIC GAIN Gain FIC 0.0~1000.0 0.1﹪ 100.0 Can
T3-11 TERMINAL FIC BIAS Bias FIC -100.0~ 0.1﹪ 0.0 Can
+100.0
T3-12 FILTER AVG TIME Analog input filter 0.00~2.00 0.01sec 0.00 Cannot
time constant
42
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
opuput
T4-04 TERMINAL MA+ SEL Monito MA+ 1~31 1 3 Cannot
selection
T4-05 TERMINAL MA+ GAIN Gain MA+ 0.0~2.50 0.01 0.50 Can
opuput
T4-06 TERMINAL MA+ BIAS Bias MA+ -10.0~+10.0 0.1﹪ 0.0 Can
opuput
T4-07 AO LEVEL SELECT Analog output signal 0,1 1 0 0:0~+10V Cannot
level selection 1:-10V~+10V
Terminal Constants
address
P1-02 MOL TIME CONST Protection time 0.1~5.0 0.1 1.0 Cannot
P2-04 PWRL V/F RAMP T Voltage recovery time 0.0~2.0 0.1sec 0.3*2 *2 Cannot
Power Loss
P2-05 PUV DET LEVEL Undervoltage 150~210 1V 190*3 *3:440V setup Cannot
220 *2
P2-06 KEB FREQUENCY Deceleration rate 0.0~100.0 0.1 0.0 Cannot
43
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
P4-01 SPD AGREE LEVEL Detection levrl 0.0~400.0 0.1HZ 0.0 Cannot
Reference Detection
P4-02 SPD AGREE WIDTH Detection width 0.0~20.0 0.1HZ 2.0 Cannot
P4-03 SPD AGREE LVL + - Detection levrl 0.0~±400.0 0.1HZ 0.0 Cannot
(+/-)
Protection Constants
P4-04 SPD AGREE WDTH +- Detection width 0.0~20.0 0.1HZ 2.0 Cannot
(+/-)
P4-05 REF LOSS SEL Operstion frequency 0,1 1 0 0:Stop Cannot
reference is missing 1:operation 80% continues
P5-01 NUM OF RESTARTS Number at auto 0~10 1 0 Cannot
restart attempts
P5-02 RESTART SEL Auto restart 0,1 1 0 0:Not output Cannot
operation selection 1:output
0:over Det Disabled
1:Det during speed agree
Torque detection only/ operation
P6-01 TORQ DET 1 SEL selection 1 0~4 1 0 continues after Det Cannot
2:Det during run operation
continues after Det
Torque Detection
P6-03 TORQ DET 1 TIME Torq detection time1 0.0~10.0 0.1sec 0.1 Cannot
P6-06 TORQ DET 2 TIME Torq detection time2 0.0~10.0 0.1sec 0. Cannot
44
Digital Constant No. Digital Operator Constant Name Setting Min Factory Data Selection RUN
P7-01 TORQ LIMIT FWD Forward torque limit 0~300 1﹪ 200 Cannot
Torque Limit
P7-02 TORQ LIMIT REV Reverse torque limit 0~300 1﹪ 200 Cannot
P7-03 TORQ LMT FWD RGN Forward regeneration 0~300 1﹪ 200 Cannot
torque limit
P7-04 TORQ LMT REV RGN Reverse regeneration 0~300 1﹪ 200 Cannot
torque limit
1 :Enabled
P8-01 DB RESISTOR PROT INT DB resistor 0,1 1 0
P8-02 OH PRE-ALARM LVL OH pre-alarm level 50~110 1deg 95 Cannot
Hardware Protection
SELECT SEL
1:Enabled
O2-02 OPERS STOP KEY STOP key during 0,1 1 1 0:Disabled Cannot
control circuit 1:Enabled
operation
O2-03 USER DEFAULTS User constant 0,1,2 0 0 0:stores not set Cannot
initial value 1:begins storing
2:all clear
O2-05 Freq reference 0 0:ENTER key needed
Multi-function
45