lifebelts, friction brakes, and sliding § 1910.28 Safety requirements for scaf-
attachments shall meet the design re- folding.
quirements of the ladders which they (a) General requirements for all scaf-
serve. folds. (1) Scaffolds shall be furnished
(e) Pitch—(1) Preferred pitch. The pre- and erected in accordance with this
ferred pitch of fixed ladders shall be standard for persons engaged in work
considered to come in the range of 75 that cannot be done safely from the
degrees and 90 degrees with the hori- ground or from solid construction, ex-
zontal (fig. D–11). cept that ladders used for such work
shall conform to § 1910.25 and § 1910.26.
(2) The footing or anchorage for scaf-
folds shall be sound, rigid, and capable
of carrying the maximum intended
load without settling or displacement.
Unstable objects such as barrels, boxes,
loose brick, or concrete blocks shall
not be used to support scaffolds or
planks.
(3) [Reserved]
(4) Scaffolds and their components
shall be capable of supporting without
failure at least four times the max-
imum intended load.
(5) Scaffolds and other devices men-
tioned or described in this section shall
be maintained in safe condition. Scaf-
folds shall not be altered or moved
horizontally while they are in use or
occupied.
(6) Any scaffold damaged or weak-
ened from any cause shall be imme-
diately repaired and shall not be used
FIGURE D–11—PITCH OF FIXED LADDERS until repairs have been completed.
(2) Substandard pitch. Fixed ladders (7) Scaffolds shall not be loaded in
shall be considered as substandard if excess of the working load for which
they are installed within the sub- they are intended.
standard pitch range of 60 and 75 de- (8) All load-carrying timber members
grees with the horizontal. Substandard of scaffold framing shall be a minimum
fixed ladders are permitted only where of 1,500 f. (Stress Grade) construction
it is found necessary to meet condi- grade lumber. All dimensions are nomi-
tions of installation. This substandard nal sizes as provided in the American
pitch range shall be considered as a Lumber Standards, except that where
critical range to be avoided, if possible. rough sizes are noted, only rough or
(3) Scope of coverage in this section. undressed lumber of the size specified
will satisfy minimum requirements.
This section covers only fixed ladders
(NOTE: Where nominal sizes of lumber
within the pitch range of 60 degrees
are used in place of rough sizes, the
and 90 degrees with the horizontal.
nominal size lumber shall be such as to
(4) Pitch greater than 90 degrees. Lad- provide equivalent strength to that
ders having a pitch in excess of 90 de- specified in tables D–7 through D–12
grees with the horizontal are prohib- and D–16.)
ited. (9) All planking shall be Scaffold
(f) Maintenance. All ladders shall be Grade as recognized by grading rules
maintained in a safe condition. All lad- for the species of wood used. The max-
ders shall be inspected regularly, with imum permissible spans for 2- × 9-inch
the intervals between inspections being or wider planks are shown in the fol-
determined by use and exposure. lowing table:

133
EC27OC91.011

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00143 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
§ 1910.28 29 CFR Ch. XVII (7–1–12 Edition)

Material involving the use of corrosive sub-


Nominal
stances or chemicals.
Full thickness un- (22) Wire or fiber rope used for scaf-
thickness
dressed lumber lumber fold suspension shall be capable of sup-
porting at least six times the intended
load.
Working load
(p.s.f.) ............... 25 50 75 25 50
(23) When acid solutions are used for
Permissible span cleaning buildings over 50 feet in
(ft.) ................... 10 8 6 8 9 height, wire rope supported scaffolds
shall be used.
The maximum permissible span for (24) The use of shore scaffolds or
11⁄4×9-inch or wider plank of full thick- lean-to scaffolds is prohibited.
ness is 4 feet with medium loading of 50 (25) Lumber sizes, when used in this
p.s.f. section, refer to nominal sizes except
(10) Nails or bolts used in the con- where otherwise stated.
struction of scaffolds shall be of ade- (26) Scaffolds shall be secured to per-
quate size and in sufficient numbers at manent structures, through use of an-
each connection to develop the de- chor bolts, reveal bolts, or other equiv-
signed strength of the scaffold. Nails alent means. Window cleaners’ anchor
shall not be subjected to a straight pull bolts shall not be used.
and shall be driven full length. (27) Special precautions shall be
(11) All planking or platforms shall taken to protect scaffold members, in-
be overlapped (minimum 12 inches) or cluding any wire or fiber ropes, when
secured from movement. using a heat-producing process.
(12) An access ladder or equivalent (b) General requirements for wood pole
safe access shall be provided. scaffolds. (1) Scaffold poles shall bear
(13) Scaffold planks shall extend over on a foundation of sufficient size and
their end supports not less than 6 strength to spread the load from the
inches nor more than 18 inches. poles over a sufficient area to prevent
settlement. All poles shall be set
(14) The poles, legs, or uprights of
plumb.
scaffolds shall be plumb, and securely
(2) Where wood poles are spliced, the
and rigidly braced to prevent swaying
ends shall be squared and the upper
and displacement.
section shall rest squarely on the lower
(15) Materials being hoisted onto a section. Wood splice plates shall be
scaffold shall have a tag line. provided on at least two adjacent sides
(16) Overhead protection shall be pro- and shall not be less than 4 feet 0
vided for men on a scaffold exposed to inches in length, overlapping the abut-
overhead hazards. ted ends equally, and have the same
(17) Scaffolds shall be provided with a width and not less than the cross-sec-
screen between the toeboard and the tional area of the pole. Splice plates of
guardrail, extending along the entire other materials of equivalent strength
opening, consisting of No. 18 gauge U.S. may be used.
Standard Wire one-half-inch mesh or (3) Independent pole scaffolds shall be
the equivalent, where persons are re- set as near to the wall of the building
quired to work or pass under the scaf- as practicable.
folds. (4) All pole scaffolds shall be securely
(18) Employees shall not work on guyed or tied to the building or struc-
scaffolds during storms or high winds. ture. Where the height or length ex-
(19) Employees shall not work on ceeds 25 feet, the scaffold shall be se-
scaffolds which are covered with ice or cured at intervals not greater than 25
snow, unless all ice or snow is removed feet vertically and horizontally.
and planking sanded to prevent slip- (5) Putlogs or bearers shall be set
ping. with their greater dimensions vertical,
(20) Tools, materials, and debris shall long enough to project over the ledgers
not be allowed to accumulate in quan- of the inner and outer rows of poles at
tities to cause a hazard. least 3 inches for proper support.
(21) Only treated or protected fiber (6) Every wooden putlog on single
rope shall be used for or near any work pole scaffolds shall be reinforced with a

134

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00144 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
Occupational Safety and Health Admin., Labor § 1910.28
3⁄16×2-inch steel strip or equivalent se- prevent tipping. The planks that meet
cured to its lower edge throughout its the corner putlog at an angle shall be
entire length. laid first, extending over the diago-
(7) Ledgers shall be long enough to nally placed putlog far enough to have
extend over two pole spaces. Ledgers a good safe bearing, but not far enough
shall not be spliced between the poles. to involve any danger from tipping.
Ledgers shall be reinforced by bearing The planking running in the opposite
blocks securely nailed to the side of direction at right angles shall be laid
the pole to form a support for the ledg- so as to extend over and rest on the
er. first layer of planking.
(8) Diagonal bracing shall be provided (14) When moving platforms to the
to prevent the poles from moving in a next level, the old platform shall be
direction parallel with the wall of the left undisturbed until the new putlogs
building, or from buckling. or bearers have been set in place, ready
(9) Cross bracing shall be provided be- to receive the platform planks.
tween the inner and outer sets of poles
(15) Guardrails not less than 2 × 4
in independent pole scaffolds. The free
inches or the equivalent and not less
ends of pole scaffolds shall be cross
than 36 inches or more than 42 inches
braced.
(10) Full diagonal face bracing shall high, with a mid-rail, when required, of
be erected across the entire face of pole 1 × 4-inch lumber or equivalent, and
scaffolds in both directions. The braces toeboards, shall be installed at all open
shall be spliced at the poles. sides on all scaffolds more than 10 feet
(11) Platform planks shall be laid above the ground or floor. Toeboards
with their edges close together so the shall be a minimum of 4 inches in
platform will be tight with no spaces height. Wire mesh shall be installed in
through which tools or fragments of accordance with paragraph (a)(17) of
material can fall. this section.
(12) Where planking is lapped, each (16) All wood pole scaffolds 60 feet or
plank shall lap its end supports at least less in height shall be constructed and
12 inches. Where the ends of planks erected in accordance with tables D–7
abut each other to form a flush floor, through D–12 of this section. If they are
the butt joint shall be at the centerline over 60 feet in height they shall be de-
of a pole. The abutted ends shall rest signed by a registered professional en-
on separate bearers. Intermediate gineer and constructed and erected in
beams shall be provided where nec- accordance with such design. A copy of
essary to prevent dislodgment of the typical drawings and specifications
planks due to deflection, and the ends shall be made available to the em-
shall be nailed or cleated to prevent ployer and for inspection purposes.
their dislodgment. (17) Wood-pole scaffolds shall not be
(13) When a scaffold turns a corner, erected beyond the reach of effective
the platform planks shall be laid to firefighting apparatus.
TABLE D–7—MINIMUM NOMINAL SIZE AND MAXIMUM SPACING OF MEMBERS OF SINGLE POLE
SCAFFOLDS—LIGHT DUTY
Maximum height of scaffold

20 feet 60 feet

Uniformly distributed load ................................................ Not to exceed 25 pounds per


square foot..
Poles or uprights .............................................................. 2 by 4 in ....................................... 4 by 4 in.
Pole spacing (longitudinal) ............................................... 6 ft. 0 in ........................................ 10 ft. 0 in.
Maximum width of scaffold .............................................. 5 ft. 0 in ........................................ 5 ft. 0 in.
Bearers or putlogs to 3 ft. 0 in. width .............................. 2 by 4 in ....................................... 2 by 4 in.
Bearers or putlogs to 5 ft. 0 in. width .............................. 2 by 6 in. or 3 by 4 in .................. 2 by 6 in. or 3 by 4 in.(rough).
Ledgers ............................................................................ 1 by 4 in ....................................... 11⁄4 by 9 in.
Planking ........................................................................... 11⁄4 by 9 in. (rough) ...................... 2 by 9 in.
Vertical spacing of horizontal members .......................... 7 ft. 0 in ........................................ 7 ft. 0 in.
Bracing, horizontal and diagonal ..................................... 1 by 4 in ....................................... 1 by 4 in.
Tie-ins .............................................................................. 1 by 4 in ....................................... 1 by 4 in.
Toeboards ........................................................................ 4 in. high (minimum) .................... 4 in. high (minimum).

135

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00145 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
§ 1910.28 29 CFR Ch. XVII (7–1–12 Edition)

TABLE D–7—MINIMUM NOMINAL SIZE AND MAXIMUM SPACING OF MEMBERS OF SINGLE POLE
SCAFFOLDS—LIGHT DUTY—Continued
Maximum height of scaffold

20 feet 60 feet

Guardrail .......................................................................... 2 by 4 in ....................................... 2 by 4 in.


All members except planking are used on edge.

TABLE D–8—MINIMUM NOMINAL SIZE AND MAX- TABLE D–9—MINIMUM NOMINAL SIZE AND MAX-
IMUM SPACING OF MEMBERS OF SINGLE POLE IMUM SPACING OF MEMBERS OF SINGLE POLE
SCAFFOLDS—MEDIUM DUTY SCAFFOLDS—HEAVY DUTY
Uniformly distributed load ............. Not to exceed 50 pounds Uniformly distributed load ............. Not to exceed 75 pounds
per square foot. per square foot.
Maximum height of scaffold ......... 60 ft. Maximum height of scaffold ......... 60 ft.
Poles or uprights .......................... 4 by 4 in. Poles or uprights .......................... 4 by 4 in.
Pole spacing (longitudinal) ........... 8 ft. 0 in. Pole spacing (longitudinal) ........... 6 ft. 0 in.
Maximum width of scaffold ........... 5 ft. 0 in. Maximum width of scaffold ........... 5 ft. 0 in.
Bearers or putlogs ........................ 2 by 9 in. or 3 by 4 in. Bearers or putlogs ........................ 2 by 9 in. or 3 by 5 in.
Spacing of bearers or putlogs ...... 8 ft. 0 in. (rough).
Ledgers ......................................... 2 by 9 in. Spacing of bearers or putlogs ...... 6 ft. 0 in.
Vertical spacing of horizontal 9 ft. 0 in. Ledgers ......................................... 2 by 9 in.
members. Vertical spacing of horizontal 6 ft. 6 in.
Bracing, horizontal ........................ 1 by 6 in. or 11⁄4 by 4 in. members.
Bracing, diagonal .......................... 1 by 4 in. Bracing, horizontal and diagonal .. 2 by 4 in.
Tie-ins ........................................... 1 by 4 in. Tie-ins ........................................... 1 by 4 in.
Planking ........................................ 2 by 9 in. Planking ........................................ 2 by 9 in.
Toeboards ..................................... 4 in. high (minimum). Toeboards ..................................... 4 in. high (minimum).
Guardrail ....................................... 2 by 4 in. Guardrail ....................................... 2 by 4 in.
All members except planking are used on edge. All members except planking are used on edge.

TABLE D–10—MINIMUM NOMINAL SIZE AND MAXIMUM SPACING OF MEMBERS OF INDEPENDENT POLE
SCAFFOLDS—LIGHT DUTY
Maximum height of scaffold

20 feet 60 feet

Uniformly distributed load ................................................ Not to exceed 25 pounds per


square foot..
Poles or uprights .............................................................. 2 by 4 in ....................................... 4 by 4 in.
Pole spacing (longitudinal) ............................................... 6 ft. 0 in ........................................ 10 ft. 0 in.
Pole spacing (transverse) ................................................ 6 ft. 0 in ........................................ 10 ft. 0 in.
Ledgers ............................................................................ 11⁄4 by 4 in ................................... 11⁄4 by 9 in.
Bearers to 3 ft. 0 in. span ................................................ 2 by 4 in ....................................... 2 by 4 in.
Bearers to 10 ft. 0 in. span .............................................. 2 by 6 in. or 3 by 4 in .................. 2 by 9 (rough) or 3 by 8 in.
Planking ........................................................................... 11⁄4 by 9 in ................................... 2 by 9 in.
Vertical spacing of horizontal members .......................... 7 ft. 0 in ........................................ 7 ft. 0 in.
Bracing, horizontal and diagonal ..................................... 1 by 4 in ....................................... 1 by 4 in.
Tie-ins .............................................................................. 1 by 4 in ....................................... 1 by 4 in.
Toeboards ........................................................................ 4 in. high ...................................... 4 in. high (minimum).
Guardrail .......................................................................... 2 by 4 in ....................................... 2 by 4 in.
All members except planking are used on edge.

TABLE D–11—MINIMUM NOMINAL SIZE AND TABLE D–11—MINIMUM NOMINAL SIZE AND
MAXIMUM SPACING OF MEMBERS OF INDE- MAXIMUM SPACING OF MEMBERS OF INDE-
PENDENT POLE SCAFFOLDS—MEDIUM DUTY PENDENT POLE SCAFFOLDS—MEDIUM DUTY—
Uniformly distributed load ............. Not to exceed 50 pounds
Continued
per square foot. Bracing, diagonal .......................... 1 by 4 in.
Maximum height of scaffold ......... 60 ft. Tie-ins ........................................... 1 by 4 in.
Poles or uprights .......................... 4 by 4 in.
Planking ........................................ 2 by 9 in.
Pole spacing (longitudinal) ........... 8 ft. 0 in.
Pole spacing (transverse) ............. 8 ft. 0 in. Toeboards ..................................... 4 in. high (minimum).
Ledgers ......................................... 2 by 9 in. Guardrail ....................................... 2 by 4 in.
Vertical spacing of horizontal 6 ft. 0 in. All members except planking are used on edge.
members.
Spacing of bearers ....................... 8 ft. 0 in.
Bearers ......................................... 2 by 9 in. (rough) or 2 by
10 in.
Bracing, horizontal ........................ 1 by 6 in. or 11⁄4 by 4 in.

136

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00146 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
Occupational Safety and Health Admin., Labor § 1910.28

TABLE D–12—MINIMUM NOMINAL SIZE AND (2) A medium-duty tube and coupler
MAXIMUM SPACING OF MEMBERS OF INDE- scaffold shall have all posts, runners,
PENDENT POLE SCAFFOLDS—HEAVY DUTY and bracing of nominal 2-inch O.D.
Uniformly distributed load ............. Not to exceed 75 pounds steel tubing. Posts spaced not more
per square foot. than 6 feet apart by 8 feet along the
Maximum height of scaffold ......... 60 ft. length of the scaffold shall have bear-
Poles or uprights .......................... 4 by 4 in.
Pole spacing (longitudinal) ........... 6 ft. 0 in. ers of nominal 21⁄2-inch O.D. steel tub-
Pole spacing (transverse) ............. 8 ft. 0 in. ing. Posts spaced not more than 5 feet
Ledgers ......................................... 2 by 9 in. apart by 8 feet along the length of the
Vertical spacing of horizontal 4 ft. 6 in.
members. scaffold shall have bearers of nominal
Bearers ......................................... 2 by 9 in. (rough). 2-inch O.D. steel tubing. Other struc-
Bracing, horizontal and diagonal .. 2 by 4 in.
Tie-ins ........................................... 1 by 4 in.
tural metals when used must be de-
Planking ........................................ 2 by 9 in. signed to carry an equivalent load.
Toeboards ..................................... 4 in. high (minimum). (3) A heavy-duty tube and coupler
Guardrail ....................................... 2 by 4 in.
scaffold shall have all posts, runners,
All members except planking are used on edge. and bracing of nominal 2-inch O.D.
TABLE D–13—TUBE AND COUPLER steel tubing, with the posts spaced not
SCAFFOLDS—LIGHT DUTY more than 6 feet apart by 6 feet 6
inches along the length of the scaffold.
Uniformly distributed load ............. Not to exceed 25 p.s.f. Other structural metals when used
post spacing (longitudinal) ............ 10 ft. 0 in.
Post spacing (transverse) ............. 6 ft. 0 in. must be designed to carry an equiva-
lent load.
Working levels Additional planked Maximum height
(4) Tube and coupler scaffolds shall
levels be limited in heights and working lev-
1 8 125 ft. els to those permitted in tables D–13,
2 4 125 ft. 14, and 15, of this section. Drawings and
3 0 91 ft. 0 in.
specifications of all tube and coupler
scaffolds above the limitations in ta-
TABLE D–14—TUBE AND COUPLER bles D–13, 14, and 15 of this section
SCAFFOLDS—MEDIUM DUTY shall be designed by a registered pro-
Uniformly distributed load ............. Not to exceed 50 p.s.f. fessional engineer and copies made
Post spacing (longitudinal) ........... 8 ft. 0 in. available to the employer and for in-
Post spacing (transverse) ............. 6 ft. 0 in.
spection purposes.
Additional planked
(5) All tube and coupler scaffolds
Working levels Maximum height shall be constructed and erected to
levels
support four times the maximum in-
1 6 125 ft.
2 0 78 ft. 0 in. tended loads as set forth in tables D–13,
14, and 15 of this section, or as set forth
TABLE D–15—TUBE AND COUPLER in the specifications by a registered
SCAFFOLDS—HEAVY DUTY professional engineer, copies which
shall be made available to the em-
Uniformly distributed load ............. Not to exceed 75 p.s.f. ployer and for inspection purposes.
Post spacing (longitudinal) ........... 6 ft. 6 in.
Post spacing (transverse) ............. 6 ft. 0 in. (6) All tube and coupler scaffolds
shall be erected by competent and ex-
Additional planked perienced personnel.
Working levels Maximum height
levels (7) Posts shall be accurately spaced,
1 6 125 ft. erected on suitable bases, and main-
tained plumb.
(c) Tube and coupler scaffolds. (1) A (8) Runners shall be erected along the
light-duty tube and coupler scaffold length of the scaffold located on both
shall have all posts, bearers, runners, the inside and the outside posts at even
and bracing of nominal 2-inch O.D. height. Runners shall be interlocked to
steel tubing. The posts shall be spaced form continuous lengths and coupled to
no more than 6 feet apart by 10 feet each post. The bottom runners shall be
along the length of the scaffold. Other located as close to the base as possible.
structural metals when used must be Runners shall be placed not more than
designed to carry an equivalent load. 6 feet 6 inches on centers.

137

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00147 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
§ 1910.28 29 CFR Ch. XVII (7–1–12 Edition)

(9) Bearers shall be installed trans- (2) Spacing of panels or frames shall
versely between posts and shall be se- be consistent with the loads imposed.
curely coupled to the posts bearing on (3) Scaffolds shall be properly braced
the runner coupler. When coupled di- by cross bracing or diagonal braces, or
rectly to the runners, the coupler must both, for securing vertical members to-
be kept as close to the posts as pos- gether laterally, and the cross braces
sible. shall be of such length as will auto-
(10) Bearers shall be at least 4 inches matically square and aline vertical
but not more than 12 inches longer members so that the erected scaffold is
than the post spacing or runner spac- always plumb, square, and rigid. All
ing. Bearers may be cantilevered for brace connections shall be made se-
use as brackets to carry not more than cure.
two planks. (4) Scaffold legs shall be set on ad-
(11) Cross bracing shall be installed justable bases or plain bases placed on
across the width of the scaffold at least mud sills or other foundations ade-
every third set of posts horizontally quate to support the maximum in-
and every fourth runner vertically. tended load.
Such bracing shall extend diagonally (5) The frames shall be placed one on
from the inner and outer runners up- top of the other with coupling or stack-
ward to the next outer and inner run- ing pins to provide proper vertical
ners. alinement of the legs.
(12) Longitudinal diagonal bracing
(6) Where uplift may occur, panels
shall be installed at approximately a
shall be locked together vertically by
45-degree angle from near the base of
pins or other equivalent suitable
the first outer post upward to the ex-
means.
treme top of the scaffold. Where the
(7) Guardrails not less than 2 × 4
longitudinal length of the scaffold per-
inches or the equivalent and not less
mits, such bracing shall be duplicated
than 36 inches or more than 42 inches
beginning at every fifth post. In a simi-
high, with a mid-rail, when required, of
lar manner, longitudinal diagonal brac-
1- × 4-inch lumber or equivalent, and
ing shall also be installed from the last
toeboards, shall be installed at all open
post extending back and upward to-
sides on all scaffolds more than 10 feet
ward the first post. Where conditions
above the ground or floor. Toeboards
preclude the attachment of this brac-
shall be a minimum of 4 inches in
ing to the posts, it may be attached to
height. Wire mesh shall be installed in
the runners.
accordance with paragraph (a)(17) of
(13) The entire scaffold shall be tied
this section.
to and securely braced against the
building at intervals not to exceed 30 (8) All tubular metal scaffolds shall
feet horizontally and 26 feet vertically. be constructed and erected to support
(14) Guardrails not less than 2×4 four times the maximum intended
inches or the equivalent and not less loads.
than 36 inches or more than 42 inches (9) To prevent movement, the scaf-
high, with a mid-rail, when required, of fold shall be secured to the building or
1×4-inch lumber or equivalent, and structure at intervals not to exceed 30
toeboards, shall be installed at all open feet horizontally and 26 feet vertically.
sides on all scaffolds more than 10 feet (10) Maximum permissible spans of
above the ground or floor. Toeboards planking shall be in conformity with
shall be a minimum of 4 inches in paragraph (a)(9) of this section.
height. Wire mesh shall be installed in (11) Drawings and specifications for
accordance with paragraph (a)(17) of all frame scaffolds over 125 feet in
this section. height above the base plates shall be
(d) Tubular welded frame scaffolds. (1) designed by a registered professional
Metal tubular frame scaffolds, includ- engineer and copies made available to
ing accessories such as braces, brack- the employer and for inspection pur-
ets, trusses, screw legs, ladders, etc., poses.
shall be designed and proved to safely (12) All tubular welded frame scaf-
support four times the maximum in- folds shall be erected by competent and
tended load. experienced personnel.

138

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00148 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
Occupational Safety and Health Admin., Labor § 1910.28

(13) Frames and accessories for scaf- building wall. Planking shall be nailed
folds shall be maintained in good re- or bolted to outriggers.
pair and every defect, unsafe condition, (5) Where there is danger of material
or noncompliance with this section falling from the scaffold, a wire mesh
shall be immediately corrected before or other enclosure shall be provided be-
further use of the scaffold. Any broken, tween the guardrail and the toeboard.
bent, excessively rusted, altered, or (6) Where additional working levels
otherwise structurally damaged frames are required to be supported by the
or accessories shall not be used. outrigger method, the plans and speci-
(14) Periodic inspections shall be fications of the outrigger and scaf-
made of all welded frames and acces- folding structure shall be designed by a
sories, and any maintenance, including registered professional engineer.
painting, or minor corrections author- (f) Masons’ adjustable multiple-point
ized by the manufacturer, shall be suspension scaffolds. (1) The scaffold
made before further use. shall be capable of sustaining a work-
(e) Outrigger scaffolds. (1) Outrigger ing load of 50 pounds per square foot
beams shall extend not more than 6 and shall not be loaded in excess of
feet beyond the face of the building. that figure.
The inboard end of outrigger beams, (2) The scaffold shall be provided
measured from the fulcrum point to with hoisting machines that meet the
the extreme point of support, shall be requirements of a nationally recog-
not less than one and one-half times nized testing laboratory. Refer to
the outboard end in length. The beams § 1910.7 for definition of nationally rec-
shall rest on edge, the sides shall be ognized testing laboratory.
plumb, and the edges shall be hori-
zontal. The fulcrum point of the beam TABLE D–16—MINIMUM NOMINAL SIZE AND
shall rest on a secure bearing at least MAXIMUM SPACING OF MEMBERS OF OUT-
RIGGER SCAFFOLDS
6 inches in each horizontal dimension.
The beam shall be secured in place Medium
Light duty
against movement and shall be se- duty
curely braced at the fulcrum point Maximum scaffold load ............... 25 p.s.f. ..... 50 p.s.f.
against tipping. Outrigger size ............................. 2×10 in ...... 3×10 in.
(2) The inboard ends of outrigger Maximum outrigger spacing ....... 10 ft 0 in .... 6 ft 0 in.
beams shall be securely supported ei- Planking ...................................... 2×9 in ........ 2×9 in.
Guardrail ..................................... 2×4 in ........ 2×4 in.
ther by means of struts bearing against Guardrail uprights ....................... 2×4 in ........ 2×4 in.
sills in contact with the overhead Toeboards (minimum) ................ 4 in ............ 4 in.
beams or ceiling, or by means of ten-
sion members secured to the floor (3) The platform shall be supported
joists underfoot, or by both if nec- by wire ropes in conformity with para-
essary. The inboard ends of outrigger graph (a)(22) of this section, suspended
beams shall be secured against tipping from overhead outrigger beams.
and the entire supporting structure (4) The scaffold outrigger beams shall
shall be securely braced in both direc- consist of structural metal securely
tions to prevent any horizontal move- fastened or anchored to the frame or
ment. floor system of the building or struc-
(3) Unless outrigger scaffolds are de- ture.
signed by a licensed professional engi- (5) Each outrigger beam shall be
neer, they shall be constructed and equivalent in strength to at least a
erected in accordance with table D–16. standard 7-inch, 15.3-pound steel I-
Outrigger scaffolds designed by a reg- beam, be at least 15 feet long, and shall
istered professional engineer shall be not project more than 6 feet 6 inches
constructed and erected in accordance beyond the bearing point.
with such design. A copy of the de- (6) Where the overhang exceeds 6 feet
tailed drawings and specifications 6 inches, outrigger beams shall be com-
showing the sizes and spacing of mem- posed of stronger beams or multiple
bers shall be kept on the job. beams and be installed in accordance
(4) Planking shall be laid tight and with approved designs and instruc-
shall extend to within 3 inches of the tions.

139

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00149 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
§ 1910.28 29 CFR Ch. XVII (7–1–12 Edition)

(7) If channel iron outrigger beams sional engineer, and supervised by a


are used in place of I-beams, they shall competent, designated person.
be securely fastened together with the (g) Two-point suspension scaffolds
flanges turned out. (swinging scaffolds). (1) Two-point sus-
(8) All outrigger beams shall be set pension scaffold platforms shall be not
and maintained with their webs into less than 20 inches no more than 36
vertical position. inches wide overall. The platform shall
(9) A stop bolt shall be placed at each be securely fastened to the hangers by
end of every outrigger beam. U-bolts or by other equivalent means.
(10) The outrigger beam shall rest on (2) The hangers of two-point suspen-
suitable wood-bearing blocks. sion scaffolds shall be made of wrought
(11) All parts of the scaffold such as iron, mild steel, or other equivalent
bolts, nuts, fittings, clamps, wire rope, material having a cross-sectional area
and outrigger beams and their fas- capable of sustaining four times the
tenings, shall be maintained in sound maximum intended load, and shall be
and good working condition and shall designed with a support for guardrail,
be inspected before each installation intermediate rail, and toeboard.
and periodically thereafter. (3) When hoisting machines are used
(12) The free end of the suspension on two-point suspension scaffolds, such
wire ropes shall be equipped with prop- machines shall be of a design tested
er size thimbles and be secured by and approved by a nationally recog-
splicing or other equivalent means. nized testing laboratory. Refer to
The running ends shall be securely at- § 1910.7 for definition of nationally rec-
tached to the hoisting drum and at ognized testing laboratory.
least four turns of rope shall at all
(4) The roof irons or hooks shall be of
times remain on the drum.
wrought iron, mild steel, or other
(13) Where a single outrigger beam is
equivalent material of proper size and
used, the steel shackles or clevises
design, securely installed and an-
with which the wire ropes are attached
chored. Tie-backs of three-fourth inch
to the outrigger beams shall be placed
manila rope or the equivalent shall
directly over the hoisting drums.
serve as a secondary means of anchor-
(14) The scaffold platform shall be
age, installed at right angles to the
equivalent in strength to at least 2-
face of the building whenever possible
inch planking. (For maximum planking
spans see paragraph (a)(9) of this sec- and secured to a structurally sound
tion.) portion of the building.
(15) Guardrails not less than 2 × 4 (5) Guardrails not less than 2 × 4
inches or the equivalent and not less inches or the equivalent and not less
than 36 inches or more than 42 inches than 36 inches or more than 42 inches
high, with a mid-rail, when required, of high, with a mid-rail, when required, of
1 × 4-inch lumber or equivalent, and 1- × 4-inch lumber or equivalent, and
toeboards, shall be installed at all open toeboards, shall be installed at all open
sides on all scaffolds more than 10 feet sides on all scaffolds more than 10 feet
above the ground or floor. Toeboards above the ground or floor. Toeboards
shall be a minimum of 4 inches in shall be a minimum of 4 inches in
height. Wire mesh shall be installed in height. Wire mesh shall be installed in
accordance with paragraph (a)(17) of accordance with paragraph (a)(17) of
this section. this section.
(16) Overhead protection shall be pro- (6) Two-point suspension scaffolds
vided on the scaffold, not more than 9 shall be suspended by wire or fiber
feet above the platform, consisting of ropes. Wire and fiber ropes shall con-
2-inch planking or material of equiva- form to paragraph (a)(22) of this sec-
lent strength laid tight, when men are tion.
at work on the scaffold and an over- (7) The blocks for fiber ropes shall be
head hazard exists. of standard 6-inch size, consisting of at
(17) Each scaffold shall be installed least one double and one single block.
or relocated in accordance with designs The sheaves of all blocks shall fit the
and instructions, of a registered profes- size of rope used.

140

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00150 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
Occupational Safety and Health Admin., Labor § 1910.28

(8) All wire ropes, fiber ropes, slings, eighth inch. The stringers shall be tied
hangers, platforms, and other sup- together with the tie rods not less than
porting parts shall be inspected before one-quarter inch in diameter, passing
every installation. Periodic inspections through the stringers and riveted up
shall be made while the scaffold is in tight against washers on both ends.
use. The flooring strips shall be spaced not
(9) On suspension scaffolds designed more than five-eighth inch apart ex-
for a working load of 500 pounds no cept at the side rails where the space
more than two men shall be permitted may be 1 inch. Ladder-type platforms
to work at one time. On suspension shall be constructed in accordance with
scaffolds with a working load of 750 table D–17.
pounds, no more than three men shall (ii) Plank-type platforms shall be
be permitted to work at one time. Each composed of not less than nominal 2×8-
workman shall be protected by a safety inch unspliced planks, properly cleated
lifebelt attached to a lifeline. The life- together on the underside starting 6
line shall be securely attached to sub-
inches from each end; intervals in be-
stantial members of the structure (not
tween shall not exceed 4 feet. The
scaffold), or to securely rigged lines,
plank-type platform shall not extend
which will safely suspend the workman
beyond the hangers more than 18
in case of a fall.
(10) Where acid solutions are used, inches. A bar or other effective means
fiber ropes are not permitted unless shall be securely fastened to the plat-
acid-proof. form at each end to prevent its slipping
(11) Two-point suspension scaffolds off the hanger. The span between hang-
shall be securely lashed to the building ers for plank-type platforms shall not
or structure to prevent them from exceed 10 feet.
swaying. Window cleaners’ anchors (iii) Beam platforms shall have side
shall not be used for this purpose. stringers of lumber not less than 2×6
(12) The platform of every two-point inches set on edge. The span between
suspension scaffold shall be one of the hangers shall not exceed 12 feet when
following types: beam platforms are used. The flooring
(i) The side stringer of ladder-type shall be supported on 2- and 6-inch
platforms shall be clear straight- crossbeams, laid flat and set into the
grained spruce or materials of equiva- upper edge of the stringers with a snug
lent strength and durability. The rungs fit, at intervals of not more than 4 feet,
shall be of straight-grained oak, ash, or securely nailed in place. The flooring
hickory, at least 11⁄8 inch in diameter, shall be of 1×6inch material properly
with seven-eighth inch tenons mortised nailed. Floorboards shall not be spaced
into the side stringers at least seven- more than one-half inch apart.
TABLE D–17—SCHEDULE FOR LADDER-TYPE PLATFORMS
Length of platform (feet)

12 14 & 16 18 & 20 22 & 24 28 & 30

Side stringers, minimum cross section (finished sizes):


At ends (in.) ...................................................................... 13⁄4×23⁄4 13⁄4×23⁄4 13⁄4×3 13⁄4×3 13⁄4×31⁄2
At middle (in.) ................................................................... 13⁄4×33⁄4 13⁄4×33⁄4 13⁄4×4 13⁄4×41⁄4 13⁄4×5
Reinforcing strip (minimum) 1 ................................................... .................. .................. .................. .................. ..................
Rungs 2 ..................................................................................... .................. .................. .................. .................. ..................
Tie rods:
Number (minimum) ........................................................... 3 4 4 5 6
Diameter (minimum) ......................................................... 1⁄4 in 1⁄4 in 1⁄4 in 14 ⁄ in 1⁄4 in.

Flooring, minimum finished size (in.) ....................................... 12⁄ ×23⁄4 12⁄ ×23⁄4 12⁄ ×23⁄4 ⁄ × ⁄
12 34 12⁄ ×23⁄4
1 A 1⁄8x7⁄8-in. steel reinforcing strip or its equivalent shall be attached to the side or underside full length.
2 Rungs shall be 11⁄8-in. minimum, diameter with at least 7⁄8-in. diameter tenons, and the maximum spacing shall be 12 in. cen-
ter to center.

(h) Stone setters’ adjustable multiple- working load of 25 pounds per square
point suspension scaffolds. (1) The scaf-
fold shall be capable of sustaining a

141

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00151 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
§ 1910.28 29 CFR Ch. XVII (7–1–12 Edition)

foot and shall not be overloaded. Scaf- power units or manually operated
folds shall not be used for storage of winches, shall be a type tested and list-
stone or other heavy materials. ed by a nationally recognized testing
(2) The hoisting machine and its sup- laboratory. Refer to § 1910.399(a)(77) for
ports shall be of a type tested and list- definition of listed, and § 1910.7 for na-
ed by a nationally recognized testing tionally recognized testing laboratory.
laboratory. Refer to § 1910.399(a)(77) for (2) [Reserved]
definition of listed, and § 1910.7 for na- (3) All power-operated gears and
tionally recognized testing laboratory. brakes shall be enclosed.
(3) The platform shall be securely fas-
(4) In addition to the normal oper-
tened to the hangers by U-bolts or
other equivalent means. ating brake, all-power driven units
(4) The scaffold unit shall be sus- must have an emergency brake which
pended from metal outriggers, iron engages automatically when the nor-
brackets, wire rope slings, or iron mal speed of descent is exceeded.
hooks which will safely support the (5) Guards, mid-rails, and toeboards
maximum intended load. shall completely enclose the cage or
(5) Outriggers when used shall be set basket. Guardrails shall be no less than
with their webs in a vertical position, 2 by 4 inches or the equivalent in-
securely anchored to the building or stalled no less than 36 inches nor more
structure and provided with stop bolts than 42 inches above the platform. Mid-
at each end. rails shall be 1 by 6 inches or the equiv-
(6) The scaffold shall be supported by alent, installed equidistant between
wire rope conforming with paragraph the guardrail and the platform.
(a)(22) of this section, suspended from Toeboards shall be a minimum of 4
overhead supports. inches in height.
(7) The free ends of the suspension (6) The hoisting machines, cables,
wire ropes shall be equipped with prop- and equipment shall be regularly serv-
er size thimbles, secured by splicing or iced and inspected after each installa-
other equivalent means. The running
tion and every 30 days thereafter.
ends shall be securely attached to the
hoisting drum and at least four turns (7) The units may be combined to
of rope shall remain on the drum at all form a two-point suspension scaffold.
times. Such scaffold shall comply with para-
(8) Guardrails not less than 2 by 4 graph (g) of this section.
inches or the equivalent and not less (8) The supporting cable shall be
than 36 inches or more than 42 inches straight for its entire length, and the
high, with a mid-rail, when required, of operator shall not sway the basket and
1- by 4-inch lumber or equivalent, and fix the cable to any intermediate
toeboards, shall be installed at all open points to change his original path of
sides on all scaffolds more than 10 feet travel.
above the ground or floor. Toeboards (9) Equipment shall be maintained
shall be a minimum of 4 inches in and used in accordance with the manu-
height. Wire mesh shall be installed in facturers’ instructions.
accordance with paragraph (a)(17) of (10) Suspension methods shall con-
this section. form to applicable provisions of para-
(9) When two or more scaffolds are graphs (f) and (g) of this section.
used on a building or structure they (j) Boatswain’s chairs. (1) The chair
shall not be bridged one to the other
seat shall be not less than 12 by 24
but shall be maintained at even height
inches, and of 1-inch thickness. The
with platforms butting closely.
(10) Each scaffold shall be installed seat shall be reinforced on the under-
or relocated in accordance with designs side to prevent the board from split-
and instructions of a registered profes- ting.
sional engineer, and such installation (2) The two fiber rope seat slings
or relocation shall be supervised by a shall be of 5⁄8-inch diameter, reeved
competent designated person. through the four seat holes so as to
(i) Single-point adjustable suspension cross each other on the underside of
scaffolds. (1) The scaffolding, including the seat.

142

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00152 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
Occupational Safety and Health Admin., Labor § 1910.28

(3) Seat slings shall be of at least 3⁄8- height. Wire mesh shall be installed in
inch wire rope when a workman is con- accordance with paragraph (a)(17) of
ducting a heat producing process such this section.
as gas or arc welding. (l) Bricklayers’ square scaffolds. (1) The
(4) The workman shall be protected squares shall not exceed 5 feet in width
by a safety life belt attached to a life- and 5 feet in height.
line. The lifeline shall be securely at- (2) Members shall be not less than
tached to substantial members of the those specified in Table D–18.
structure (not scaffold), or to securely (3) The squares shall be reinforced on
rigged lines, which will safely suspend both sides of each corner with 1- by 6-
the worker in case of a fall. inch gusset pieces. They shall also have
(5) The tackle shall consist of correct braces 1 by 8 inches on both sides run-
size ball bearing or bushed blocks and ning from center to center of each
properly spliced 5⁄8-inch diameter first- member, or other means to secure
grade manila rope. equivalent strength and rigidity.
(6) The roof irons, hooks, or the ob- (4) The squares shall be set not more
ject to which the tackle is anchored than 5 feet apart for medium duty scaf-
shall be securely installed. Tiebacks folds, and not more than 8 feet apart
when used shall be installed at right for light duty scaffolds. Bracing 1×8
angles to the face of the building and inches, extending from the bottom of
securely fastened to a chimney. each square to the top of the next
(k) Carpenters’ bracket scaffolds. (1) square, shall be provided on both front
The brackets shall consist of a tri- and rear sides of the scaffold.
angular wood frame not less than 2 by
TABLE D–18—MINIMUM DIMENSIONS FOR
3 inches in cross section, or of metal of
BRICKLAYERS’ SQUARE SCAFFOLD MEMBERS
equivalent strength. Each member
shall be properly fitted and securely Members Dimensions
joined. (inches)
(2) Each bracket shall be attached to Bearers or horizontal members ....................... 2 by 6.
the structure by means of one of the Legs ................................................................. 2 by 6.
following: Braces at corners ............................................. 1 by 6.
Braces diagonally from center frame ............... 1 by 8.
(i) A bolt no less than five-eighths
inch in diameter which shall extend (5) Platform planks shall be at least
through the inside of the building wall. 2- by 9-inch nominal size. The ends of
(ii) A metal stud attachment device. the planks shall overlap the bearers of
(iii) Welding to steel tanks. the squares and each plank shall be
(iv) Hooking over a well-secured and supported by not less than three
adequately strong supporting member. squares.
The brackets shall be spaced no more (6) Bricklayers’ square scaffolds shall
than 10 feet apart. not exceed three tiers in height and
(3) No more than two persons shall shall be so constructed and arranged
occupy any given 10 feet of a bracket that one square shall rest directly
scaffold at any one time. Tools and ma- above the other. The upper tiers shall
terials shall not exceed 75 pounds in ad- stand on a continuous row of planks
dition to the occupancy. laid across the next lower tier and be
(4) The platform shall consist of not nailed down or otherwise secured to
less than two 2- by 9-inch nominal size prevent displacement.
planks extending not more than 18 (7) Scaffolds shall be level and set
inches or less than 6 inches beyond upon a firm foundation.
each end support. (m) Horse scaffolds. (1) Horse scaffolds
(5) Guardrails not less than 2 by 4 shall not be constructed or arranged
inches or the equivalent and not less more than two tiers or 10 feet in
than 36 inches or more than 42 inches height.
high, with a mid-rail, when required, of (2) The members of the horses shall
1- by 4-inch lumber or equivalent, and be not less than those specified in
toeboards, shall be installed at all open Table D–19.
sides on all scaffolds more than 10 feet (3) Horses shall be spaced not more
above the ground or floor. Toeboards than 5 feet for medium duty and not
shall be a minimum of 4 inches in more than 8 feet for light duty.

143

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00153 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
§ 1910.28 29 CFR Ch. XVII (7–1–12 Edition)

(4) When arranged in tiers, each horse shall be designed based on design re-
shall be placed directly over the horse quirements for the special span. The
in the tier below. overhang of each end of the platform
(5) On all scaffolds arranged in tiers, planks shall be not less than 1 foot and
the legs shall be nailed down to the not more than 18 inches.
planks to prevent displacement or (5) When one needle beam is higher
thrust and each tier shall be substan- than the other or when the platform is
tially cross braced. not level the platform shall be secured
against slipping.
TABLE D–19—MINIMUM DIMENSIONS FOR
HORSE SCAFFOLD MEMBERS (6) All unattached tools, bolts, and
nuts used on needle beam scaffolds
Members Dimensions shall be kept in suitable containers.
(inches)
(7) One end of a needle beam scaffold
Horizontal members or bearers ....................... 3 by 4. may be supported by a permanent
Legs ................................................................. 11⁄4 by 41⁄2. structural member conforming to para-
Longitudinal brace between legs ..................... 1 by 6.
Gusset brace at top of legs ............................. 1 by 8. graphs (a) (4) and (8) of this section.
Half diagonal braces ........................................ 11⁄4 by 41⁄2. (8) Each man working on a needle
beam scaffold 20 feet or more above the
(6) Horses or parts which have be- ground or floor and working with both
come weak or defective shall not be hands, shall be protected by a safety
used. life belt attached to a lifeline. The life-
(7) Guardrails not less than 2 by 4 line shall be securely attached to sub-
inches or the equivalent and not less stantial members of the structure (not
than 36 inches or more than 42 inches scaffold), or to securely rigged lines,
high with a mid-rail, when required, of which will safely suspend the workman
1- by 4-inch lumber or equivalent and in case of a fall.
toeboards, shall be installed at all open (o) Plasterers’, decorators’, and large
sides on all scaffolds more than 10 feet area scaffolds. (1) Plasterers’, decora-
above the ground or floor. Toeboards tors’, lathers’, and ceiling workers’ in-
shall be a minimum of 4 inches in side scaffolds shall be constructed in
height. Wire mesh shall be installed in accordance with the general require-
accordance with paragraph (a)(17) of
ments set forth for independent wood
this section.
pole scaffolds.
(n) Needle beam scaffold. (1) Wood nee-
dle beams shall be in accordance with (2) Guardrails not less than 2 by 4
paragraph (a) (5) and (9) of this section, inches or the equivalent and not less
and shall be not less than 4 by 6 inches than 36 inches or more than 42 inches
in size, with the greater dimension high, with a mid-rail, when required, of
placed in a vertical direction. Metal 1- by 4-inch lumber or equivalent, and
beams or the equivalent conforming to toeboards, shall be installed at all open
paragraph (a) (4) and (8) of this section sides on all scaffolds more than 10 feet
may be used. above the ground or floor. Toeboards
(2) Ropes or hangers shall be provided shall be a minimum of 4 inches in
for supports. The span between sup- height. Wire mesh shall be installed in
ports on the needle beam shall not ex- accordance with paragraph (a)(17) of
ceed 10 feet for 4- by 6-inch timbers. this section.
Rope supports shall be equivalent in (3) All platform planks shall be laid
strength to 1-inch diameter first-grade with the edges close together.
manila rope. (4) When independent pole scaffold
(3) The ropes shall be attached to the platforms are erected in sections, such
needle beams by a scaffold hitch or a sections shall be provided with con-
properly made eye splice. The loose end necting runways equipped with sub-
of the rope shall be tied by a bowline stantial guardrails.
knot or by a round turn and one-half (p) Interior hung scaffolds. (1) [Re-
hitch. served]
(4) The platform span between the (2) The suspended steel wire rope
needle beams shall not exceed 8 feet shall conform to paragraph (a)(22) of
when using 2-inch scaffold plank. For this section. Wire may be used pro-
spans greater than 8 feet, platforms viding the strength requirements of

144

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00154 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
Occupational Safety and Health Admin., Labor § 1910.28

paragraph (a)(22) of this section are tened, held, or equipped with devices so
met. as to prevent slipping.
(3) For hanging wood scaffolds, the (5) The wood platform planks shall be
following minimum nominal size mate- not less than 2 inches nominal in
rial is recommended: thickness. Both metal and wood plat-
(i) Supporting bearers 2 by 9 inches form planks shall overlap the bearing
on edge. surface not less than 12 inches. The
(ii) Planking 2 by 9 inches or 2 by 10 span between supports for wood shall
inches, with maximum span 7 feet for not exceed 8 feet. Platform width shall
heavy duty and 10 feet for light duty or be not less than 18 inches.
medium duty. (6) Not more than two persons shall
(4) Steel tube and coupler members occupy any given 8 feet of any ladder-
may be used for hanging scaffolds with jack scaffold at any one time.
both types of scaffold designed to sus- (r) Window-jack scaffolds. (1) Window-
tain a uniform distributed working jack scaffolds shall be used only for the
load up to heavy duty scaffold loads purpose of working at the window
with a safety factor of four. opening through which the jack is
placed.
(5) When a hanging scaffold is sup-
(2) Window jacks shall not be used to
ported by means of wire rope, such wire
support planks placed between one win-
rope shall be wrapped at least twice
dow jack and another or for other ele-
around the supporting members and
ments of scaffolding.
twice around the bearers of the scaf-
(3) Window-jack scaffolds shall be
fold, with each end of the wire rope se-
provided with suitable guardrails un-
cured by at least three standard wire-
less safety belts with lifelines are at-
rope clips.
tached and provided for the workman.
(6) All overhead supporting members Window-jack scaffolds shall be used by
shall be inspected and checked for one man only.
strength before the scaffold is erected. (s) Roofing brackets. (1) Roofing
(7) Guardrails not less than 2 by 4 brackets shall be constructed to fit the
inches or the equivalent and not less pitch of the roof.
than 36 inches or more than 42 inches (2) Brackets shall be secured in place
high, with a mid-rail, when required, of by nailing in addition to the pointed
1- by 4-inch lumber or equivalent, and metal projections. The nails shall be
toeboards, shall be installed at all open driven full length into the roof. When
sides on all scaffolds more than 10 feet rope supports are used, they shall con-
above the ground or floor. Toeboards sist of first-grade manila of at least
shall be a minimum of 4 inches in three-quarter-inch diameter, or equiva-
height. Wire mesh shall be installed in lent.
accordance with paragraph (a)(17) of (3) A substantial catch platform shall
this section. be installed below the working area of
(q) Ladder-jack scaffolds. (1) All lad- roofs more than 20 feet from the
der-jack scaffolds shall be limited to ground to eaves with a slope greater
light duty and shall not exceed a than 3 inches in 12 inches without a
height of 20 feet above the floor or parapet. In width the platform shall ex-
ground. tend 2 feet beyond the projection of the
(2) All ladders used in connection eaves and shall be provided with a safe-
with ladder-jack scaffolds shall be ty rail, mid-rail, and toeboard. This
heavy-duty ladders and shall be de- provision shall not apply where em-
signed and constructed in accordance ployees engaged in work upon such
with § 1910.25 and § 1910.26. roofs are protected by a safety belt at-
(3) The ladder jack shall be so de- tached to a lifeline.
signed and constructed that it will bear (t) Crawling boards or chicken ladders.
on the side rails in addition to the lad- (1) Crawling boards shall be not less
der rungs, or if bearing on rungs only, than 10 inches wide and 1 inch thick,
the bearing area shall be at least 10 having cleats 1×11⁄2 inches. The cleats
inches on each rung. shall be equal in length to the width of
(4) Ladders used in conjunction with the board and spaced at equal intervals
ladder jacks shall be so placed, fas- not to exceed 24 inches. Nails shall be

145

VerDate Mar<15>2010 10:28 Jul 30, 2012 Jkt 226115 PO 00000 Frm 00155 Fmt 8010 Sfmt 8010 Q:\29\226115.XXX ofr150 PsN: PC150
§ 1910.29 29 CFR Ch. XVII (7–1–12 Edition)

driven through and clinched on the un- rigged lines, which will safely suspend
derside. The crawling board shall ex- the workman in case of a fall.
tend from the ridge pole to the eaves (v) Scope. This section establishes
when used in connection with roof con- safety requirements for the construc-
struction, repair, or maintenance. tion, operation, maintenance, and use
(2) A firmly fastened lifeline of at of scaffolds used in the maintenance of
least three-quarter-inch rope shall be buildings and structures.
strung beside each crawling board for a [39 FR 23502, June 27, 1974, as amended at 43
handhold. FR 49746, Oct. 24, 1978; 49 FR 5321, Feb. 10,
(3) Crawling boards shall be secured 1984; 53 FR 12121, Apr. 12, 1988]
to the roof by means of adequate ridge
hooks or equivalent effective means. § 1910.29 Manually propelled mobile
(u) Float or ship scaffolds. (1) Float or ladder stands and scaffolds (tow-
ship scaffolds shall support not more ers).
than three men and a few light tools, (a) General requirements—(1) Applica-
such as those needed for riveting, bolt- tion. This section is intended to pre-
ing, and welding. They shall be con- scribe rules and requirements for the
structed in accordance with paragraphs design, construction, and use of mobile
(u) (2) through (6) of this section, un- work platforms (including ladder
less substitute designs and materials stands but not including aerial ladders)
provide equivalent strength, stability, and rolling (mobile) scaffolds (towers).
and safety. This standard is promulgated to aid in
(2) The platform shall be not less providing for the safety of life, limb,
than 3 feet wide and 6 feet long, made and property, by establishing minimum
of three-quarter-inch plywood, equiva- standards for structural design require-
lent to American Plywood Association ments and for the use of mobile work
Grade B-B, Group I, Exterior. platforms and towers.
(3) Under the platform, there shall be (2) Working loads. (i) Work platforms
two supporting bearers made from 2×4- and scaffolds shall be capable of car-
inch, or 1×10-inch rough, selected lum- rying the design load under varying
ber, or better. They shall be free of circumstances depending upon the con-
knots or other flaws and project 6 ditions of use. Therefore, all parts and
inches beyond the platform on both appurtenances necessary for their safe
sides. The ends of the platform shall and efficient utilization must be inte-
extend about 6 inches beyond the outer gral parts of the design.
edges of the bearers. Each bearer shall (ii) Specific design and construction
be securely fastened to the platform. requirements are not a part of this sec-
(4) An edging of wood not less than tion because of the wide variety of ma-
3⁄4×11⁄2 inches, or equivalent, shall be
terials and design possibilities. How-
placed around all sides of the platform ever, the design shall be such as to
to prevent tools from rolling off. produce a mobile ladder stand or scaf-
(5) Supporting ropes shall be 1-inch fold that will safely sustain the speci-
diameter manila rope or equivalent, fied loads. The material selected shall
free from deterioration, chemical dam- be of sufficient strength to meet the
age, flaws, or other imperfections. test requirements and shall be pro-
Rope connections shall be such that tected against corrosion or deteriora-
the platform cannot shift or slip. If two tion.
ropes are used with each float, each of (a) The design working load of ladder
the two supporting ropes shall be stands shall be calculated on the basis
hitched around one end of a bearer and of one or more 200-pound persons to-
pass under the platforms to the other gether with 50 pounds of equipment
end of the bearer where it is hitched each.
again, leaving sufficient rope at each (b) The design load of all scaffolds
end for the supporting ties. shall be calculated on the basis of:
(6) Each workman shall be protected
Light—Designed and constructed to carry a
by a safety lifebelt attached to a life- working load of 25 pounds per square foot.
line. The lifeline shall be securely at- Medium—Designed and constructed to carry
tached to substantial members of the a working load of 50 pounds per square
structure (not scaffold), or to securely foot.