Beruflich Dokumente
Kultur Dokumente
VD Distribution transformers.
Binder 1/1
Operation and
Maintanance instruction 7
HV - Bushings
General Documentation
LV - Bushings
List of Aux components
Spare parts
Off Load Tap Changer 8
Pressure Valve PG50
English
Vendor references
Technical Instruction
DGPT2 9
SO 855894940
Safety Datasheet
Vendor Documentation
Binder 1 of 1
Specific/General
Distributions
Transformer
Purchase No.
4-1445344-496060 A
English
Vendor references
SO 855894940
Scope of Supply
Design Freeze
FLS Tag No. Rated Power Rated power Siemens
Equipment code kVA @ 40°C kVA @ 42°C Serial No.
1/1
2016.05.06
s
¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Siemens Zrt
Technical description Item ID: 9141140956
1/1
2016.05.06
s
¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Siemens Zrt
Technical description Item ID: 9141141277
1/1
2016.05.06
s
¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Siemens Zrt
Technical description Item ID: 9141141292
1/1
2016.05.06
s
¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Siemens Zrt
Technical description Item ID: 9141141331
1/1
2016.05.06
Siemens Zrt. Csepel
H-1214 Budapest, Hungary
II. Rákóczi Ferenc út 189.
Phone: (+36 1) 471 1100
Fax: (+36 1) 471 1130
www.siemens.hu/trafo Operation and Maintenance
Instructions
Hermetically sealed liquid-immersed distribution
transformers 50 to 2500 kVA
Hermetically sealed
Application Area Description
liquid-immersed distribution
These operating instructions are for hermetically sea-
transformers 50 to 2500 kVA led liquid-immersed three-phase distribution transfor- Tank
mers with rated power of 50-2500 kVA and up to max
36 kV equipment voltage. They are also applicable for Hermetically sealed liquid-immersed distribution trans-
Operating Instructions single-phase transformers. formers are usually made with cooling fins. All four sides
The instructions are generally valid for mineral oil-im- are made of corrugated metal plates that are welded to-
Contents Page mersed transformers, but equally applicable if any ot- gether on the four corners. Some special tanks have co-
her liquid is used for insulation. oling fins on only 1, 2 or 3 sides.
See chapter on cooling and dielectric liquid.
The number, depth and length of the cooling fins are
Application Area . . . . . . . . . . . . . . . . . . . . . 3
calculated in such a way as to provide a safe dissipa-
Description . . . . . . . . . . . . . . . . . . . . . . . . . 3 tion for the heat generated inside the transformer. The
1 2 3
Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4 cooling fins of the transformer tanks provide the nec-
Tap changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 5 essary mechanical stability and resist cyclical pressure
changes for the entire lifetime of the transformer.
Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 8 At the bottom of the transformer tank (in the “basin”),
Cooling and dielectric liquid . . . . . . . . . . . . . . . . . . . . . 6 you can find the drain valve as prescribed by EN 50216-4.
Its purpose is to drain the cooling liquid. Some models
Safety Instruction . . . . . . . . . . . . . . . . . . . . 6
are made without a drain valve.
General instruction . . . . . . . . . . . . . . . . . . . 6
The lower frame equipped with rollers is connected to
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 7
the basin. The rollers (if applicable) can be easily ad-
Checking after delivery . . . . . . . . . . . . . . . . . . . . . . . . .7 justed for lengthwise or crossways moving.
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 The earthing of the transformer can be provided by
Preparation for operation . . . . . . . . . . . . . . . . . . . . . . . .7 M12 earthing bolts. See the outline drawing (to be fo-
und among the transport documentation) for the
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 6
exact position of earthing bolts.
7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 8 At the shorter end of the cover there is a thermometer
Operation under nominal conditions . . . . . . . . . . . . . . 8 pocket as prescribed by EN 50216-4. Its exact location
Overload capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 is marked in the outline drawing. Some models are
Hermetically sealed transformer, completely immersed made without a thermometer pocket.
Star-point load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 in liquid, tank with flexible corrugated wall
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 9 The liquid filling tube serves for filling up with liquid
In general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 and also as the holder of a safety tool (safety valve or
hermetic safety device). Some models are made with-
Tightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1 Liquid filling tube (if applicable) out a liquid filling tube; in their case liquid should be
Tap changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 drained through the filling opening on the top cover
Safety devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2 Low voltage bushing of the transformer.
Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3 High voltage bushing
Tap changer
Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 4 Thermometer pocket (if applicable)
Filling up the dielectric liquid . . . . . . . . . . . . . . . . . . . . 9 5 Lifting lug Tap changers are placed horizontally under the cover.
Hermetic sealing of the transformer . . . . . . . . . . . . . 10 6 Drain valve (if applicable) They serve to change the tapping of the high voltage
coils, and to switch between serial-parallel or delta-star
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . 10 7 Rollers (if applicable)
connections of coil sections.
Troubleshooting . . . . . . . . . . . . . . . . . . . . 10 8 Lashing lug
Liquid leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Liquid temperature too high . . . . . . . . . . . . . . . . . . . . 10
Safety device becomes active . . . . . . . . . . . . . . . . . . . 10
2 3
Hermetically sealed
Application Area Description
liquid-immersed distribution
These operating instructions are for hermetically sea-
transformers 50 to 2500 kVA led liquid-immersed three-phase distribution transfor- Tank
mers with rated power of 50-2500 kVA and up to max
36 kV equipment voltage. They are also applicable for Hermetically sealed liquid-immersed distribution trans-
Operating Instructions single-phase transformers. formers are usually made with cooling fins. All four sides
The instructions are generally valid for mineral oil-im- are made of corrugated metal plates that are welded to-
Contents Page mersed transformers, but equally applicable if any ot- gether on the four corners. Some special tanks have co-
her liquid is used for insulation. oling fins on only 1, 2 or 3 sides.
See chapter on cooling and dielectric liquid.
The number, depth and length of the cooling fins are
Application Area . . . . . . . . . . . . . . . . . . . . . 3
calculated in such a way as to provide a safe dissipa-
Description . . . . . . . . . . . . . . . . . . . . . . . . . 3 tion for the heat generated inside the transformer. The
1 2 3
Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4 cooling fins of the transformer tanks provide the nec-
Tap changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 5 essary mechanical stability and resist cyclical pressure
changes for the entire lifetime of the transformer.
Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 8 At the bottom of the transformer tank (in the “basin”),
Cooling and dielectric liquid . . . . . . . . . . . . . . . . . . . . . 6 you can find the drain valve as prescribed by EN 50216-4.
Its purpose is to drain the cooling liquid. Some models
Safety Instruction . . . . . . . . . . . . . . . . . . . . 6
are made without a drain valve.
General instruction . . . . . . . . . . . . . . . . . . . 6
The lower frame equipped with rollers is connected to
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 7
the basin. The rollers (if applicable) can be easily ad-
Checking after delivery . . . . . . . . . . . . . . . . . . . . . . . . .7 justed for lengthwise or crossways moving.
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 The earthing of the transformer can be provided by
Preparation for operation . . . . . . . . . . . . . . . . . . . . . . . .7 M12 earthing bolts. See the outline drawing (to be fo-
und among the transport documentation) for the
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 6
exact position of earthing bolts.
7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 8 At the shorter end of the cover there is a thermometer
Operation under nominal conditions . . . . . . . . . . . . . . 8 pocket as prescribed by EN 50216-4. Its exact location
Overload capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 is marked in the outline drawing. Some models are
Hermetically sealed transformer, completely immersed made without a thermometer pocket.
Star-point load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 in liquid, tank with flexible corrugated wall
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 9 The liquid filling tube serves for filling up with liquid
In general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 and also as the holder of a safety tool (safety valve or
hermetic safety device). Some models are made with-
Tightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1 Liquid filling tube (if applicable) out a liquid filling tube; in their case liquid should be
Tap changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 drained through the filling opening on the top cover
Safety devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2 Low voltage bushing of the transformer.
Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3 High voltage bushing
Tap changer
Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 4 Thermometer pocket (if applicable)
Filling up the dielectric liquid . . . . . . . . . . . . . . . . . . . . 9 5 Lifting lug Tap changers are placed horizontally under the cover.
Hermetic sealing of the transformer . . . . . . . . . . . . . 10 6 Drain valve (if applicable) They serve to change the tapping of the high voltage
coils, and to switch between serial-parallel or delta-star
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . 10 7 Rollers (if applicable)
connections of coil sections.
Troubleshooting . . . . . . . . . . . . . . . . . . . . 10 8 Lashing lug
Liquid leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Liquid temperature too high . . . . . . . . . . . . . . . . . . . . 10
Safety device becomes active . . . . . . . . . . . . . . . . . . . 10
2 3
Operation of the top changer is possible on the cover, Upon client’s request, the high voltage porcelain bus- error alert is generated by embedded electrical con-
only if the transformer is de-energized. hings may be equipped with coordinating spark-gaps tacts. (The model delivered is provided on the outline
in order to provide curved diversion against impulse drawing, and the original manual is included.)
Bushings voltage. The size of the spark-gap between the horns
can be changed. For the recommended values, see // Pressure relay
Bushings used on the high voltage side are usually Bushings used on the low voltage side are usually se- the outline drawing.
according to Standard EN 50180. Frequently used lected from among the following models: As an option, transformers may also be ordered equip-
models: Safety devices ped with a pressure sensor installed onto their cover.
The pressure sensor has the function of giving an alert
// Thermometer if the overpressure generated inside the transformer
exceeds the value set by the manufacturer. The error
As an option, different types of temperature measuring alert is generated by embedded electrical contacts.
devices can be connected to the transformers. All of (The model delivered is provided on the outline draw-
these are built in to the thermometer pocket on the co- ing, and the original manual is included.)
ver, serving to measure the temperature of the liquid in
the warmest part, right under the cover. The so-called // Integrated safety device
dial type thermometers are equipped with a local screen
and one or more contact points. A separate device sho- As an option, transformers may also be ordered equip-
uld be used for the evaluation of the PT100-based sen- ped with an integrated safety device installed onto
sors’ signals. (The model delivered is provided on the their cover. The integrated safety device provides in-
Porcelain bushing outline drawing, and the original manual is included.) formation about temperature, pressure, liquid level
as per standard EN 50386 and gases formed due to internal fault. A detailed de-
Porcelain bushing (Um=12-36 kV; Im=250-1000 A) (Um=1.1 kV; Im=250A - 3150A) scription is available in the original manual of the de-
vice. (The model delivered is provided on the outline
Porcelain bushing
drawing, and the original manual is included.)
as per standard DIN 42539
(Um=3.6 kV; Im=250A - 3150A)
If the safety device is installed at a later stage, it is im-
portant to read the instructions regarding the opening
of Siemens transformers (see Installation).
// Gas relay
Plug-in outer cone bushing As an option, transformers may also be ordered equ-
(Um=12-36 kV; Im=250-1000 A) ipped with a Buchholz (gas) relay installed onto their
cover. The Buchholz relay accumulates gases deriving
from any internal fault of the transformer and the air
that may get into the transformer through leaks. The
Busbar bushings
as per standard EN 50387
(Um=1.1 kV; Im=250A - 2500 A)
4 5
Operation of the top changer is possible on the cover, Upon client’s request, the high voltage porcelain bus- error alert is generated by embedded electrical con-
only if the transformer is de-energized. hings may be equipped with coordinating spark-gaps tacts. (The model delivered is provided on the outline
in order to provide curved diversion against impulse drawing, and the original manual is included.)
Bushings voltage. The size of the spark-gap between the horns
can be changed. For the recommended values, see // Pressure relay
Bushings used on the high voltage side are usually Bushings used on the low voltage side are usually se- the outline drawing.
according to Standard EN 50180. Frequently used lected from among the following models: As an option, transformers may also be ordered equip-
models: Safety devices ped with a pressure sensor installed onto their cover.
The pressure sensor has the function of giving an alert
// Thermometer if the overpressure generated inside the transformer
exceeds the value set by the manufacturer. The error
As an option, different types of temperature measuring alert is generated by embedded electrical contacts.
devices can be connected to the transformers. All of (The model delivered is provided on the outline draw-
these are built in to the thermometer pocket on the co- ing, and the original manual is included.)
ver, serving to measure the temperature of the liquid in
the warmest part, right under the cover. The so-called // Integrated safety device
dial type thermometers are equipped with a local screen
and one or more contact points. A separate device sho- As an option, transformers may also be ordered equip-
uld be used for the evaluation of the PT100-based sen- ped with an integrated safety device installed onto
sors’ signals. (The model delivered is provided on the their cover. The integrated safety device provides in-
Porcelain bushing outline drawing, and the original manual is included.) formation about temperature, pressure, liquid level
as per standard EN 50386 and gases formed due to internal fault. A detailed de-
Porcelain bushing (Um=12-36 kV; Im=250-1000 A) (Um=1.1 kV; Im=250A - 3150A) scription is available in the original manual of the de-
vice. (The model delivered is provided on the outline
Porcelain bushing
drawing, and the original manual is included.)
as per standard DIN 42539
(Um=3.6 kV; Im=250A - 3150A)
If the safety device is installed at a later stage, it is im-
portant to read the instructions regarding the opening
of Siemens transformers (see Installation).
// Gas relay
Plug-in outer cone bushing As an option, transformers may also be ordered equ-
(Um=12-36 kV; Im=250-1000 A) ipped with a Buchholz (gas) relay installed onto their
cover. The Buchholz relay accumulates gases deriving
from any internal fault of the transformer and the air
that may get into the transformer through leaks. The
Busbar bushings
as per standard EN 50387
(Um=1.1 kV; Im=250A - 2500 A)
4 5
Cooling and dielectric liquid Installation ATTENTION!
Transformer oils are made from mineral oils through DANGER! Relevant standards regarding insta-
distillation and refining. llation and safety, as well as the inst-
They have a low viscosity; their density is around General instruction In case of faulty transport, falling units ructions of safe operation issued by the
0.86 g/cm3 at 20 °C; their flash point is between can cause injury to persons or damage to local authority, should be strictly follo-
140 and 160°C and their dielectric characteristics are Independent of the safety instruction specified in this the unit. wed.
excellent. description, local rules, regulations, directives and
standards regarding the operation of electrical equip- I Make sure that the lifting and transport devices suit
Quality requirements are set by standard IEC 60296. ment, as well as the protection of labour, health and the requirements of composition and load capa- If the transformer is an indoor type, it must be instal-
The transformer is filled up with a liquid according to the environment, are valid. city. led in a covered space, in a so-called transformer cell.
the client’s request. The default type can be found on The five safety rules of electrotechnics must be kept I Ensure even load distribution and centre of gravity. Ventilation of the cell should be ensured to provide
the rating plate and in the technical description. during the maintenance of the products and their parts I In case of rigging by crane, make sure to use all proper cooling for the transformer.
described in this manual: lifting lugs as indicated on the outline drawing.
Waste treatment, disposal: used transformer oil quali- Asymmetric lifting may lead to damage to the The transformer should be positioned at an appropri-
fies as hazardous waste as per Directive 2000/532/EC – De-energising product or physical injury. ate distance from the walls of the cell in order to allow
on the list of hazardous waste, where it is coded – Ensuring that there is no switching-back I The transformer can only be moved by fork lift truck unobstructed airflow for the cooling.
13 03 07* EWC, among mineral-based non-chlorina- – Verifying uncharged (off-voltage) state. by lifting it on the spots marked with stickers. Ensure
ted insulating and heat transmission oils. Waste treat- – Earthing and short circuiting. even load distribution and be aware of the risks of If the transformer is installed equipped with rollers, at
ment should be in accordance with corresponding – Enclosing or covering adjacent parts under voltage. tipping. least two of the rollers have to be fixed to prevent dis-
legislation. placement.
Proper use.
Upon the client’s request, the transformer can be Checking after delivery. If standard transformers are installed at an altitude hig-
filled up with silicon liquid as well (as per standard The Transformer and its accessories are in compliance her than 1000 m it has to be considered that, with the
IEC 60836) or synthetic organic ester (as per stan- with the legal rules, prescriptions and standards valid Transformers leave the factory filled up with liquid and increase in altitude and the decrease in the air’s den-
dard IEC 61099). These must never be mixed with at the time of delivery. They are suitable for proper use ready for operation. Their completeness and intactness sity, the dielectric strength of the air - a determining
mineral oil. The default dielectric liquid type can with a high level of safety. must be checked upon arrival to site. factor in the external arching distances (approximately
be found on the rating plate and in the technical 6% decrease per 500 m) - also decreases. The dissipa-
description. Should there be any damage done to the product, re- ting heat volume of the tank and hence the perfor-
sponsibilities and allocation of costs should be discus- mance of the transformer, therefore, also tend to
sed with the transporter, if possible, in the presence of decrease (by about 2% per 500 m).
Safety Instruction DANGER! a Siemens representative. The factory, too, should be
informed via the Siemens representative. Preparation for operation
Signal terms and definitions Requirements for the trouble-free and
safe operation of the transformer: Separately shipped temperature measuring and cont-
ATTENTION! rolling devices (if any) have to be screwed into the
DANGER! I Always take into consideration Operation and Main- thermometer pockets filled with oil.
tenance Instructions Detailed information on liquid leakage in
The signal means that physical injuries I Employ only qualified personnel. the “Liquid leakage” chapter. Unused thermometer pockets should also be filled up
may occur if the required safety rules I Ensure that transport and storage of the device are with oil to prevent corrosion. The pockets are sealed
and instruction are not kept. done in a professional way. with a 1” screw-plug.
« Always comply with the safety instructions. I Ensure that the installation and commissioning of Installation
the device are done in a professional way. The safety devices are usually equipped with a connec-
I Pay close and continued attention to operation and Siemens transformers can be installed indoors or out- tion. The connections have to be connected to the cir-
maintenance. doors. The type of the product can be found in the cuit leading into the control room (see original user
ATTENTION! I Observe the installation, operation and safety regu- technical description. manuals of the devices and the wiring diagram).
lations valid at the site of installation.
The signal means that product or envi- All screws and all threaded joints have to be checked
ronmental damage may occur if the rele- for tightness. Screws connecting to the bushings have
vant safety rules are not kept. to be tightened with the nominal torque set in chart
« Always comply with the safety instructions. no. 1. These torque values are set assuming the use of
grease or oil lubricant. The torque value has to be
6 7
Cooling and dielectric liquid Installation ATTENTION!
Transformer oils are made from mineral oils through DANGER! Relevant standards regarding insta-
distillation and refining. llation and safety, as well as the inst-
They have a low viscosity; their density is around General instruction In case of faulty transport, falling units ructions of safe operation issued by the
0.86 g/cm3 at 20 °C; their flash point is between can cause injury to persons or damage to local authority, should be strictly follo-
140 and 160°C and their dielectric characteristics are Independent of the safety instruction specified in this the unit. wed.
excellent. description, local rules, regulations, directives and
standards regarding the operation of electrical equip- I Make sure that the lifting and transport devices suit
Quality requirements are set by standard IEC 60296. ment, as well as the protection of labour, health and the requirements of composition and load capa- If the transformer is an indoor type, it must be instal-
The transformer is filled up with a liquid according to the environment, are valid. city. led in a covered space, in a so-called transformer cell.
the client’s request. The default type can be found on The five safety rules of electrotechnics must be kept I Ensure even load distribution and centre of gravity. Ventilation of the cell should be ensured to provide
the rating plate and in the technical description. during the maintenance of the products and their parts I In case of rigging by crane, make sure to use all proper cooling for the transformer.
described in this manual: lifting lugs as indicated on the outline drawing.
Waste treatment, disposal: used transformer oil quali- Asymmetric lifting may lead to damage to the The transformer should be positioned at an appropri-
fies as hazardous waste as per Directive 2000/532/EC – De-energising product or physical injury. ate distance from the walls of the cell in order to allow
on the list of hazardous waste, where it is coded – Ensuring that there is no switching-back I The transformer can only be moved by fork lift truck unobstructed airflow for the cooling.
13 03 07* EWC, among mineral-based non-chlorina- – Verifying uncharged (off-voltage) state. by lifting it on the spots marked with stickers. Ensure
ted insulating and heat transmission oils. Waste treat- – Earthing and short circuiting. even load distribution and be aware of the risks of If the transformer is installed equipped with rollers, at
ment should be in accordance with corresponding – Enclosing or covering adjacent parts under voltage. tipping. least two of the rollers have to be fixed to prevent dis-
legislation. placement.
Proper use.
Upon the client’s request, the transformer can be Checking after delivery. If standard transformers are installed at an altitude hig-
filled up with silicon liquid as well (as per standard The Transformer and its accessories are in compliance her than 1000 m it has to be considered that, with the
IEC 60836) or synthetic organic ester (as per stan- with the legal rules, prescriptions and standards valid Transformers leave the factory filled up with liquid and increase in altitude and the decrease in the air’s den-
dard IEC 61099). These must never be mixed with at the time of delivery. They are suitable for proper use ready for operation. Their completeness and intactness sity, the dielectric strength of the air - a determining
mineral oil. The default dielectric liquid type can with a high level of safety. must be checked upon arrival to site. factor in the external arching distances (approximately
be found on the rating plate and in the technical 6% decrease per 500 m) - also decreases. The dissipa-
description. Should there be any damage done to the product, re- ting heat volume of the tank and hence the perfor-
sponsibilities and allocation of costs should be discus- mance of the transformer, therefore, also tend to
sed with the transporter, if possible, in the presence of decrease (by about 2% per 500 m).
Safety Instruction DANGER! a Siemens representative. The factory, too, should be
informed via the Siemens representative. Preparation for operation
Signal terms and definitions Requirements for the trouble-free and
safe operation of the transformer: Separately shipped temperature measuring and cont-
ATTENTION! rolling devices (if any) have to be screwed into the
DANGER! I Always take into consideration Operation and Main- thermometer pockets filled with oil.
tenance Instructions Detailed information on liquid leakage in
The signal means that physical injuries I Employ only qualified personnel. the “Liquid leakage” chapter. Unused thermometer pockets should also be filled up
may occur if the required safety rules I Ensure that transport and storage of the device are with oil to prevent corrosion. The pockets are sealed
and instruction are not kept. done in a professional way. with a 1” screw-plug.
« Always comply with the safety instructions. I Ensure that the installation and commissioning of Installation
the device are done in a professional way. The safety devices are usually equipped with a connec-
I Pay close and continued attention to operation and Siemens transformers can be installed indoors or out- tion. The connections have to be connected to the cir-
maintenance. doors. The type of the product can be found in the cuit leading into the control room (see original user
ATTENTION! I Observe the installation, operation and safety regu- technical description. manuals of the devices and the wiring diagram).
lations valid at the site of installation.
The signal means that product or envi- All screws and all threaded joints have to be checked
ronmental damage may occur if the rele- for tightness. Screws connecting to the bushings have
vant safety rules are not kept. to be tightened with the nominal torque set in chart
« Always comply with the safety instructions. no. 1. These torque values are set assuming the use of
grease or oil lubricant. The torque value has to be
6 7
verified after a few weeks, and the screws have to be The voltage ratio has to be controlled with an approp- Maintenance
tightened if needed. riate measuring instrument at every tapping position
and/or at every tapping outlet. The result has to be the In general
Nominal current 250 A 630 A 1250 A 2000 A 3150 A
same at all three phases.
Bushing stem M12 M20 M30 M42 M48
ATTENTION! Earthing
(copper or bronze) 20 Nm 70 Nm - - -
After these preparatory measures the transformer can
Bushing terminal M12 M12 M12 M12 M12
be connected to the network. Afterwards it can be run Maintenance can only be performed The earthing of the transformer must be checked.
(steel bolt) 40 Nm 40 Nm 40 Nm 40 Nm 40 Nm
with no load, then loaded. If, however, the transfor- by qualified and authorized personnel,
For other connecting parts please follow the manufacturer’s instructions. mer is operated in parallel with another one, it is nec- in full compliance with the rules of tech- Filling up the dielectric liquid
essary to make sure, before the establishment of the nical safety.
Chart no. 1 nominal tightening torque parallel connection, that there is no potential diffe- Low liquid levels can cause serious damage to the
rence between the corresponding terminals of the transformer. If you are not sure whether the transfor-
The tank and cover have to be earthed in accordance transformers. Before any maintenance operation is performed, all mer is in proper condition, please contact a Siemens
with the specifications. switches before and after the transformer must be swit- representative before a liquid refill.
Hermetically closed transformers are completely filled Operation ched off. Every line connection must be short-circuited
up with liquid. There is no need to check the liquid le- and earthed. Standard EN 50110 must be observed. Though the dielectric liquid needed for filling was ob-
vel. Upon the client’s request an liquid level indicator Operation under nominal conditions tained directly from the transformer’s manufacturer or
can be included; in this case we enclose specific inst- Siemens transformers have low maintenance needs. from the liquid’s manufacturer in sealed barrels, the
ructions for the liquid level indicator. The transformer operates under nominal conditions condition of which seems entirely satisfactory, it is still
if nominal current runs on the secondary side, while Siemens’ hermetically sealed liquid-cooled transfor- advisable to check the dielectric stability of the liquid in
Preliminary Checks nominal voltage is connected to the primary side. The mers must not be opened and its bushings must not every barrel.
full load secondary voltage is different from a nomi- be de-aerated.
Check the data provided on the rating plate on the nal no-load voltage, and this is caused by the voltage Hoses, pumps and containers used for filling must be
transformer tank. If the transformer is operated in pa- change due to the load current that also depends on Hermetical sealing ensures that no moisture gets into cleaned beforehand and flushed with the new, treated
rallel with another transformer, particular attention the power factor of the load. The change in voltage, the insulating liquid of the transformers; never there- liquid.
should be paid to the voltage ratio, the vector group when converted to the secondary nominal voltage, is fore take an liquid sample from the transformer.
and the impedance voltage. The tap changer should proportional to the load current and at nominal cur- Should the transformer be urgently opened, for exam-
be set to a system voltage matching the supply net- rent it can reach the impedance voltage value given Tightness ple for mounting a protective device in contact with
work voltage, and the same is true for the other com- in the rating plate. Inductive load causes voltage the liquid, repairs, replacing a bushing or a gasket, the
mutators (if the transformer is a dual voltage device). drop, while capacitive load (negative power factor) It must be checked that the transformer runs with no procedure is as follows:
causes voltage increase. oil leak at standard operating temperature.
Reliability of the earthing should be checked. Bushing
insulators should be cleaned. The functioning of the Overload capacity Tap changer ATTENTION!
Buchholz (gas) relay should be checked (using the test
button), and the temperature control device should Standard IEC 60076-7 Loading guide for oil-immer- If the transformer voltage ratio needs to be changed, On transformers without a filling tube
also be checked according to the operating manual. sed power transformers forms the basis of the load the tap changer of the de-energized transformer should and/or a drain valve, a professional repair
capacity of oil immersed transformers with universal be switched through all the tapping positions several involving the hermetic seal can only be
As a quick check-through and in order to ensure that validity, in which life span is taken into account. It is times in order to clean the contact surfaces. After this, carried out with tools ordered from the
there is no serious damage done to the device that can- necessary to remember that the observed oil tempe- the desired transfer ratio can be set based on the con- manufacturer. Contact a Siemens repre-
not be seen externally but may have been done during rature values that can be measured at overload are nection diagram. sentative.
transport, it is advisable to check and verify uninter- not indicative of the actual temperatures of the coils.
rupted conduction, as well as the insulation resistance Safety devices
between the windings and between the windings and Star-point load 1.Drain the cooling and dielectric liquid through the
the earth by an isolation resistance meter (e.g. a 3000V Operation of the safety devices should be checked drain valve, until the flow stops.
one by Megger). The following type of continuous load is permissible according to the enclosed original manuals.
In a new transformer the insulation resistances are nor- on the secondary terminals of the three-phase trans- 2. Take the threaded nut off the filling tube or take
mally more than 1000 Mohms. former: Bushings the protective device off and drain the liquid until
For a Yyn vector group, it is 10% of the nominal cur- the liquid level is approximately 50 mm below the
It is of fundamental importance to make certain that rent, while in the case of a Dyn, Yzn or Dzn vector Bushings have to be cleaned and checked for potential cover (check it through the filling tube with a level
the insulators are clean and dry during testing. group it is 100% of the nominal current. damage, and the proper position of the arcing horns. meter).
The fixing and the lead out screws have to be tighte-
ned if needed.(see chart no. 1.) 3. Carry out the necessary work on the transformer.
8 9
verified after a few weeks, and the screws have to be The voltage ratio has to be controlled with an approp- Maintenance
tightened if needed. riate measuring instrument at every tapping position
and/or at every tapping outlet. The result has to be the In general
Nominal current 250 A 630 A 1250 A 2000 A 3150 A
same at all three phases.
Bushing stem M12 M20 M30 M42 M48
ATTENTION! Earthing
(copper or bronze) 20 Nm 70 Nm - - -
After these preparatory measures the transformer can
Bushing terminal M12 M12 M12 M12 M12
be connected to the network. Afterwards it can be run Maintenance can only be performed The earthing of the transformer must be checked.
(steel bolt) 40 Nm 40 Nm 40 Nm 40 Nm 40 Nm
with no load, then loaded. If, however, the transfor- by qualified and authorized personnel,
For other connecting parts please follow the manufacturer’s instructions. mer is operated in parallel with another one, it is nec- in full compliance with the rules of tech- Filling up the dielectric liquid
essary to make sure, before the establishment of the nical safety.
Chart no. 1 nominal tightening torque parallel connection, that there is no potential diffe- Low liquid levels can cause serious damage to the
rence between the corresponding terminals of the transformer. If you are not sure whether the transfor-
The tank and cover have to be earthed in accordance transformers. Before any maintenance operation is performed, all mer is in proper condition, please contact a Siemens
with the specifications. switches before and after the transformer must be swit- representative before a liquid refill.
Hermetically closed transformers are completely filled Operation ched off. Every line connection must be short-circuited
up with liquid. There is no need to check the liquid le- and earthed. Standard EN 50110 must be observed. Though the dielectric liquid needed for filling was ob-
vel. Upon the client’s request an liquid level indicator Operation under nominal conditions tained directly from the transformer’s manufacturer or
can be included; in this case we enclose specific inst- Siemens transformers have low maintenance needs. from the liquid’s manufacturer in sealed barrels, the
ructions for the liquid level indicator. The transformer operates under nominal conditions condition of which seems entirely satisfactory, it is still
if nominal current runs on the secondary side, while Siemens’ hermetically sealed liquid-cooled transfor- advisable to check the dielectric stability of the liquid in
Preliminary Checks nominal voltage is connected to the primary side. The mers must not be opened and its bushings must not every barrel.
full load secondary voltage is different from a nomi- be de-aerated.
Check the data provided on the rating plate on the nal no-load voltage, and this is caused by the voltage Hoses, pumps and containers used for filling must be
transformer tank. If the transformer is operated in pa- change due to the load current that also depends on Hermetical sealing ensures that no moisture gets into cleaned beforehand and flushed with the new, treated
rallel with another transformer, particular attention the power factor of the load. The change in voltage, the insulating liquid of the transformers; never there- liquid.
should be paid to the voltage ratio, the vector group when converted to the secondary nominal voltage, is fore take an liquid sample from the transformer.
and the impedance voltage. The tap changer should proportional to the load current and at nominal cur- Should the transformer be urgently opened, for exam-
be set to a system voltage matching the supply net- rent it can reach the impedance voltage value given Tightness ple for mounting a protective device in contact with
work voltage, and the same is true for the other com- in the rating plate. Inductive load causes voltage the liquid, repairs, replacing a bushing or a gasket, the
mutators (if the transformer is a dual voltage device). drop, while capacitive load (negative power factor) It must be checked that the transformer runs with no procedure is as follows:
causes voltage increase. oil leak at standard operating temperature.
Reliability of the earthing should be checked. Bushing
insulators should be cleaned. The functioning of the Overload capacity Tap changer ATTENTION!
Buchholz (gas) relay should be checked (using the test
button), and the temperature control device should Standard IEC 60076-7 Loading guide for oil-immer- If the transformer voltage ratio needs to be changed, On transformers without a filling tube
also be checked according to the operating manual. sed power transformers forms the basis of the load the tap changer of the de-energized transformer should and/or a drain valve, a professional repair
capacity of oil immersed transformers with universal be switched through all the tapping positions several involving the hermetic seal can only be
As a quick check-through and in order to ensure that validity, in which life span is taken into account. It is times in order to clean the contact surfaces. After this, carried out with tools ordered from the
there is no serious damage done to the device that can- necessary to remember that the observed oil tempe- the desired transfer ratio can be set based on the con- manufacturer. Contact a Siemens repre-
not be seen externally but may have been done during rature values that can be measured at overload are nection diagram. sentative.
transport, it is advisable to check and verify uninter- not indicative of the actual temperatures of the coils.
rupted conduction, as well as the insulation resistance Safety devices
between the windings and between the windings and Star-point load 1.Drain the cooling and dielectric liquid through the
the earth by an isolation resistance meter (e.g. a 3000V Operation of the safety devices should be checked drain valve, until the flow stops.
one by Megger). The following type of continuous load is permissible according to the enclosed original manuals.
In a new transformer the insulation resistances are nor- on the secondary terminals of the three-phase trans- 2. Take the threaded nut off the filling tube or take
mally more than 1000 Mohms. former: Bushings the protective device off and drain the liquid until
For a Yyn vector group, it is 10% of the nominal cur- the liquid level is approximately 50 mm below the
It is of fundamental importance to make certain that rent, while in the case of a Dyn, Yzn or Dzn vector Bushings have to be cleaned and checked for potential cover (check it through the filling tube with a level
the insulators are clean and dry during testing. group it is 100% of the nominal current. damage, and the proper position of the arcing horns. meter).
The fixing and the lead out screws have to be tighte-
ned if needed.(see chart no. 1.) 3. Carry out the necessary work on the transformer.
8 9
CAUTION! If silicon liquid and any other dielectric liquid is used,
please contact a Siemens representative to help
The contents of the liquid’s safety data choose the appropriate type of gasket.
sheet must be kept in order to avoid inju- If a liquid leakage is discovered along the welds, call
ries or damage to health, and the neces- our service team by all means.
sary personal protective equipment must
be provided. DANGER!
If a leakage continues for a long time at a threaded If the transformer is shut down by any of the safety
connection point, the gasket will become damaged devices, please do not switch it back on without iden-
and lets in the air and, with it, moisture will get into tifying the reason for the activation of the safety de-
the transformer. It should first be attempted to tighten vice. Further details can be found in the original user
the screws, and if this yields no result the gasket must manual of the safety device.
be replaced. The material of the gaskets depends on
the dielectric liquid used.
In the case of mineral oil and synthetic organic ester:
oil resistant rubber (NBR)
10 11
Siemens Zrt. Csepel
H-1214 Budapest, Hungary
II. Rákóczi Ferenc út 189.
Phone: (+36 1) 471 1100
Fax: (+36 1) 471 1130
www.siemens.hu/trafo Operation and Maintenance
Instructions
Hermetically sealed liquid-immersed distribution
transformers 50 to 2500 kVA
Aux. Components on the different sizes of transformers
HV-Bushing
LV-Bushing acc. to EN 50386
1.1kV 1250A bottom flag
LV Bushing according to
EN50386
1.1kV 2000A
LV Bushing according to
EN50386
1.1kV 3150A
Tap-changer head Tap-changer head: metal actuator
Type
Pressure limit
Housing
Cap
Shaft
Washer
Nut
O-ring
TECHNICAL INSTRUCTIONS
DGPT2@
TECH.INSTRUCTIONS Page
,) Rev
N" T/{OT-0021 Date:24/06174
DGPT2@ 1 6
AUTOMATION 2OOO g
I- INSTALLATION (COMPLETELY FILLED HERMETIC
TRANSFORMERS)
l.l Preamble
The following installation procedure is given for information only. Automation 2000
cannot be held responsible for its execution.
Drain tap
Level indicator
Fixing hook
float
2.L Preamble
The following installation procedure is given for information only. Automation 2000
cannot be held responsible for its execution.
Sampling tap
IB insert
TECH.INSTRUCTIONS Page
Rev
N'T/NOT-0021 Date:2.A/06ft4
DGPT2@ 3 6
AUTOMATION 2OOO
TIcTTTENING PRECAUTIoNS
INhen you tighten the HMï bolts on the DGPT2ø fixing hooks, make sure that:
Ln¿.TT,nooFNES S PRECAUTIoNS
The DGPT2@ drnin tap's leakproofness is insured by a FPM seal positioned at the root of
the scr ew thre ad under cut.
NEVER USE Teflono tape (or similar tape) to insure the DGPT2o drain tap's
=
leakproofness through its screw thread.
3- ELECTRICAL OPERATION
3.L Preamble
Gas discharge is usually due to an electrical defect in the transformer active parf
creating an electrical arc not strong enough to cause an instantaneous pressure
increase.
NORMAL LEVEL
Reed contact(s)
Triggering float C
Indicator float a o o
o a
Terminal
Reed
3', 2' 1 J 2 7 block
o cco
G2 G1.
(øs an option)
When the gas volume inside the gas accumulation tank reaches a certain value
(depending on the dielectric density), the Reed contact changes position.
Dielectric density < 1 t Volume < 140 cms
Dielectric density = 1 ) Volume = 1.40 cm: (t5 cm:)
Dielectric density > L Ð Volume > L40 cms
NORMAL PRESSURE
a
Setting system Terrninal
6' 5' 4' block
a c
P2 Pl.
(øs an option)
When the tank pressure reaches the set-point value (10.01 bar), the pressure switch's
contact changes position.
3.2.3 Temperøture
Thermostats' contacts
T1 setting
system NOO Nc NoO NC
C C
T2 setting
eco
system
Terminal
t2 tl 10 9 block
coe a
BB
T2 T1.
When the dielectric temperature reaches the set-point value (t2.5"C), the
thermostaf s contact changes position.
TECH.INSTRUCTIONS Page
Rev
N" TA0T-002L Date:24/06fl4
DGI'f2@ 6 6
AUTOMATION 2OOO
4- TESTS
4.l Precautions
Beþre cørrying out the tests, make sure:
. That the transformer is not powered.
. To carefully check the wiring system.
. That the electric interlocking system is powered so that the loops can be tested
up to the final element (e.g. LED for alarm functiory actuators
for trigger function).
4.2Gas discharge
Element concerned: Reed contøct
Moving a magnet (minimum Ø 22 mm, thickness Reed
housing
10 mm) under the Reed housing (or on the side) will
change the contacfs position. Magnet
Check that the loop is operating correctly.
4.4 Temperature
CRACKS
5.3 Chemical and solvent prohibited with the DGPT2@ plastic body
A F
Acetone Fluorodichloromethane
Acrylonitrile Formic acid, concentrated
Allyl alcohol Furfuralcohol
Ammonium sulfide,40%
Amyl alcohol G
Aniline Gasoline (5% methanol)
Glacial acetic acid
B
Benzaldehyde H
Benzoic acid* Hydrazine hydrate, S0%
Bromine,liquid Hydrochloric acid, concentrated
L,3-butanediol
1,4-butanediol I
Z3-butanediol Isoamyl alcohol
n-butyl alcohol Isopropanol
t-butyl alcohol
Butylene glycol M
Methylene chloride
C Methyl ethyl ketone
Chloroform
Chlorosulfuric acid N
Crotonaldehyde Nitric acid,2%
Cyclohexane Nitric acid,10o/o
Nitric acid,3}%
D
1,2-dichloroethane P
L,2-dichloroethylene Potassium chlorate*
Difl uoromonochloromethane n-propanol
Dimethylformamide Propylene glycol
1,4-dioxane
s
E Sulfuric acid, concentrated
Ethyl alcohol
Ethylamine,33% T
Ethylene diamine Tartaric acid*
Ethylene glycol
TECH.INSTRUCTIONS Page
Rev
N'T/!OT-0021 Date:24/06fl4
DGPf2@ I 6
AUTOMATION 2OOO g
6- TECHNICAL DATA
6.5 Thermostats
- 2 adjustable independent fluid expansion thermostats
- Ambient temperafure compensation
- Change-over contacts
- Setting scale: 40-1,40"C
- Setting accuracy: +2.5"C
- Measure accuracy: +3"C at 60oC, +L.s"C at 90"C
TECH. INSTRUCTIONS Page
Rev
N'T/NOT-0021 Date:24/06fl4
DGIT2@ 10 6
AUTOMATION 2OOO
6.6 Thermometer
- 1 fluid expansion thermometer with tracking pointer access that can be sealed
by lead
Indicøtor diameter: 50 mm
- Ambient temperafure compensation
- Tracking pointer indicating maximum temperature reached
- Display scale: 40-150"C
- Reading accuracy: +L"C
- Measure accuracy: +4"C at60"C, +L.soc at 90"C
6.7 Fitting
- Fitting at thebase of the housing through a flange in composite with a thermowell
to be installed on a 60 mm diameter opening (FPM seal and fixing hooks supplied).
Flønge diameter:8S mm
Thermotttell:104 mm (length), 27-24mm (diameter from top to bottom end)
- The flanse and the thermowell do not conduct electricitv.
)
alP'qq
148
Flange axis
28
2',25
297
44
ø85
ø97
104
8- OPTIONS
with an offset
2GDz 2 gas contacts
The DGPT2o is equipped with two Reed contacts, whose triggering thresholds are
offset by 40 cma approximately.
Conforming to IEC EN 50216:3 Standard, the Reed contacts change position when
the gas inside the transparent body reaches a volume between 100 and 200 cm¡.
€.ñåß
FA: thermometer visible on the cover side
The graduated dial of the thermometer is visible on
the cover side of the metal housing.
li
l
L Reed contact
Spare part for Standard DGPT2@.
TECH.INSTRUCTIONS Page
Rev
N'T/NOT-0021 Date:24/06fl4
DGPT2@ 15 6
AUTOMATION 2OOO
Antimagnetic shield
This accessory has been designed to prevent
spurious releases of the DGPT2o's Reed contact in
highly magnetic environments.
Made of AISI 430 ferromagnetic stainless steel, it is
supplied with its fixing screw.
Drain tap
Spare part made of nickel plated brass.
Fixing hooks
Spare parts made
steel.
of steel or AISI 316L stainless
\)er{
1?'-
Flat seal for drain tap
Spare part made of FPM for drain tap with or with-
out popoff relief valve.
TECH.INSTRUCTIONS Page
Rev
N'T/NOT-0021 Date:24/06fl4
DGFf2@ t6 6
Conforms to Regulation (EC) No. 1907/2006 (REACH), Annex ll, as amended by Commission Regulation (EU) 2015/830
Nytro Libra I
NYTVIU'
SAFETY DATA SHEET \
Date of printing 2016-02-19
Date of issue/ Date of revision 2016-02-19
Date of previous issue 2015-09-17
Version 2
Date of issue/Date of revision 201G02-19 Date of previous issue 201í09-17 Version :2 1/35
Gonforms to E No. 1907/2006 Annex Il
Nytro Libra
Signalword Danger
Hazard statements H304 - May be fatal if swallowed and enters airways
Precautionary statements
Prevention Not applicable.
Response P30l + P310 + P331 - lF SWALLOWED: lmmediately cail a pOISON CENTER or
physician. Do NOT induce vomiting.
Storage P405 - Store locked up.
Disposal P501 - Dispose of contents and container in accordance with all local, regional,
national and international regulations.
Annex XVll - Restrictions on Not applicable.
the manufacture, placing on
the market and use of
certain dangerous
substances, mixtures and
articles
Date of issue/Date of revision i 2016-02-19 Date of previous issue 201t09-17 Version :2 2/35
Conforms to ulation No. 1907/2006 H Annex ll
Nytro Libra
Annex I Nota L applies to the base oil(s) in this product. Nota L - The classification as a carcinogen need not apply if it
can be shown that the substance contains less than 3 % DMSO extract as measured by lP 346.
There are no additional ingredients present which, within the current knowledge of the supplier and in the
concentrations applicable, are classified as hazardous to health or the environment, are PBTs or vPvBs or have been
assigned a workplace exposure limit and hence require reporting in this section.
Tvpe
[1] Substance classified with a health or environmental hazard
[2] Substance with a workplace exposure limit
[3] Substance meets the criteria for PBT according to Regulation (EC) No. 1907/2006, Annex Xlll
[4] Substance meets the criteria for vPvB according to Regulation (EC) No. 1907/2006, Annex XIll
[5] Substance of equivalent concern
Accidental high pressure injection through the skin requires immediate medical
attention. Do not wait for symptoms to develop.
lngestion Always assume that aspiration has occurred. Do not induce vomiting. Can enter
lungs and cause damage. lf vomiting occurs, the head should be kept low so that
vomit does not enter the lungs. Seek professional medical attention or send the
casualty to a hospital. Do not wait for symptoms to develop.
Before attempting to rescue casualties, isolate area from all potential sources of
ignition including disconnecting electrical supply. Ensure adequate ventilation and
check that a safe, breathable atmosphere is present before entry into confined
spaces.
Date of issue/Date of revision 201 6-02-19 Date of previous issue :201*09-17 Version :2 3/35
Conforms to No. 1907/2006 Annex ll
Nytro Libra
Unsuitable extinguishing Do not use direct water jets on the burning product; they could cause splattering
media and spread the fire. Simultaneous use of foam and water on the same surface is to
be avoided as water destroys the foam.
Note : recommended measures are based on the most likely spillage scenarios for
this material; however, local conditions (wind, air temperature, wave/current
direction and speed) may significantly influence the choice of appropriate actions.
For this reason, local experts should be consulted when necessary. Local
Date of issue/Date of revision 201 6-02-19 Date of previous l'ssue :201*09-17 Vers¡on :2 4/35
Gonforms to ulation No. 1907/2006 REAC Annex ll
Nytro Libra
Large spillages: full body suit of chemically resistant and thermal resistant material
should be used. Work gloves providing adequate chemical resistance, specifically to
aromatic hydrocarbons. Note : gloves made of PVA are not water-resistant, and are
not suitable for emergency use. Safety helmet, antistatic non-skid safety shoes or
boots. Goggles and /or face shield, if splashes or contact with eyes is possible or
anticipated.
Respiratory protection : A half or full-face respirator with filte(s) for organic vapours
(and when applicable for H2S) a Self Contained Breathing Apparatus (SCBA) can
be used according to the extent of spill and predictable amount of exposure. lf the
situation cannot be completely assessed, or if an oxygen deficiency is possible, only
SCBA's should be used.
6.2 Environmental precautions Prevent product from entering sewers, rivers or other bodies of water. lf necessary
dike the product with dry earth, sand or similar non-combustible materials. ln case
of soil contamination, remove contaminated soil and treat in accordance with local
regulations.
ln case of small spillages in closed waters (i.e. ports), contain product with floating
barriers or other equipment. Collect spilled product by absorbing with specific
floating absorbents.
lf possible, large spillages in open waters should be contained with floating barriers
or other mechanical means. lf this is not possible, control the spreading of the
spillage, and collect the product by skimming or other suitable mechanical means.
The use of dispersants should be advised by an expert, and, if required, approved
by local authorities.
Prevent the risk of slipping. Take precautionary measures against static discharge.
Avoid splash filling of bulk volumes when handling hot liquid product.
Date of issue/Date of revision 2016-02-19 Date ofprevioøs rcsue 201 t09-17 Version :2 5/35
Conforms to n No. 1907/2006 Annex Il
Nytro Libra
7.2 Conditions for safe Storage area layout, tank design, equipment and operating procedures must comply
storage, including any with the relevant regional, national or local legislation. Storage installations should
incompatibilities be designed with adequate bunds in case of leaks or spills. Cleaning, inspection
and maintenance of internal structure of storage tanks must be done only by
properly equipped and qualified personnel as defìned by national, local or company
regulations.
Keep only in the original container or in a suitable container for this kind of product.
Keep container tightly closed and sealed until ready for use. Do not store in
unlabelled containers. Containers that have been opened must be carefully resealed
and kept upright to prevent leakage. Empty containers may contain harmful,
flammable/combustible or explosive residue or vapours. Do not cut, grind, drill, weld,
reuse or dispose of containers unless adequate precautions are taken against these
hazards. Store locked up. Protect from sunlight.
Recommended monitoring lf this product contains ingredients with exposure limits, personal, workplace
procedures atmosphere or biological monitoring may be required to determine the effectiveness
of the ventilation or other control measures and/or the necessity to use respiratory
protective equipment. Reference should be made to monitoring standards, such as
the following: European Standard EN 689 (Workplace atmospheres - Guidance for
the assessment of exposure by inhalation to chemical agents for comparison with
limit values and measurement strategy) European Standard EN 14042 (Workplace
atmospheres - Guide for the application and use of procedures for the assessment
of exposure to chemical and biological agents) European Standard EN 482
(Workplace atmospheres - General requirements for the performance of procedures
for the measurement of chemical agents) Reference to national guidance
documents for methods for the determination of hazardous substances will also be
required.
DNELs/DMELS
Date of issue/Date of revision 2416-02-19 Date of previous issue :201109-17 Version :2 6/35
Conforms to ulation No. 1907/2006 REAC Annex ll
Nytro Libra
Date of issudDate of revision :201602-19 Date of previous lssøe :201109-17 Version :2 7/35
Conforms to ulation No. 1907/2006 Annex ll
Nytro Libra
10.3 Possibility of hazardous Under normal conditions of storage and use, hazardous reactions will not occur.
reactions
1 0.5 lncompatible materials Keep away from extreme heat and oxidizing agents.
10.6 Hazardous lncomplete combustion is likely to give rise to a complex mixture of airborne solid
decomposition products and liquid particulates, gases, including carbon monoxide, H2S, SOx (sulfur oxides)
or sulfuric acid and unidentified organic and inorganic compounds.
Date of issudDate of revision 2016-02-19 Date of previous rbsue :201*09-17 Version :2 9/35
Conforms to lation E No. 1907/2006 Annex ll
Nytro Libra
Date of issudDate of revision 2016-02-19 Date of previous issue 201 5-09-17 Vers¡on :2 10/35
Conforms to ulation No. 1907/2006 REAC , Annex ll
Nytro Libra
based
Distillates (petroleum), solvent-refined light naphthenic ASPIRATION HAZARD - Category 1
Date of issue/Date of revision 2016-02-19 Date of previous r'ssue 201í09-17 Version :2 1 1/35
Conforms to ulation No. 1907/2006 Annex ll
Nytro Libra
Date of issue/Date of revision :2016-02-19 Date of previous lssøe 201*09-17 Version :2 1?J35
Conforms to ulation No. 1907/2006 Annex ll
Nytro Libra
12.6 Other adverse effects lnsoluble in water. Spills may form a film on water surfaces causing physical
damage to organisms. Oxygen transfer could also be impaired.
Packaoino
Methods of disposal The generation of waste should be avoided or minimised wherever possible. Waste
packaging should be recycled. lncineration or landfill should only be considered
when recycling is not feasible.
14.2 UN proper
shipping name
14.3 Transport
hazard class(es)
14.4 Packing
group
14.5 No No. No No.
Environmental
hazards
Additional
information
14.6 Special precautions for Transport within user's premises: always transport in closed containers that are
user upright and secure. Ensure that persons transporting the product know what to do in
the event of an accident or spillage.
Date of issue/Date of rev¡s¡on 2016-02-19 Date of previous rbsue :201*09-17 Version :2 1 3/35
Conforms to ulation No. 1907/2006 Annex ll
Nytro Libra
Date of issue/Date of revision 2016-02-19 Date of previous issue :201109-17 Version :2 14/35
Conforms to No. 1907/2006 Annex ll
Nytro Libra
Procedure used to derive the classification according to Regulation IEC) No. 127212008 ICLP/GHSI
Classification Justification
Asp. Tox. 1, H304 Calculation method
Sweden
Full text of abbreviated H H304 May be fatal if swallowed and enters ainrays.
statements
Full text of classifications Asp. Tox. 1, H304 ASPIRATION HAZARD - Category 1
lcLP/GHSI
Date of printing 2016-02-19
Date of issue/ Date of revision 2016-02-19
Date of previous issue 2015-09-17
Version 2
Notice to reader
Ïo the best of our knowledge, the information contained herein is accurate. However, neither the above-named
supplier, nor any of its subsidiaries, assumes any liability whatsoever for the accuracy or completeness of the
information contained herein.
Final determination of suitability of any material is the sole responsibility of the user. All materials may present unknown
hazards and should be used with caution. Although certain hazards are described herein, we cannot guarantee that
these are the only hazards that exist.
Date of ìssue/Date of revision :2016-02-19 Date ofprevious Á*sue 201*09-17 Version :2 1il35
l.
Nytro Libra twMtus
Annex to the extended Safety Data Sheet (eSDS) \
lndustrial
ldentification of the substance or mixture
Product definition Mixture
Product name Nytro Libra
Section 1 - Title
Short title of the exposure Distribution of substance- lndustrial (Other Lubricant Base Oils, 1P346<3%, H304)
scenario
List of use descriptors ldentified use name: Distribution of substance - lndustrial
Process Category: PROC01, PROCO2, PROC03, PROCO4, PROCO8a, PROC08b,
PROCog, PROC15
Substance supplied to that use in form of: Substance
Sector of end use: SU03
Subsequent service life relevant for that use: No.
Environmental Release Category: ERC04, ERC05, ERC06a, ERC06b, ERC06c,
ERC06d, ERC07, ESVOC SpERC 1.1b.v1
Market sector by type of chemical product: Not applicable.
Article category related to subsequent service life: Not applicable.
Environmental contributing Distribution of substance
scenanos
Health Contributing scenarios Distribution of substance
Number of the ES 9.3.1b
lndustry Association Concawe
2012
Generic exposure scenario 01a
Processes and activities Bulk loading (including marine vessel/barge, rail/road car and IBC loading) of
covered by the exposure substance within closed or contained systems, including incidental exposures during
scenario its sampling, storage, unloading, maintenance and associated laboratory activities.
Add itional information lndustrial
Process sampling
No other specific measures identified
Laboratory activities
No other specific measures identified
Storage
Store substance within a closed system.
Conditions and measures related to personal protection and hygiene
Personal protection See Section I of the safety data sheet (general health and safety measures)
See Section 8 of the safety data sheet (personal protective equipment).
communicated via the safety data sheet by use of the following phrase: Do not ingest.
lf swallowed then seek immediate medical assistance.
l.
Nytro Libra MVTUIU'
Annex to the extended Safety Data Sheet (eSDS) \
lndustrial
ldentification of the substance or mixture
Product definition Mixture
Product name Nytro Libra
Section 1 - Title
Short title of the exposure Formulation & (re)packing of substances and mixtures- lndustrial (Other Lubricant
scenario Base Oils, 1P346<3%) '
List of use descriptors ldentified use name: Formulation and (re)packing of substances and mixtures -
lndustrial
Process Gategory: PROCO1, PROCO2, PROC03, PROCO4, PROC0S, PROC08a,
PROC08b, PROCog, PROC14, PROCI5
Substance supplied to that use in form of: Substance
Sectorofend use: SU10
Subsequent service life relevant for that use: No.
Environmental Release Category: ERC02, ESVOC SpERC 2.2.v1
Market sector by type of chemical product: Not applicable.
Article category related to subsequent service life: Not applicable.
Environmental contributing Formulation and (re)packing of substances and mixtures
scenarios
Health Contributing scenarios Formulation and (relpacking of substances and mixtures
Number of the ES 9.4.1b
lndustry Association Concawe
2012
Generic exposure scenario 02
Processes and activities Formulation, packing and re-packing of the substance and its mixtures in batch or
covered by the exposure continuous operations, including storage, materials transfers, mixing, tabletting,
scenario compression, pelletisation, extrusion, large and smallscale packing, sampling,
maintenance and associated laboratory activities.
Add itional information lndustrial
Contributing scenario controlling worker exposure for 0: Formulation and (re)packing of substances and mixtures
Product characteristics Liquid, vapour pressure < 0.S kpa at STp
Concentration of substance Covers percentage substance in the product up to 100% (unless stated differenfly).
in mixture or article
Physicalstate Liquid
Frequency and duration of Covers daily exposures up to I hours (unless stated differently)
use
operational
Other given Operation is carried out at elevated temperature (> 20'C above ambient
workers
conditions affecting temperature) Assumes a good basic standard of occupational hygiene is
exposure implemented
Aspiration hazard if swallowed.
Aspiration means the entry of a liquid substance directly into the trachea and lower
respiratory tract.
Aspiration of hydrocarbon substances can result in in severe acute effects such as
chemical pneumonitis, varying degree of pulmonary injury or death.
This propefi relates to the potential for low viscosity material to spread quickly into
the deep lung and cause severe pulmonary tissue damage.
Classification of a hydrocarbon substance for aspiration hazard is made on the
basis of reliable human evidence or on the basis of physical properties.
Do not induce vomiting as there is high risk of aspiration.
lF SWALLOWED: lmmediately call a POISON CENTER or physician.
Process sampling
No other specific measures identified
Storage
Store substance within a closed system.
Conditions and measures related to personal protection and hygiene
Personal protection See Section I of the safety data sheet (general health and safety measures)
See Section I of the safety data sheet (personal protective equipment).
Exposure estimation and reference to its source - Environment: 2: Formulation and (re)packing of substances and
mixtures
Exposure assessment Not available.
(environment):
Exposure estimation The Hydrocarbon Block Method has been used to calculate environmentalexposure
with the Petrorisk model.
Exposure estimation and reference to its source - Workers: 1: Formulation and (re)packing of substances and mixtures
Exposure assessment Not available.
(human):
Exposure estimation The ECETOC TRA tool has been used to estimate workplace exposures unless
otheruvise indicated.
I
Oate of issue/Date of revision ^(ES Revision date) 2435
Nytro Libra Formulation & (re)packing of substances and mixtures-
lndustrial (Other Lubricant Base O/g 1P346<3%)
lndustrial
ldentification of the substance or mixture
Product definition Mixture
Product name Nytro Libra
Section 1 - Title
Short title of the exposure Manufacturer of substance- lndustrial (Other Lubricant Base Oils, 1P346<3%, H304)
scenario
List of use descriptors ldentified use name: Manufacture of substance - lndustrial
Process Category: PROCO1, PROCO2, PROC03, PROC04, PROCO8a, PROCO8b,
PROC15
Substance supplied to that use in form of: Substance
Sector of end use: SU03, SU08, SU09
Subsequent service life relevant for that use: No.
Environmental Release Gategory: ERC04, ESVOC SpERC 1.'t.v1
Market sector by type of chemical product: Not applicable.
Article category related to subsequent service life: Not applicable.
Environmental contributing Manufacture of su bstance
scenarios
Health Contributing scenarios Man ufacture of su bstance
Number of the ES 9.1 .1 b
lndustry Association Concawe 2012
Generic exposure scenario 01
Processes and activities Manufacture of the substance or use as a process chemical or extraction agent
covered by the exposure within closed or contained systems. lncludes incidental exposures during recycling/
scenario recovery, materialtransfers, storage, sampling, associated laboratory activities,
maintenance and loading (including marine vessel/barge, road/rail car and bulk
container).
Add itional information lndustrial
Process sampling
No other specific measures identified
Laboratory activities
No other specific measures identified
I
Oate of issue/Date of revision ^(ES Revision date) 26/35
Nytro Libra Manufacturer of substance- lndustrial (Other Lubricant Base
Oils,lP346<3%, H304)
Predicted exposures are not expected to exceed the DN(M)EL when the risk
management measures/operational conditions outlined in section 2 are implemented
Available hazard data do not enable the derivation of a DNEL for dermal irritant
effects. Available hazard data do not support the need for a DNEL to be established
for other health effects. Risk management measures are based on qualitative risk
characterisation.
L
Nytro Libra rwrwu,
Annex to the extended Safety Data Sheet (eSDS) \
lndustrial
ldentification of the substance or mixture
Product definition Mixture
Product name Nytro Libra
Section 1 - Title
Short title of the exposure Uses in Functional fluids - lndustrial (Other Lubricant Base Oils, 1P346<3%, H304)
scenario
List of use descriptors ldentified use name: Functional Fluids - lndustrial
Process Gategory: PROCO1, PROCO3, PROCO8a, PROC08b, PROCO2, PROC04,
PROC09
Substance supplied to that use in form of: Substance
Sector of end use: SU03
Subsequent service life relevant for that use: No.
Environmental Release Gategory: ERC07,
Market sector by type of chemical product: Not applicable.
Article category related to subsequent service life: Not applicable.
Environmental contributi ng Functional Fluids
scenarios
Health Contributing scenarios Functional Fluids
Number of the ES 9.37.1b
lndustry Association Concawe
2012
Generic exposure scenario 13a
Processes and activities Use as functional fluids e.g. cable oils, transfer oils, coolants, insulators, refrigerants,
covered by the exposure hydraulic fluids in industrial equipment including maintenance and related material
scenario transfers.
Add itional information lndustrial
I
Oate of issue/Date of revision ^(ES Revision date) 28/35
Nytro Libra Uses rn Functionalfluids - lndustrial (Other Lubricant Base
Oils, 1P346<3%, H304)
Storage
Store substance within a closed system.
Conditions and measures related to personal protection and hygiene
Personal protection See Section I of the safety data sheet (general health and safety measures).
See Section 8 of the safety data sheet (personal protective equipment).
Predicted exposures are not expected to exceed the DN(M)EL when the risk
management measures/operational conditions outlined in section 2 are implemented.
Available hazard data do not enable the derivation of a DNEL for dermal irritant
effects. Available hazard data do not support the need for a DNEL to be established
for other health effects. Risk management measures are based on qualitative risk
l.
Nytro Libra NVIUAS
Annex to the extended Safety Data Sheet (eSDS) \
Professional
ldentification of the substance or mixture
Product definition Mixture
Product name Nytro Libra
Section 1 - Title
Short title of the exposure Uses in Functionalfluids - Professional (Other Lubricant Base Oils, 1P346<3%, H304)
scenario
List of use descriptors ldentified use name: Functional Fluids - Professional
Process Category: PROCO1, PROC02, PROCO3, PROCO8a, PROCO9, PROC2O
Substance supplied to that use in form of: Substance
Sector of end use: SU22
Subsequent service life relevant for that use: No.
EnvironmentalRelease Category: ERC09a, ERC09b, ESVOC SpERC 9.13b.v1
Market sector by type of chemical product: Not applicable.
Article category related to subsequent service life: Not applicable.
Environ mental contri buting Functional Fluids
scenarios
Health Contributing scenarios Functional Fluids
Number of the ES 9.38.1b
lndustry Association Concawe
2012
Generic exposure scenario 13b
Processes and activities Use as functional fluids e.g. cable oils, transfer oils, coolants, insulators, refrigerants,
covered by the exposure hydraulic fluids in professional equipment including maintenance and related
scenario material transfers.
Additional information Professional
I
Oate of issue/Date of revision ^(ES Revision date) 32/35
Nytro Libra Uses rn Functional fluids - Professional (Other Lubricant
Base O/s, 1P346<3%, H304)
Storage
Store substance within a closed system.
Conditions and measures related to personal protection and hygiene
Personal protection See Section I of the safety data sheet (general health and safety measures).
See Section I of the safety data sheet (personal protective equipment).
I
Oate of issue/Date of revision ^(ES Revision date) 34/35
Nytro Libra Uses rn Functional fluids - Professional (Other Lubricant
Base Oþ 1P346<3%, H304)
Predicted exposures are not expected to exceed the DN(M)EL when the risk
management measures/operational conditions outlined in section 2 are implemented.
Available hazard data do not enable the derivation of a DNEL for dermal irritant
effects. Available hazard data do not support the need for a DNEL to be established
for other health effects. Risk management measures are based on qualitative risk
characterisation.
Irispectorate Antwerp NV
Romeynsweel 14
2030 Antwerpen
Belgium
Ce ificate of Analysis
PRODUCT: Nytro Libra DELIVERED FROM: Shoretank 555
BATCH NO: T555-160717 DATE BATCH: 20-julí-2016
BATCH REF NO: N2016111484/LN13375-13742 LOCATION: LBC Antwerp
-
All test results in this COA comply with specified limits n the corresponding Nynas AB Product Data Sheet (PDS).
PCB compounds shall be none detectable, in accordance w th methods ASTM D4059 or IEC 61619.
For the latest PDS edition or for complete Nynas AB specifications regarding specific products, please visit www.nynas.com
or contact your local sales contact.
behalf of Nynas AB
„11 services are endei ed in accordance with irispectorate Antwerp~ General Ferret and Conditions of business, available on request
expectorate Antwerp NV
Romeyneweel 14
2030 Antwerpen
Belgium
Tel: ÷32(0)35460888
Fax: +32 (0)3 5460880
operations@inspectorate.be
www.lnspectorate.com —
Cert~fkate of Ana~vs~s
PRODUCT: Nytro Libra DELIVERED FROM: Shoretank 571
BATCH NO: 9-39-T453-160717 DATE BATCH: 28-juli-2016
BATCH REF NO: N2016/12147/LN14141-14217 LOCATION: LBC Antwerp
-
~rateAntwerNV:
~y~s,~__ Method Unit Results
~ ASTM D4052 ‚I Iso 12185 kg/dm3 0,8771
~ ASTM D4052,/ ISO 12185 kci,’clti’~,, 0,8740
Viscosity at 40°C ASTM D445./ ISO 3104 ~__ ~
~j~j~oi~’j_,___. ~ °C 149
CoIourASTM ASTMD1500 «
All test results in this C0A comply with specified limits In the corresponding Nynas AB Product Data Sheet (PDS).
PCB compounds shall be none detectable, In accordance with methods ASTM D4059 or JEC 61619.
For the latest P05 editIon or for complete Nynas AB specifications regarding specific products, please visit www.nynas.com
or contact your local sales contact.
CO~’RL~MAN SVEN
‚ Jta;n5~’’~l
“
“
.‚— ~CC6i~ t~I3ht3i 54,6 6,1 lift
~ hid ~
„ f~,4ii,srdSdw,.’si4tO~W ~U.. „~ . .
VAr w es
o’ias 326 t23 411 SL’iViCSS am mendemetl in accoidai’ce with Inspectomate Antwerp’s Gansrai feirns and Conditions of husin~ss, available on request
Inspec’ ate Antwerp NV
lomeynsweel 14 t’~
2030 Aetwerpen
Belgium :
Tel: +32 (0)3 546 0888
Fax: ±32 (0>35460880
operalions@inspectoratebe AWIIL~
Www. in spectorate.com
~_
Cert~tkate of Ana1~ys~s
PRoDucT~ Nytro Taurus DELIVERED FROM: Shoretank 602
BATCH NO: 100-T443-160622C DATE BATCH: 14-jufl-2016
BATCH REF NO: N2016/10953/LN12735 LOCATION: LBC Antwerp
-
RECEIVER: bc stock
All tCst rasults ír< tins C0A comply wíth soecified límiis ín the corresponding Nynas AS Product Data Sheet (PDS).
PCB compounds shall be none detectable, ín accordance with methods ASTM 04059 or IEC 61619.
For ~he latest PDS edítion or tor complete Nynas AS specifications regarding specific products, please v<sit www.nynas.com
or contact your local sales contact,
‚~o’. ‘v )‘iX’1
‘v’’. ‘ 3 <
‘.: <o ‚ ~23 ‘ . ow ‚~‘. < .‘ <Oo,,3 O „~‚ ~ “‘0<, .y,’,’,.,,” <O’~,, ‚v’<’<< ‚‘1, ‘1 0’«’,< iii 00<’ l,vQ,,< 01,),, O~<, <‚ „‘,‚Civ O,’,< ‘01v«
Width:
80 cm < Fastening process
Type of transformer:
OIL < 110 cm Number of ratchet straps: 2
Made by: Róbert Hortobágyi Number of transformers in one row: 2
Date: 15 June 2011
Modifications: 1. One end of the ratchet strap must be hooked into the eye on one 1.
side of the truck!
*it is required on both sides of the transformers.
Travel direction 2. Pull the ratchet strap through the eyes on the oil transformers and
make sure it does not contact the transformers! *it is required on both sides of the transformers.
2.
Method of fastening
3. Hook the other end of the ratchet strap into the eye on the
opposite side of the truck and then tighten the ratchet strap using the 3.
ratchet clip!
*it is required on both sides of the transformers.
1. The technical condition of the transportation vehicle must meet requirements given in the announcement of readiness for delivery and in the freight order (load bearing capacity, transformer
dimensions).
2. It is not necessary to use a tilt truck for the transportation of the cargo. Irrespective of the weather conditions, the cargo may be transported without a tilt protection, but it is recommended to
transport it under a cover to protect the product against other physical effects.
3. Transformers may not be transported on a trailer or by railway due to the effects of higher vibration and the dynamic loads.
4. The platform must be clean, undamaged, smooth and free from slip and tilting.
5. The carrier must use 2 pieces of 4 m long two-part fastening strap with a min. load bearing capacity of 3.5 t, provided with a tightening ratchet and end hooks for the fastening of each pair of
transformers. The straps must be undamaged and the signals for qualification and load-bearing capacity must be visible. DO NOT use any material or tool (chain, wire, rope etc.) other than the
required straps!
6. Factory made cargo fastening eyes must be available for the fastening at the necessary parts of the vehicle in sizes and at positions so that the transformers can be placed between the eyes. It is
allowed to fasten the cargo to holes on the sides of the multilock undercarriage, if this is safe.
7. The driver is responsible for the fastening of the cargo. A worker of SIEMENS Zrt. is responsible for the handling of local equipment (crane, hand tools etc.).
8. Fastening must not damage or deform the transformer and units assembled to it.
9. If the above requirements in any part or in full are not met THE LOADING AND TRANSPORTATION MAY BE REFUSED!
10. The transformers must be fastened and lifted with a crane - with two ropes - or a fork-lift truck with a sufficient load-bearing capacity at the special lifting points during loading and unloading.
DO NOT use any other equipment for lifting and handling! IT IS STRICTLY FORBIDDEN to slide or drag transformers without skids. IT IS STRICTLY FORBIDDEN to stand or climb on
the transformer and its parts.
11. DO NOT modify the fastening of the already controlled cargo or reload the cargo during transportation!
12. Requirements beyond the above, and possible deviations (housings or transformers fastened to pallets etc.) are included in the announcement of readiness for delivery and in the freight order.
Travel direction 2. Pull the ratchet strap through the eyes on the oil transformer and
make sure it does not contact the transformer!
2.
*it is required on both sides of the transformer.
Method of fastening
3. Hook the other end of the ratchet strap into the eye on the 3.
opposite side of the truck and then tighten the ratchet strap using the
ratchet clip!
*it is required on both sides of the transformer.
1. The technical condition of the transportation vehicle must meet requirements given in the announcement of readiness for delivery and in the freight order (load bearing capacity, transformer
dimensions).
2. It is not necessary to use a tilt truck for the transportation of the cargo. Irrespective of the weather conditions, the cargo may be transported without a tilt protection, but it is recommended to
transport it under a cover to protect the product against other physical effects.
3. Transformers may not be transported on a trailer or by railway due to the effects of higher vibration and the dynamic loads.
4. The platform must be clean, undamaged, smooth and free from slip and tilting.
5. The carrier must use 2 pieces of 4 m long two-part fastening strap with a min. load bearing capacity of 5 t, provided with a tightening ratchet and end hooks for the fastening of each transformer.
The straps must be undamaged and the signals for qualification and load-bearing capacity must be visible. DO NOT use any material or tool (chain, wire, rope etc.) other than the required straps!
6. Factory made cargo fastening eyes must be available for the fastening at the necessary parts of the vehicle in sizes and at positions so that the transformers can be placed between the eyes. It is
allowed to fasten the cargo to holes on the sides of the multilock undercarriage, if this is safe.
7. The driver is responsible for the fastening of the cargo. A worker of SIEMENS Zrt. is responsible for the handling of local equipment (crane, hand tools etc.).
8. Fastening must not damage or deform the transformer and units assembled to it.
9. If the above requirements in any part or in full are not met THE LOADING AND TRANSPORTATION MAY BE REFUSED!
10. The transformers must be fastened and lifted with a crane - with two ropes - or a fork-lift truck with a sufficient load-bearing capacity at the special lifting points during loading and unloading.
DO NOT use any other equipment for lifting and handling! IT IS STRICTLY FORBIDDEN to slide or drag transformers without skids. IT IS STRICTLY FORBIDDEN to stand or climb on
the transformer and its parts.
11. DO NOT modify the fastening of the already controlled cargo or reload the cargo during transportation!
12. Requirements beyond the above, and possible deviations (housings or transformers fastened to pallets etc.) are included in the announcement of readiness for delivery and in the freight order.