ISA POWER PRIVATE LIMITED

7.5MW BIOMASS BASED POWER PLANT

PUMP DATA UNIT MCW ACW RWT CTMW AWT ETP


RATED FLOW CU.M/HR 1075 250 105 42 105 15
RATED HEAD MWC 25 50 16 10.5 20 23
COLD EFFECIENCY AT RATED FLOW % 82 79.5 74 69 74 42
RUNOUT FLOW CU.M/HR 1300 345 134 60 164 35
RUNOUT HEAD MWC 15 37 14 8.2 15.3 18
RUNOUT EFFECIENCY % 60 65 73 67 72 55
BKW AT RATED FLOW WITH COLD EFFECIENCY KW 98.14 47.08 6.80 1.91 8.50 2.46
MAXIMUM POWER WITH RATED IMPELLER WITH
COLD EFFECIENCY KW 92.90 56.13 7.35 2.10 9.96 3.2741
MOTOR KW SELECTED KW 110 55 7.5 2.2 11 3.7
COMMENTS OK CHECK OK OK OK OK

AGEC 3/1/2005 REV 0


MALWA POWER PROJECT PRIVATE LIMITED
PUMP KW CALCULATION
PUMP DATA UNIT MCW DMWT ETP
RATED FLOW CU.M/HR 1040 5.5 14
RATED HEAD MWC 24 75 17
COLD EFFECIENCY AT RATED FLOW % 82 22 57
RUNOUT FLOW CU.M/HR 1200 42 41
RUNOUT HEAD MWC 20 55 9.1
RUNOUT EFFECIENCY % 82 22 57
BKW AT RATED FLOW WITH COLD EFFECIENCY KW 91.15 5.61 1.25
MAXIMUM POWER WITH RATED IMPELLER WITH
COLD EFFECIENCY KW 83.66 30.01 1.87096
MOTOR KW SELECTED KW 110 7.5 2.2
COMMENTS OK CHECK OK

NOTE :
1.ACW NOT ORDERED
2.DMWT PUMP KW 7.5 IS ACCEPTABLE FOR THIS
PROJECT
ECO FREN PRIVATE LIMITED
PUMP KW CALCULATION FOR LOAD LIST
PUMP DATA UNIT MCW ACW RWT
RATED FLOW CU.M/HR 1025 250 8.2
RATED HEAD MWC 35 50 20
COLD EFFECIENCY AT RATED FLOW % 82 79.5 74
BKW AT RATED FLOW WITH COLD EFFECIENCY KW 131.01 47.08 0.66
CTMW DMWT ETP
60.26 5.5 15
15 50 25
69 74 42
3.92 1.11 2.67
ISA POWER PRIVATE LIMITED
PUMP KW CALCULATION FOR LOAD LIST
PUMP DATA UNIT MCW ACW RWT
RATED FLOW CU.M/HR 1025 250 7.4
RATED HEAD MWC 35 50 20
COLD EFFECIENCY AT RATED FLOW % 82 79.5 74
BKW AT RATED FLOW WITH COLD EFFECIENCY KW 131.01 47.08 0.60
CTMW DMWT ETP
40.2 5.5 15
15 50 25
69 74 42
2.62 1.11 2.67