Protective Relay Testing

Why Test? Which Tests? W


The Recommended Practice for Electrical Equipment
Maintenance, ANSI/NFPA 70B, states:
Different for each type of relay. Determined by
manufacturer’s recommendations and special h
“8.9.7.2 Since protective relays...play such an
application considerations. NETA procedures include: y
important part in the prevention of hazard to • Inspection for mechanical problems
personnel and plant equipment, THEY SHOULD
BE GIVEN FIRST LINE MAINTENANCE ATTENTION.


Pickup on each operating element
Timing at three points on curve T
Furthermore, since the only time they operate
is during an abnormal electric power system


Target and seal-in operation
Special tests for restraint, directional overcurrent,
e
condition, THE ONLY WAY TO ASSURE CORRECT and other special operating elements s
OPERATION IS BY A COMPREHENSIVE INSPECTION,
MAINTENANCE AND TESTING PROGRAM.”


Insulation tests
Actual breaker trip test t
A relay may only need to operate for 0.15 seconds in


Peripheral and auxiliary device tests
Function test
?
its 30+ year life. Failure to operate as intended can
result in extensive damage, extended power outages, Test Equipment, Information and Expertise

Protective Relay Testing


and loss of life. Required
NETA • Calibrated current and voltage sources (1 and
(InterNational Electrical Testing Association) 3 phase) must not have excessive distortion of
reports show waveform
12% Failure Rates • Calibrated timing devices with start/stop circuits
on Protective Relays Tested • Phase shifters and phase angle meters
• Test jacks, relay cases, and test leads
A comprehensive testing program should simulate • Manufacturer’s literature and curves
fault and normal operating conditions of the relay. • Thorough knowledge of test equipment and relays
Acceptance testing, commissioning, and start-up will • Power system short circuit and coordination study
include control power tests, CT and PT tests, and any with recommended protective device settings
other device testing associated with the protective
relay. Routine preventive maintenance testing will
also be required.

How Often?
Most manufacturers recommend annually. Operating
experience determines frequency (environment, level
of reliability expected, age, failure rates, etc.). The
typical interval recommended by ANSI/NFPA 70B is
one to three years.