Beruflich Dokumente
Kultur Dokumente
Worksheets
Summary
This appendix contains all of the worksheets needed to program the
panel, calculate NAC requirements and battery requirements.
Content
Battery calculation worksheet • 206
Notification appliance circuit calculations worksheet • 209
Introduction • 209
What you’ll need • 209
Worksheet method • 211
Equation method • 212
Notification appliance voltage drop calculation worksheet • 215
Device loop maximum wire length worksheet • 217
Correlation groups worksheet • 223
Device settings worksheet • 224
Loop worksheet • 226
Panel configuration worksheet • 227
Panel operation worksheet • 230
Zone settings worksheet • 231
Control panel
(use Worksheet A and place totals here)
Auxiliary/smoke power
(use Worksheet B and place totals here)
NAC 1
NAC 2
NAC 3
NAC 4
Total current
÷ 60
+ = mAh
1.2
mAh
1,000
Notes
[1] Battery size may not exceed 26 Ah for UL/ULC systems. Refer to Appendix A and “Battery wiring” for battery
details.
SA-DACT dialer 41 41
SA-ETH network 34 34
card
Totals (mA)
(transfer totals to Battery Calculation Worksheet)
Notes
[1] 64 pt.: 155
250/500 pt.: 172
[2] 64 pt.: 204
250/500 pt.: 267
RPM 20 270
RLCD(F) 98 113
RLCD-C(F) 99 115
RLED-C(F) 28 62
LED24 6 34
Totals (mA)
(transfer totals to Battery Calculation Worksheet)
Note
[1] Enter 1 regardless of how many are installed. Only the first SIGA-UM or SIGA-MAB in the alarm state draws
current. The other ones do not because the system load sheds additional modules in alarm.
Introduction
This topic shows you how to determine the maximum cable length
of a notification appliance circuit (NAC) for a given number of
appliances.
Two methods are presented: worksheet and equation. The
worksheet method is simpler, but your installation must meet the
criteria listed on the worksheet. If your installation does not meet
these criteria, you need to use the equation method.
The methods given here determine cable lengths that work under all
operating conditions. The calculations ensure that the required
operating voltage and current will be supplied to all notification
appliances. To do this, we assume these two worst-case conditions:
• The voltage at the NAC terminals is the minimum provided by
the power supply
• The notification appliances are clustered at the end of the NAC
cable
Other, more detailed methods that distribute the appliance load
along the NAC cable may indicate that longer cable runs are
possible.
Worksheet method
Use this worksheet to determine the maximum cable length of a
notification appliance circuit for a given number of appliances.
Use this worksheet only if all the appliances are regulated. That is,
they must have a minimum operating voltage of 16 V. For other
appliances, use the “Equation method.”
Load factor (64 point panel) × 0.20 0.20 0.20 0.20 V/A
Minimum voltage = V
Maximum resistance =
2 2 2 2
[1] Total of the maximum operating currents for all appliances as specified for FWR power. See the appliance installation
sheets for operating currents.
[2] This voltage drop is valid for regulated notification appliances only. For unregulated appliances, see “Equation method,”
later in this topic.
[3] Use the manufacturer’s published wire resistance expressed in ohms per foot. For typical values, see Table 1, later in this
topic.
Equation method
Wire resistance
Typical wire resistances are shown in the following table.
Itot = Ia
Where:
Ia = appliance maximum current
See the appliance installation sheets for Ia. Remember to use
the maximum operating current specified for FWR power.
2. Calculate the minimum voltage (Vm).
Vm = Vs (Itot × K)
Where:
Vs = source voltage
Itot = total current (from above)
K = load factor
64 point panel: For the power supply, Vs is 20.4 V and K is 0.20 V/A.
250/500 point panel: For the power supply, Vs is 20.4 V and K is
0.24 V/A
3. Calculate the allowable voltage drop (Vd) between the power
supply and the appliances.
Vd = Vm Va
Where:
Vm = minimum voltage (from above)
Va = appliance minimum voltage
For regulated notification appliances, Va is 16 V. For special
application notification appliances, Va is the lowest operating
voltage specified on the appliance installation sheet.
4. Calculate the maximum resistance (Rmax) for the wire.
Rmax = Vd / Itot
Where:
Vd = voltage drop
Itot = total current
5. Calculate the maximum length of the cable (Lc), based on the
maximum resistance allowed, the resistance of the wire, and
the number of wires in the cable (two).
Lc = (Rmax / Rw) / 2
Where:
Rmax = maximum resistance
Rw = wire resistance factor
64 point panel
Notes
[1] Use the manufacturer’s published wire resistance expressed in
ohms per foot. For typical values, see Table 1 in the “Notification
appliance circuit calculations worksheet.”
[2] Use the Maximum operating current at worst-case VFWR from
the installation or catalog sheet of each device.
[3] For UL regulated notification appliances, this voltage must not
drop below 16 VFWR. For other devices, get the minimum
operating VFWR from the installation or catalog sheet.
500,000 pF
10 ft
(3 m) 200 ft
(61 m)
FACP J
30 ft
(9 m)
200 ft 100 ft
(61 m) (30 m)
J J
100 ft 1000 ft
(30 m) (305 m)
Table 2: Longest allowable circuit path with zero SIGA-UMs or SIGA-MABs configured for 2-wire smoke detectors
Table 3: Longest allowable circuit path with 1 to 5 SIGA-UMs or SIGA-MABs configured for 2-wire smoke detectors
Table 4: Longest allowable circuit path with 6 to 10 SIGA-UMs or SIGA-MABs configured for 2-wire smoke detectors
0 101 to 125 0 0 0 0 0 0
1 to 25 101 to 125 0 0 0 0 0 0
26 to 50 101 to 125 0 0 0 0 0 0
51 to 75 101 to 125 0 0 0 0 0 0
76 to 100 101 to 125 0 0 0 0 0 0
101 to 125 101 to 125 0 0 0 0 0 0
Table 5: Longest allowable circuit path with 11 to 15 SIGA-UMs or SIGA-MABs configured for 2-wire smoke detectors
0 51 to 75 0 0 0 0 0 0
1 to 25 51 to 75 0 0 0 0 0 0
26 to 50 51 to 75 0 0 0 0 0 0
51 to 75 51 to 75 0 0 0 0 0 0
76 to 100 51 to 75 0 0 0 0 0 0
101 to 125 51 to 75 0 0 0 0 0 0
0 76 to 95 0 0 0 0 0 0
1 to 25 76 to 95 0 0 0 0 0 0
26 to 50 76 to 95 0 0 0 0 0 0
51 to 75 76 to 95 0 0 0 0 0 0
76 to 100 76 to 95 0 0 0 0 0 0
101 to 125 76 to 95 0 0 0 0 0 0