NUMERICAL INSTABILITIES

IN
POWER SYSTEM TRANSIENT SIMULATIONS
By
Antonio Emilio Angueth de Araujo
B. Sc. (Electrical Engineering) Universidade Federal de Minas Gerais, Brazil
M. Sc. (Electrical Engineering) Universidade Federal de Minas Gerais: Brazil

A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF


THE REQUIREMENTS FOR THE DEGREE OF
DOCTOR OF PHILOSOPHY

in
THE FACULTY OF GRADUATE STUDIES
ELECTRICAL ENGINEERING

We accept this thesis as conforming


to the required standard

THE UNIVERSITY OF BRITISH COLUMBIA


June 1993
© Antonio Emilio Angueth de Araujo, 1993
In presenting this thesis in partial fulfilment of the requirements for an advanced degree at
the University of British Columbia, I agree that the Library shall make it freely available
for reference and study. I further agree that permission for extensive copying of this
thesis for scholarly purposes may be granted by the head of my department or by his
or her representatives. It is understood that copying or publication of this thesis for
financial gain shall not be allowed without my written permission.

Electrical Engineering
The University of British Columbia
2075 Wesbrook Place
Vancouver, Canada
V6T 1W5

Date: `3 9 3
Abstract

In power system simulations, control systems act upon the electric power system in
a variety of ways. There is, therefore, a necessity of simulating the control system
equations together with the power system equations. This is the case not only in
stability studies, but also in the simulation of electromagnetic transient phenomena.
Because of the different structure of the two sets of equations, computational
efficiency can be improved if both sets of equations are solved separately, with the

result from one set of equations showing up in the other set of equations one or more
time steps later. This procedure, however efficient, can lead to numerical instability.
In the simulation of the control system itself, the modelling of nonlinearities in

closed loops poses some problems as well. The most efficient way of handling a
nonlinear block is to open the closed loop and use, instead of the current value of
the variable, a predicted value of the feedback path. This can also lead to numerical
instabilities.
In this thesis a simultaneous solution of the control and power system equations
is proposed. For the cases of nonlinearities in closed loops, an iterative solution is
suggested. The implementation of the method is carried out in the Electromagnetic
Transients Program (EMTP).
Several comparisons between the proposed and other methods are performed. In
cases in which the analytical solution is not available, the comparison is made against
the results of the TAGS package ("Transient Analysis of Control Systems") which

ii
is integrated with the EMTP version of DCG/EPRI ("Development Coordination
Group/Electric Power Research Institute").
It is shown through simple, but typical, case studies that the proposed method is
not only accurate and efficient, but also numerically stable, thus representing a sig-
nificant improvement to the ability of the EMTP to reliably simulate electromagnetic
transients in power systems when control systems are involved.

iii
Table of Contents

Abstract^ ii

List of Tables^ viii

List of Tables^ viii

List of Figures^ ix

List of Figures^ xii

1 Introduction^ 1

2 Literature Review^ 4
2.1 Introduction ^4
2.2 EMTP-TACS Approach ^4
2.3 TACS Solution Method ^6
2.3.1 Transfer Functions - Linear Blocks ^6
2.3.2 Nonlinear Function Blocks ^8
2.3.3 Transfer Function with Limiters ^9
2.3.4 TACS-EMTP Interface ^ 11
2.4 Time Delays in the TACS-EMTP Approach ^ 12
2.5 Final Remarks ^ 14

iv
3 Time Delays and the Stability and Accuracy of the Simulation^15
3.1 Introduction ^15
3.2 Numerical Instability ^16
3.2.1 DC Circuit ^16
3.2.2 Arc modelling ^18
3.2.3 Sinusoidal Oscillator ^20
3.3 Stable Inaccurate Results ^21
3.3.1 Internal Time Delays ^21
3.3.2 Converter Simulation - External Time Delays ^ 22

4 Simultaneous Solution of Power and Control System Equations ^25


4.1 Introduction ^25
4.2 Basic Considerations ^26
4.2.1 Elimination of the External Time Delay ^ 26
4.2.2 Elimination of the Internal Time Delays ^ 26
4.3 Actual Implementation ^ 28
4.3.1 Interface Between the Written Program and the EMTP . ^28
4.3.2 Capabilities of the Program ^33

5 Comparison Between Simultaneous and Non-simultaneous Approach


41
5.1 Introduction ^41
5.2 Control System Case Studies ^ 42
5.2.1 Second-Order Linear System ^ 42
5.2.2 Static and Dynamic Limiters in Open Loops ^ 42
5.2.3 FORTRAN Function in a Closed Loop ^ 44
5.2.4 Special Element Block ^ 44
5.3 Simulations of Control and Power Systems ^ 44
5.3.1 Arc Modelling ^ 44
5.3.2 Single-Phase Variable Load ^ 48
5.3.3 Three-Phase Variable Load ^ 53
5.3.4 Simple HVDC System Model ^ 64
5.4 Converter Simulations ^70
5.4.1 Single-Phase Thyristor Rectifier Bridge ^72
5.4.2 Three-Phase Thyristor Inverter ^72
5.4.3 Remarks on Converter Simulation with the EMTP ^ 72
5.5 Final Remarks ^ 76

6 Conclusions^ 81

Bibliography^ 83

A Interpreter Basic Principles^ 86


A.1 Compilation of Arithmetic Expressions ^ 87
A.2 From Infix to Polish Notation ^ 89
A.3 Evaluation of a Reverse Polish expression ^ 100

B SS and EMTP Input Files^ 113


B.1 Control System Case Studies - SS Input Files Only ^ 113
B.1.1 Second-Order linear system (Section 5 2 1)^ 113
B.1.2 Static and Dynamic Limiters (Section 5.2.2) ^ 114
B.1.3 FORTRAN Function in a Closed Loop (Section 5.2.3) ^ 116
B.1.4 Special Element Blocks (Section 5.2.4) ^ 117

vi
B.2 Control and Power System Case Studies - SS and EMTP Input Files 119
B.2.1 Arc Modelling (Section 5.3.1) ^ 119
B.2.2 Single-Phase Variable Load (Section 5.3.2) ^ 120
B.2.3 Step Load Variation (Section 5.3.3) ^ 122
B.2.4 Pulse Load Variation (Section 5.3.3) ^ 125
B.2.5 Load Variation with Thyristor Controlled Reactor (Section 5.3.3)128
B.2.6 HVDC System Simple Model (Section 5.3.4) ^ 135
B.2.7 Single-Phase Thyristor Rectifier Bridge (Section 5.4) ^ 138
B.2.8 Three-Phase Thyristor Inverter (Section 5.4) ^ 141

vii
List of Tables

A.1 Simple Precedence Function ^ 89


A.2 Transformation of a — b x c + d/5 into Reverse Polish ^ 90
A.3 Input and Stack Precedence Functions ^ 91

viii
List of Figures

1.1 Interaction between power system and control system ^ 2

2.1 Typical diagram of a control system ^ 5


2.2 Transfer function block ^ 7
2.3 Control system with linear transfer function blocks ^ 8
2.4 Nonlinear function blocks ^ 9
2.5 Static and dynamic limiters ^ 10
2.6 Time delay between TACS and EMTP ^ 11
2.7 Possible simultaneous solution with TACS-EMTP ^ 13

3.1 Numerical instability in a DC circuit ^ 16


3.2 Current and Voltage in the circuit of Figure 3.1 ^ 17
3.3 Arc modelling with EMTP-TACS ^ 18
3.4 z-transform domain analysis ^ 19
3.5 Numerical instability in the arc modelling ^ 19
3.6 Block diagram and exact solution of^(t)^x(t) = 0 [1] ^ 20
3.7 Instability due to the internal time delay ^ 21
3.8 Inaccuracy due to the internal time delay [1] 22
3.9 Three-phase thyristor inverter current - TACS inaccurate result [2] 24

4.1 Partition of the augmented matrix ^ 27


4.2 Compensation method in the EMTP ^ 29

ix
4.3 Subroutine CONNEC and its interface with the EMTP ^ 30
4.4 Control actions upon the power system ^ 31
4.5 Matrix formation inside CONNEC ^ 32
4.6 Controlled integrator block ^36

5.1 Second-order linear system: (a) Diagram; (b) Solution for a unit step
input. ^43
5.2 Static limiter: (a) Diagram; (b) Simulation results. ^45
5.3 Dynamic limiter: (a) Diagram; (b) Simulation results ^46
5.4 Nonlinearity in a closed loop: (a) Diagram; (b) Simulation results [1] ^47
5.5 Special element blocks - Diagram and simulation results (source =
cos wt, w = 377 rad/s and time delay = 2 ms). ^ 47
5.6 Arc modelling - superposition of the analytical and the SS simulation
results ^48
5.7 R-L load representation; c = R/L ^ 49
5.8 Active power variation ^ 50
5.9 Block diagram - Single-phase variable load [1] ^51
5.10 Simulation Results: (a) TACS solution [1]; (b) SS results ^52
5.11 Sample power system [1]. ^ 54
5.12 Diagram of the Thevenin reduced system [1]. ^ 54
5.13 Load modelling - step variation [1] ^56
5.14 (a) Load variation - step variation, (b) TACS simulation result [1], (c)
SS simulation result. ^57
5.15 Load modelling - pulse variation [1]. ^58
5.16 (a) Load variation - pulse variation, (b) TACS simulation result [1],
(c) SS simulation result. ^59
5.17 Thyristor controlled reactor: (a) Circuit diagram; (b) Circuit model;
(c) TCR s-domain model ^ 61
5.18 Basic TCR voltage controller - ic/L modelling [1] ^62
5.19 TCR and its control system - a simple model ^62
5.20 SS block diagram. ^63
5.21 Load variation. ^64
5.22 Load variation without TCR: (a) TACS simulation [1]; (b) SS simulation. 65
5.23 Load variation with TCR: (a) TACS simulation [1]; (b) SS simulation. 66
5.24 Power system with a DC line [1]. ^ 67
5.25 Id and a modelling [1] ^68
5.26 EMTP-SS simulation diagram [1]. ^ 68
5.27 (a) Voltage tracking system; (b) DC system equations; (c) AC current
injection [1] ^69
5.28 IDC, ALPHA and IACF comparisons; (a) TACS simulation [1]; (b) SS
simulation. ^70
5.29 Voltage at bus 1 (BUS1) comparison; (a) TACS simulation [1]; (b) SS
simulation. ^71
5.30 Single-phase thyristor rectifier. ^73
5.31 Single-phase rectifier simulations - voltage vd: (a) TACS results; (b)
SS results ^74
5.32 Closing and opening of EMTP switches. ^ 75
5.33 Backtracking procedure. ^77
5.34 Inverter simulation: instability due to thyristor misfiring ^78

xi
Acknowledgements

To my wife Angela, for her having put aside her own career and interests to kindly
accompany me and, with love, make my undertaking possible. To my children Thiago
and Henrique, who made my life a little more complicated but full of love and fun.
To Dr. H.W. Dommel and Dr. J.R. Marti for their invaluable help, direction and
advice. To Dr. Nelson Santiago for his help during the period of my thesis writing.
To my colleagues for making my stay at UBC memorable.
Finally, to CNPq (Brazilian Research Council), to Universidade Federal de Minas
Gerais and to The University of British Columbia for their financial support.

xii
Chapter 1

Introduction

During the 1960's and 1970's the modelling and simulation of power systems transient
phenomena reached a high degree of sophistication. Numerical techniques, as well as
models of various power system components, were developed for digital transient
simulation software packages.
With the increased use of HVDC transmission systems, and the wide application
of other power electronic devices in power systems, it became necessary to simulate
the control systems acting upon the power system in addition to the power system
itself. This is very important in cases where the dynamic interactions between the
control and the power system are of major concern.
In general, the control system acts upon the power system in three different ways:

• issuing commands to open or close switches and thyristors;

• controlling voltage sources; or

• controlling current sources.

The decisions made by the control system are based on the information which it

receives from the power system, such as node or branch voltages, branch currents or
state of the switches. Figure 1.1 depicts the general situation.

1
Chapter 1. Introduction^ 2

switch status
voltage
Power current
System

'-7
Control
switch command System
voltage
current

Figure 1.1: Interaction between power system and control system

The power system component models are relatively easy to incorporate into nodal
network equation representations. Control system components are not as easy to
model. They do not fit into the nodal network representation, and the associate
matrices are not symmetric.
The easiest and most efficient way of handling these differences, is to simulate

the power system equations separately from the simulation of the control system
equations. Both sets of equations are solved separately, and then interfaced with
each other through the exchange of information about the values of the parameters
which they share. This introduces time delays between both solutions and makes the
solution procedure non-simultaneous.
The simulation of the control system itself may require some special treatment as
well. Whenever a nonlinearity exists in a closed loop in the control system, there is

an efficient and non-simultaneous procedure to overcome this difficulty - opening the


loop and using the past value as the actual value of the output of the feedback path.
Chapter 1. Introduction^ 3

Non-simultaneity is the basis for the efficiency of the solution method outlined
above. However, this procedure can lead to two distinct and important problems -
inaccuracy and numerical instability.
These two problems are addressed in this thesis. A general simultaneous solution
method of the control and power system equations is proposed. Comparisons between
the proposed and other methods, showing its accuracy and stability, are performed.
The thesis is divided into six chapters as outlined below:

• Chapter One - Introduction

• Chapter Two - Literature Review ^ An overview of the relevant technical


literature is presented.

• Chapter Three - Effects of Time Delays on the Stability and Accuracy of the
Simulation ^ The main objective of this chapter is to identify the most
important effects of time delays (non-simultaneity) on the stability and accuracy
of the solution.

• Chapter Four - Simultaneous Solution of Power and Control System Equations


^ The proposed method is described and the implementation of the method
is discussed.

• Chapter Five - Comparison between simultaneous and non-simultaneous ap-


proaches ^ The objective here is to show the main advantages and limita-
tions of the simultaneous approach when compared with the other approaches.
This is done through several case studies.

• Chapter Six - Conclusions


Chapter 2

Literature Review

2.1 Introduction

Several current digital computer programs for power system transient analysis are
known as "Electromagnetic Transients Program". Most of them are variations of the
basic EMTP [3]. See reference [4] for a complete description of the various versions.
Control system simulation capabilities were originally added to the BPA EMTP
(Bonneville Power Administration EMTP). Although other programs not directly
related to the EMTP exist which are able to simulate control and power systems, this
chapter will cover only the EMTP-related literature, because of the wide-spread use
of the EMTP compared to other programs.

2.2 EMTP-TACS Approach

One of the first works on the simulation of control and power systems using general
purpose programs was done by L. Dube and H. Dommel [5]. Their technique was
incorporated into a digital computer program called TACS (Transient Analysis of

Control Systems), which became part of the EMTP. TACS is still used today in the
DCG/EPRI EMTP. The main objective at that time was the simulation of HVDC
converter controls.

4
Chapter 2. Literature Review^ 5

From internal
source To EMTP
G(s) Kl/s Vcos(180- P)

From EMTP Sensor

Figure 2.1: Typical diagram of a control system

Some important features of TACS are:

• its code is independent of the EMTP, and interfaces with the EMTP with one
time step delay;

• it can accept arbitrary interconnections of a set of control system building


blocks;

• it solves the control system equations by implicit integration with the trape-
zoidal rule.

Figure 2.1 shows a typical diagram of a control system to be simulated by the


EMTP-TACS approach, where the control receives some information from the net-

work, performs some actions and then gives information back to the network.
Although there have been many additions to the TACS set of blocks over the years
[6], the basic blocks used to simulate any control system are:

• transfer functions — s-domain rational polynomial functions which are the


most basic building blocks in a control system;

• sources — time dependent sources, such as DC, pulse, step, etc;


^

Chapter 2. Literature Review^ 6

• Fortran expressions — a general function given by a Fortran statement which


describes the relationships between the inputs and the output of a block;

• devices — preprogrammed subsystems of control systems, such as relay oper-


ated switches, sample and track circuits, etc.

2.3 TACS Solution Method


2.3.1 Transfer Functions — Linear Blocks

A general transfer function block is shown in Figure 2.2. It describes a relationship


between the output X and the inputs Ui as a rational function G(s) = N(s)/D(s)
with a gain K and m < n. Such an n-th order transfer function is transformed into a
system of first-order differential equations which are integrated with the trapezoidal
rule. After eliminating internally created state variables for second and higher order
derivatives, a single equation relating the output to the inputs is formed:

cx(t) = K • d • u(t) -+ hist(t — At) , (2.1)

where u is the sum of all input variables. The coefficients c and d are calculated using
the recursive formula:

(-2) i {^(i 2 \i+i d . +1 ' • • • + (71 ( rdn},


i^ (At) ) At

where ei ) is the binomial coefficient, and

n^2 •
co = E() 2 D i
i . 0 At

where c = co . The formulas for d are found replacing D by N in the above formulas.
Chapter 2. Literature Review^ 7

Ul

+N s+.+Ns
0 1
U2 U X
K n
D + D s + + Dn s
O l

U3

Figure 2.2: Transfer function block

The calculation of the history term hist(t — At) is not simple and the reader is

referred to Chapter 4 and reference [7] for details.


After discretizing all transfer functions, it is possible to build a matrix equation

(A)(X) = (hist).

To clarify this point, assume the system of Figure 2.3 is to be simulated [7].
Applying Eq. 2.1 to the blocks of this figure, the related matrix equation will be

/ xi
Ca Ka da Ka d a 0 Kada 0 x2 (hist a
—Kbd b 0 0 Cb 0 Kbdb X3 histb
(2.2)
—K c d, c, 0 0 0 0 x4 hist
0 0 Cd — K add 0 0 U1 histd
\ U2

If u i and u 2 are known sources at each time step, the unknowns are x l , x 2 , x 3 and
x 4 . The previous equation can be written as follows:

(A x )(x) = (hist) — (A xu )(u),^ (2.3)


Chapter 2. Literature Review^ 8

-U2

Ul X1 X4
a b

Figure 2.3: Control system with linear transfer function blocks

where
( Ca Ka d a Ka d a 0
—Kbdb 0 0 Cb
A xe =--
—Kc d, c, 0 0
0 0 cd —Kddd
and
—Ka da 0
0^Kb db
ASU
0^0
(
0^0
The Equations 2.3 can now be solved for the unknowns at each time step. Trian-
gular factorization and ordering techniques with a sparsity storage scheme are used
in the solution. The factorization is performed once, and at each time step there is
one forward solution and one back substitution [5].

2.3.2 Nonlinear Function Blocks

Nonlinear function blocks are not included in the previous simultaneous solution of
the whole system. Instead, they are solved sequentially as soon as their input signals
become available at some stage in the back substitution mentioned above.
Chapter 2. Literature Review^ 9

System System System System


—4 Section N.L. Section Section N.L. Section
A B

Open Loop^Closed Loop


System System
Section N.L. Section

Delay 1--
Decoupling
Figure 2.4: Nonlinear function blocks

In an open loop configuration, the nonlinearity does not pose any problem since
its input does not depend on its output. Problems arise in a closed loop configuration,
where the sequential solution forces the introduction of a time-delay to decouple the
input from the output of the nonlinear block (see Figure 2.4).
The introduction of this time delay occurs whenever a nonlinear block exists inside
a closed loop configuration. Many of the Fortran Functions and Devices blocks are
nonlinear and are likely to cause the introduction of such time delays, which the
program user may not even be aware of.

2.3.3 Transfer Function with Limiters

The general transfer function block has an additional feature that enables the user to

use two types of limiters. The function of these limiters is to limit the output of the
block if a certain condition is reached.
The output of the static limiter shown in Figure 2.5 is
Chapter 2. Literature Review^ 10

x
G(s)

Xrain

Static Limiter Dynamic Limiter

Figure 2.5: Static and dynamic limiters

Ku if Xmin < Ku < Xmas,


x = xmin if Ku < xmin,
Xmas if Ku> Xmas.

Each of the three equations above is a linear algebraic equation of the form of
Eq. 2.1, with c = d = 1, hist = 0 inside the limits, and c = 1, d = 0, hist =
(X mas or x rnin ) at the limits.
Contrary to static limiters, the limiting action of dynamic limiters changes the
dynamic behaviour of the transfer function block. These limiters are applied only
for first-order transfer functions [7]. The equations for the dynamic limiter are (see
Figure 2.5)

I
x +T"t = Ku if X sa m < X < X mas ,
X = X m i a^if X < Xmin and (Ku — x) < 0,
x = X mas^if x> X mas and (Ku — x) > 0.

The dynamic limiter equations can also be put in the format of Eq. 2.1. Inside
the limits, the coefficients are:

d = K;
2T
c^(1+ —A7 );
2t
hist = Ku(t —^(1 )x(t At).
At
— — —
Chapter 2. Literature Review^ 11

t-2At^t-/.t
EMTP

TACS
t-20t t-:At

Figure 2.6: Time delay between TACS and EMTP

Outside the limits the coefficients are the same for both limiters.
Although both types of limiters fit into Eq. 2.1, when they occur in closed loops

their input will depend on their output. This situation is similar to the case of non-
linear blocks where the introduction of time delays is unavoidable. This is discussed
in Section 2.4.

2.3.4 TACS-EMTP Interface

As mentioned before, TACS solves the set of control system equations independently
from the EMTP and has to communicate with it to exchange information on how the
control action is supposed to influence the power system. Figure 1.1 in Chapter 1
outlines the interface process between both programs. It is clear from this figure
that for TACS to issue any control signal to the power system it must have received
information from the EMTP previously. Figure 2.6 shows how the process takes place

as a function of time.
TACS solves the control system equations from (t — 20t) to (t — At). Then it
gives the values of the variables to the EMTP. The EMTP solves the power system
equations for (t — At) to (t). At t, the EMTP gives to TACS the values of the variables
Chapter 2. Literature Review ^ 12

in order for TACS to advance the solution from (t - At) to (t). Therefore, the EMTP
always uses information from TACS delayed by one time step.

2.4 Time Delays in the TACS-EMTP Approach

To summarize what has been discussed so far, there are two types of time delays in
the TACS-EMTP approach:

• Time delay between TACS and the EMTP - external time delays;

• Time delays generated by TACS itself due to nonlinear blocks or transfer func-

tion blocks with limiters - internal time delays.

In 1983/84 Ma Ren-ming made some revisions to the original TACS code with
respect to the order in which the blocks of the control system are solved [7, 8]. One
of the objectives of this revision was to decrease the possibility of the introduction of
internal time delays in a variety of situations.

To illustrate the process, consider Figure 2.7. It consists of 10 transfer function


blocks with three of them having limits. The first four blocks form an independent set
of equations, as do the last four blocks. To simultanously solve the system comprising
the first four blocks, the output of F2 must be calculated first. This means that its

equation (Eq. 2.1) must be the last equation of equations 2.3 (the first one to be
solved during the backsubstitution - see Section 2.3.1). The limits constraints are
applied as soon as the output is available. With the output of F2 known, the output

of F3 can be calculated and its equation must be solved next in the backsubstitution
process. Then F4 and Fl are solved in this order. F5 and F6 are solved next and in
the last set of four blocks the order is: F10 -+F7 -*F8
Chapter 2. Literature Review^ 13

HI HI

Fl F2 F5 F6
HI

LOW LOW

F4 F3
LOW

Figure 2.7: Possible simultaneous solution with TACS-EMTP

The ordering used in this case avoids the introduction of time delays in the solution
procedure, but the ordering approach is far from general. Any ordering scheme fails
if there are two limiters in one single closed loop.

In addition, an ordering algorithm is needed to detect the loops with limiters or


nonlinear blocks. Although TACS-EMTP has a built-in ordering routine, a recent
improvement [9] has thoroughly dealt with this subject.
In terms of what types of problems time delays can cause in the simulation of

control and power systems, Lima [10] showed in 1985 that a numerical instability
can arise in the simulation of an arc of a circuit breaker, due to the time delay
between TACS and EMTP. A more recent work [11] describes numerical instability
in simulations of a lead acid battery (DC circuit) due to the same time delay.

Examples of numerical oscillations and inaccuracies due to internal time delays


are described in [1].

In 1986/87 a study of several problems concerning TACS, after about ten years of
existence, was carried out at The University of Wisconsin [12]. This work classifies,
among others, the problem of time delays within TACS and between TACS and
EMTP as a major TACS problem. It also contains examples of numerically bounded
Chapter 2. Literature Review^ 14

oscillations caused by this problem.

2.5 Final Remarks

The major work related to the elimination of time delays is reference [8]. This work
reduces many of the internal time delays, but not completely. The problem of the
time delay between TACS and EMTP has not been considered either by that work
or by any other work.
The importance of the present thesis lies in the fact that it addresses the problem
of eliminating both types of time delays. How important this is will become clear in
the next chapter, where the effects of the time delays in transient simulations will be
considered. Several cases of inaccuracy, instabilities and bounded oscillations will be
analyzed.
Chapter 3

Time Delays and the Stability and


Accuracy of the Simulation

"...if the feedback is delayed too long, oscillations will happen. A simple example that illustrates feedback instability
is the common home shower. Typically the shower begins with the water too cold, and the user turns up the hot water
to get the temperature he wants. If the adjustment is too strong (he turns the knob too far), he will soon find that
the shower is too hot, whereupon he rapidly turns back to cold and soon finds it is too cold. If the reactions are too
strong, or alternately the total system (pipes, valve, and human) is too slow, there will result a "hunting" that grows
more and more violent as time goes on."
R.W. Hamming°

° Numerical Methods for Scientists and Engineers — Dover Publications — New York — 1973.

3.1 Introduction

The objective of this chapter is to illustrate, with examples, the numerical instabil-
ity and stable inaccurate results that arise from the introduction of time delays in

transient simulations. The examples used are purposely simple to show the concepts
involved. However, some of them have practical importance in specific applications
as well.

15
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation^16

R= I

t= 0

b
TACS EMTP

Figure 3.1: Numerical instability in a DC circuit

3.2 Numerical Instability


3.2.1 DC Circuit
Figure 3.1 shows a circuit to be simulated by TACS-EMTP [11]. The switch and
resistor R2 are simulated inside the EMTP and the voltage source V and resistor R 1
are simulated inside TACS. TACS gives to the EMTP the voltage Va b and the EMTP
gives to TACS the current I, as indicated in the figure. TACS is, therefore, working
as a current controlled voltage source.
At any time step n,
Vab(n)
I(n) = R2

where Va b(n) is the latest value TACS gives to the EMTP. As TACS lags one time
step behind the EMTP,

Kb(n) = 1 — R i I(n — 1).

Figure 3.2 shows a plot of I versus t for the first 10 time steps, using the two
previous formulas for different values of the ratio K = R I /R2 (0.5, 1 and 1.5).
From the values of I(n) and Va t, given in the formulas above one can get the
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation ^17

40
K=1.5
e
z . 0.75

2, 0.5 C' 0
112
0.25 -20

0 -40 ^
0 2^4^6 10 0^2^4^6^8^10
Time (s) Time (s)

Figure 3.2: Current and Voltage in the circuit of Figure 3.1

following difference equation:

1^R 1 T(^
I(n) = ^1 ).
)
— R2 °-1 '

Applying the z-transform technique [13]

1^R1
= — — Z-1/(2).
R2 R2

Solving for /(z) gives


z
^/R2
/(z)
z Ri/R2
The pole of /(z) is z = —R 1 /R 2 . The stability of the solutions /(z) is guaranteed
if the poles zi satisfy jzil < 1. Therefore for /(z) to be stable, R 1 < R2. When
R l = R2) 121 = 1 and there is a bounded oscillation around the correct value. For
R2 = 2R1 (K = 1.5) the solution is clearly unstable (see Figure 3.2).
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation ^18

I(t) = (I/R,2 )V(t-At)

EMTP

TACSI V 1 / R2

(a) (b)

Figure 3.3: Arc modelling with EMTP-TACS

3.2.2 Arc modelling

Consider the circuit of Figure 3.3a where the resistor R2 is simulated by a current

source inside TACS [10]. The simulation arrangement is shown in Figure 3.3b. This
circuit can be used to model an arc in a circuit breaker by allowing R2 to vary
according to the arc characteristic.

The EMTP-TACS program discretizes the differential equation of the system using
the trapezoidal rule of integration. If the system Laplace transform algebraic equation
is available, it is possible to directly obtain the z-transform difference equation by
replacing s in the Laplace domain by (2/At) (z=-1
z ) [14]. The circuit of Figure 3.3b is,

therefore, transformed to the circuit of Figure 3.4.


Carrying out the stability analysis for the current I one obtains

I(z) = v1 /Zi
1 j_ (ZR2)(Z1
1 +Z2)
Z1 Z2

The poles of I(z) are the roots of

1+
(zR 2 )(Z1 + Z2 )
Zi Z2
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation ^19

Ze--(2/At)[(z 1)/(z+1)]L
-

Figure 3.4: z-transform domain analysis

100

".7e 50

-50

-100 -

-150 ^
0 1^2^3^4^5^6^7
Time (Rs)

Figure 3.5: Numerical instability in the arc modelling

With At.— 0 these roots are:

z = 1 and z = Ri/R2.

For R 1 > R2 the system is unstable even with At^0. Figure 3.5 shows one
unstable simulation for L 0.3H, R 1 = 10051, R2 = 10Q and At = 10ms.
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation ^20

20 40 60 80 100
Time (s)

Figure 3.6: Block diagram and exact solution of (t) x(t) = 0 [1]

3.2.3 Sinusoidal Oscillator

The examples of instabilities that have been shown so far are caused by the time delay
between the power system solution and the control system solution. The example of
this section illustrates the effect of time delays inside the control system solution
procedure [1].
Consider the block diagram of Figure 3.6 that represents the differential equation

(t) x(t) = 0^x(0) = 0, i(0) = 1.

The exact solution of this equation is also shown in Figure 3.6. The introduction
of one time delay in the feedback path of the block diagram causes the system to
become unstable (see Figure 3.7).
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation ^21

20 40 60 80 100
Time (s)

Figure 3.7: Instability due to the internal time delay

3.3 Stable Inaccurate Results


3.3.1 Internal Time Delays

As mentioned before, according to the EMTP-TACS approach, only pure transfer


function blocks will be solved simultaneously (see Chapter 2). The introduction of

any other type of control system block in closed loops will introduce time delays in
the solution procedure.
Figure 3.8 shows an example of the effect of the introduction of a Fortran func-

tion block in a closed loop control system [1]. The function used in the example
is the x 1 function which would not have had any influence on the system output

if the simulation had correctly been performed. The output of the system with the
TACS-introduced time delay jumps to 1.0 instantaneously l . In this case, not only the
1 The latest information from R.H. Lasseter of July 15, 1993 indicates that the wrong answer is
not only caused by the time delay, but by a coding error as well. The time delay by itself will still
produce incorrect answers, in the form of damped oscillations around the correct solution.
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation^22

OUT

0
— TACS solution

Correct solution

^
20^40^60^80 100
Time (ms)
Figure 3.8: Inaccuracy due to the internal time delay [1]

time delay, but also the ordering scheme [1], makes TACS work inaccurately. Note
that the system is stable throughout the simulation.

3.3.2 Converter Simulation — External Time Delays

A recent paper [2] shows another case of the effect of time delays in the simulation of

control and power system equations. A simulation of a three-phase thyristor inverter is


described. The comparison between the EMTP-TACS and the simultaneous solution
is shown Figure 3.9.

The three-phase inverter described in the paper is the one simulated in [15] using
the EMTP-TACS approach and is also shown in Figure 3.9. To show how sensitive
Chapter 3. Time Delays and the Stability and Accuracy of the Simulation ^23

an inverter is to the variation of its firing angle, consider the following values:

VLL^480V at 60Hz;

L l = 0.2mH;
L2 = 1.0mH;

Ld = 16mH;

E = 600V;
Firing angle a = 150°.

The simulation is performed with a discretizing time step At = 50ps. A time delay
of one At means a time delay of 1.08° electric degrees at 60 Hz. The inverter current

Id as a function of a is given by [16]

1.35VLL cos a + E
Id^= ^
3wL3/71-

where L, = L1 + L2. With the values shown above one has:


648.23 cos(150)+600 =
0.432 89.39A for a = 150°,
Id =
=
648.23 cos(151)+600
0.432^76.49A for a = 151°.

The difference between the two values above is approximately 14.4%. From Figure

3.9 the value of Id which TACS calculates at t = 80ms is 50A.


Chapter 3. Time Delays and the Stability and Accuracy of the Simulation^24

Ld

80

"? 60
t
2 40
ii
0
20

^
90 100
Time (ms)

Figure 3.9: Three-phase thyristor inverter current - TACS inaccurate result [2]
Chapter 4

Simultaneous Solution of Power


and Control System Equations

"There are no good, general methods for solving systems of more than one nonlinear equation."
W.H. Press, et al."
"...so Newton's method finds its chief use after we have got ourselves close to a root."
Forman S. Actonb

a Numerical Recipes — The Art of Scientific Computing, Second Edition — Cambridge University Press — 1992.
b Nurnerical Methods That Work — Mathematical Association of America — Washington, D.C. — 1990.

4.1 Introduction

The general concept of the simultaneous solution of the power system and the con-
trol system sets of equations is developed in this chapter. It involves two distinct
procedures, each one of them dealing with the elimination of one type of time delay.
The implementation of the concepts is carried out in one of the many versions of
the EMTP. The main concerns during the implementation were: to keep the EMTP

code modifications to a minimum, and to write a code capable of simulating significant


case studies while keeping the code to a reasonable size.

The code was written as a development code for testing ideas. At this stage, no
attempt towards optimizing parts of the code was done.

25
Chapter 4. Simultaneous Solution of Power and Control System Equations ^26

4.2 Basic Considerations


4.2.1 Elimination of the External Time Delay

The basic idea of the simultaneous solution is to assemble both sets of equations (from
the power and from the control systems) in one single matrix equation. By doing this,
the time delay between the solution of both sets of equation is eliminated.
The assembling procedure would produce an augmented matrix which is not sym-
metric in general (see Chapter 2, Eq. 2.2). This fact must be accounted for in a full
implementation of this method in the EMTP code, which, currently, handles only
symmetric matrices.
The present EMTP code works with symmetric matrices only, while TACS must
work with non-symmetric ones. In the proposed scheme, the augmented matrix con-
sists of the elements of both matrices put together, plus the connection elements
between the power and control systems (these elements are hidden by the nonsimul-
taneous approach currently in use). The number of these elements depends on the
number of elements in the power system controlled by the control system. This does
not include switch opening or closing commands. A reasonable assumption is that
this number is small. Therefore, the nonsymmetric augmented matrix would require

more memory for storage (compared to the sum of memory required by the two sepa-
rate matrices, one symmetric and the other nonsymmetric), as well as a small amount
of extra computational time to handle the connection elements.

4.2.2 Elimination of the Internal Time Delays

The existence of internal time delays is due to nonlinearities in closed loops inside
the control system. Therefore, to eliminate them, iterations must be allowed.
Chapter 4. Simultaneous Solution of Power and Control System Equations ^27

Y ^Y Linear Equations
11 12
Y ^Y Nonlinear Equations
21 22

Figure 4.1: Partition of the augmented matrix

Although the two opening statements of this chapter sound discouraging, the cho-
sen method for solving nonlinear equations was the Newton-Raphson procedure. This
method has fast convergence close to the root. The efficiency of the entire implemen-
tation will depend on this fast convergence characteristic. As for the closeness to
the root, except at moments of discontinuity of the solution (switching operations),
the previous value of a variable will constitute a very good guess for its present root
(value).

The application of the Newton-Raphson method to the whole augmented matrix


would be very inefficient. Therefore, the procedure used is similar to the one described
in [17]. The iterative method is confined only to those elements which contain the
nonlinearities .

Figure 4.1 shows the partition of the augmented matrix, which is necessary to
isolate the nonlinear elements. Note that the nonlinear elements are not only those
from the control system, but also those from the power system. By the same token,
the linear part of the matrix contains linear elements from both systems.

The reduction of the matrix to the nonlinear element matrix is illustrated in what
Chapter 4. Simultaneous Solution of Power and Control System Equations ^28

follows. The complete matrix equation is

[[ 1;12 11 1 m[2Y(11 ,] t )1 ) [(e 12 (( tt )) 1 ) — ( [[ kik2 1)^(4.4)

where the vector [ei(t)] not only contains the node voltages in the power system, but
also includes the control system block outputs (see Chapter 2, Eq. 2.2).
The vector [ki] includes the history terms from both systems; and

x1
x2
= (
x n,
is the vector of nonlinear variables which [Y22(Y, 1)] depends on. The submatrix
[Y22(Y,t)} contains the information about the nonlinear elements and the submatrix
[Y21 ] contains the information on how those elements are interconnected to the other
elements. Therefore, Eq. 4.4 can be reduced to the subset 2:

({1'22(Y, t )} - [Y21][Yii]
-1
[ Y12])[e2(t) ] = [ k2] - [Y211[Y111 -1 [k1].

This is the equation that is to be solved by the Newton-Raphson method.

4.3 Actual Implementation


4.3.1 Interface Between the Written Program and the EMTP

One of the methods used by the EMTP to handle nonlinearities is the compensation
method. This method excludes the nonlinear branch from the network and replaces
it by a current source (see Chapter 12 of [7]). The value of the current will depend
on the Thevenin equivalent network (seen from the nonlinear element nodes) and on

the nonlinear characteristic itself. Therefore, the equation of the network and of the
Chapter 4. Simultaneous Solution of Power and Control System Equations ^29

v
km Network Equation
/ Element Equation
Linear
Network
Solution
km i km

Figure 4.2: Compensation method in the EMTP

nonlinear element must be solved simultaneously. Fig 4.2 illustrates the situation.
The way of describing the nonlinear characteristic is, normally, point by point in the
EMTP input file.

The MicroTran version of the EMTP [18] makes this compensation method ap-
proach accessible through an interface which does not require any code changes in
the EMTP proper. The EMTP calculates at each time step the Thevenin equivalent

circuit of the network seen from whatever nodes are specified in the input file. It then
calls (at the same time step) a subroutine "CONNEC" to which it passes the values
of the Thevenin impedance and voltage (open circuit voltage) through the argument
list. This subroutine must return the value of the currents through the nonlinear
elements (Figure 4.3). Therefore, CONNEC enables the user to write a piece of code
to describe his/her own nonlinear elements and to interface these elements with the

EMTP, without having to touch the EMTP code itself. The important feature here is
that, although the nonlinear elements are not included directly in the EMTP matrix,
Chapter 4. Simultaneous Solution of Power and Control System Equations^30

Z'Thev ' open


EMTP >^ CONNEC
(Linear Network)

Current

Figure 4.3: Subroutine CONNEC and its interface with the EMTP

they are solved simultaneously with the network equations.


In the simultaneous solution method implementation, full advantage of the CON-
NEC facility was taken. All code additions (except for the part of program that
reads the control system input file and parts of the interpreter - discussed later on)
were implemented inside CONNEC. Any controlled power system element must be
considered as a nonlinear element to be included inside CONNEC together with the
control system equations in this approach.
Two consequences of working inside CONNEC must be pointed out:

• all the nonlinear elements to be modelled, regardless where they come from

(control or power system), must be included in CONNEC, since the network

must be linear for the compensation method to be applied; and

• there are actually two matrices being built (one inside the EMTP and the other
one inside CONNEC).
Chapter 4. Simultaneous Solution of Power and Control System Equations ^31

Z They
.-..././..",-
Control Vcontrol Vopen
System
T ^
'input ^ •^

(a)
Vinput

Control 'control
System
^•

(b)
Figure 4.4: Control actions upon the power system

As mentioned before (Chapter 1), there are three ways through which the con-
trol system may act upon the network: switch commands (put aside for a while);
controlled voltage source; and controlled current source. The two controlled source
situations are depicted in Figure 4.4.

Figure 4.4a shows the case of a current controlled voltage source. In this situation,
the equation to be included in the control system equations is

Vcontrol — ZThev X 'input = Vopen,


Chapter 4. Simultaneous Solution of Power and Control System Equations ^32

Figure 4.5: Matrix formation inside CONNEC

while in the case of Figure 4.4b (voltage controlled current source), the equation is

Vinput + ZThev X 'control = Vopen•

This is done for each branch which is acted upon by the control system. A typical
matrix formation inside CONNEC is shown in Figure 4.5.

The switch commands are handled separately. CONNEC controls the firing time
of thyristors and requires the EMTP to actually fire them. The firing action appears
as changes in the Thevenin equivalent circuit of the network.
Chapter 4. Simultaneous Solution of Power and Control System Equations ^33

4.3.2 Capabilities of the Program

In what follows, the program capabilities are outlined. The elements which the pro-
gram can model are similar to those modelled by TACS. The input format for elements
similar to TACS elements use similar formats to facilitate the translation of TACS
input files. The present implementation can handle most (but not all) of the TACS
blocks and is sufficient to allow fairly complex cases to be simulated.

Linear Elements

Linear elements are transfer functions blocks, which model any n th -order transfer
function of the form

\ Output^No +^+ + Nm S m
G°) — Input K Do + D 1 s + + Dnsn
Figure 2.2 of Chapter 2 shows this type of block.
For transient solutions, the Laplace operator s can be replaced by the differential
operator Tic transforming the equation above into the following differential equation:

dx^dnxit, , du^, dmu


D o x^+ • • • -4- .u n ^= ix wf o^4- • • • + v m )
dt^dtn^dt^dtm

This equation can now be decomposed into a system of n first-order differential equa-
tions, as follows:

dx^dx1 dx,,--1
x1 = x2 =^• • • x n = ^
dt'^dt '^dt
du^dui^dum_i
u1 = U2 -=^Um = ^
dt^dt^dt

The differential equation becomes an algebraic equation

Do x + D i +.. . + D rix , = K (Nou^+... + Armum).


Chapter 4. Simultaneous Solution of Power and Control System Equations ^34

The trapezoidal rule of integration can now be used to numerically integrate the
first - order differential equations . The internal variables x; can then be expressed as

2
xt = t xi_ 1 — {x1(t — Ot) + Qt xi_1(t —fit)}

u7 = Qt 2lj_1 — {u,(t — Ot) + Qt u^_1(t — Ot)},

for i=1. .. nand j = 1.. .m.


Expressing x n in terms of x n _ 1 and then x n _ 2 in terms of xn_1 and so on, only x
is left at the end of this process. If the same procedure is used for u, the following
output -input relationship is found:

cx(t) = K d • u(t) + hist(t — Ot).

The history terms are recursively calculated using the following formulation:

hist 1 = Kd i u(t) — c i x(t) — hist l (t — Ot) + hist 2 (t — zt)

histt = Kd u(t) — c;x(t) — hist1(t — Ot) + histi +l (t — Lit)


;

hist n = Kdn u(t) — c n x(t)

where hist = hist 1 .

The coefficients c and d are calculated once using the recursive formula:

) n(2 ( 2 ),+1d t+1 + ... +


c, = ca_ 1 + (-2)'{ z (2 )'D1 + z + 1
i Ot^i^Ot^i Ot )ndn}, (
^

Chapter 4. Simultaneous Solution of Power and Control System Equations ^35

where (a.) is the binomial coefficient, and

n^2 •
co = E()'Di
i.0 At
where c = co . The formulas for d are found replacing D by N in the above formulas.
The current implementation accepts up to 5 (five) different signals as inputs of
this block. Therefore, the input in the equation above can be

Input = +u1 u 2 u 3^u5.

The transfer function block also accepts the two types of limiters described in
Chapter 2 (Figure 2.5) - static and dynamic limiters.

FORTRAN Blocks

The FORTRAN blocks accept fairly general FORTRAN expressions as the relationship

between their output and input. One can have, for example,

a
= 3.6 • e -1-35.4 - 4.822 • e -217 • xP + 1.2217.
Xp

The program accepts the following operators and functions:

algebraic operators^: +, - , *, /, **
relational operators^: .EQ., .NE., .LT., .LE., .GE., .GT.
logical operators^: .0R., .AND., .NOT., .EQV., .NEQV.

FORTRANfunctions^:SIN, COS, TAN, COTAN, SINH, COSH, TANH,

ASIN, ACOS, ATAN, EXP, LOG, LOG10, SQRT, ABS

Appendix A gives a complete description of the FORTRAN block capabilities.


Chapter 4. Simultaneous Solution of Power and Control System Equations ^36

Inputs (up to 5)

Cntrl> 0 (Do + L • Do • OUT(t) =


K • INPUT(t)-1- hist(t — At)
where
hist(t) = K • INPUT(t)—
(Do — nt • D 1 ) • OUT(t)
^ Cntrl< 0 OUT(t) = named_reset(t)
Cntrl Named_Reset

Figure 4.6: Controlled integrator block

Special Elements

There are four blocks, called special element blocks, that play a special role described
bellow.

Time delay^This block delays the input by


- T S.

RMS block^This block calculates the RMS value of the input in


the previous 360° electrical degrees.

Controlled integrators^This block is a normal integrator that accepts two


controlling signals. Figure 4.6 illustrate how the ele-
ment works.

Point to point functions The general output-input relationship of this block


- -

is given point by point (two-column format) in the


input file.

Sources

Several types of sources have been implemented in the program. They are listed
below (cf. [6]):
Chapter 4. Simultaneous Solution of Power and Control System Equations ^37

• Sources with User-defined parameters

Source Type User-defined Parameters


Sinusoidal amplitude and frequency
Pulse start time, amplitude, period and width
Ramp start time, period and amplitude
Level Signal amplitude

• Built-in sources

Internal Name Output


TIMEX simulation time in seconds
ISTEP number of the current simulation time step
DELTAT size of the time step (TIMEX=ISTEP x DELTAT)
ZERO 0.0
MINUS1 —1.
PLUS1 1.
INFNTY -boo (very large number)
PI 7r

The Interpreter

The basic function of the interpreter is to compile a FORTRAN-like expression written


in an input file - describing the input-output relationship of a FORTRAN block - in a
way that the program can calculate the value of the expression given the values of

its variables. This is done in a sequence of subroutines shown in Appendix A. The


basic principles behind the construction of such an interpreter are also discussed in
that appendix.
The process of taking the expression from the input file and transforming it into
a vector of symbols to be evaluated from the values of the constituent variables, is
divided into two parts. The first part consists of taking the expression and building

the vector of symbols. Each FORTRAN block gives rise to a specific vector of symbols.
Chapter 4. Simultaneous Solution of Power and Control System Equations ^38

This is done outside the time loop. The second part of the process occurs inside the
time loop and is the evaluation of the expressions according to the values which their

variables take.

Initialization

The network steady-state initialization is performed by the EMTP. An ideal situa-


tion would be a simultaneous steady-state solution of the network and the control
system. Although a feasible alternative [19], this has not been implemented in the
EMTP-TACS program.
For the purpose of this thesis, only a DC initialization was implemented. This

initialization is simpler and yet does not limit too much the range of the program
applications.
The DC initialization process assumes that the input and output signals of the
control system blocks are DC quantities in steady state. In this case, the output-input
relationship of a linear (transfer function) block is

, No
Xpc = ----
„ UDC•
o

This equation fits into the same format of Eq. 2.1, Chapter 2 with c = 1, d = No /Do ,
and hist = 0 and a system of equations is formed and solved for the unknowns xpc.

Integrators pose a problem for this procedure because D o = 0 for this type of
linear block. Therefore, their steady-state output must be supplied by the user.
Since the initialization procedure implemented at this time is not iterative, it
cannot calculate the output of nonlinear blocks. The user must supply those values
to the program for the time being.
Chapter 4. Simultaneous Solution of Power and Control System Equations ^39

The Newton Method

• The "Dishonest" Newton Method


There is a provision in the program to speed up the Newton-Raphson method
with the so-called "dishonest" Newton method. Assume one has a vector of
nonlinear functions Ft involving variables x i (i = I, 2, ... , n) expressed as fol-
,

lows:
x2,..., x 7i ) = 0^i = 1,2,...,n.

If x denotes the variable vector and F denotes the function vector, at iteration h

Jx(h) • (5x = — F x (h)

where
aFi
ax e .

The solution vector is then modified at each iteration

x(h+1)(h)^r
= X + OX.

The "dishonest" Newton method calculates the Jacobian matrix J only once (in-
stead of at each time step) and this is done outside the iterative loop. Therefore,
the steps, after calculating the Jacobian matrix, are:

J^= —F X( h )

and
x (h+1) = x(h) Sx.

The application of this method is controlled by the user, who can disable the
normal Newton method from the input file.
Chapter 4. Simultaneous Solution of Power and Control System Equations ^40

• The calculation of the Jacobian matrix


The Jacobian matrix is numerically calculated by the program from the values
of the functions. The term Ji; of the matrix is calculated as follows:

aF, Fi (x i ,...,x i +Ax i ,...,x n )—Fi (x i ,...,x i —Ax i ,...,x,,)


ax^ 2 • Ax e
If the initial increment Ax i is not enough to provide small increments in the
function Fi, it is automatically divided by half and the Jacobian matrix is
calculated again.

Memory Limitation of the Current Implementation

The compilation of the current PC-implementation is performed by a compiler that


addresses only 640 kB of memory. Although this poses a restriction on the number of
elements in the EMTP and in the number of blocks in the control system simulation
program, the implementation is capable of simulating cases with a considerable degree
of complexity.
Chapter 5

Comparison Between
Simultaneous and
Non-simultaneous Approach

5.1 Introduction

This chapter presents several cases simulated with the simultaneous solution pro-
gram (SS) described in the previous chapter. It also compares results with TACS
simulations, where available.
The case studies give an overall view of the behaviour of the implementation of
SS, exploring key issues such as accuracy, efficiency and stability.

To focus the attention on these key issues, the cases presented here were chosen to
be simple, without any additional unnecessary complexity. They can be considered,
however, prototype situations that can occur in more complex cases where the key
issues are difficult to identify.
The first group of cases consists of simulations where only the control system is
involved. Static and dynamic limiters, as well as nonlinear functions in closed loops,
are simulated.

The second group contains cases where the control system and the network work
together. The cases illustrate the strength of the simultaneous solution approach.

41
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 42

For the reader's reference, Appendix B shows the input files for SS and the EMTP
(when available) of all cases discussed in this chapter.

5.2 Control System Case Studies

This set of cases shows the behaviour of SS in simulations involving control systems
alone. The EMTP part of it is disabled and only the program described in the
previous chapter is active.
Although the cases are simple, they are useful to show how the program performs
in general. Note that the case of Section 5.2.3 shows an important advantage of SS
over TACS.

5.2.1 Second-Order Linear System

Figure 5.1a shows the diagram of the following second-order transfer function:
\ Output w2
s 2 gw,i s + co n2
H(s) = Input —^
This system has an analytical solution for a step input [20]:
1
Output(t) = 1 — — • e - wn t • sin(wOt + 0)

where /13 = — 4. 2 and 0 = tan' Og.


Figure 5.1b shows the SS simulation for the case where w = 4.0 rad/s, = 0.125
and unit step input. The analytical result is superimposed to, and is indistinguishable
from the SS result.

5.2.2 Static and Dynamic Limiters in Open Loops

Two simple cases are considered in this section. They are taken from Chapter 5 of

reference [1].
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 43

Output
^>
S

Input

(a)

1.6

1.2

0.8 \f\i \ --------

0.4

o
o 2^4^6^8^10
Time (s)
(b)

Figure 5.1: Second-order linear system: (a) Diagram; (b) Solution for a unit step
input.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 44

Figure 5.2a shows the diagram of a static limiter system. Figure 5.2b shows its
solutions with and without the static limiter. Figure 5.3 illustrates a similar situation
for a dynamic limiter.

5.2.3 FORTRAN Function in a Closed Loop

As mentioned earlier, a nonlinear function in a closed loop can lead TACS to produce
wrong results. Figure 3.8 of Chapter 3 is reproduced in Figure 5.4, with the SS
solution added.

5.2.4 Special Element Block

To illustrate the application of special element blocks, Figure 5.5 shows a system uses
many of them. Some of these blocks will again be used in more realistic cases in
subsequent sections.

5.3 Simulations of Control and Power Systems

In this section, both the SS and the EMTP are active. The cases show the behaviour of

both programs working together, and demonstrate the advantages of the simultaneous
solution as the cases are presented.

For these cases, Appendix B shows not only the SS input files, but also the related
EMTP files.

5.3.1 Arc Modelling

Section 3.2.2 of Chapter 3 mentions a case of severe instability due to EMTP-TACS


interaction. This case is, therefore, a good test for the new program. Figure 5.6 shows

the superposition of the analytical and the SS simulation results for the system of
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 45

2.0
^
u 1000 X
s
-2.0

Static Limiter

(a)
u(t), x(t)
6^
x(t) - without limiter x(t) - with limiter
4
2
0
-2
-4
-6
0 0.04^0.08 0.12
Time (s)

(b)

Figure 5.2: Static limiter: (a) Diagram; (b) Simulation results.


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 46

u> 1000
S
/
-0.5

Dynamic Limiter

u(t), x(t) (a)


6
4
2
0
-2
-4
-6
0 0.04^0.08 0.12
Time (s)

(b)

Figure 5.3: Dynamic limiter: (a) Diagram; (b) Simulation results.


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 47

3
+5
OUT
2
0
— TACS solution
1-
SS and Correct solutions
0^
0^20^40^60^80^100
Time (ms)
Figure 5.4: Nonlinearity in a closed loop: (a) Diagram; (b) Simulation results N.

^var2 var3 ^var4 var5^ var6


Time
y—x2 K=1 *1 Delay RMS --->

var5 var4 var6

varl
^
0.02 0.04
time (s)

Figure 5.5: Special element blocks - Diagram and simulation results (source = cos wt,
w = 377 rad/s and time delay = 2 ms).
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 48

0 ^
0^0.1 0.2
Time (s)
Analytical solution: i(t) 1 ^ri R, t,
Ril1R2^e - I'

Figure 5.6: Arc modelling - superposition of the analytical and the SS simulation
results.

Figure 3.4 with the same parameters used in Figure 3.5. Both results are practically
identical.

5.3.2 Single-Phase Variable Load

Figure 5.7a shows an R-L load, of which the active power P is variable (time-
dependent), and the ratio P/Q is kept constant [1}.
Such an R-L circuit has a Laplace domain representation as shown in Figure 5.7b
if zero initial conditions are assumed. The block diagram representation of the circuit
is shown in Figure 5.7c.
The assumed variation of the active power P is shown in Figure 5.8 and the system
parameters are as follows:

R= 3 SI (P/Q = 3 - for L. 2.653 mH)


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 49

(a)
I(s)
1
>^ >
(b)

1
s -1- c
Source Fortran s-Block
Block
(c)

Figure 5.7: R-L load representation; c= R/L.


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 50

P (W) 15

1.5

50 100 150 200 Time (s)

Figure 5.8: Active power variation.

E m = 3.1623 V

It can be shown [1] that the value of L is dependent on the value of P as follows:
1 2wP ,P Q
L =^kQ+ TD )

where Q is the reactive power and P/Q = R/wL.


If P/Q is kept constant, L will depend only on P. Therefore, the variation of
power shown in Figure 5.8 can be accomplished by varying 1/L from 377 (1.5 W) to
3770 (15 W).
The block diagram for this variable load problem is shown in Figure 5.9. The
variable load is modelled as a control system inside SS and the sinusoidal source
(e(t) = sin wt) is modelled inside the EMTP. PINST is the instantaneous power and

PAVER is the average power in the circuit'.


1 The instantaneous power of any electrical component is p(t) = v(t) • i(t), where v(t) is the voltage
across the component and i(t) is the current through it. The average power over one period of time
P is
1 f
P =^t p(t)dt.
If the voltage and current waveforms have half wave symmetry, P can be calculated using
T = I/2f = 0.00833 s for 60 Hz. The values of P can be found continuously using the rolling
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 51

Signal from
EMTP to SS

K=1
SCR / IOUT
PINST
SCR*(CONS
+PULSE) ^> s + 1131
- -) *
Sinusoidal
Source CONS PULSE^IOUT
120
377 3393
\_.
Sources Delay
Controlled 0.00833
Current Source

PAVER
v

Network SS

Figure 5.9: Block diagram - Single-phase variable load [1].


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 52

-15 ^
0 40^80^120 160 200
Time (s)

20
(a)
15
10
5
0 -:.2"N,_."
-- — ..---

-5 -
-10 — iout
-15
0 40^80^120 160^200
Time (s)

(b)
Figure 5.10: Simulation Results: (a) TACS solution [1]; (b) SS results.

The simulation results obtained with TACS and SS are shown in Figure 5.10
for the current and the average power (PAVER). Note that both programs produce
practically identical results.
average power P(t) [1, Chapter 2] as follows:
1 f^1 f—T
P(t) = 7 ,- 0 p(t)dt — T 0^p(t)dt.
.,

Note that the second integral has the value of the first integral delayed by T seconds.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 53

5.3.3 Three-Phase Variable Load

The next three case studies are related to the 230 kV power system of Figure 5.11 [1].
The Thevenin equivalent circuit of the subsystem inside the dashed line is calculated
as seen from bus 7. The reduced system is shown in Figure 5.12 along with the
variable load connected to bus 13. The Thevenin equivalent values are (in sequence
values):

Zero Sequence:
Ro = 0.13 SI
L o = 27.71 mH
Positive Sequence:
= 0.06 C2
L i = 39.99 mH.

The sequence values of the transmission lines are:

Zero Sequence:
Ro = 0.03167 SZ/km
L o = 3.222 mH/km
Co = 0.00787 pF/km
Positive Sequence:
R l = 0.0243 Il/km
= 0.9238 mH/km
Cl = 0.0126 pF/km.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 54

r
It T 50 MVA
13.8 kV 5 0.9 pf
4
500/v1i/A 10%
2
400 MVA1
. 200 MVA 200 MV 10
X"=12% X=10% mi -IN 0.9pf
42 200MVA 200
500 MVA
.

..- 10%iC MVA 10


X"=1 3 n 100MVA
90 mi 15mi I
12

60 mi 230kV 1 00MVI
10%
^J
180 mi

200 MVA
50 MVA 50 M A 0.9 pf
X"=12% X =10%

Figure 5.11: Sample power system [1].

They A Bus7A ^BuslA B111112A

Three Phase
They B Thevenin Bus7B Bus1B Busl2B
Equivalent ^
T ev C Sequence Bus7C Bus1C^Bus12C
Values 144.4 km three phase 24.14 km three phase
transmission lime^transmission lime
Transformer

Bus 13
IL13 A
Sources Variable
Load

Figure 5.12: Diagram of the Thevenin reduced system [1].


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 55

The line lengths are:

from bus 1 to bus 7 — / 1 _ 7 = 144.4 km


from bus 1 to bus 12 — 4-12 = 24.14 km.

The transformer between bus 12 and bus 13 is represented by its series inductance:

LT = 70.16 mH seen from the 230 kV side.

As in the single-phase variable load case, it is assumed that the ratio

Active Power^P
= 3.042
Reative Power Q wL

will remain constant during the load variation..


In this case [1, Chapter 2]
1^P3
— 41.63 • V2:
where
P3 is the three-phase power in MW and
Vpu is the per unit value when K ase is 230000/0 . .

The variable load, as in the previous case, is simulated inside either TACS or SS.

Step Load Variation

The load modelling diagram for this case is shown in Figure 5.13. The load variation
is shown in Figure 5.14a. There are four three-phase power levels with the following
corresponding values of 1/L:

= 0.1795 for 9.5 MW;


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 56

IL13
Network as in Figure 5.12 CBA
Network
SS Bus13A Bus13B Bus13C
K=1 Sources K=1 Sources K=1
0.1795 2.3715 2.8650 1.2293
CONS1 OONS2 CC NS3 C 3NS4

Busl3A* Bus13B* Bus13C*


:CONS1+CONS24 ;CONS1+CONS2+ CONS1+CONS2+
CONS3+CONS4) CONS3+CONS4) CONS3+CONS4)

INT A INT_B INT_C


1 1 1
s+1146 s+1146 s+1146

PINSTA 120

Delay PA
8.3ms

Figure 5.13: Load modelling - step variation [1].

1
= 2.551 for 114 MW;

1
= 5.416 for 190 MW;

1
= 6.645 for 206 MW.

The voltage of phase A on bus 1 is shown in Figures 5.14b and 5.14c for TACS and
SS simulations. The good agreement between the results is readily noticeable.
^
^
^

Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 57

206
190
114

9.5

40 80^120 160^200
Time (ms)
(a)
300
>^200
100
a)
0)^0
cu
4-.^-100

-200
-300
0 40^80^120 160 200
Time (ms)
(b)
300
5 200
..^100
a)
co^0
al
.....^ -100
0
>^-200
-300 ^
0 40^80^120 160 200
Time (ms)
(c)

Figure 5.14: (a) Load variation — step variation, (b) TAGS simulation result [1], (c)
SS simulation result.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 58

IL13
Network as in Figure 5.12 CBA
Network
SS Bus 13A Bus 13B Busl3C
K=1 Source K=1 K=1
Sourc
5.2364 0.1795
CONS2 CONS1

Busl3A* Busl3B* Busl3C*


(CONS1+CONS2) (CONS1+CONS2) CONS1+CONS2)

INT—A INT_B
1 1 1
s+1146 s+1146 s+1146

PINSTA 120
8
x
Delay
PA
8.3ms

Figure 5.15: Load modelling - pulse variation [1].

Pulse Load Variation

The load modelling diagram used to simulate this case is shown in Figure 5.15. Fig-
ure 5.16 shows the load variation and the voltage at phase A on bus 1 for both TACS
and SS simulations, respectively. Both results are practically identical.

Load Variation with Thyristor Controlled Reactor

A thyristor controlled reactor (TCR) is the basic building block of static Var com-
pensators (SVC). It is usually connected in parallel with a fixed capacitor. The TCR
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 59

186.2

9.8
^
0 40^80^120^160^200
Time (ms)
(a)
300 ^
200
100
a)
-100 —
O
>^-200 -
-300 ^
0 40^80^120^160 200
Time (ms)
(b)
300
5- 200
100
rn 0
ca -100 —
0
>^-200 -
-300 ^
0 40^80^120 160 200
Time (ms)
(c)

Figure 5.16: (a) Load variation — pulse variation, (b) TACS simulation result [1], (c)
SS simulation result.
^

Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 60

consists of an inductor in series with an anti-parallel thyristor (two oppositely poled


thyristors), which conduct on half-cycles of the supply frequency as indicated in Fig-
ure 5.17a.
The RMS value of the fundamental component of the current through inductor is

Il^— sin ,
= ^ ),
wL^ 7r

where o is the conduction interval. This current has the same value as that of a
-

a — sin °-
normal inductor with L n „,,„ / = L/K where IC = ^ (cf. Figure 5.17b).
ir
If all current harmonics are neglected, the inductance of Figure 5.17b is the fun-
damental frequency model for the TCR of Figure 5.17a, which leads to the block
diagram of Figure 5.17c.

The TCR control system is represented, in this model, by the parameter IC. A
basic voltage controller for the TCR is shown in Figure 5.18 [1].
A voltage coming from the power system (VRMS pu ) is compared with the unity
source (UNITY). The difference is integrated with a gain and multiplied by 1/L.
If VRMS p .—UNITY> 0, a positive error signal is provided to the integrator. Epu,
which plays the role of IC in this model, and BLgam (K/L in Figure 5.17c) will increase.
The TCR and its control system is shown in Figure 5.19. This constitutes a simple

TCR model which ignores harmonics.


Consider again the power system of Figure 5.12. Capacitors are added to bus 1
(7 pF) to provide the necessary dynamic range of capacitive reactive power [1]. A
TCR is also added to bus 1 with L = 0.8 H.

The block diagram for the SS simulation is shown in Figure 5.20. In the first sim-
ulation, the TCR is disconnected from the network. The variable load is assumed to
have the variation of Figure 5.21. The TACS and SS results are shown in Figure 5.22.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 61

ma
Current fundamental component: / 1 = lirma
VW
( a -sin a
7r I
) .

(a)
L/K
Mirn a — sin a
IC = ^
7r
I^i(t)>^I
I ^I
I <^ v(t) ^> I
(b)
V(s)
I(s)
S
x/L
(c)
Figure 5.17: Thyristor controlled reactor: (a) Circuit diagram; (b) Circuit model; (c)
TCR s-domain model
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 62

Figure 5.18: Basic TCR voltage controller - K/L modelling [1].

Vrmspu V (from the network)


E
P
/^
1
BLgam
L
I (to the
^ network)
UNITY 0

Figure 5.19: TCR and its control system - a simple model.


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 63

Network
SS Bus1A^Bus1B^Bus1C
K=1 K=1
EMTP1^EMTP2

^VRMS^ VRMSpu
I
EMTP3

1 300
RMS 132.7876
Epu
^PLUS1
Source

CD

CD

Figure 5.20: SS block diagram.


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 64

P (MW) 209

9.5

50 100 150 200 Time (s)

Figure 5.21: Load variation.

With the same load variation, the TCR is connected to the network and the
simulations result are shown in Figure 5.23. Note the excellent agreement between
TACS and SS simulations.

5.3.4 Simple HVDC System Model

Assume that the following modifications are made in the power system of Figure 5.11:

• capacitors at bus 1 and 10 are removed;

• generation at bus 3 is increased from 200 to 500 MW;

• the double circuit lines between bus 2 and 9 are removed; and

• load at bus 10 is increased from 300 to 500 MVA.

To make the system operational under these circumstances, the AC transmission


line between bus 1 and 2 is now replaced by a DC line carrying 400 MW. The reactive
power consumption of the two converters is assumed to be compensated locally.
Figure 5.24 shows the system under study [1]. Three events will be simulated:

• initial DC current ramp-up (from 0% at time zero up to 100% at 50 ms);


^

Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 65

270
Vrms
180
90
a) 0
cu
-90
O
-180 -
-270 ^
0 40^80^120 160 200
Time (ms)
(a)

f7 111
^270 ^
j^180^► A^kAA^A
90 ^
a)
0)^o
as
4-^-90 -
-180 -
-270
0 40^80^120^160^200
Time (ms)
(b)

Figure 5.22: Load variation without TCR: (a) TACS simulation [1]; (b) SS simulation.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 66

270 ^
Vrms
5' 180k-
/
90
G)
0
cc;
-90 —
0
-180 -
-270
0 40^80^120^160^200
Time (ms)
(a)

f ll I T T T
270
180
Vrms
>
.. 90
a) 0
0)
co
.... -90 —
>
O
-180 — i I A A A
-270 ^
0^ 40^80^120 160
Time (ms)
(b)

Figure 5.23: Load variation with TCR: (a) TACS simulation [l]; (b) SS simulation.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 67

1
SOOMVA
50 MVA^500MVA 120 mi
0.9 pf 500MVA 400 MW^DC line
3 1 50 00 MVA

200 10
MVA 200 MVA mi^ 0.9pf
500 MVA 6
11 100MVA

As 00 MVA
60 mi
90 mi
200M VA
9
15 mi
12
0.95 pf
11
100MVA

300 MVA
50 MVA 0.9 pf
50 MVA

Figure 5.24: Power system with a DC line [1].

• DC line to ground fault at 100 ms, followed by

• a complete DC load rejection at 150 ms.

To simulate these events in terms of the converter current (Id ) and firing angle
(a), the diagram of Figure 5.25 is used.
The AC system of Figure 5.24 is reduced to its single-phase equivalent, and the
HVDC system is simulated using the current injection method [1]. Figure 5.26 illus-
trates the simulation diagram.
In addition to the modelling for Id and a (Figure 5.25), there are three more
subsystems to be simulated. They are (Figure 5.27): the voltage tracking system,
the DC system itself, and the AC current injection system. The reader is referred to
reference [1] for a complete description of this system.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 68

Magnitude = 1.6
Turns on at t = 50 ms Source
IDC

Ramp up to 1.6
in 50 ms Source
TIMEX ^-286*XP
107.79* (X111
^)1 X1*(X.GE.0)
^>3.6*6 135"3:4.822*e 17."+1.2217
0.1
ALPHA
Source
Magnitude = 0.31416

Figure 5.25: Id and a modelling [1].

V( t)

IACF IDC
SS
ALPHA

Figure 5.26: EMTP SS simulation diagram [1].


-
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 69

from Network
K=1

cos cot Vm= (CPC1+SPS1)


Vm

CV CP cos cot + SP sin cot


Vm ^> cV
sin cot Cl* sin o)t -S1 cos cot
eV — 8V
Vm

(a)

^
IDC cV^eV
1
Ilpk — +elan:DC
a=0.8933 coe(DT) cos(AF) ^
2*Xc*IDC IACF
0'43 *Vm term = cV*ces, + eV*sin,

we coe(AF) + coe(DT) IACF = - Ilpk*term


2

(b)^ (c)

Figure 5.27: (a) Voltage tracking system; (b) DC system equations; (c) AC current
injection [1].
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 70

ALPHA

IACF
40^80^120 160 200
Time (ms)
(a)

ALPHA

160^200
Time (ms)
(b)

Figure 5.28: IDC, ALPHA and IACF comparisons; (a) TACS simulation [1]; (b) SS
simulation.

Four parameters from the TACS solution were compared against the SS solution:
currents IDC and IACF; firing angle ALPHA; and voltage at bus 1 (BUS1). Figures
5.28 and 5.29 show the results of both solutions.

5.4 Converter Simulations

Converter simulations were briefly discussed in Chapter 3, Section 3.3.2. This section
presents additional results concerning the thyristor rectifier and inverter simulations.
Comparisons between TACS and SS results are also provided.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 71

300

100
0)
co -100
0

-300
40^80^120^160 200

Time (ms)
(a)
300

100
a)
0)
co^-100
0

-300
0^40^80^120 160 200

Time (ms)
(b)

Figure 5.29: Voltage at bus 1 (BUS1) comparison; (a) TACS simulation [1]; (b) SS
simulation.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 72

5.4.1 Single Phase Thyristor Rectifier Bridge


-

A single-phase thyristor rectifier is shown in Figure 5-30a. The main functions of its
controller with its block diagram appears in Figure 5-30b. The TACS [16] and SS
simulation results for this rectifier are shown in Figure 5-31.
Although the curve of id is the same in both simulations, the curve of v d shows a
difference. The TACS solution presents pronounced peaks at the times of thyristor
firings (see Figure 5.31). It was possible to reproduce these peaks with the SS program
by introducing, artificially, one time delay between the program and the EMTP. This
shows that the origin of the peaks is the external time delay between TACS and
EMTP.

5.4.2 Three Phase Thyristor Inverter


-

In the case of a three-phase thyristor inverter, the effect of the external time delay
between TACS and EMTP appears on the DC side current (id). Figure 3.9 shows the
inverter diagram and the TACS and SS simulation results. As stated before, there is

a difference of 14% between the two currents. If, again, one artificially introduces a
time delay between SS and the EMTP, it is possible to reproduce the TACS results.

5.4.3 Remarks on Converter Simulation with the EMTP

Although not apparent from the discussion above, there is an extra non-simultaneous
phenomenon in effect in the thyristor converter simulations. This effect is a charac-
teristic of the EMTP and is present both in the SS and TACS results.

Thyristors are modelled by the EMTP as controlled switches. Their closing times
are controlled by the equations describing the firing angle control. The opening action
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 73

From (a)
EMTP
K=1 h
rsA
To EMTP


To EMTP


Source 120 RAMP
Comparator PLS1-2 Delay Block PLS34

1.0 S / :RAMP .GE. VCONTL, 1/2 cycle

Source VCONTL
0.25
VSA

RAMP
■11
Firing PLS1-2 PLS3-4
Signals
t
(b)
Figure 5.30: Single-phase thyristor rectifier.
^
•^

Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 74

270 -

^d 200 -

a)
130 -
60-^
vd
^ho
Cd^-10 -
430 ^-
0
-150 ^
35^ 36 37

Time (s)
(a)
200 r-
>^
1 30 -
Pili^
60 -
CD
b.0^-10 -
Cd
17(
4dri.
" - - 80—

-150 ^
35 36 37

Time (s)
(b)

Figure 5.31: Single-phase rectifier simulations — voltage vd: (a) TACS results; (b) SS
results.
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 75

i ?witch opens
SWITCH

current forced to
zero in the next step

T FIRE
1

closed here

Figure 5.32: Closing and opening of EMTP switches.

takes place as soon as the current goes through zero, from a positive to a negative
value.
Since the EMTP uses a fixed time step to integrate the differential equations of
the system, the closing and opening actions will generally not occur at the specified
instants of time [7]. Instead, there is a delay between the desired time and the real
one. Figure 5-32 illustrates the situation for a given firing angle. The closing action
takes place at the time step nearest to TFIRE (some EMTP versions may close at the

time step following TFIRE [7]). The opening action takes place after the current has
gone through zero, which is detected by the current sign change.
As presented in [21] this problem can be eliminated by the following procedure:

1. interpolation to obtain the variables at the point of discontinuity (switch open-

ing or closing); and

2. integration of the system equations after the discontinuity over two half time

steps (At/2) using the backward Euler method, to properly re-initialize the
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 76

history terms of all the system components [14].

The interpolation is performed to catch the exact moment of the discontinuity.


The use of the backward Euler method is necessary to re-initialize the variables
after the switch operation. Reference [7] suggests that the integration over just one
half time step after the interpolation is enough to re-initialize all the variables. This is
true only for isolated lumped elements, when one can assume that either a constant
voltage (across capacitances) or constant current (through inductances) will occur
during the one half time backward Euler step. One of those two conditions is essential
for re-initializations of the variables at the instant of discontinuity.
For elements connected either in series or in parallel, two backward Euler integra-

tion over two half time steps are needed to provide the right re-initialization for the
variables of the system. This method is illustrated in Figure 5.33.
The effectiveness of the backtracking procedure can be seen in Figure 5.34, where
the inverter of Figure 3.9 is simulated with the normal EMTP (EMTP in the figure)
and with a modified version of the EMTP that includes the backtracking method
(bktrack in the figure). Because the normal EMTP misfires the thyristors, its solu-
tion shows a short-circuit of the inverter that does not exist, as demonstrated by the

modified EMTP solution. The time step used in the simulations was 200ps.

5.5 Final Remarks

As mentioned in the introduction to this chapter, the case studies presented here were
intended to show the performance of a new, more accurate and stable approach of
the simultaneous solution, when compared to the current non-simultaneous option.
In general, when TACS performs well, so does the proposed method in terms
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 77

i( t) interpolation
iLt? ........

--->
t t o +A t
t - At 1
:

et^et
2^2
1

a ........, b
Vab
\..-----^---.-^ 1
1

1 t CLOSE^I
t + At
41, a^ ■ CLOSE
t - At^t

At^At
2^2

backward Euler steps

Figure 5.33: Backtracking procedure.


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 78

1000
EMTP
a)
c3)
500 bktrack
0

C
0 LiartA ^ vi
a)
L..

'5 -500
vd
-1000
0.16 0.185 0.21 0.235 0.26
Time (s)

Figure 5.34: Inverter simulation: instability due to thyristor misfiring


Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 79

of accuracy. In those cases where there is an instability in the TACS solution, the
proposed method outperforms TACS, showing no instability in its solution. In cases
where an analytical solution exists, it is possible to observe how accurate the SS
approach performs.
The efficiency of the SS method is related to the application of the Newton-
Raphson method, which is used whenever there is a nonlinearity in a closed loop.
Nonlinearities outside closed loops pose no problem since they do not require any
iterative solution method. As mentioned in Chapter 4, for slowly converging cases,
there is an option of the "dishonest" Newton method, which can speed up the solution
somewhat. Although most of the cases simulated by the author, and the great ma-
jority of the cases shown in this thesis, do not require more than three iterations, on
average, at each time step, some cases may require more than three iterations [2]. This
situation is caused by the fact that the convergence of the Newton-Raphson method
can be guaranteed only if one is close enough to a root. Since almost any kind of
equation can be simulated with SS, one cannot guarantee either fast convergence, nor
convergence per si, in the general case.
As mentioned before, at each time step, the guess for the value of the root is
normally its previous value. This may be sufficient in the majority of situations. In
cases of poor convergence, one may try to improve the method of prediction of the

present value of the root. The author has performed a theoretical analysis on the
stability and accuracy of various prediction method [22] and has implemented the
linear prediction method in the current version of the SS program. The application
of the linear prediction method is controlled by the user.

The case shown in Figure 5.24, for example, required 8 iterations to converge
when the normal guess method is used (previous value) and the "dishonest" Newton
Chapter 5. Comparison Between Simultaneous and Non-simultaneous Approach 80

method is applied. If the linear prediction and the full Newton method is applied the
number of iterations decreases to 4.

Timing is not shown in this thesis because the code developed is not a production
code. In a production code, simulation time would increase because of iterations, but
that is better than having unreliable answers.
Chapter 6

Conclusions

The main contributions of this thesis are:

• it proposes and describes a method for solving the network equations and the

control system equations simultaneously;

• it describes the implementation of the method within the framework of the


EMTP, which is one of the most widely used general purpose programs for the
calculation of transient phenomena in electric power system;

• it presents a set of case studies showing the main characteristics of the present
implementation and how well it performs when compared with other existing
implementations.

The proposed method of simultaneous solution of the control and power systems
equations has proved to be, not only accurate, but also stable. A number of example
circuits were simulated to illustrate the inaccuracy and instability problems that can

occur when artificial time delays are introduced in the simulation (as in TACS). The
situations typified in the case studies are likely to occur in more complex simulations
where the effect of these time delays can be much harder to isolate.
On the programming side, the main objective was to write enough code to demon-
strate the feasibility of the proposal. Code optimization was not considered during

81
Chapter 6. Conclusions^ 82

the development of the ideas. In this sense, more work has to be done if this code is
to become production-grade code.
It may be appropriate to indicate some of the improvements which the current
implementation might need to be transformed into a useful general-purpose code. The
first decision is related to the question whether the control system should be simulated
inside a subroutine (as it is in the current implementation). A better solution would
be to merge the control and network equations into one single system of equations.
This would require a major code modification in the EMTP. The new code would
have to be able, among other things, to handle non-symmetric matrices. Sparsity
techniques would still be applied.
One necessary modification in the current SS code, in the case of a major code
revision, is the implementation of a procedure similar to the CDA, to damp numerical
oscillations originating from within the control system. The current CDA procedure
is capable of damping only numerical oscillations caused by events occurring inside
the network.
Although the implementation has performed well in terms of accuracy and stabil-
ity, some cases may pose some problems in terms of efficiency, requiring an excessive
number of iterations. To better guess the value of the variables and improve the
convergence of the Newton method, prediction methods should be further studied.

Another possibility for improvements is the interpreter of functions outlined in


Appendix A. This interpreter can be extensively improved and, perhaps, also be
used as a front-end interpreter which can allow digital control systems to be read in
from the EMTP input file.
Bibliography

[1] R.H. Lasseter. EMTP Workbook IV. Electric Power Research Institute, Palo
Alto - California, 1989.
[2] A.E.A. Araujo, H.W. Dommel, and J.R. Marti. Simultaneous Solution of Power
and Control Systems Equations. Paper 93 WM 241-0-PWRS, IEEE PES Winter
Power Meeting, Columbus, Ohio, 1993.
[3] H.W. Dommel. Digital Computer Solutions of Electromagnetic Transients in
Single- and Multiphase Networks. Trans. Power App. and Syst., PAS-88:388-
399, 1969.
[4] W.F. Long. Power Systems Analysis Using Electromagnetic Transients Pro-
grams. IEEE/PES Transmission and Distribution Conference, September 1991.

[5] L. Dube and H. W. Dommel. Simulation of Control Systems in an Electro-


magnetic Transients Program with TA CS. In Proceedings of IEEE PICA Conf.,
pages 266-271, 1977.
[6] Bonneville Power Administration, Portland-Oregon. Electromagnetic Transients
Program Rule Book, April 1982.

[7] H. W. Dommel. Electromagnetic Transients Program Reference Manual (EMTP


Theory Book). Department of Electrical Engineering - The University of British
Columbia, Vancouver - Canada, 1986.
[8] Ma Ren-ming. The Challenge of Better EMTP-TACS Variable Ordering. EMTP
Newsletter, 4(4):1-6, August 1984.
[9] D.G. Chapman, A.J. Helse, F.L. Alvarado, and N.J. Balu. Ordering and Initial-
ization Algorithms for Control Systems Models. IEEE Trans. Power Delivery,
3(3):1189-, July 1988.
[10] J.A. Lima. Numerical Instability due to EMTP-TACS Inter-relation. EMTP
Newsletter, 5(1):21-33, 1985.

83
Bibliography^ 84

[11] M. Ceraolo. A Case of Numerical Oscillations caused by the TACS-EMTP In-


terface. EMTP Newsletter, 5(3):4-10, September 1992.

[12] R.H. Lasseter. Tacs improvements - classification of problems - final report.


Technical report, Department of Electrical and Computer Engineering - Univer-
sity of Wisconsin, Madison, June 1987.
[13] Robert A. Gabel and Richard A. Roberts. Signals and Linear Systems. John
Wileys & Sons, Inc., New York - USA, 1987.
[14] J.R. Marti and J. Lin. Suppression of Numerical Oscillations in the EMTP.
IEEE Trans. on Power Syst., 5(2):394 402, May 1990.
-

[15] N. Mohan. Computer Exercises for Power Electronics Education. Department


of Electrical Engineering-University of Minnesota, Minneapolis, 1990.
[16] N. Mohan, T.M. Undeland, and W.P. Robbins. Power Electronics Converters,
-

Applications and Design. John Wiley & Sons, New York - USA, 1989.

[17] H.W. Dommel. Nonlinear and Time Varying Elements in Digital Simulation of
-

Electromagnetic Transients. Trans. Power App. and Syst., PAS-90:2561-2567,


November-December 1971.
[18] MicroTran Power System Analysis Corporation, Vancouver-Canada. Transients
Analysis Program Reference Manual, 1991.

[19] X.J. Cheng and C. Hatziadoniu. A Gradient-Based Algorithm for the State Ini-
tialization of Control Systems. IEEE Trans. on Power Syst., 6(4):1349-1355,
November 1991.
[20] Richard C. Dorf. Modern Control System. Addison-Wesley Publishing Company,
Inc, New York - USA, 1989.
[21] A.E.A. Araujo, H.W. Dommel, and J.R. Marti. Converter Simulations with the
EMTP: Simultaneous Solution and Backtracking Technique. Paper APT 286-
18 - Accepted for publication, Joint International Power Conference (IEEE -
NTUA) - Athens Power Tech, September 5-8, 1993, Athens, Greece.
[22] A.E.A. Araujo, H.W. Dommel, and J.R. Marti. Numerical Instabilities in Power
System Transients Simulations. In Proceedings of the IASTED Conference,
Power Systems and Engineering, pages 176-180, 1992.
Bibliography^ 85

[23] Jean-Paul Trembley and Paul G. Sorenson. The theory and Practice of Compiler
Writing. McGraw-Hill Book Company, New York — USA, 1985.

[24] S. Bhattacharya. Personal communication to Dr. H. W. Dommel. 1991.


Appendix A

Interpreter Basic Principles

This appendix is based on references [23] and [24]. Its objective is to broadly de-
scribe the principles used to write the interpreter which reads, from the input file,
FORTRAN-like mathematical expressions and calculates their values, given the values
of their variables, at each time step.
The project of the interpreter begins with the definitions about the syntax, the
operators, the functions, types of variables and function arguments it will accept.
These definitions for the present interpreter are as follows:

algebraic operators^: +, - , *, / , **
relational operators^: .EQ . , . NE . , . LT . , . LE . , . GE . , . GT .
logical operators^: .0R., .AND., .NOT., .EQV., .NEQV.
FORTRAN functions^:SIN, COS, TAN, COTAN, SINH, COSH, TANH,

ASIN, ACOS, ATAN, EXP, LOG, LOG10, SQRT, ABS


variables^: any 6 character alphanumeric name
arguments^: any variable or any numerical arguments,
either integer or real
parenthesis nesting^: accepted

In addition, all the rules for constructing standard FORTRAN expressions apply.

86
A.1 Compilation of Arithmetic Expressions

The way an arithmetic expression is written in the input file is the normal way to
write them, for example: (a + b) (c d). This type of expression is called infix

expression. This format is easier to understand but it is not efficient to evaluate.


A complex expression in the infix format normally requires parenthesization. The
expression below is known as a fully parenthesized expression
^
((w (x / y))^(z x 5)).
^
2 3^1^2
The integers below the algebraic operators specify the parenthetical level of each
operator. To evaluate this expression, the subexpression which contains the operator
with the highest parenthetical level is calculated first. If two or more operators
have the same parenthetical level, they are evaluated from left to right. The process
continues with the subexpressions at the next highest levels until all the operations
have been performed.

The repeated scanning of an infix expression can be avoided if it is first transformed


to a parenthesis free format such as

(operand) (operand)(operator) ^(suffix)

or
(operator) (operand) (operand) ^(prefix)

instead of the infix form

(operand) (operator) (operand) ^(prefix).

The prefix and suffix forms of the notation are also called prefix Polish and reverse
Polish, respectively.

87
The evaluation of a Polish expression is much easier than the related infix expres-
sion. The infix expression

(x x ((y + z) — 5))

has the following reverse polish equivalent form

xyz + 5 — x.

A reverse Polish expression can be evaluated by applying the following rules re-
peatedly until all operators have been processed:

1. Find the leftmost operator in the expression.

2. Select the two operands immediately preceding the operator found in step 1.

3. Perform the indicated operation.

4. Replace the operator and its operands with the result.

The previous reverse Polish expression is evaluated as follows (applying the four
rules above):
a
-------,
First evaluation x yz + 5 — x ---3 (y + z).

#
„....-.....,
Second evaluation x a5 — x —4 (y + z) — 5.
'Y
e....—"—.,
Final evaluation x/9 x -- 7 = x x ((y + z) — 5)).

Comparing this evaluation process with the evaluation of the infix expression
shown previously, one can see how much easier it is to calculate Polish expressions.

88
Table A.1: Simple Precedence Function

Symbol Precedence
f
— 1
x, / 2
Variables and
nonnegative integers 3
0

A.2 From Infix to Polish Notation

The conversion of an infix expression without parenthesis to a reverse Polish expres-

sion requires an operator precedence function and the use of a stack. As seen above,
in both forms of the Polish format (suffix and prefix) the variables and constants ap-
pear in the same order as in the infix format. The operators, however, are reordered
and this is the reason for the use of a stack. The output of the conversion is put in
an output string.
For the simple example discussed in this section, assume the existence of the

four arithmetic operators, variables and nonnegative integers. Table A.1 shows the
precedence function for this case. The special symbol # has the smallest precedence
value in the table and is used to initialize the stack and to ensure that the stack is
always nonempty.
The stack is initialized with the symbol #. The algorithm to be described is mainly
based on the comparison of the precedent function value of the current input and the
precedent function value of the top element of the stack. If the precedent value of
the input symbol is greater than that of the symbol on top of the stack, then the

89
Table A.2: Transformation of a— b x c+ d/5 into Reverse Polish

Current input Contents of stack ^Reverse Polish


symbol^(rightmost symbol is expression
top of stack)^(output string)

a^#a
a
b^#—b^a
x^#— x^ab
c^#— x c^ab
#+^abc x —
d^#+d^abc x —
/ #+/^abc x —d
5^#+/5^abc x —d
tt^ abc x —d5 +

current input symbol is pushed onto the stack and the next input symbol is scanned.

If, however, the precedence value of the current input symbol is less than or equal to
that of the stack top symbol, this top element is written in the output string. After
this, the same current input symbol is compared to the new element on the stack.
The process stops when all the input symbols have been analyzed. This algorithm is
illustrated in Table A.2, for the infix expression a — b x c+ d/5.
To handle more complex parenthesized expressions two precedent functions are
needed: the input precedence function f and the stack precedence function g. The
right and left parenthesis perform the same function as the special symbol # in the
simple algorithm previously described. Table A.3 shows the two functions for the
implementation of this thesis.
The complete algorithm to translate infix to reverse Polish is:

90
Table A.3: Input and Stack Precedence Functions

Symbol^ Input precedence Stack precedence


function, f^function, g
(^ 21^—1
variables and constants^19^20
intrinsic function (COS, SIN, etc.) 17^18
** (exponential)^16^15
*, /^ 13^14
+, -^ 11^12
.EQ.,.NE.,.GE.,.GT.,.LT.,.LE. ^9^10
.NOT.^ 7^8
.AND.^ 5^6
.OR.^ 3^4
.EQV.,NEQV.^ 1^2
0^not inserted in stack
)^ —1^not inserted in stack

1. Initialize

TOP 4- 1
NEXT 4- STACK(TOP)
OUTBUFFER 4- "

2. Scan the infix expression

Repeat through step 5 while there are unprocessed


tokens (symbols)

3. Get next input token and set right parenthesis flag

91
LAST 4 NEXT
-

NEXT 4-- GET_NEXT_TOKEN (INFIX)


RIGHTJ'AREN 4-- false

4. Put in the stack if token higher precedence than NEXT

Repeat while f (NEXT)< g(STACK (TOP) )


TEMP STACK (TOP)
-

TOP 4 - TOP - 1
if f (NEXT) < g(TEMP) then
OUTBUFFER 4 OUTBUFFER//TEMP
-

end if
if TOP=0 then
write(Invalid expression')
end if

5. Push NEXT to STACK but not `)' or ' , '. The function of the delimiter 'Y is
to separate arguments of an intrinsic function. Therefore this delimiter must
not close the left parenthesis. Its action is similar to a right parenthesis and a
comma should not be inserted in the stack at any time.

if not RIGHT_PAREN and NEXT comma then


TOP 4 - TOP + 1
STACK (TOP) 4-- NEXT
end if

6. Finished? or error

92
if TOP=0 then
exit the program
el se

write('1nvalid expression)
end if

The FORTRAN code for the precedence function f and g is shown right below. Next
it is shown the FORTRAN code for subroutine POLISH, which transforms a infix to a
reverse Polish expression. The subroutine EVAL (also shown below) takes the output of
POLISH (OUTPUT) and transforms it into a character vector that has, in each position,

a different token of the reverse Polish expression.

INTEGER FUNCTION PFUNC(X)


CHARACTER*6 X
C^This Integer Function gives the input precedence function f
C^Logical operators
IF(X .EQ. '.EQV. ' .OR. X .EQ. '.NEQV.') THEN
PFUNC = 1
ELSE IF(X .EQ. '.OR. ^') THEN
PFUNC = 3
ELSE IF(X .EQ. '.AND. ') THEN
PFUNC = 5
ELSE IF(X .EQ. '.NOT. ') THEN
PFUNC = 7
C^Relational operators
ELSE IF(X .EQ. '.EQ.^' .OR. X .EQ. '.NE.^' .0R.
1^X .EQ. '.LE.^' .OR. X .EQ. '.LT.^' .OR.
2^X .EQ. '.GE.^' .OR. X .EQ. '.GT.^') THEN
PFUNC = 9
C^Arithmetic operators
ELSE IF(X .EQ. '+ ^' .OR. X .EQ.^') THEN
PFUNC = 11
ELSE IF(X .EQ. '* ^' .OR. X .EQ. '/^') THEN

93
PFUNC = 13
C^Exponential
ELSE IF(X .EQ.^'** ') THEN
PFUNC = 16
C^Intrinsic functions
ELSE IF(X .EQ. 'COS ' .OR. X .EQ. 'ACOS^' .OR.
1^X .EQ. 'SIN ' .OR. X .EQ. 'ASIN^' .OR.
2^X .EQ. 'TAN ' .OR. X .EQ. 'ATAN^' .0R.
3^X .EQ. 'ATAN2 ' .OR. X .EQ. 'TANH^' .OR.
4^X .EQ. 'COSH ' .OR. X .EQ. 'SINH^') THEN
PFUNC = 17
ELSE IF(X .EQ. 'DIM ' .OR. X .EQ. 'AMOD^' .OR.
1^X .EQ. 'SIGN ' .OR. X .EQ. 'ALOG^' .OR.
2^X .EQ. 'SQRT ' .OR. X .EQ. 'ALOG10' .OR.
3^X .EQ. 'EXP ' .OR. X .EQ. 'ABS^' ) THEN
PFUNC = 17
C^Parenthesis
ELSE IF(X .EQ. '(^') THEN
PFUNC = 21
ELSE IF(X .EQ. ')^') THEN
PFUNC = -1
C^Delimiter
ELSE IF(X .EQ.^') THEN
PFUNC = 0
C^Variables and Constants
ELSE
PFUNC = 19
ENDIF
RETURN
END

INTEGER FUNCTION GFUNC(X)


CHARACTER*6 X
C^This Integer Function gives the stack precedence function g
C^Logical operators
IF(X .EQ. '.EQV.' .OR. X .EQ. '.NEQV.') THEN
GFUNC = 2
ELSE IF(X .EQ. '.OR.') THEN
GFUNC = 4

94
^

ELSE IF(X .EQ. '.AND.') THEN


GFUNC = 6
ELSE IF(X .EQ. '.NOT.') THEN
GFUNC = 8
C^Relational operators
^ELSE IF(X^.EQ.^'.EQ.' .OR.^X^.EQ.^'.NE.' .OR.
1^X^.EQ.^'.LE.' .OR.^X^.EQ.^'.LT.' .OR.
2^X^.EQ.^'.GE.' .OR.^X^.EQ.^'.GT.') THEN
GFUNC = 10
C Arithmetic operators
ELSE IF(X^.EQ.^'+ '^.OR.^X^.EQ. ') THEN
GFUNC = 12
ELSE IF(X^.EQ.^'* '^.OR.^X^.EQ.^'/ ') THEN
GFUNC = 14
C Exponential
ELSE IF(X .EQ. '** ') THEN
GFUNC = 15
C Intrinsic functions
ELSE IF(X^.EQ. 'COS ' .OR. X .EQ. 'ACOS ' .OR.
1^X^.EQ. 'SIN ' .OR. X .EQ. 'ASIN ' .OR.
2^X^.EQ. 'TAN ' .OR. X .EQ. 'ATAN ' .OR.
3^X^.EQ. 'ATAN2 ' .OR. X .EQ. 'TANH ' .OR.
4^X^.EQ. 'COSH ' .OR. X .EQ. 'SINH ') THEN
GFUNC = 18
ELSE IF(X .EQ. 'DIM ' .OR. X .EQ. 'AMOD ' .OR.
1^X^.EQ. 'SIGN ' .OR. X .EQ. 'ALOG ' .OR.
2^X^.EQ. 'SQRT ' .OR. X .EQ. 'ALOG10' .OR.
3^X^.EQ. 'EXP ' .OR. X .EQ. 'ABS^' ) THEN
GFUNC = 18
C^Parenthesis
ELSE IF(X .EQ. '(^') THEN
GFUNC = -1
ELSE IF(X .EQ. ')^') THEN
GFUNC = -1
C^Delimiter
ELSE IF(X .EQ.^') THEN
GFUNC = 0
C^Variables and Constants
ELSE

95
^

GFUNC = 20
ENDIF
RETURN
END

SUBROUTINE POLISH(INPUT,OUTPUT)
C^Transforms a expression from the infix to reverse Polish form. In
C^the transformation, it uses two functions: input precedence
C^function PFUNC; and stack precedence function GFUNC.
C^INPUT has its tokens separated by colons (delimiter). For example,
C^COS;(;VAR1;+;VAR2;) for the infix expression COS(VAR1+VAR2)
C^OUTPUT also has its tokens separated by colons. For example, for
C^the same infix expression, OUTPUT would be VAR1;VAR2;+;COS.
CHARACTER*6 COMMA
CHARACTER*400 INPUT, OUTPUT, OUTBUF
INTEGER^TOP, PFUNC, GFUNC, IBUF, POINTR
INTEGER^SIX, BUFSIZ, MAXSTK
LOGICAL^RPAREN
PARAMETER^(SIX = 6, BUFSIZ = 400)
PARAMETER^(MAXSTK = 100, COMMA =
CHARACTER*6 STKTOP, STACK(MAXSTK), NEXT, BLANK6
EXTERNAL^PFUNC, GFUNC
DATA^BLANK6/'
C^Initialize variables
DO 10 I = 1, BUFSIZ
OUTBUF(I:I) = BLANK6(1:1)
10^CONTINUE
DO 15 I = 1, MAXSTK
STACK(I)^= BLANK6
15^CONTINUE
IBUF = 1
TOP = 1
POINTR = 1
STACK(TOP) = '(
C^Get next token
100 CONTINUE
C^Get the next token from the input string and put in the
C^variable NEXT. If no more token is available ISTAT is set
C^to ZERO otherwise ISTAT is one.

96
NEXT = BLANK6
J = 0
ISTAT = 1
DO 50 I = POINTR, BUFSIZ
IF(INPUT(I:I) .EQ.^GOTO 60
IF(INPUT(I:I) .NE. BLANK6(1:1)) THEN
J = J + 1
IF(J .GT. SIX) THEN
WRITE(*,*) 'TOKEN IS GREATER THAN 6 CHARACTERS'
STOP 'INTERNAL ERROR'
ENDIF
NEXT(J:J) = INPUT(I:I)
ENDIF
50^CONTINUE
C^Check for J ?
IF(J .GT. 0) THEN
WRITE(*,*) 'LAST TOKEN DOES NOT HAVE A ENDING DELIMITER'
STOP 'ERROR'
ENDIF
ISTAT = 0
60^CONTINUE
C^Reset the pointer
POINTR = I + 1
IF(ISTAT .EQ. 0) THEN
NEXT = ')
ENDIF
C^Set right parenthesis flag
RPAREN = .FALSE.
C^Start
STKTOP = STACK(TOP)
70^IF(PFUNC(NEXT) .LE. GFUNC(STKTOP)) THEN
TOP = TOP - 1
IF(PFUNC(NEXT) .LT. GFUNC(STKTOP)) THEN
CALL TOBUFF(IBUF,OUTBUF,STKTOP)
ELSE
RPAREN = .TRUE.
GOTO 150
ENDIF
IF(TOP .EQ. 0) THEN

97
WRITE(*,*) 'INVALID EXPRESSION'
STOP 'ERROR'
ENDIF
STKTOP = STACK(TOP)
GOTO 70
ENDIF
150 CONTINUE
C^Push NEXT to STACK but not ")" or ","
C^The function of the delimiter "," is to separate arguments of an
C^intrinsic function. Therefore, this delimiter must not close the
C^left parenthesis. Its action is similar to a right parenthesis
C^and a comma should not be inserted in the stack at any time.
IF((.NOT. RPAREN) .AND. NEXT.NE . COMMA) THEN
TOP = TOP + 1
IF(TOP .GT. MAXSTK) THEN
WRITE(*,*) 'STACK OVERFLOW'
STOP 'ERROR'
ENDIF
STACK(TOP) = NEXT
ENDIF
C^Continue till ISTAT = 0
IF(ISTAT .NE. 0) THEN
GOTO 100
ENDIF
C^Finished?
IF(TOP .EQ. 0) THEN
OUTPUT = OUTBUF
RETURN
ELSE
WRITE(*,*) 'INVALID EXPRESSION'
STOP 'ERROR'
ENDIF
END

SUBROUTINE TOBUFF(IBUF,BUFF,TOKEN)
C^Routine TOBUFF writes the token to the output buffer OUTBUF.
C^It also trims each token and inserts a token delimiter ';'
C^after each token.
PARAMETER^(SIX = 6, BUFSIZ = 400)

98
CHARACTER*400 BUFF
CHARACTER*6^TOKEN, TRIMTK
C^Trims the incoming token
J = 0
DO 10 I = 1, SIX
IF(TOKEN(I:I) .NE. ") THEN
J = J + 1
TRIMTK(J:J) = TOKEN(I:I)
ENDIF
10^CONTINUE
IF(IBUF .LE. BUFSIZ) THEN
IF(J .GT. 0) THEN
BUFF(IBUF:80) = TRIMTK(1:J) // ';'
IBUF = IBUF + J + 1
ENDIF
ENDIF
RETURN
END

SUBROUTINE EVAL(OUTPUT,N,ISTACK)
C^Creates a stack ISTACK (a vector) that contains, in each position,
C^one token of OUTPUT. ISTACK has a proper form to be evaluated by
C^subroutine CALCU.
IMPLICIT^REAL*8 (A-H O-Z), INTEGER*4 (I-N)
2

PARAMETER^(NSTKSIZ=400,NVAR=30)
CHARACTER*400 OUTPUT
CHARACTER*6 ISTACK(NVAR)
N = 0
K = 0
DO 10 I = 1, NVAR
ISTACK(I) = '
10^CONTINUE
DO 50 I = 1, NVAR
J = 0
100^CONTINUE
K = K + 1
IF(K .LE. 400) THEN
IF(OUTPUT(K:K) .EQ. ';') GOTO 50
IF(OUTPUT(K:K) .NE. ") THEN

99
J = J + 1
IF(J .LE. 6) THEN
ISTACK(I)(J:J) = OUTPUT(K:K)
ELSE
GOTO 50
ENDIF
ENDIF
GOTO 100
ENDIF
GOTO 200
50^CONTINUE
200 CONTINUE
DO 400 I = 1, NVAR
IF(ISTACK(I) .NE.^') N = N + 1
400 CONTINUE
RETURN
END

A.3 Evaluation of a Reverse Polish expression

To evaluate the reverse Polish expression the following algorithm is used:

1. Initialize

TOP 4- 0
VALUE 4- 0

2. Scan the reverse Polish expression

Repeat through step 5 while there are unprocessed


tokens (symbols)

3. Get next input token

1 00
NEXT < — GET_NEXT_TOKEN (REVERSE)

4. Check if it is an operand (control system variable or real number)

if NEXT = operand then


TOP 4-- TOP + 1
STACK (TOP) = Value_of_(NEXT)
GOTO step 3
end if

5. Find what type of operator? Apply proper operations

6. Finished? or error

if TOP=1 then
VALUE = STACK (TOP)
exit the program
else
write(Invalid expression')
end if

The general algorithm to read the infix expression from the control system input
file and transforms it into a reverse Polish expression to be calculated at each time
step is described below.

1. Outside the time loop.

(a) Read infix expression and take all the blank characters out of it.

101
(b) Separate the tokens by colons (delimiters).

(c) Call subroutine POLISH

(d) Call subroutine EVAL

2. Inside the time loop — Call, at each time step, the subroutine CALCU (FORTRAN
code shown below) to evaluate the expression (following the algorithm above).
CALCU has the ability to recognize control system variable from real numbers
that could appear in the FORTRAN expressions.

C^Interpreter

SUBROUTINE CALCU(ISTACK,N,VALUE,II)
IMPLICIT^REAL*8 (A-H 2 O-Z), INTEGER*4 (I-N)
PARAMETER^(NSTKSIZ=400,NVAR=30,NFOR=18)
CHARACTER*6 ISTACK(NSTKSIZ),IVAR
CHARACTER*6 CHECK1, CHECK2
DIMENSION^STACK(NSTKSIZ)
EXTERNAL^RGHTJST,CONVERTION
INCLUDE^VAR1

C^Initialize
ITOP = 0

C^Start traversing the input stack (N tokens)

DO 10 I = 1, N
C^Check for a operator

IF(ISTACK(I) .EQ. '+^') THEN


IF(ITOP .LT. 2) THEN
WRITE(*,*) 'ERROR IN + OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ELSE
VALUE = STACK(ITOP) + STACK(ITOP-1)

102
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ENDIF
ELSE IF(ISTACK(I) .EQ. '-^') THEN
IF(ITOP .GT. 1) THEN
VALUE = STACK(ITOP-1) - STACK(ITOP)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE IF (ITOP .EQ. 1) THEN
STACK(ITOP) = -STACK(ITOP)
ELSE
WRITE(*,*) 'ERROR IN - OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '*^') THEN
IF(ITOP .GT. 1) THEN
VALUE = STACK(ITOP-1) * STACK(ITOP)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN * OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '/^') THEN
IF(ITOP .GT. 1) THEN
IF(STACK(ITOP) .EQ. O.DO) THEN
WRITE(*,*) 'DIVISION BY ZERO;'
WRITE(*,20) II
CALL ERROR('Error')
STOP
ENDIF
VALUE = STACK(ITOP-1) / STACK(ITOP)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN / OPERATION'
WRITE(*,20) II

103
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) . EQ. '** ^') THEN
IF(ITOP .GT. 1) THEN
IF(STACK(ITOP-1) .LT. 0.D0) THEN
WRITE(*,*) 'EXPONENTIATION OF NEGATIVE NUMBER'
WRITE(*,20) II
CALL ERROR('Error')
STOP
ENDIF
VALUE = STACK(ITOP-1) ** STACK(ITOP)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN ** OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'COS^') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DCOS(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN COSINE OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'SIN^') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DSIN(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN SINE OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'TAN^') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DTAN(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN TAN OPERATION'

104
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'COSH ') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DCOSH(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN COSH OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'SQRT ') THEN
IF(ITOP .GE. 1) THEN
IF(STACK(ITOP) .LT. O.DO) THEN
WRITE(*,*) 'SQUARE ROOT OF NEGATIVE NUMBER'
WRITE(*,20) II
CALL ERROR('Error')
STOP
ENDIF
STACK(ITOP) = DSQRT(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN SQRT OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'EXP^') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DEXP(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN EXP OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'ACOS ') THEN
IF(ITOP .GE. 1) THEN
IF(STACK(ITOP).LT.-1.DO.OR.STACK(ITOP).GT.1.D0) THEN
WRITE(*,*) 'ACOS ARGUMENT EITHER >1 OR <-1;'
WRITE(*,20) II
CALL ERROR('Error')

105
STOP
ENDIF
STACK(ITOP) = DACOS(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN ACOS OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'ASIN ') THEN
IF(ITOP .GE. 1) THEN
IF(STACK(ITOP) .LT. O.DO) THEN
WRITE(*,*) 'ASIN ARGUMENT EITHER >1 OR <1;'
WRITE(*,20) II
CALL ERROR('Error')
STOP
ENDIF
STACK(ITOP) = DASIN(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN ASIN OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'ATAN ') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DATAN(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN ATAN OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'TANH ') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DTANH(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN TANH OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'SINH ') THEN

106
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DSINH(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN SINH OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'ALOG ') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DLOG(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN ALOG OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'ALOG10') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DLOG10(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN ALOG10 OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. 'ABS ^') THEN
IF(ITOP .GE. 1) THEN
STACK(ITOP) = DABS(STACK(ITOP))
ELSE
WRITE(*,*) 'ERROR IN ABS OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.EQV. ') THEN
IF(ITOP .GT. 1) THEN
K = 1
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE

107
ELSE
WRITE(*,*) 'ERROR IN .EQV. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.NEQV.') THEN
IF(ITOP .GT. 1) THEN
K = 2
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .NEQV. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.OR. ') THEN
IF(ITOP .GT. 1) THEN
K = 3
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .OR. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.AND. ') THEN
IF(ITOP .GT. 1) THEN
K = 4
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE

108
ELSE
WRITE(*,*) 'ERROR IN .AND. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.NOT. ') THEN
IF(ITOP .GE. 1) THEN
K = 5
A = STACK(ITOP)
CALL CONVERTION1(A,VALUE)
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .NOT. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.EQ. ') THEN
IF(ITOP .GT. 1) THEN
K = 6
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .EQ. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.NE. ') THEN
IF(ITOP .GT. 1) THEN
K = 7
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .NE. OPERATION'

109
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.LE. ') THEN
IF(ITOP .GT. 1) THEN
K = 8
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .LE. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.LT. ') THEN
IF(ITOP .GT. 1) THEN
K = 9
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .LT. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.GE. ') THEN
IF(ITOP .GT. 1) THEN
K = 10
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .GE. OPERATION'

110
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE IF(ISTACK(I) .EQ. '.GT. ') THEN
IF(ITOP .GT. 1) THEN
K = 11
A = STACK(ITOP-1)
B = STACK(ITOP)
CALL CONVERTION(A,B,VALUE,K)
ITOP = ITOP - 1
STACK(ITOP) = VALUE
ELSE
WRITE(*,*) 'ERROR IN .GT. OPERATION'
WRITE(*,20) II
STOP 'ERROR'
ENDIF
ELSE

C^It must be an operand, therefore place the operand on the


C^top of the stack

ITOP = ITOP + 1
READ(ISTACK(I),*,IOSTAT=NERROR) STACK(ITOP)
IF(NERROR .GT. 0) THEN
READ(ISTACK(I),'(1A6)') CHECK1
CALL RGHTJST(CHECK1)
C^Check if the operand is a control system variable or a real number.
C^If it is a variable, its value is in T_IVAR.
DO 9 KK = 1, LL(II)
CHECK2 = IVAR(II,KK)
IF(CHECK1 .EQ. CHECK2) STACK(ITOP) = T_IVAR(II,KK)
9^CONTINUE
ENDIF
ENDIF
10^CONTINUE

C^Check if ITOP = 1

IF( ITOP .EQ. 1) THEN

111
VALUE = STACK(1)
ELSE
WRITE(*,30) ITOP
WRITE(*,20) II
WRITE(*,40) N
ENDIF
20 FORMAT(' FORTRAN EXPRESSION it',I3)
30 FORMAT(' ERROR IN THE END OF STACK - ITOP =',I3)
40 FORMAT(' NTOKENS = ',I3)
RETURN
END
Appendix B

SS and EMTP Input Files

B.1 Control System Case Studies — SS Input Files


Only
B.1.1 Second-Order linear system (Section 5.2.1)
C Second-order linear system -- step unit response
C
C^s-block^1/s
^
1 VAR2 + VAR1 - LOOP2 1.D0
1.D0
1.D0
C
C^s-block -- 1/s
^
1^OUT - LOOP1 + VAR2 1.D0
1.D0
1.D0
C
C^k-block -- *16
0 VAR1 +SOURCE^ 16.D0
C
C^k-block^auxiliar block
0 LOOP1 + OUT^ 1.D0
C
C^k-block -- *16
0 LOOP2 + OUT^ 16.D0
C

C^source block -- unit step function


^
21SOURCE^1.D0 O.DO
C

C^fortran expression block

113
C
C^output variables
33 OUT VAR1
C

C^connection variables

C
C^initial conditions
77 VAR2^O.DO
77 OUT^O.DO
C

C^end of file

B.1.2 Static and Dynamic Limiters (Section 5.2.2)


C^Static limiter
C
C^k-block^auxiliar block
INP + SRC23 + AUX
C
C^k-block^auxiliar block
AUX + SRC21
C
C^s-block^(10**3)/s
1 VAR1 + INP
1.D0
1.D0
C
C^k-block -- limiter block
OUT + VAR1^ 1.D0 -2.D0 2.D0
C

C^source blocks -- input square wave


21 SRC21^-1.D0^ O.DO
23 SRC23^2.D0^20.D-3^10.D-3^ O.DO
C

C^fortran expression block

114
C^output variables
33 INP OUT
C

C^connection variables

C^initial conditions
77 OUT^-4S.D-1
C

C^end of file -- static limiter

C^Dynamic limiter
C
C^k-block^auxiliar block
INP + SRC23 + AUX^ 1.D0
C
C^k-block^auxiliar block
AUX + SRC21^ 1.D0
C
C^s-block^(10**3)/s with limits (-.6,1.5)
1 OUT + INP 1.D3-5.D-1 1.5D0
1.D0
1.D0
C

C^source blocks -- input square wave


21 SRC21^-1.D0^ O.DO
23 SRC23^2.D0^20.D-3^10.D-3^ 0.D0
C

C^fortran expression block

C^output variables
33 INP OUT
C

C^connection variables

115
C

C^initial conditions
77^OUT^-6.D-1
C

C^end of file

B.1.3 FORTRAN Function in a Closed Loop (Section 5.2.3)


C FORTRAN function in a closed loop -- Work Book IV
C
C^s-block
1 VAR1 -FDBACK +SOURCE^ 1.D0
6.D0^1.D0
1.D0
C
C^k-block
0 VAR2 + VAR1 1.D0
C
C^k-block
0 OUT + VAR2 1.D0-2.D-3 2.D-3
C
C^k-block
OFDBACK + OUT 25.D-2
C

C^source block
22SOURCE^1.D0^-60.D0^90.0
C

C^Fortran expression block

C^output variables
33 OUT VAR2FDBACK
C

C^connection variables

116
^

C^initial conditions

C^end of file

B.1.4 Special Element Blocks (Section 5.2.4)


C RMS, NONLINEAR FUNCTION, TIME DELAY AND FORTRAN EXPRESSION BLOCKS
C
&CASE37.OUT^(Output file name)
&CASE37.AUX^(Auxiliar file name - shows how SS reads the input file)
&YN^(Apply fast Newton Method)(Save number of iterations)
C^k-block
0 VAR1 + SCR^ 1.D0
C
C

C^Time delay block


66 VAR5 VAR4^2.D-3
C

C^source block
22^SCR^1.D0^60.D0
C

C^Fortran expression block


99 VAR4 =VAR2*1.D0
C

C^point-to-point nonlinear function --> y = x**2


88 VAR2^VAR1
C
C^x^ y
C
-2.D0^4.D0
-1.05D0^1.1025D0
-1.D0^1.D0
-9.5D-01^9.03D-01
-9.0D-01^8.10D-01
-8.5D-01^7.22D-01
-8.0D-01^6.40D-01
-7.5D-01^5.62D-01

117
-7.0D-01 4.90D-01
-6.5D-01 4.22D-01
-6.0D-01 3.60D-01
-5.5D-01 3.02D-01
-5.0D-01 2.50D-01
-4.5D-01 2.02D-01
-4.0D-01 1.60D-01
-3.5D-01 1.22D-01
-3.0D-01 9.00D-02
-2.5D-01 6.25D-02
-2.0D-01 4.00D-02
-1.5D-01 2.25D-02
-1.0D-01 1.00D-02
-5.0D-02 2.50D-03
0.D0 0.D0
6.00D-02 2.50D-03
1.00D-01 1.00D-02
1.50D-01 2.25D-02
2.00D-01 4.00D-02
2.50D-01 6.25D-02
3.00D-01 9.00D-02
3.60D-01 1.22D-01
4.00D-01 1.60D-01
4.50D-01 2.02D-01
5.00D-01 2.50D-01
5.60D-01 3.02D-01
6.00D-01 3.60D-01
6.50D-01 4.23D-01
7.00D-01 4.90D-01
7.50D-01 5.63D-01
8.00D-01 6.40D-01
8.50D-01 7.23D-01
9.00D-01 8.10D-01
9.50D-01 9.03D-01
1.D0 1.D0
1.05D0 1.1025D0
1.1D0 1.21D0
2.D0 4.D0
99999.D0
C

C^RMS block
^
60 VAR6 VAR5 60.D0
C

118
C^output variables
33 VAR1 VAR4 VAR5 VAR6
C

C^initial conditions
^
77 VAR2 1.D0
^
77 VAR4 1.D0
C

C^end of file

B.2 Control and Power System Case Studies


SS and EMTP Input Files
B.2.1 Arc Modelling (Section 5.3.1)
EMTP Input File
&LIMA.INP^ SS input file

^ Case identification card


Resistor as a voltage contolled current source ^-1
*
^ Time card
.0001^.2

^ Lumped RLC branch


1^2^ 300.
2^ 100.
^
92^2 11
2.^0.
9999999.
$>>>>>>>End of level 1: Linear and nonlinear elements<<<<<<<<<
$>>>>>>>End of level 2: Switches and piecewise linear elements
*
^ Voltage or current sources
11^1 1^1
$>>>>>>>End of level 3: Sources<<««<<<««<<<<<««««<<<<<
1^**** All voltages will be printed ****
$>>>>>>>Level 5: End of data case<<<<<<<<<<<<<<<<<<<<<<<

119
SS Input File
C^Arc modelling
C
&LIMA.OUT^ Input file name
&LIMA.AUX^ Auxiliar file name
&YN^(Apply fast Newton Method?),(Save number of iterations?)
C
C^k-block
0 ITACS + VEMTP^ 1.D-1
C

C^output variables
33 ITACS
C

C^connection variables -- variables shared by SS and EMTP


44 ITACS VEMTP^0.D0
C

C^initial conditions
^
77 ITACS 0.D0
C

C^end of file

B.2.2 Single-Phase Variable Load (Section 5.3.2)


EMTP Input File
C^Single phase variable load
C
C
&CASE17.0UT
&CASE17.AUX
&YN
C
C
C^s-block
1 ITACS +^INT^ 1.D0
1131.^1.D0
1.D0
C
C s -block

120
1^PB + PINST^ 1.D0
1.D0
120.D0
C
C^k-block
0 AUX1 + SRC21 377.D0
C
C^k-block
0 AUX2 + VEMTP 1.D0
C
C^k-block
0 AUX5 + SCR23 1.D0
C
C^k-block
0 PAVER +^PB - PDEL 1.D0
C

C^time-delay block
66 PDEL^PB^8.33D-3
C

C^source block
21 SRC21^1.D0
^ ^
23 SCR23^3393.D0 1.D-1 5.D-2^ 5.D-2
C

C^Fortran expression block


99 INT = AUX2*(AUX1+AUX5)
99 PINST = AUX2*ITACS
C

C^output variables
33 ITACS PAVER
C

C^connection variables
44 ITACS VEMTP^31623D-4
C

C^initial conditions
^
77^INT 0.D0
^
77 PINST 0.D0
^
77^PB O.DO
C

121
C^end of file

SS Input File
&CASE17.INP

^ Case identification card


Resistor as a voltage contolled current source

^ Time card
0.00005^0.2^ 1
*
^ Lumped RLC branch
1^2^1.D-19
92^2
2.^O.
9999999.
$>>>>>»End of level 1: Linear and nonlinear elements<<<<<<<<<
$>>>>>>>End of level 2: Switches and piecewise linear elements

^ Voltage or current sources


14^1 1^3.1623^60.
$>>>>>>>End of level 3: Sources «««««««««««««««<
1^**** All voltages will be printed ****
$>>>>>>>Level 5: End of data case<<<<<«««««««««

B.2.3 Step Load Variation (Section 5.3.3)


EMTP Input File
&CASE22.INP
C^.^ .^. Case identification card
THREE-PHASE VARIABLE LOAD-STEP VARIATION
C LOAD REPRESENTED INSIDE SS (NODE BUS13A)
C
C^ . Time card
50.E-6^.2^1
C
C^.^ .^. Symmetric pi circuit
1 THEVA BUS7A^83.E-3^35.
2 THEVB BUS7B^23.E-3^-5.^83.E-3^35.
3 THEVC BUS7C^23.E-3^-5.^23.E-3^-5. 83.E-3^35.
C
C^.^ . Lumped RLC branch

122
^

BUS1A 4.011
BUS1B 4.011
BUS1C 4.011
BUS12ABUS13A 70.16
BUS12BBUS13B 70.16
BUS12CBUS13C 70.16
92 IL13A
2.^0.
9999999.
^
92 IL13B IL13A
^
92 IL13C IL13A
C
C^. .^. Constant-parameters line
-1 BUS7A BUS1A .03167 3.222.00787 144.4
-2 BUS7B BUS1B .0243 .9238^.0126 144.4
-3 BUS7C BUS1C
-1 BUS1ABUS12A .03167 3.222.00787 24.14
-2 BUS1BBUS12B .0243 .9238^.0126 24.14
-3 BUS1CBUS12C
$ = = End of level 1: Linear and nonlinear elements ^
BUS13A IL13A^0.^99999.
BUS13B IL13B^0.^99999.
BUS13C IL13C^0.^99999.
$ = = = End of level 2: Switches and piecewise linear elements
C
C^.^ .^. Voltage or current sources
14 THEVA 1 187.79 60. -1.
14 THEVB 1 187.79 60. -120. -1 .
14 THEVC 1 187.79 60. 120. -1.
$ = = = End of level 3: Sources
C
C^ . Voltage-output nodes
BUS1A
$ = = = End of level 4: User-defined voltage output
$ = = = Level 5: End of data case ^

SS Input File
C^CASE22.INP
C
C^Phase A
C
C^s-block
^
1ITACSA + INT_A 1.D0
11468.D-1^1.D0

123
^

1.D0
C
C^k-block
^
O AUX2A +VEMTPA 1.D0
C
C^Phase B
C
C^s-block
^
1ITACSB + INT_B 1.D0
11468.D-1^1.D0
1.D0
C
C^k-block
^
O AUX2B +VEMTPB 1.D0
C
C^Phase C
C
C^s-block
^
1ITACSC + INT_C 1.D0
11468.D-1^1.D0
1.D0
C
C^k-block
^
O AUX2C +VEMTPC 1.D0
C
C Auxiliar Blocks
C
C^k-block
O CONS1 +SRC211^ 1.D0
C
C^k-block
O CONS2 +SRC212^ 1.D0
C
C^k-block
O CONS3 +SRC213^ 1.D0
C
C^k-block
O CONS4 +SRC214^ 1.D0
C
C^k-block
O AUX2 + CONS1 + CONS2 + CONS3 + CONS4 ^ 1.D0
C

C^source block

124
21SRC211^1795.D-4
21SRC212 23715.D-4 5.D-2
21SRC213 28650.D-4 1.D-1
21SRC214 12293.D-4 15.D-2
C

C^fortran expression block


99 INT_A =AUX2A*AUX2
99 INT_B =AUX2B*AUX2
99 INT_C =AUX2C*AUX2
C

C^output variables
33 CONS4
C

C^connection variables
44ITACSAVEMTPA^0.D0
44ITACSBVEMTPB^O.DO
44ITACSCVEMTPC^0.D0
C

C^initial conditions
^
77 INT_A O.DO
^
77 INT_B O.DO
^
77 INT_C O.DO
C

C^end of file

B.2.4 Pulse Load Variation (Section 5.3.3)


EMTP Input File
kCASE23.INP
C^.^ .^. Case identification card
THREE-PHASE VARIABLE LOAD-PULSATING LOAD VARIATION
C LOAD REPRESENTED INSIDE SS (NODE BUS13A)
C
C^.^ . Time card
50.E-'6^.2^1 1
C
C^.^ . Symmetric pi circuit
1 THEVA BUSTA^0.083334.563

125
^

^ ^
2 THEVB BUS7B 0.0233-5.427 0.083334.563
^ ^ ^
3 THEVC BUS7C 0.0233-5.427 0.0233-5.427 0.083334.563
C
C^.^ . Lumped RLC branch
^
BUS1A 4.011
^
BUS1B 4.011
^
BUS1C 4.011
^
BUS12ABUS13A 70.16
^
BUS12BBUS13B 70.16
^
BUS12CBUS13C 70.16
92 IL13A
2.^0.
9999999.
^
92 IL13B IL13A
^
92 IL13C IL13A
C
C^.^ .^. Constant-parameters line
-1 BUS7A BUS1A .03167 3.222.00787 144.4
-2 BUS7B BUS1B .0243 .9238^.0126 144.4
-3 BUS7C BUS1C
-1 BUS1ABUS12A .03167 3.222.00787 24.14
-2 BUS1BBUS12B .0243 .9238^.0126 24.14
-3 BUS1CBUS12C
$ = = End of level 1: Linear and nonlinear elements ^
BUS13A IL13A^0. 99999.
BUS13B IL13B^0. 99999.
BUS13C IL13C^0. 99999.
$ = = = End of level 2: Switches and piecewise linear elements
C
C^. .^. Voltage or current sources
14 THEVA 1^187.79 60.
14 THEVB 1^187.79 60.^-120.
14 THEVC 1^187.79^60.^120.
$ = = = End of level 3: Sources ^
C
C^.^ . Voltage-output nodes
BUS1A
$ = = = End of level 4: User-defined voltage output
$ = = = Level 5: End of data case ^

SS Input File
C^CASE23.INP
C
C^Phase A

126
^
^

C
C^s-block
^
1ITACSA + INT_A 1.D0
11468.D-1^1.D0
1.D0
C
C^k-block
^
0 AUX2A +VEMTPA 1.D0
C
C^k-block
^
O AUX3A +ITACSA 1.D0
C
C^Phase B
C
C^s-block
^
1ITACSB + INT_B 1.D0
11468.D-1^1.D0
1.D0
C
C^k-block
^
O AUX2B +VEMTPB 1.D0
C
C^k-block
^
O AUX3B +ITACSB 1.D0
C
C^Phase C
C
C^s-block
^
1ITACSC + INT_C 1 .DO
11468.D-1^1.D0
1.D0
C
C^k-block
^
O AUX2C +VEMTPC 1.D0
C
C^Auxiliary blocks
C
C^k-block
^
O AUX3C +ITACSC 1.D0
C
C^k-block
^
O CONS1 + SRC21 1.D0
C
C^k-block

127
^

0 CONS2 + SRC23^ 1.D0


C
C^k-block
^
0 AUX2 + CONS1 + CONS2 1.D0
C

C^source block
21 SRC21^1795.D-4
^ ^
23 SRC23^524.D-2 1.D-1 5.D-2^ 5.D-2
C

C^fortran expression block


99 INT_A =AUX2A*AUX2
99 INT_B =AUX2B*AUX2
99 INT_C =AUX2C*AUX2
C

C^output variables
33 AUX2B
C

C^connection variables
44ITACSAVEMTPA^0.D0
44ITACSBVEMTPB^0.D0
44ITACSCVEMTPC^0.D0
C

C^initial conditions
^
77 INT_A 0.D0
^
77 INT_B O.DO
^
77 INT_C O.DO
C

C^end of file

B.2.5 Load Variation with Thyristor Controlled Reactor


(Section 5.3.3)

Without TCR
EMTP Input File
&CASE24.INP
C

128
C^.^ .^. Case identification card
THREE-PHASE VARIABLE LOAD WITHOUT TCR
C LOAD REPRESENTED INSIDE Ss (NODE BUS13A)
C
C^.^ . Time card
^
50.E-6^.2^1 1
C
C^.^ . Symmetric pi circuit
1 THEVA BUS7A^0.083334.563
2 THEVB BUS7B^0.0233-5.427^0.083334.563
3 THEVC BUS7C^0.0233-5.427^0.0233-6.427^0.083334.563
C
C^.^ . Lumped RLC branch
BUS1A^ 7.
BUS1B^ 7.
BUS1C^ 7.
BUS12ABUS13A^ 70.16
BUS12BBUS13B^ 70.16
BUS12CBUS13C^ 70.16
92 IL13A^ 11
2.^0.
9999999.
92 IL13B^IL13A^ 2
92 IL13C^IL13A^ 3
C
C^.^ .^. Constant-parameters line
-1 BUS7A BUS1A^.03167 3.222.00787 144.4
-2 BUS7B BUS1B^.0243 .9238 .0126 144.4
-3 BUS7C BUS1C
-1 BUS1ABUS12A^.03167 3.222.00787 24.14
-2 BUS1BBUS12B^.0243 .9238 .0126 24.14
-3 BUS1CBUS12C
$ = = End of level 1: Linear and nonlinear elements ^
BUS13A IL13A^O.^99999.
BUS13B IL13B^O.^99999.
BUS13C IL13C^O.^99999.
$ = = = End of level 2: Switches and piecewise linear elements
C
C^.^ . Voltage or current sources
14 THEVA 1^187.79^60.^ -1.
14 THEVB 1^187.79^60.^-120.^ -1.
14 THEVC 1^187.79^60.^120.^ -1.
$ = = = End of level 3: Sources ^
C

129
C^.^ . Voltage-output nodes
BUS1A
$ = = = End of level 4: User-defined voltage output
$ = = = Level 5: End of data case ^

SS Input File
C^CASE24.INP
C
&CASE24.0UT
&CASE24.AUX
&YN
C
C
C^Phase A
C
C^s-block
1ITACSA + INT_A 1.D0
11468.D-1^1.D0
1.D0
C
C^k-block
O CONS1 +SRC211 1.D0
C
C^k-block
O CONS2 +SRC212 1.D0
C
C^k-block
0 CONS3 +SRC213 1.D0
C
C^k-block
0 CONS4 +SRC214 1.D0
C
C^k-block
O AUX2A +VEMTPA 1.D0
C
C^k-block
O AUX2 + CONS1 + CONS2 + CONS3 + CONS4 1.D0
C
C^Phase B
C
C^s-block
1ITACSB + INT_B 1.D0
11468.D-1^1.D0
1.D0

130
C
C^k-block
^
0 AUX2B +VEMTPB 1.D0
C
C^Phase C
C
C^s-block
^
1ITACSC + INT_C 1.D0
11468.D-1^1.D0
1.D0
C
C^k-block
^
0 AUX2C +VEMTPC 1.D0
C

C^source block
21SRC211^1795.D-4
21SRC212^O.DO^ 5.D-2
21SRC213^64658.D-4^ 1.D-1
21SRC214^O.DO^ 15.D-2
C

C^fortran expression block


99 INT_A =AUX2A*AUX2
99 INT_B =AUX2B*AUX2
99 INT_C =AUX2C*AUX2
C

C^RMS meter block


60 VRMS AUX2A^60.DO
C

C^output variables
33 VRMS
C

C^connection variables
44ITACSAVEMTPA^0.D0
44ITACSBVEMTPB^O.DO
44ITACSCVEMTPC^0.D0
C

C^initial conditions
77 INT_A^ O.DO

131
^
77 INT_B 0.D0
^
77 INT_C 0.DO
C

C^end of file

With TCR
EMTP Input File
&CASE25.INP
C
C^.^ .^. Case identification card
THREE-PHASE VARIABLE LOAD WITH TCR AT BUS 1
C LOAD REPRESENTED INSIDE SS (NODE BUS13A)
C
C^. . Time card
50.E-6 .2 1 1
C
C^.^.^. . Symmetric pi circuit
1 THEVA BUS7A 0.083334.663
2 THEVB BUS7B 0.0233-5.427^0.083334.563
3 THEVC BUS7C 0.0233-5.427^0.0233-5.427 0.083334.563
C
C^. . Lumped RLC branch
BUS1A 7.
BUS1B 7.
BUS1C 7.
BUS12ABUS13A 70.16
BUS12BBUS13B 70.16
BUS12CBUS13C 70.16
IL13A 6389.^5571.
IL13B 6389.^5571.
IL13C 6389.^5571.
IX13A 177.36154.65
IX13B 177.36154.65
IX13C 177.36154.65
92^TCRA 1
2.^O.
9999999.
92^TCRB TCRA 2
92^TCRC TCRA 3
C
C^. .^. Constant-parameters line
-1 BUS7A BUS1A^.03167 3.222.00787 144.4

132
-2 BUS7B BUS1B .0243 .9238^.0126 144.4
-3 BUS7C BUS1C
-1 BUS1ABUS12A .03167 3.222.00787 24.14
-2 BUS1BBUS12B .0243 .9238^.0126 24.14
-3 BUS1CBUS12C
$ = = End of level 1: Linear and nonlinear elements
BUS13A IL13A 0. .1 .0001
BUS13B IL13B 0. .1 .0001
BUS13C IL13C 0. .1 .0001
BUS13A IX13A .1 999999. .0001
BUS13B IX13B .1 999999. .0001
BUS13C IX13C .1 999999. .0001
BUS1A^TCRA 0. 99999.
BUS1B^TCRB 0. 99999.
BUS1C^TCRC 0. 99999.
$ = = =^End of level 2: Switches and piecewise linear elements ^
C
C^. . Voltage or current sources
14 THEVA 1^187.79 60. -1.
14 THEVB 1^187.79 60. -120. -1.
14 THEVC 1^187.79 60. 120. -1.
$ = = = End of level 3: Sources
C
C . Voltage-output nodes
BUS1A
$ = = = End of level 4: User-defined voltage output
$ = = = Level 5: End of data case ^

SS Input File
C^CASE25.INP
C
&CASE25.0UT
&CASE25.AUX
&YN
C
C
C^s-block 300/s
1 EPU +VRMSPU - UNITY 300.D0
1.D0
1.D0
C
C
C^k-block
^
0 BLGAM + EPU 125.D-2 0.D0125D-2

133
C
C
OVRMSPU + VRMS 7630823661.D-12
C
C^k-block
O UNITY + SRC21 1.D0
C
C^k-block
O EMTP1 +VEMTP1 1.D0
C
C^k-block
O EMTP2 +VEMTP2 1.D0
C
C^k-block
0 EMTP3 +VEMTP3 1.D0
C
C^Phase A - Busi
C^s-block 1/s
1ITACS1 + BGAMA 1.D0
1.D0
1.D0
C
C^Phase B - Busi
C^s-block^1/s
1ITACS2 + BGAMB 1.D0
1.D0
1.D0
C
C^Phase C - Bus1
C^s-block 1/s
1ITACS3 + BGAMC 1.D0
1.D0
1.D0
C

C^source block
21 SRC21^1.D0
C

C^fortran expression block


99 BGAMA =EMTP1*BLGAM
99 BGAMB =EMTP2*BLGAM
99 BGAMC =EMTP3*BLGAM
C

134
^

C^RMS meter block


60 VRMS EMTP1^60.DO
C

C^output variables
33VRMSPU
C

C^connection variables
44ITACS1VEMTP1^0.D0
44ITACS2VEMTP2^0.D0
44ITACS3VEMTP3^0.D0
C

C^initial conditions
77 BGAMA^ 0.D0
77 BGAMB^ 0.D0
77 BGAMC^ 0.D0
77 EPU^ 0.D0
77ITACS1^ 0.D0
77ITACS2^ 0.D0
77ITACS3^ 0.D0
C

C^end of file

B.2.6 HVDC System Simple Model (Section 5.3.4)


EMTP Input File
&CASE40.INP

^ Case identification card


CSTP alone - Time delay block - 2nd case
*
^ Time card
5.D-5^.2^2^1^ 1
*
^ Lumped RLC branch
^
SCR BUS1 1.1572 44.58
^
BUS1 9.66
92 BUS1
2.^0.

135
9999999.
$>>>>>>>End of level 1: Linear and nonlinear elements<<<<<<<<<
$>>>>>>>End of level 2: Switches and piecewise linear elements

^ Voltage or current sources


14^SCR 1^187.794^60.^67.43^ -1.0
$>>>>>>>End of level 3: Sources«<<<<<<<<<<<<<<<<<<<<<<<<<<<<<
BUS1
$>>>>>>>Level 5: End of data case<<<<<<<««<<<<«««<<

SS Input File
C CASE40.INP
C BASIC HVDC MODELS - FIG. 7-10 - WORKBOOK IV - CHAP 7 - PAGE 7-12
C
&CASE40_1.0UT^ Input file name
&CASE40_1.AUX^ Auxiliar file name
&YN^(Apply fast Newton Method?),(Save number of iterations?)
C
C
C^k-block
O IDC +SCR211 + AUX3 + DCF^ 1.D0
C
C^k-block
O X + AUX2 +SCR212^ 1.D0
C
C^k-block
O ALPHA + CONT +SCR215^ 1.D0
C
C^k-block
^
0 AUX3 + SCR24 1.D0
C
C^k-block
^
O AUX4 +SCR216 1.D0
C
C^k-block
^
O BUS1 + VEMTP 1.D0
C
C^k-block
^
O AUX1 +^PI 1.D0
C
C^k-block
^
O XC +SCR213 1.D0
C
C^k-block

136
^

O A +SCR214^ 1.D0
C
C^s-block^120/s
1^C1P + PRODC^ 120.D0
1.D0
1.D0
C
C^s-block^120/s
1 S1P + PRODS 120.D0
1.D0
1.D0
C
C^k-block
O C1 +^C1P -^C1D^ 1.D0
C
C^k-block
O S1 +^S1P -^S1D^ 1.D0
C
C^k-block
O AUX2 + TIMEX^ 1.D0
C

C^Time delay block


66^C1D^ClP^1667.D-5
66^S1D S1P^1667.D-5
C

C^source block
21SCR211^1.6 50.D-3^150.D-3
21SCR212^-0.1
21SCR213^9.08
21SCR214^0.8933
21SCR215^0.31416
21SCR216^107.79
24 SCR24^1.6 50.D-3^ 50.D-3
25 TIMEX
25^PI
C

C^Fortran expression blocks


99 DCF^=1.D6*AUX4*(ABS(XP)**3.15)*EXP((0.0-286.)*XP)
99 CONT =3.6*EXP((0.0-1.0)*135.*XP)-4.822*EXP((0.0-217.)*XP)+1.222
99^XP =(ABS(X))*(X.GE.0)
99^at =120*AUX1*AUX2

137
99 PRODC =BUS1*COS(wt)
99 PRODS =BUS1*SIN(wt)
99^VM =SQRT(C1*C1+S1*S1)
99^CV =(C1*COS(wt)+S1*SIN(wt))/VM
99^SV =(C1*SIN(wt)-S1*COS(wt))/VM
C
C^DC system equation
C
99 PHI^=ACOS(COS(ALPHA)-(XC*IDC)/(A*SQRT(3)*VM))
C
C^AC current injection
C
99 IACF =(CV*COS(PHI)+SV*SIN(PHI))*A*2.0*SQRT(3)*IDC/AUX1
C

C^output variables
33^C1^CV IDC ALPHA
C

C^connection variable
44 IACF VEMTP^77.614
C

C^initial conditions
77^C1P^ 1.D0
77^S1P^ O.DO
77 DCF^ 0.D0
77 CONT^ O.DO
77 PRODC^77.614
77 PRODS^ O.DO
77^VM^ 3.6
77^CV^ 1.D0
77^SV^ 0.D0
77 PHI^.31434D0
77 IACF^ 0.D0
77^XP^ 0.D0
77^wt^ O.DO
C

C^end of file

B.2.7 Single-Phase Thyristor Rectifier Bridge (Section 5.4)


EMTP Input File

138
^

&MOHAN5.INP
C^.^ .^. Case identification card
1-PHASE THYRISTOR RECTIFIER
C
C^.^ . Time card
50.0E-6^50.0E-3 ^ .5E-3
C
C^.^ . Lumped RLC branch
VSA VMA^ 0.2
VMA^VA^ 1.0
POSP^POS^ 16.0
POS NEG^2.0
POSP NEG^1.0E9
POSP^VA^200.0^1.0
POSP^POSP^VA
VA NEG POSP^VA
NEG POSP^VA
POSA POSP^0.01
POSG POSP^0.01
^
92 VSA 1
4.
0.
9999999.
92 POS VSA 2
$ = = End of level 1: Linear and nonlinear elements
C
C^.^ . Time-controlled switch
-1^VA POSA^ 0.002^60. 1
-1^NEG^ 0.002^60. 2
-1^POSG^ 0.002^60. 3
-1^NEG^VA^ 0.002^60. 4
$ = = = End of level 2: Switches and piecewise linear elements
C
C^.^ .^. Voltage or current sources
14^VSA^169.7^60.0^-90.0
$ = = = End of level 3: Sources
C^.^.^.^.^.^.^. Voltage-output nodes
VSA POSP
$ = = = End of level 4: User-defined voltage output
$ = = = Level 5: End of data case

SS Input File
C^MOHAN5.INP
C

139
&MOHAN5.0UT^ Input file name
&MOHANS.AUX^ Auxiliar file name
&YY^(Apply fast Newton Method?),(Save number of iterations?)
C
C^k-block
0 VSA + VEMTP^ 1.D0
OVCONTL +SRC211^ 1.D0
CO AUX1 + AUX^ 1.D0
OPLS1-2 + AUX^ 1.D0
C

C^Time delay blocks


66PLS3-4PLS1-2 0.00833333
C66 AUX2 AUX1^50.D-6
C

C^controlled integrator block


^ ^
58 RAMP+SRC212 VSA 120.^1.
C

C^source blocks
21SRC211^0.25
21SRC212^1.
C

C^fortran expression
99 AUX = RAMP .GE. VCONTL
C

C^output variables
33 RAMPPLS1-2PLS3-4
C

C^connection variables
44 ICSTP VEMTP^0.D0
55PLS1-2
55PLS1-2
55PLS3-4
S5PLS3-4
C

C^end of file

140
^

B.2.8 Three-Phase Thyristor Inverter (Section 5.4)


EMTP Input File
&MOHAN8.INP
C^.^ . Case identification card
3-PHASE THYRISTOR INVERTER
C
C^ . Time card
50.0E-6 100.0E-3^ .5E-3
C
C^.^ . Lumped RLC branch
VSA VMA^ 0.2
VSB VMB VSA VMA
VSC VMC VSA VMA
VMA^VA^ 1.0
VMB^VB VMA^VA
VMC^VC VMA^VA
POSP^POS^ 16.0^ 1
POS^NEG^1.0E-6
NEG^VA^1.0E5
NEG^VB^1.0E5
NEG^VC^1.0E5
POSP NEG^1.0E9^ 2
VSA VSC^1.0E9^ 2
92 VSA^ 1
4.
4.
9999999.
92 VSC VSA 2
$ = = End of level 1: Linear and nonlinear elements
C
C^.^ . Time-controlled switch
-1^VA POSP^ 2.E-3^60. 1
-1^NEG^VC^ 2.E-3^60. 2
-1^VB POSP^ 2.E-3^60. 3
-1^NEG^VA^ 2.E-3^60. 4
-1^VC POSP^ 2.E-3^60. 5
-1^NEG^VB^ 2.E-3^60. 6
$ = = = End of level 2: Switches and piecewise linear elements
C
C^ .^. Voltage or current sources
14^VSA^391.9^60.0^-60.0
14^VSB^391.9^60.0^-180.0
14^VSC^391.9^60.0^-300.0

141
^

11^POS-1 -600.0E6
11^NEG-1^600.0E6
$ = = = End of level 3: Sources ^
C^ .^. Voltage-output nodes
VSA
$ = = = End of level 4: User-defined voltage output
$ = = = Level 5: End of data case ^

SS Input File
C^MOHAN8.INP
C
C MOHAN8_1.PLO - Simultaneous solution
C MOHAN8_2.PLO - One time-step delay
C MOHAN8_3.PLO - Two time-step delay
C
&MOHAN8.0UT^ Input file name
&MOHAN8.AUX^ Auxiliar file name
&YN^(Apply fast Newton Method?),(Save number of iterations?)
C
C^k-block
0^VSA +VEMTPA 1.D0
0^VSC +VEMTPC 1.D0
0^VSAC +^VSA - VSC 1.D0
OVCONTL +SRC211 1.D0
0^AUX1 +^AUX 1.D0
0^AUX3 +^AUX2 1.D0
0 PULS1 +^AUX4 1.D0
C

C^Time delay blocks


66 PULS2 PULS1 0.00277778
66 PULS3 PULS2 0.00277778
66 PULS4 PULS3 0.00277778
66 PULS5 PULS4 0.00277778
66 PULSE PULS5 0.00277778
66^DCMP^AUX1 250.D-6
66^AUX4^AUX3 100.D-6
C

C^controlled integrator block


^ ^
58 RAMP+SRC212 VSAC 120.^1.
C

C^source blocks

142
21SRC211 .833333333
21SRC212^1.
C

C^fortran expression
99 AUX = RAMP .GE. VCONTL
99 AUX2 = (.NOT. DCMP) .AND. AUX1
C99 GATE1 = PULS1 .OR. PULS2
C99 GATE2 = PULS2 .OR. PULS3
C99 GATE3 = PULS3 .OR. PULS4
C99 GATE4 = PULS4 .OR. PULS5
C99 GATES = PULS5 .OR. PULS6
C99 GATE6 = PULS6 .0R. PULS1
C

C^output variables