Sie sind auf Seite 1von 6

Simultaneous Fault Analysis

Anubha Gupta Sunil V Chandran S S Bhat


M. Tech student M. Tech Student Associate Professor
Dept of Electrical Engg Dept of Electrical Engg Dept of Electrical Engg
VNIT VNIT VNIT
Nagpur, India Nagpur, India Nagpur, India
anubha.gupta24@gmail.com sunilvarickayil@gmail.com ssbhat@gmail.com

Abstract- Power system designing and protection symmetrical components which is referred in this
Is one of the challenging issues since very old paper. Various constraints between the symmetrical
times. Faults are the major hurdles in that. component currents and voltages have been shown
Hence it is always better to take precautions which in table I [7].
involve study of system under various fault
conditions. This paper describes the generalized Under the normal fault analysis condition
method for solving any combination of analyzing occurrence of fault on any phase is not a
simultaneousbalanced and lanced faults and difficult problem but in case of simultaneous faults
calculating symmetrical fault port currents. This
occurrence of faults on different phases has to be
method can be applicable irrespective of any
combination of faults, any number of faults and their
considered. Usually, mutual coupling is present
location. between the lines but that is not considered in this
paper.
Keywords—Simultaneous faults, fault port voltage,
fault port current For doing fault analysis the major issue is to
I. INTRODUCTION modify the impedance matrix according to the
By simultaneous faults it is understood that one changes occurring in the system due to the fault.
or more faults occurring simultaneously and it is This modification can be addition or deletion of a
quite difficult to analyse more than one fault bus as given in [8]. The connection of the sequence
occurring at the same time. The reason for the network is also one of the important points to be
occurrence of such faults may be due to lightening considered [7].
stroke, human made accidents etc. For power
system designing and protection it is inevitable to
calculate all bus voltages and currents under all II. SEQUENCE NETWORK INTERCONNECTION
possible circumstances. In general faults mainly
The interconnection between the sequence
occur sequentially rather than simultaneously.
networks must be such that that all the limitations
Keeping the aspect of protection in mind it is
and the boundary conditions for that particular fault
desirable to compute the voltage and current during
must be fulfilled. From table II it can be seen that
and after the occurrence of first and second fault.
for some faults the currents of all sequence
For accomplishing this, system has to be monitored
networks at the fault point are equal and the sum of
under all kinds of faulted situations. There are
the voltages of all sequence network is zero from
different types of faults which may be categorized
which we can conclude that the sequence networks
as balanced and unbalanced faults. These
are connected in series with each other. Similarly,
simultaneous faults may be any combination of
for other types of faults voltages of all sequence
these balanced and unbalanced faults. Balanced
networks are equal and the sum of all the sequence
faults are symmetrical faults for example three
currents is equal to zero from which we can
phase short circuit fault, three phase open circuit
conclude that the sequence networks are connected
fault and unbalanced faults are for example short
in parallel.
circuit faults – single line to ground fault, double
line to ground fault [1]. In case of simultaneous faults it is not as simple
A number of methods have been formulated in as in case of single fault analysis. In very few
last few decades for calculating simultaneous faults combinations of faults these networks fulfill the
such as two-step compensation method by G. Gross connection constraints. This difficulty mainly arises
and H.W. Hong in 1982[2], [3]. In [4], [5] and [6] due to the occurrence of faults on different phases.
different generalized approach has been given for To overcome this problem Z. X. Han has
simultaneous fault analysis. The method given in recommended using phase shifting transformers to
[4] is based on multiple port theory and theory of shift the voltages and currents accordingly in order

978-1-4799-7169-5/14/$31.00 ©2014 IEEE


33
to meet the boundary conditions [4]. Ideal turns C Ic = 0
ration is given as: Va+IaZ = 0
Z
Vb+IbZ = 0

(1) Double Phase open A Ib = Ic = 0


Z Va + IaZ = 0
where I and V are the primary current and B Ic = Ia = 0
Vb + IbZ = 0
voltage respectively of ideal phase shifting
transformer and I’ and V’ are secondary current
and voltage of ideal phase shifting transformer.

TABLE I. CONSTRINTS BETWEEN SYMMETRICAL C Ia = Ib = 0


CURRENTS AND VOLTAGES FOR DIFFERENT FAULTS Vc + IcZ = 0

S.No Fault Current Voltage Constraints


Constraints III. BASIC NETWORK EQUATION
1 Single I1=I2=I0 V1+V2+V0=0
Line to I1=a2 I2=aI0 V1+a2 V2+aV0=0 Basic equations for any n bus system may be
Ground I1=aI2=a2 I0 V1+aV2+a2 V0=0 given as [9]:
Fault
2 Line to I1= -I2, I0 = 0 V1 = V2
Line Fault I1= - a2 I2, I0 = V1 = a2 V2 (2)
0 V1 = aV2 where Ybus is n×n admittance matrix and Vbus and
I1= - aI2, I0 = Ibus are n×1 voltage and current vector respectively.
0
3 Double I1+I2+I0=0 V1=V2=V0
Vbus can be obtained by using equation (2)
Line to I1+a2 I2+aI0=0 V1=a2 V2=aV0
Ground I1+aI2+a2 I0=0 V1=aV2=a2 V0 Vbus = [Zbus] Ibus (3)
Fault
4 One I1+I2+I0=0 V s1=V s2=V s0 where [Zbus] = [Ybus]-1 i.e. impedance matrix of size
Phase I1+a2 I2+aI0=0 Vs1=a2Vs2=aVs0
Open I1+aI2+a2 I0=0 Vs1=aVs2=a2 Vs0 n×n.
Fault
5 Two I1=I2=I0 Vs1+V s2+V s0=0 In matrix form we can write the above equation as
Phase I1=a2 I2=aI0 Vs1+a2Vs2+aVs0=0 follows:
Open I1=aI2=a2 I0 Vs1+aVs2+a2Vs0=0
Fault

(4)
TABLE II. BOUNDARY CONDITIONS FOR DIFFERENT
TYPES OF FAULTS where ZI I and ZII II are known as driving point
impedance and ZI II and ZII I are known as transfer
Type of fault Specific Boundary condition impedance [4].
phase
Single line to ground fault A Ib = Ic = 0
Va+IaZd=0 Hence, when fault occurs anywhere on the
B Ic = Ia = 0 system impedance matrix changes accordingly.
Vb+IbZd=0 Here in this paper in case of simultaneous faults we
C Ia = Ib = 0
Zd Vc+IcZd=0
are going to calculate fault port matrix as given in
[4]. According to the multiple port theory each
Double line to ground fault A Vb+Ib Z=Vc+Ic Z = - fault point is considered as a port. In a port the
(Ib+Ic)Zd current coming out of one terminal should be equal
Ia = 0 to the current entering another terminal [1].
B Vc+Ic Z=Va+Ia Z = -
Z Z
(Ic+Ia)Zd
Ib = 0 IV. FAULT PORT MATRIX
Zd
C Va+Ia Z=Vb+Ib Z = -
(Ia+Ib)Zd
In [2] although the short circuit fault was
Ic = 0 occurring but during simulating it the impedance
matrix i.e. Zbus was used unchanged. But usually
Single phase open A Ia = 0 we cannot consider it like that as the fault may
Vb+IbZ = 0
Vc+IcZ = 0 occur at any point on the network. Always
B Ib = 0 considering a fault point as an addition of bus may
Vc+IcZ = 0 make the calculations difficult. Hence Z. X. Han
Va+IaZ = 0 has devised the method of fault port matrix which
is easy to understand and lesser the computation
time as well.

34
A. Fault port matrix elements
Taking case of a general short circuit fault at any
point k on any line as shown in fig. 2 and assuming
the injected current to be Ik and voltage at that point
be Vk the equations may be:
– (5) Fig. 3. Short circuit fault and open circuit fault occurring
– 1 (6) simultaneously
– (7)
where r is the distance between point i and k. Further these equations are manipulated using
the method given in [9]. Considering the line i-j is
switched open and two sample buses s and t have
been inserted in the circuit. Method used in [9]
demonstrates the modification of Zbus by addition
and deletion of the bus. So here opening of line s-t
will act as opening of the branch.

Transfer impedance between the fault point k


and any bus m after opening of the branch is given
as:
Fig. 1. Short Circuit fault at point k 1 (13)
driving point impedance is given as:
In the formation of fault port matrix it is
assumed that the unity current is injected at any bus 1 (14)
m and the voltage at port k is equal to the transfer impedance between fault point k and
impedance between m and k. Therefore, terminal t is given as:

1 (8) 1 1 (15)
where Zmk is the transfer impedance. where the terms Cm, Ci, Ck and P can be described
as:
For finding the driving point impedance the , x=m,k,i (16)
equation is:
(17)
1 2 2 2 1
1 (9) To understand these equations in a better way one
may refer to reference [9].
If two short circuit faults are occurring B. Methods
simultaneously on the same line as shown in fig 3
The method given in this paper is the review of
then the transfer impedance can be given as:
the method given by Z. X. Han in [4]. Considering
N number of faults occurring out of which M are
1 1 1
series faults and N-M are the parallel faults.
1 1 (10)
The equation for these faults may be given as
follows [4]:

(18)
Fig. 2. Two short circuit faults occurring simultaneously at k
and k’
where VS(i), IS(i) and VS(0) are voltage, current and
open circuit voltage of series type fault having size
If a short circuit fault and an open circuit fault M×1.
occur simultaneously on the same line as shown in VP(i), IP(i) and VP(0) are voltage, current and open
fig 4 then the driving impedance will be given as circuit voltage of parallel type fault having size (N-
follows: M)×1.
ZSS(i), ZSP(i), ZPS(i) and ZPP(i) are the impedance
1 (11) matrices of sizes M×M, M×(N-M), (N-M)×M and
transfer impedance for the same will be given as: (N-M)×(N-M) respectively and i = 0,1,2
representing zero, positive and negative sequence
1 (12) network respectively.
35
,
Performing partial inversion on equation (18) we 0
(22)
obtain the following equations: 0

,
Substituting equation (22) in equation (19) series
(19) fault port voltages and parallel fault port currents
can be calculated.
where ASS(i) = ZSS(i) – ZSP(i)ZPP(i)ZPS(i) This method has been computationally
-1 implemented and the results are shown in this paper
ASP(i) = ZSP(i) – ZPP(i) using the algorithm.
APS(i) = ZPP(i)-1 – ZPS(i) V. FLOWCHART[4]

APP(i) = ZPP(i)-1 Below given is an algorithm implementing the


above given method. First and foremost load flow
VS(0,0) = VS(0) – ZSP(1)ZPP(1)-1VP(0) is to be done to get the reference values to see the
changes occurred after faults. Also, the open circuit
IP(0) = - ZPP(1)-1VP(0) voltage mentioned in equation (18) will be equal to
the voltages obtained from the load flow. Hence, it
is one of the major parts of the flowchart.
Since here simultaneous faults are considered
therefore phase shifting transformers might be
needed. Using equation (19) The admittance matrices formed here are sparse
in nature. The computation time is saved using
admittance matrix in load flow analysis. Then these
matrices are transformed into impedance matrices
for further calculation. Fault port matrix is formed
0 0 based on the method given above. Bus voltages and
0 0 currents of the buses affected by occurrence of the
, fault are calculated.
(20)

where NS(i) and NP(i) are turn ratio matrices of the


ideal phase shifting transformer having sizes M×1
and (N-M)×1 respectively.

According to the boundary conditions given in


table 2 for series and parallel faults equation (20)
can be further simplified as:

,
0
(21)
0
where

, ,

, ,

, ,

, ,

Solving equation (21) series fault port currents


and parallel fault port voltages can be calculated as
given below:
36
Start

Enter the data required for


load flow analysis

Perform the base case load


flow
Fig. 5. Circuit Diagram

Fig. 5 shown above represents a four bus system


Form Y bus matrices for all whose line data and bus data are given below in
three sequence networks table III and table IV.

TABLE III. LINE DATA


Input types of faults from to
bus bus R X Y/2 R0 Xo
1 2 0.0101 0.05 0.05 0.003 0.013
Form fault port matrices for all
1 3 0.0074 0.037 0.04 0.002 0.009
sequence network and open
circuit voltage for positive 2 4 0.0074 0.037 0.04 0.002 0.009
sequence network is calculated 3 4 0.0127 0.064 0.06 0.003 0.016

TABLE IV. BUS DATA

Solve for the boundary currents


and voltages Bus Pg Qg Pload Qload V(p.u) Angle type
1 0 0 50 30.99 1 0 1
2 0 0 170 105.4 1 0 2

Calculate bus voltages and 3 0 0 200 123.9 1 0 2


currents on the selective basis 4 318 0 80 49.58 1.02 0 3

For single line to ground fault occurring on bus 2


and 4 simultaneously as shown in fig. 6 fault port
currents are given in table V:
Next yes
fault
analysis?

no

Start

Fig. 4. Flowchart

VI. RESULT
Data for a four bus system was taken from [10]
and the above method was implemented on that
system. Giving different kinds of faults as input Fig. 6. Single line to ground fault on bus 2 and 4
results are given below. simultaneously

37
MELCON-96,8th Mediterranean Electrotechnical
Table V. THREE COMPONENTS OF FAULT CURRENTS Conference, pp 721-725, 1996
[7] J. R. Mortlock,“The Evaluation of Simultaneous Faults
Bus Positive Negative Zero on Three Phase Systems”, Journal of Institution of
No. Sequence Sequence Sequence Electrical Engineers-Part II : Power Engineering,, vol.
2 1.1672 1.1672 0.32661 94, pp. 166-190, 1947
4 1.1212 1.1212 0.2324 [8] T. E. DyLiacco and K. A. Ramarap, "Short-circuit
calculation for Multiline Switching and End Fault",
IEEE Transaction on Power Apparatus and systems,vol.
Fault port currents for a single line to ground PAS-89, No.6, pp.1226-1237, 1970.
fault on bus 2 and open circuit fault on bus 4 is [9] M.Etezadi-Amoli, “Simultaneous Fault Analysis Using
shown in fig. 7: The Generalised Method of Fault Analysis”,
Proceedings of the Twenty-First Annual Norht
American Power Symposium, pp 188-191, 1989
[10] John J. Grainger and William D. Stevenson, Jr, Power
System Analysis,McGraw-Hill Publication, Inc.

Fig. 7. Single line to ground fault on bus 2 and open circuit fault
on bus 4

The fault port currents for the above mentioned


condition is given in table VI.

TABLE VI. THREE COMPONENTS OF FAULT CURRENTS

Bus Positive Negative Zero


No. Sequence Sequence Sequence
2 0.064093 0.064093 0.064247
4 0.031969 0.031969 0.031969

VII. CONCLUSION
The generalized method for doing simultaneous
fault analysis have been discussed and results of
calculated fault port current and voltages have been
shown.

REFERENCES
[1] P. M. Anderson, Analysis of Faulted Power Systems,
The Iowa State University Press, 1973.
[2] G.GROSS, H.W.HONG, “A two-step compensation
method for solving short circuit problems”, IEEE
Transaction on Power Apparatus and Systems,
vol.PAS-101, pp. 1322-1331, 1982.
[3] G.GROSS, H.W.HONG, “A two-step compensation
method for solving short circuit problems”, IEEE
Transaction on Power Apparatus and Systems,
vol.PAS-101, pp. 1322-1331, 1982.
[4] Z.X. Han, "Generalized Method of Analysis of
Simultaneous Faults in Electric Power System". IEEE
Transactions on Power Apparatus and System &, Vol
PAS-101, pp. 3933-3942, October 1982.
[5] V.BRANDWAJN, W.F.TINNEY, “Generalized method
of fault analysis”,
IEEE Transaction on Power Apparatus and Systems,
vol.PAS-104, pp. 1301-1306, 1985
[6] R.BUALOTI, P.Pugliese, F.Torelli, M.Trovato,”A
Generalised Method For Simultaneous Fault Analysis”,

38

Das könnte Ihnen auch gefallen