Project: ETAP Page: 1

Location: 12.6.0H Date: 10-01-2019


Contract: SN:

Engineer: Study Case: SC


Filename: PWI-10purwodadi Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

ANSI Standard
3-Phase, LG, LL, & LLG Fault Currents
30-Cycle Network

Swing V-Control Load Total

Number of Buses: 1 0 11 12

XFMR2 XFMR3 Reactor Line/Cable Impedance

Number of Branches: 1 0 0 10 0

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load

Number of Machines: 0 1 0 0 0

System Frequency: 60.00 Hz

Unit System: English


Project Filename: PWI-10purwodadi

Output Filename: C:\ETAP 1260\PWI-10purwodadi\SC1.SA2


Adjustments

Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C
Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV
Sub-sys %Mag. Ang.

Bus1 SWNG 150.000 150.000 1 100.00 0.00

Bus2 Load 20.000 20.000 1 100.00 -30.00

Bus3 Load 20.000 20.000 1 100.00 -30.00

Bus4 Load 20.000 20.000 1 100.00 -30.00

Bus5 Load 20.000 20.000 1 100.00 -30.00

Bus6 Load 20.000 20.000 1 100.00 -30.00

Bus7 Load 20.000 20.000 1 100.00 -30.00

Bus8 Load 20.000 20.000 1 100.00 -30.00

Bus9 Load 20.000 20.000 1 100.00 -30.00

Bus11 Load 20.000 20.000 1 100.00 -30.00

Bus12 Load 20.000 20.000 1 100.00 -30.00

Bus13 Load 20.000 20.000 1 100.00 -30.00

12 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP.
Line/Cable Input Data

Ohms or Siemens per 1000 ft per Conductor (Cable) or per Phase (Line)
Line/Cable Length

ID Library Size Adj. (ft)


% Tol. #/Phase T (°C) R1 X1 Y1 R0 X0

Cable1 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable2 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable3 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable4 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable5 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable6 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable7 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable9 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable10 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Cable11 20MALN3 240 10826.8 0.0 1 75 0.0136550 0.0385023

Line / Cable resistances are listed at the specified temperatures.


2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z

T1 3960.500 150.000 20.000 12.50 45.00 0 0 0

2-Winding Transformer Grounding Input Data

Grounding

Transformer Rating Conn. Primary Secondary


ID MVA Prim. kV Sec. kV Type Type kV Amp Ohm Type

T1
3960.500 150.000 20.000 D/Y Solid
Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X

T1 2W XFMR Bus1 Bus2


0.01 0.32

Cable1 Cable Bus2 Bus3


3.70 10.42

Cable2 Cable Bus5 Bus4


3.70 10.42

Cable3 Cable Bus6 Bus5


3.70 10.42

Cable4 Cable Bus7 Bus6


3.70 10.42

Cable5 Cable Bus8 Bus7


3.70 10.42

Cable6 Cable Bus9 Bus8


3.70 10.42

Cable7 Cable Bus3 Bus9


3.70 10.42

Cable9 Cable Bus4 Bus11


3.70 10.42

Cable10 Cable Bus11 Bus12


3.70 10.42

Cable11 Cable Bus12 Bus13


3.70 10.42
Power Grid Input Data

% Positive Seq. Impedance % Zero Seq. Impedance


Power Grid Connected Bus Rating 100 MVA Base Groundin 100 MVA Base
g
ID ID MVASC kV X/R R X Type X/R

sumber Bus1 4274.614 150.000 2.35 0.91610 2.15256 Wye - Solid

Total Power Grids (= 1 ) 4274.614 MVA


SHORT- CIRCUIT REPORT

Fault at bus: Bus13

Prefault voltage = 20.000 kV = 100.00 % of nominal bus kV ( 20.000 kV)


= 100.00 % of base kV ( 20.000 kV)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0

Bus13 Total 0.00 2.550 0.00 140.05 133.88

Bus12 Bus13 9.77 2.550 9.93 135.51 129.77

# Indicates fault current contribution is from three-winding transformers

* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Short-Circuit Summary Report

30 Cycle - 3-Phase, LG, LL, & LLG Fault Currents

Prefault Voltage = 100 % of the Bus Nominal Voltage

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault


ID kV Real Imag. Mag. Real Imag. Mag. Real Imag. Mag.

Bus13 20.00 0.853 -2.403 2.550 0.258 -1.098

All fault currents are symmetrical momentary (30 Cycle network) values in rms kA

* LLG fault current is the larger of the two faulted line currents
Short-Circuit Summary Report

Bus Positive Sequence Imp. (ohm) Negative Sequence Imp. (ohm) Zero Sequence Imp
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus13 20.000 1.51532 4.26728 4.52835 1.51532


019

Revision: Base
mal

Tie PD Total

0 0 11

Total

0 1
Y0

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665

0.0368910 0.1972665
Phase Shift

Type Angle

0 0 12.5000 Dyn 30.000

Secondary
kV Amp Ohm
nce, Pos. Seq., 100 MVAb
Z Y

0.32

11.06

11.06

11.06

11.06

11.06

11.06

11.06

11.06

11.06

11.06
ro Seq. Impedance
100 MVA Base
R0 X0

4.46 0.984258 4.38592


equence Impedances
om Bus"
MVA base
X0

133.88 1.128 1.128 3.79E+001 1.07E+002 9.99E+001 5.34E+002

129.77 1.128 1.128 3.79E+001 1.07E+002 9.99E+001 5.34E+002


*Line-to-Line-to-Ground
Real Imag. Mag.

1.128 2.081 0.739 2.208 2.009 1.093 2.287


Zero Sequence Imp. (ohm)

4.26728 4.52835 3.99438 21.37022 21.74032