Short-Circuit Analysis
ANSI Standard
3-Phase, LG, LL, & LLG Fault Currents
30-Cycle Network
Number of Buses: 1 0 11 12
Number of Branches: 1 0 0 10 0
Number of Machines: 0 1 0 0 0
Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
Transmission Line Resistance: Yes Individual
12 Buses Total
Ohms or Siemens per 1000 ft per Conductor (Cable) or per Phase (Line)
Line/Cable Length
Grounding
T1
3960.500 150.000 20.000 D/Y Solid
Branch Connections
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Short-Circuit Summary Report
All fault currents are symmetrical momentary (30 Cycle network) values in rms kA
* LLG fault current is the larger of the two faulted line currents
Short-Circuit Summary Report
Bus Positive Sequence Imp. (ohm) Negative Sequence Imp. (ohm) Zero Sequence Imp
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
Revision: Base
mal
Tie PD Total
0 0 11
Total
0 1
Y0
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
0.0368910 0.1972665
Phase Shift
Type Angle
Secondary
kV Amp Ohm
nce, Pos. Seq., 100 MVAb
Z Y
0.32
11.06
11.06
11.06
11.06
11.06
11.06
11.06
11.06
11.06
11.06
ro Seq. Impedance
100 MVA Base
R0 X0