Beruflich Dokumente
Kultur Dokumente
7 CEMAT
Content
Platform Architecture Guide 1
1 Preface 4
2 System Overview 5
3 System components 7
3.1 Typical Example Configuration with SIMATIC PCS 7-CEMAT 7
3.2 Central and distributed Process I/O Systems 8
3.2.1 SIMATIC ET 200S 8
3.2.2 SIMATIC ET 200iSP (For Use Directly in Ex Area to Zone 1) 9
3.3 Automation Systems (Controllers) 11
3.4 Bus Systems (Communication) 14
3.4.1 System Bus 14
3.4.2 Time synchronization 20
3.4.3 Field Bus 22
3.4.4 OpenPCS 7 for process data evaluation and management 24
3.4.5 Coupling to Third-Party Systems 25
3.5 Operator Station CEMAT Server 26
3.6 Operator Station CEMAT Client 27
3.6.1 Overview 27
3.7 CEMAT Operator Interface 28
3.7.1 Process pictures 28
3.7.2 General 28
3.7.3 Text and color layout 29
3.7.4 Block Icons and Bitmaps 29
3.7.5 Faceplates 35
3.7.6 Faceplates - secondary dialog 'Diagnosis' 38
3.7.7 Faceplates - secondary dialog 'Extended Diagn. with Interlock' 40
3.7.8 Faceplates Details APL- Interlock' 41
3.7.9 Faceplates - secondary dialog 'Alarm' 42
3.7.10 Faceplates - secondary dialog 'Statistic and Maintenance' 43
3.7.11 Faceplates - secondary dialog 'Info' 47
3.7.12 Faceplates - secondary dialog 'Parameter' 53
3.7.13 Faceplates - secondary dialog 'Status' 54
3.7.14 Faceplates - secondary dialog 'Object' 55
3.7.15 Faceplates - secondary dialog 'Group/Route Assignment' 57
3.7.16 Faceplates - secondary dialog 'Help' 57
3.7.17 CEMAT- Trend Groups 58
3.7.18 CEMAT Message Functionality 66
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 1
CEMAT Platform Architecture Guide
Appendix 114
A Appendix A 115
A.1 Module Description (Function Overview) 115
A.1.1 General module structure 115
A.1.2 C_DRV_1D Unidirectional Drive 119
A.1.3 C_DRV_2D Bi-directional drive 123
A.1.4 C_DAMPER Damper 127
A.1.5 C_VALVE Valve 132
A.1.6 Variable Speed Drive (VSD) 135
A.1.7 C_SIMOS Adapter for SIMOCODE 137
A.1.8 C_GROUP Group 139
A.1.9 C_ROUTE Route 144
A.1.10 C_SELECT Selection 148
A.1.11 C_ANNUNC Annunciation module 150
A.1.12 C_PROFB Process feedback block 153
A.1.13 C_MEASUR Measuring value block 156
A.1.14 C_PID PID controller 160
2 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 3
CEMAT Platform Architecture Guide
1 Preface
Purpose of this Documentation
This document should explain what a CEMAT-Holcim PCS standard system is.
It should briefly define how the Siemens solution fulfils the Holcim requirements.
This document can also help Siemens sales engineers in defining what system can be
provided to Holcim.
The documentation contains recommendations and information for planning and building
PCS7 CEMAT automation solutions with a content of
- Standard system architecture
- Brief description of the system components (building blocks)
- Design & Engineering considerations
- Project planning example (implementation reference)
- Training requirements
- Price reference/calculation
- System performance calculation
- Simulation and testing
Required Knowledge
This documentation is intended for persons involved in configuration, engineering and
servicing of automation systems. (Automation experts, PCS project managers and project
engineers.)
4 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
2 System Overview
Our solution for a process control system, as it is shown in the typical layout on top, is
SIMATIC PCS7 V8.0 with CEMAT V8.0.
SIMATIC PCS7 is the process control system in the Siemens automation concept "Totally
Integrated Automation". The process control system builds on standard SIMATIC S7
components. Software packages, as CEMAT, add typical control system functions to these
components to form the basis for the functional scope of SIMATIC PCS7.
The system is continuously being adapted to our customers’ requirements. To protect our
customers’ investments, compatibility with earlier versions is always a primary consideration
in this ongoing improvement, enabling you to build, operate and maintain a state-of-the art
control solution that will prove its benefits now and in the future.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 5
CEMAT Platform Architecture Guide
System Architecture
The client/server architecture of SIMATIC PCS7 supports up to 12 redundant servers as well
as up to 32 clients per server; at the same time. The quantity framework per server is being
raised to 8,500 process control objects.
This means the system can be scaled from the starter package with about 100 process
control objects stations to the full expansion up to about 60,000 process control objects.
A wide range of applications can therefore be equipped with a uniform system platform, from
pilot plants up to high-capacity and complex processes such as a full-scale cement plant with
more Lines.
Automation layer
For the actual automation system, we are proposing the use of AS 416-2 controllers with the
ET200S Remote I/Os.
The connection of the distributed I/O will be done by the central assembly with integrated
PROFIBUS-DP interfaces or with a discrete DP Interface module (CP 443-5).
Operating Stations
To meet the HMI requirements, we offer a client-server structure. The redundancy ensures
that the alarm and tag logging archives are synchronised in both systems when one of the
two servers is switched on again after a failure.
Bus systems
The connection between the control and monitoring layer and the process components is
done via a Resilient Fast Ethernet bus. As the transmission medium for the bus system, we
have selected twisted pair cables inside buildings and fibre-optic ring between buildings to
which the individual components are connected via SCALANCE network devices.
Engineering system
SIMATIC PCS 7 provides uniform engineering system based on the WINDOWS XP operating
system for configuring I&C installations, and supports the system-wide and plant-wide
processing of projects.
In every engineering phase of a plant, from initial configuring right through to operational
support, the same tools are used for all work on the project database. Thus the project data
are generated and updated using identical tools throughout the entire service life of the plant.
Open import and export functions allow the engineering system to be integrated into the
existing infrastructure of the overall plant configuration.
Remote diagnosis is possible by default using a modem and a remote computing software
package.
Simulation of the logic is possible with PLCsim Software or in combination with a controller.
The instrumentation layer can be easily configured and managed by means of PDM (Process
Device Manager), the SIMATIC Asset Management tool, providing full access to all Profibus
instrumentation
6 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
3 System components
• Engineering station
• Red. Server / client structure
If you need information about these features, please contact one of your regional SIEMENS
partners.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 7
CEMAT Platform Architecture Guide
Characteristics such as
modularity and consistency,
flexible adaptability to the plant structure,
minimum cabling and engineering requirements,
low commissioning, servicing and lifecycle costs and a
wide range of technical options
are the main reasons why distributed process peripherals are now predominant: ET 200S
remote I/Os in conjunction with classical field/process devices and HART field devices or
intelligent field/process devices directly on PROFIBUS.
Design
Main components of the ET 200S distributed I/O system:
Terminal modules enable the electrical and mechanical connection of the I/O modules
and carry the terminals for the process wiring:
- TM-P terminal modules for power modules
- TM-E terminal modules for electronics modules
- TM-DS/TM-RS terminal modules for motor starters and TMxB expansion modules
IM 151 interface module for connecting the PROFIBUS DP to the ET 200S station. The
terminal module is included in the scope of delivery.
Power modules for PM-E electronics modules and PM-D motor starters
- For individual grouping of load and sensor supply voltages and their monitoring, as
well as for the safe shutting down of digital output modules with PROFIsafe
- For supplying and monitoring the auxiliary voltages for motor starters, as well as for
the shutting down of a complete group of motor starters
8 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Features
Connection via PROFIBUS-DP (redundant starting in 05/2005)
Redundant pluggable power supply
Direct connection to intrinsically safe PROFIBUS DP via RS485iS coupler
Transmission rate up to 1.5 Mbits/s
Max. 32 modules per station
Possible connection of sensors/actuators in Ex area to zone 0
Module replacement during operation
Parameter assignment during operation
Addition of stations/modules during operation
Diagnostic alarm
Time stamping
P30 degree of protection
Temperature range –20°C to +60°C
For configuration please download the “ET200_Config_Tool” from the Support page.
Further I/O Modules from 3.party can be used with GSD Files.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 9
CEMAT Platform Architecture Guide
10 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The automation systems are supplied as preassembled, tested complete systems consisting
of:
Rack with 9 or 18 slots
Controllers 414, 416 and 417
24 VDC or 120/230 VAC power supply
Internal RAM of 1.4 to 20 Mbytes
Swappable memory card with 1 to 16 Mbytes of RAM
Preferred Hardware is :
6ES7416-3ES06-0AB0
SIMATIC S7-400, CPU 416-3 PN/DP CENTRAL
PROCESSING UNIT WITH: 16 MB WORKING MEMORY,
(8 MB KB CODE, 8 MB DATA), INTERFACES: 1. IF MPI/DP
12 MBIT/S (X1), 2. IF ETHERNET/PROFINET (X5), 3. IF
IF964-DP PLUGABLE (IF1)
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 11
CEMAT Platform Architecture Guide
http://www.automation.siemens.com/simatic/controller/index_76.htm
12 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Technical Data
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 13
CEMAT Platform Architecture Guide
Industrial Ethernet is used as the “Plant automation bus” as well as “Plant Control bus”
for multi-user systems with client/server architecture.
“Plant automation
bus”
14 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 15
CEMAT Platform Architecture Guide
SCALANCE X Overview
16 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 17
CEMAT Platform Architecture Guide
18 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 19
CEMAT Platform Architecture Guide
20 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The SICLOCK TC 400 central plant clock is used in a Windows domain for time synchronize
of the OS.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 21
CEMAT Platform Architecture Guide
PROFIBUS DP PROFIBUS PA
Data transmission RS485 RS485-IS Fiber optic MBP
9.6 kBit/s -1.5 9.6 kBit/s - 12
Transmission rate 9.6 kBit/s - 12 Mbit/s Mbit/s Mbit/s 31,25 kBit/s
Cable Shielded 2-wire Shielded 2-wire Plastic, glass Shielded 2-wire
EEx(ia/ib)
Type of protection EEx(ib)
Topology Line Line Ring, star Line, tree
Stations per segment 32 32 - 32
Stations per network 126 126 126 -
1.000m at 187.5 1.000m at 187.5 Plastic:; max. 80 m 1,900m: Standard
kbit/s 400m at 500 kbit/s 400m at 500 multimode fiber: 2-3 1,900m: Eex(ib)
kbit/s kbit/s km single mode
200m at 1.5 Mbit/s 200m at 1.5 Mbit/s fiber: >15km
Cable length per @ 12 Mbit/s 1,000m: Eex(ia)
segment 100m at 12 Mbit/s
Signal refresh
repeaters Max. 9 Max. 9 unlimited
22 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 23
CEMAT Platform Architecture Guide
The process data of SIMATIC PCS 7 V8.0 can be made available to a higher level system via
an OpenPCS 7 server for the purpose of production planning and process data evaluation
and management.( Expert Optimizer, TIS, Laboratory- and Shipping/Receiving- Automation)
(see also “Design Criteria for Process Control and Electrical Equipment” Chapter 5.8)
The OpenPCS 7 Interface is based on the OPC Version 2.0 specifications (Openness,
Productivity, Collaboration), which mainly use the DCOM technology (Distributed Component
Object Model) from Microsoft for the communication between applications.
The Open PCS 7 Station provides the following data:
Archive tags are read transparently across computer boundaries, i.e. a read job will
automatically be continued on the CAS once the archive limit on the OS server is reached.
The OpenPCS 7 Server collects data distributed over various SIMATIC PCS 7 industrial
workstations, e.g. OS servers or CAS, for the OPC clients:
OPC HDA clients, e.g. reporting tools, can specifically request historical data by specifying
the
start and end of a time interval.
OPC A&E clients at production and management level receive messages from the OPC A&E
server incl. all process auxiliary values, in line with their subscription.
Filter mechanisms limit data transmission to selected and changed data.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 24
Platform Architecture Guide CEMAT
Open PCS 7 Station, OS client and client applications (OPC or OLE/DB) on one common
PC.
This configuration is recommended for small-sized plants.
Generally, Open PCS 7 Station can perform data access to an OS server or CAS.
Configuration of multiple station system with client/server architecture for medium and
large sized plants.
The Open PCS 7 Station is equipped with two network cards. The OPC clients are
connected via network (office network).
As additional protection it is possible to install a firewall.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 25
CEMAT Platform Architecture Guide
In case of an system architecture with redundant OS servers, the OS clients are switched
over to the backup server in the event of a fault. Background processes permanently monitor
important server applications for faults which may then result in a redundant switchover.
Automatic synchronization of process data, message archives and user archive is carried out
when the partner server starts up again.
The communication network identified as Plant-Automation-Bus is implemented with standard
SIMATIC NET components such as switches( X408 ), network cards, communications
processors (CP), cables etc.
OS archiving
The operator system already includes a high-
performance archiving system based on Microsoft
SQL Server with cyclic archives for short-term
saving of process values and messages/ events
(alarms).
26 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 27
CEMAT Platform Architecture Guide
Working
area
Button area
3.7.2 General
All displays and graphics that show real time data are automatically updated when the display
or graphic is on a screen. Updates do not require operator initiation.
The system provides an overview of the alarm status of all areas which can be viewed by an
operator, no matter which graphic is displayed.
28 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
In accordance with the representation type the block icon can contain the following
information:
Plant identification (TagName)
Symbolic status display of the AS module
Setpoint, actual value
Annunciation / operating status display
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 29
CEMAT Platform Architecture Guide
The symbol shows green color if the equipment is running and grey if the equipment is not in
operation.
The Tagname is highlighted if the motor is not ok:
Note: Depending on the available space in the process picture the Tagname can be the
complete Name of the equipment, e. g. 123_BC1 or only the second part without the area
code, e. g. BC1.
With an additional indication around the TAG the status for Sequence Test, Bad Quality and
Override (Simulation) can be shown.
Orange Override or Simulation (e. g. for the limit switches of the valve)
Violet Not ready (Sequence test mode)
Red Fault
30 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 31
CEMAT Platform Architecture Guide
The Tagname is invisible as long as there is no fault. For the status indication the following
background colors are used:
The following colors are used to indicate the status of the measure:
Yellow Warning
Red Fault
Orange Override or Simulation
Warn-Objects
Drives, which are not required for the production process, can be projected as Warn-Drives
(Parameter WMOD=1). In case of a breakdown the group will continue running, etc. they can
start again. Then the malfunction signal is yellow.
32 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Beside the status information it shows the Sep Point, the actual value and the Output
(Manipulated Value).
Block icons for modules which provide data for the information system:
For the block C_RUNNT the symbol shows the following information:
For the block C_COUNT the symbol shows the following information:
Bitmaps
A wide range of bitmaps for Cement Applications are available in the Standard Directory
D:\CEM_V6\Bitmpas\ and can be used for the design of the Process pictures.
The bitmaps must be copied into the <WinCC-Project directory>\GraCS of the Server Project.
The distribution to other OS Projects can be done with a batch file.
The bitmaps for the Symbols (Drives, Valves) from Version 4.12 of CEMAT can also be used.
You find further models on the CD under CD:\Additional_Information\CEM_DRAFTS.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 33
CEMAT Platform Architecture Guide
34 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
3.7.5 Faceplates
A single mouse-click on the block icon opens the faceplate of the object. The faceplate
provides detailed information and allows control and monitoring of the associated AS module.
The Faceplate is divided in general sections:
- Heading line
- Object description
- Module status display
- Object function operator commands
- Setpoint functions
- Analog Process Value
- Current or Power function
- Invocation buttons for secondary dialog
(1) Keep the Faceplate on top if the process picture has been changed.
(2-5) the message status is displayed.
(2) Alarm, (3) Warning, (4) System, (5) Operation
(6) If there is an alarm in this module, it can be acknowledged using the respective button.
(7) Worst Input signal State
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 35
CEMAT Platform Architecture Guide
36 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
value is shown in the „actual Setpoint“ field. Without Setpoint tracking the OS Setpoint will be
shown and the external Setpoint is only in the Diagnosis Dialog visible. Without external
Setpoint the Setpoint Input is checked for Low limit SP_LLM and High limit SP_HLM.(see
diagnosis dialog). There is no further evaluation in the drive block, the Setpoint is directly
written to the output SP_O . With click on the “Process value” field the Faceplate of the
connected Analogvalue will be open.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 37
CEMAT Platform Architecture Guide
38 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
(13) Enabled
Under 'Enabled' it can be seen which functions are enabled by the program.
(15) Faults
Colored squares indicate faults.
Signal status "0" = gray (no fault)
"1" = red (fault)
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 39
CEMAT Platform Architecture Guide
The CEMAT Interlock dialog displays only a (5) textual description of the inputs, its logical
state and the (6) subsequent interconnection.
The input text describes the error (max. 16 characters).
In an error situation, the input text is displayed with a red background.
40 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 41
CEMAT Platform Architecture Guide
Inside the (3) operation- and (5) process list it is possible to scroll up and down or change the
archives.
The structure of (4) Operation list is as follow: Date, Time, Tag and Operation (with user, text
and value)
The structure of (7) Process list is as follow: Date, Time, Tag, Event and Fault Class
Depending on (9) selection button it is also possible to show additional Signal faults as RL2 or
SL01 (7)
With button (10) reset the standard selection will be shown and with button (8) the two lists
will be updated.
(11) Close the dialog
42 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 43
CEMAT Platform Architecture Guide
44 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The "Device Overview" button (14) opens the following Dialog where the Device Information
can be entered. Closing the window the information is stored in the User Archive C_Info.
Caution: In the Maintenance Dialog the Device information is not automatically refreshed.
You have to press "Refresh Display" in order to display the actualized data.
The Device Information is part of the user Archive C_Info and can also be imported via CSV
file.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 45
CEMAT Platform Architecture Guide
The CEMAT Maintenance List shows all drives which are enabled for Maintenance (each
object with Interval value > 0) and its Maintenance status.
The list can be opened using the button "Maintenance Info Overview" in the Maintenance
faceplate or via a separate button from any process picture.
The filter function can be used to search for specific objects. Use "Refresh" button on order to
update the list.
Scroll bar can be used to scroll fore and back. You will always see the 20 objects before ore
behind.
46 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
(9) Input and Output information with absolute and symbolic address, DP Bus/ Address and
Slot.
The Text files for I/O Info can be created with an Excel Macro based on the data from the
HW-Configuration and the Process object view. Refer to chapter 09_Engineering_Tools.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 47
CEMAT Platform Architecture Guide
48 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
(3) MCC Data with information about the location and Fuse and Bimetall setting
(9) The chronological messages of the Object will be shown together. (alarm and operation)
(12) Open file with MCC information (only .jpg)
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 49
CEMAT Platform Architecture Guide
Additional User Documents can be linked to each Object via Information Dialog.
(The function is optional and must be configured accordingly):
In the Folders Input/Output, MCC Data and AS Hardware and Software a button will open
respective drawings:
Folder 'AS hardware' Construction of the cabinet in which the AS is installed which this object
belongs to (cabinet assignment).
For this function, the File names of the documents must coincide with the object name.
50 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The additional Buttons at the bottom of the information dialog can be used to open a Sound
file, a Video, a Operatin procedure, a Function description, a Loop diagram, an Electrical
schematic or a MCC Data .
General function desc. Descriptions of general functions for this object (USER)
as doc, pdf, xls
For this function, the file names must be entered under 'Service'.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 51
CEMAT Platform Architecture Guide
52 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Process parameters
This dialog is used to configure the controller parameters.
Curve window
A curve window displays the setpoint, actual value, and the manipulated value. The Ruler
button displays a ruler and the associated display of the values for W, X, Y at this ruler
position.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 53
CEMAT Platform Architecture Guide
The following will be indicated in the table (from the left to the right):
(2) Index, (3) Tag of the faulty object, (4) fault type, (5)comment from the module.
The actualization button,(7) number of messages and the (8) WinCC server name are
indicated at the left bottom side.
With the (9) “abort button” the function will be terminated and with (10) “Close” the dialog will
be closed.
54 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 55
CEMAT Platform Architecture Guide
A click on the soft key „save“ (7) stores the new tree structure to the user archive.
Single click on the soft key (6), reads the objects again from the AS and shows them unsorted
in the tree structure.
A double-click on the line opens the faceplate of the corresponding object.
(8) WinCC server name are indicated if the connection is ok
With the (9) “abort button” the function will be terminated
The window will be closed by clicking on the soft key (10) „Close“.
56 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 57
CEMAT Platform Architecture Guide
Display
Function description
On top of the Dialog the 8 curves with information of TAG (2), actual value (3), unit (4),
comment (5).
With the colored Button (1) at the beginning of each line the curve display can be switched
off/on (with left mouse button click).
With right mouse button click, each Value axis (11) can be switched off/on
If the ruler is switched on(6) the ruler -value(8), -Time(9) and –archive name(7) will be shown.
With the reset button (10) the “top area” will be initialized
58 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Icon/function Description/functionality
“ Help” Opens the help for WinCC OnlineTrendControl.
"Configuration dialog" Opens the configuration dialog, in which you can change the
properties of the OnlineTrendControl.
"First data record" Use this button to display in the trend window the trend of a tag over a
specified period of time beginning with the first archived value.
The button is enabled only if the update has been cancelled by
pressing the "Stop" icon.
"Previous data record" Use this button to display in the trend window the trend of a tag from a
period previous to the currently shown time interval.
The button is enabled only if the update has been cancelled by
pressing the "Stop" icon.
"Next data record" Use this button to display in the trend window the trend of a tag for the
period of time to follow the currently shown time interval. The button is
enabled only if the update has been cancelled by pressing the "Stop"
icon.
"Last data record" Use this button to display in the trend window the trend of a tag over a
specified period of time ending with the last archived value.
The button is enabled only if the update has been cancelled by
pressing the "Stop" icon.
"Zoom section" You can select an area by dragging the mouse in the trend window.
This section of the trend window is enlarged. You can return to the
original view using the "Normal view" button.
Zoom in/out Zooms the visualized range of values without zooming the time
coordinate. The trend is compressed for display purposes.
The 50 % mark is located in the center of the value axis.
You can use this function if a fixed value range, a linear scale, and no user-
defined scale have been set for all the trends in WinCC OnlineTrendControl.
"Move trend selection" Use the button to move the trends in the trend window along the time
coordinate and the value axis.
"Move axis selection" Use the button to move the trends in the trend window along the value
axis.
"Original view" Use the button to return to the original view from the enlarged display
of a trend.
"Start/Stop" The display update is cancelled or continued. The data is temporarily
buffered and entered again in the trend window the next time the
button is pressed.
"Print" Starts printing the trend which is visualized in the trend view. You can
specify the print request to be used for printing in the "General" tab of
the configuration dialog.
"Ruler" You can use the button to show the coordinates of a trend. The trend
data is shown in the ruler window.
The ruler window is an independent control as of PCS 7 V8.0 and will
not be shown when the OnlineTrendControl is opened via
"Load/configure trend groups". The ruler window control can be
configured in a process picture during the configuration of an
OnlineTrendControl.
"Specify statistical range" Use the button to specify the period of time for calculating the statistics
in the trend window.
"Calculate statistics" Use the button to display the statistical values in the statistics window.
The displayed values are based on a selected trend with the
configured calculation period. The button can only be pressed when a
statistics window is linked to the OnlineTrendControl.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 59
CEMAT Platform Architecture Guide
Icon/function Description/functionality
Relative scale The range of values of all trends of a group is visualized within a low
limit of 0 % and a high limit of 100 %.
You can use this function:
• If a fixed value range, a linear scale, but no user-defined scale
have been set for all the trends in WinCC OnlineTrendControl.
If you want to compare several values for the purpose of detecting process
relationships, e.g., pressure increase as a result of a rise in temperature.
Function description
Day of the week (9):Opening the trend display, the actual day of the week is shown on the
right side, the last days of a week on the left side.
With click on a “Day button“ the display switches over to offline and to
this day. The previously adjusted time range remains.
Time Range (11) The default value of time range is 30 min. selectable are 1min. up to 24h.
The Time Range can be adjusted only in offline mode.
Online (10) Online mode is predefined.
Switches back to online mode. The previously selected Time Range gets
dark gray and in order to show that no Time Range is considered.
Print With click on the printer symbol the offline view is printed. CEMAT can use
the print job C_TrendReport.rpl.
60 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
@TRG_ CEMAT_FS.pdl without Tag and online value informations, but fast select buttons.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 61
CEMAT Platform Architecture Guide
Quick View
Right mouse click on the value of block icon opens the quick view of the archive value
Quick Trend
Right mouse click on the unit of the block icon opens the quick trend management dialog. (in
case it was not open) and writes the Object TAG , actual value, unit, comment and the
archive name into the first line of the list.
62 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Every new click on the unit of the block icon will add the new TAG to the list.(1-6) (up to 8).
With an click on the button right (7) a new Trend Dialog with all curves from the archive will be
shown. (see below).
In area “Archive Management” (1) it is possible to create a new Dataset (2,9) with Name (4)
and Description (5), sorted by “selected Area” (3, 10). With the save (8) button the new
Dataset will be stored.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 63
CEMAT Platform Architecture Guide
With button “Read” (7) an before selected Dataset will be loaded an can shown in the
Trenddialog.
With button “Delete” (6) an before selected Dataset will be erased from the archive.
64 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
This option allows the display of pre-configured curve groups in full screen mode,
which means, when opening the curve group the complete screen is used as working area.
There is no alarm line, no overview range (picture tree) and no button line.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 65
CEMAT Platform Architecture Guide
Message line
The message line displays the non-acknowledged messages from the selected plant
sections.
A newly arrived message
- always appears immediately in the message line (even when operations are being
performed on the previously displayed message).
- produces an acoustical signal that continues until it is reset by clicking an
acknowledge key.
A message line can contain the following information (from left to right):
- Incoming date/time of the message
- Plant identifier
- Fault type
- Message text
- Fault class. (P = process, E = electrical, M = mechanical, S = safety (emergency off))
In case of an alarm flooding Cemat analyses and prioritizes all alarms. As a result only one
alarm will be recorded and reported in detail, while all other alarms are suppressed.
Each alarm must be acknowledged individually in the Alarm line
Only activated objects can generate alarms
Each fault is classified. Cemat distinguishes between electrical, mechanical or process faults
or local emergency shutdowns.
The following events are displayed:
- potentially dangerous process conditions
- setpoint deviations beyond pre-selected values
- blocking of a start, stop or changeover operation
- operating interruptions
66 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Color attributes
The messages are displayed in the following colors depending on the message class and
message state:
Error messages Warning messages Process messages
Message arrived white / red black / yellow white / red
Message gone black / light green black / light green black / light green
Operator Control
The three additional keys placed at the right of the message line initiate the following
functions:
- left mouse button (SC) Invoke alarm picture (Loop in Alarm). This is
the process picture in which the faulty object is
displayed.
- right mouse button (SC) open “selection of Plant Zones” dialog
- left mouse button (SC) Invoke faceplate dialog for the object. From the
faceplate you have the possibility to call the
subsequent dialogs Diagnosis and Info
- right mouse button (SC) Show the CEMAT Version dialog
- left mouse button (SC) Open the Alarm dialog (list of all non-
acknowledged alarms)
- left mouse button (SC) Acknowledge pending messages until the
message line is empty. When a message is
acknowledged, the next non-acknowledged
messages move up and an acknowledge
telegram is sent to the automation unit from
which the message came.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 67
CEMAT Platform Architecture Guide
If you open the CEMAT message list, the previously defined settings are recovered.
If you close the CEMAT message list with the ‘Close’ Button, the actual settings are saved
and the previous process picture is displayed again.
68 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 69
CEMAT Platform Architecture Guide
The CEMAT Operation list shows only the operator messages and has the following
structure:
DC on one of the column the whole working area will be sorted upward. DC again sorted
downward
Double click on a second column the working area will be sorted again. (Col. marked with 2).
Color attributes
Depending on the message class and message state, the messages are displayed in the
following colors:
Alarm Warning Process Operator Input
Message arrived white / red black / yellow white / red black / cyan
Message black / pink black / light white / pink -
acknowledged yellow
Message gone black / light green black / light green black / light green -
70 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Date / Time Date input fields from – to Can only be operated if long term is selected:
(29) Input fields for date/time.
Time input fields from – to
(30)
Refreshes the display according to the settings for
date/time.
The display of the right status line is deleted.
Refresh (31)
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 71
CEMAT Platform Architecture Guide
E Electrical
M Mechanical
S Safety (emergency off switch)
P Process-conditional
deselected by pressing the corresponding area button. Selected Areas are shown in cyan
color, deselected areas are gray.
If a area selection is stored it will be shown on the right hand site.
Status line
The status line (18) can be seen at the bottom of the CEMAT message system.
At the left side the selected message classes are displayed and at the right side you will find
the time frame. If the date/time filter is activated the right side is empty.
72 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Up to 10 files with user defined selection are displayed. You can select only one.
Cancel: The dialog is closed without selection of a new file.
Open: The dialog will be closed and the selected file is used.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 73
CEMAT Platform Architecture Guide
For MultiClients the Server name is displayed (the Server which is currently connected).
For the other station types (Single Stations or Server) the own station name is displayed.
Left mouse click on the user field opens the System Login dialog.
Right mouse clock on the user field opens the CEMAT User Information dialog below:
In the CEMAT User Information dialog you can see which authorizations are enabled for the
actual user.
The right hand side shows a list of all User Groups and Users.
74 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 75
CEMAT Platform Architecture Guide
User groups
Example for 5 User groups witch could be expanded.
Function
Master Operator
Administrator
Supervisor
Operator
Guest
User administrator x
Authorization for the Area x x x x x
System change x
Monitoring x x x x x
Process controlling x x x
Higher process control x x
Report System x x
Archive controlling x
Modify warning limits x x
Modify alarm limits x
Modify switching limits x x x
Controller parameters x
Object parameters x
System operations x
Interlocking signals x x
Enter recipe data x x
Read recipe data x x x
Info dialog value input x x x x
Info dialog Service x
parameterization
76 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The following software options expand the basic system with special functions:
Import/export assistant ( necessary for HDRS data import)
Version cross-checker
Engineering Process Safety for engineering of fail-safe systems, including SIMATIC
Safety Matrix engineering tool
SIMATIC PCS 7 asset engineering
SIMATIC PDM Process Device Manager for SIMATIC PCS 7
S7-PLCSIM for the functional testing of CFC/SFC programs
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 77
CEMAT Platform Architecture Guide
78 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The test system is mounted on a mobile test rack and contains the Hardware shown on top.
An operation console with simulation push-buttons, lamps and analog signal sources and a
separate software simulation package shall allow the simulation of I/O via the Plant field bus
and testing of any department application
The “Test station” should be also used for FAT.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 79
CEMAT Platform Architecture Guide
Simulator components
To operate I/O simulation on PCS7/S7 automation systems with profibus network, a PC has
to be provided and equipped with the following HW/SW parts listed below:
• WinMOD XT SV5.0 system software
The WinMOD simulation software is an editing- and runtime-interface for real-time
simulations. It connects a graphical interface with high-quality behaviour simulations.
Order number: W 00 50 05
• WinMOD A78 V5.x configuration software
The A78 V5.x configuration software for Profibus DP-Multislave ensures the system
coupling between the automation system (Siemens PCS7 and S7) and WinMOD.
Order number: W 01 78 15
• WinMOD PCI Profibus DP card hardware
The “WM_PCI_DP-1D” PCI Profibus card is the HW component that ensure the
physical interface between the automation system (Siemens PCS7/S7) and WinMOD.
It is a twochannel card, in order to allow two field bus networks to be emulated at the
same time.
Order number: W 09 74 1D
• Simulator PC recommended configuration:
HW: Intel Pentium 2GHz, 1Gb RAM, 20Mb free hard disk space.
SW: Microsoft Windows 2000, XP, Internet explorer 5.01 or higher.
80 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 81
CEMAT Platform Architecture Guide
Controller functions
CTRL_PID PID-Controller
C_PID3 PID-Controller with 3 Parameter tables
CTRL_S Step Controller
RATIO_P Ratio Controller
Special functions
C_ADAPT Adapter block to include non-CEMAT modules into group supervision.
C_POLY3 Polygon module with 3 outputs (used for startup / shut down Kiln)
The detailed description of the CEMAT Functions you find in the object description an in the
only help.
All other blocks from the PCS7 standard library can be used as well.
82 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 83
CEMAT Platform Architecture Guide
Automatic start/stop can also be initiated by a process condition. Automatic start via program
has to be enabled by the operator (Standby Mode)
In the Single-start mode the drives can be started and stopped individually from the operator
station. The single-start mode must be enabled by the operator in the control room. Enable
and disable has to be carried out individually per object. Enable of the single-start mode is
only possible as long as the drive is not yet running.
In the single-start mode the drive module itself generates a start-up-warning. After the start-up
warning time has elapsed the start command is given.
The single-start mode is a non-interlocked mode, which means that start and operating
conditions of the drive are not effective. Protection interlocks are still effective.
An already running drive can be switched back to automatic mode. If the interlocking
conditions are fulfilled, the drive will keep running.
A third mode allows starting and stopping of the drives from locally installed push buttons.
The so-called Local mode is mainly used for maintenance and must be enabled by the
operator in the control room. The local mode can be enabled/disabled individually per object
or for all objects within a group. Enable of the local mode is only possible as long as the
object is not yet running.
In the local mode, by default the drive module itself does not generate a start-up warning but
this can be configured.
The local mode is a non-interlocked mode, which means that start and operating conditions of
the drive are not effective.
Protection interlocks are still effective. Exception: A special protection interlock can by by-
passed in local mode by pressing the Local Start button.
An already running drive can be switched back to automatic mode. If the interlocking
conditions are fulfilled, the drive will keep running.
84 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Immediate stop
The immediate stop can be carried out via operator faceplate of the group or via program.
After pressing immediate stop, all drives are switched into automatic mode and they are
stopped instantaneously, without time delay.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 85
CEMAT Platform Architecture Guide
If a plant fault needs the attention of the operator (e. g. something has been stopped by a
wrong process condition) an alarm message will be generated. Each incoming alarm must be
acknowledged individually by the operator.
One of the main features of CEMAT is that no unnecessary alarms are generated.
Alarms are filtered per section (AREA): Only the operator who is authorized for a plant
sections will see the alarms.
A plausibility logic prevents fault messages caused by another fault
In case of general faults like power supply failure, the alarms from the modules are
blocked and only the alarm for power supply failure will be given.
If the drives are enabled for local operation, no alarm message is created.
Alarms messages are only created in Automatic mode and in Single-start mode, but only
if the drive is started or already running. Drives which are not in operation will not create
alarms.
86 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
For the setup of the PCS7 Project the Engineering rules of the Cemat Engineering Manual,
Chapter 3 must be followed.
A MultiProject must be created according to the actual plant configuration.
4.4.2 AS Engineering
After the setup of the project the CEMAT blocks are available and the application program
can be created.
For repeating functions process tag types can be created in PCS7. An Excel Tool converts
the engineering data from a “User Excel Sheet” into import files for PCS7 and creates part of
the program automatically using the IEA-Assistant of PCS7.
(See “09_Engineering_Tools_009.pdf”)
The rest of the Programming is carried out in the continuous function chart (CFC). Sequence
function chart (SFC) is not needed in CEMAT.
The block interfaces are described in the Reference Manual of CEMAT (Object descriptions).
The following page shows the general structure of the CEMAT blocks and shows an example
of the CEMAT Drive block.
Any other PCS7 block can be used in the application as well.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 87
CEMAT Platform Architecture Guide
4.4.3 OS Engineering
For the representation of the plant objects in the pictures and for the picture structure the
HOLCIM “Design Criteria for Process Control and Electrical Equipment (PART IV)” and
“HMI Screen Design Guidline” has to be followed.
88 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Failure of specifications and attachments and/or drawings to state or show materials, which
are essential to make specified equipment complete, does not relieve the vendor from the
responsibilities for furnishing such material.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 89
CEMAT Platform Architecture Guide
The project manager is the contact person and coordinator for all technical and commercial
issues throughout the period of project execution. He communicates with the project manager
of the purchaser.
With the quotation, a summary project schedule, a project loading chart and an organization
chart will be attached.
90 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
CEMAT Platform Architecture Guide
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 91
CEMAT Platform Architecture Guide
With use of HOLCIM Standard Configuration and the” General Consumers/Drive/Signal List” together with the CEMAT V8Configuration Tool it will possible to
create a budget price and Material List.
92 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
CEMAT Platform Architecture Guide
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 93
Platform Architecture Guide CEMAT
Step 2-> Define the amount of Consumers/Signals for the actual HOLCIM Cement Line
Raw Raw
Mat. Meal AFR Clinker Clinker Cement Packing
Prep. Prep. Coal Mill Prep. Prod.1 Prod.2 Grinding Shipping Auxiliary Total
Consumers Unidirectional
/Drive Drive(6000VAC) 1 2 2 2 2 2 0 0 11
Unidirectional Drive(400VAC) 50 75 90 60 262 150 50 30 767
Variable Speed Drive
(SinaGS) 5 6 10 15 10 5 0 0 51
Actuator (Damper) 2 11 12 13 70 3 20 2 133
Valve 23 22 24 20 100 15 40 20 264
Subcontrol Systems big 4 2 4 2 7 15 5 20 59
Total 85 118 142 112 451 0 190 115 72 1285
Control Clontrol Loop 3 10 14 7 24 10 0 0 68
(IN) Signals Digital 450 900 650 700 2100 1400 500 6700
Analog 20 78 50 90 300 180 20 40 778
(OUT) Signals Digital 200 250 200 400 800 500 135 135 2620
Analog 2 20 10 34 40 25 10 6 147
0
Summary Digital Total 650 1150 850 1100 2900 0 1900 135 635 9320
Device 8 10 6 10 6 9 9 58
Analog Total 22 98 60 124 340 0 205 30 46 925
Device 0 1 0 1 1 1 1 1 6
94 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
CEMAT Platform Architecture Guide
Step 3 -> Transfer the Information from the HOCIM Consumer List to the CEMAT Object table
(witch we have to use later in the CEMAT Configuration Tool )
Raw
Raw Mat. Meal AFR Clinker Clinker Cement Packing
Prep. Prep. Coal Mill Prep. Prod.1 Prod.2 Grinding Shipping Auxiliary
Unidirectional
47 72 89 59 144 120 148 45 30
Actuator (Damper) 2 11 12 13 70 30 3 20 2
Bidirectional Drive 4 5 3 3 4 5 0
Annunciation 152 220 256 190 288 300 340 220 104
Selection Module 10 10 10 10 10 10 10 20
Process Feedback(H) 10 15 18 12 14 15 30 9 6
Variable Speed Drive
5 6 10 15 2 8 5 0 0
Subcontrol Systems small 3
Subcontrol Systems big 4 2 4 2 7 3 15 5 20
Counter 10 10 10 10 10 10 10 10 20
Run Time 5 5 5 5 5 5 5 0 10
AS-Object 1 1 1 1 1 1 1 1 1
Integrator
SIMOCODE Adapter
Closed Loop Contr. PCS7 3 10 14 7 24 18 10 0 0
Analog Output 2 20 10 34 40 30 25 10 6
Bool Variable(H) 10 10 10 10 10 10 10 10 20
Interger Variable(H) 5 5 5 5 5 5 5 5 5
String Variable(H) 5 5 5 5 5 5 5 5 5
Interlock 152 220 256 190 288 300 340 220 104
Interlock5
How to use the CEMAT V8 Configuration Tool you will find in appendix C
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 95
Platform Architecture Guide CEMAT
6 Training
96 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
CEMAT Platform Architecture Guide
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 97
CEMAT Platform Architecture Guide
If there are more training required please look to the following Courses.
98 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
If the training is carried out for more than two participants, a Projector is needed.
The projector must be capable for a screen resolution of 1280x1024
If a real PLC is used the following Hardware and Software must be supplied additionally:
PCS7 AS:
1 Rack UR2 6ES7 400-1JA00-0AA0
1 PS 407 10A 6ES7 407-0KA00-0AA0
1 CPU 416-2 6ES7 416-2XK02-0AB0 (minimum)
1 CP443-1 6GK7 443-1EX11-0XE0
Process Bus:
2 Network Cables
1 HUB
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 99
CEMAT Platform Architecture Guide
100 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
7 System Performance
System Configuration
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 101
CEMAT Platform Architecture Guide
Type Profibus DP
Manufacturer Siemens
Protocol IEC 1158-2, EN 50170
Transfer speed Max. 12 Mbit/s
Number of possible nodes 96 or 125 nodes
Max. bus length 2-wire: 1000 m
Optical-fiber: up to 15 km
Cable type
- Coaxial No
- Optical-fiber 50/125 glass fiber Yes
- Miscellaneous 2-wire (Profibus type)
Bus components Optical Link Module
Interfaces
Type Profibus PA
Transfer speed max. 31 kbit/s
Protocol IEC 1158-2
Manufacturer Siemens
Number of possible field devices 31 not ex-area31
10 Ex-zone 1
102 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Process Station
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 103
CEMAT Platform Architecture Guide
104 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 105
CEMAT Platform Architecture Guide
106 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 107
CEMAT Platform Architecture Guide
108 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Pictures
Number of pictures 120 Unlimited -
Number of controls
250 approx. 800
(stat. and dyn.) per picture
Picture level 3 32
Picture size in pixel 1280x1024 10000x10000
Drive functions
- per control system 2400 6000 Distributed over several
- per AS 300 400 servers
Measured value
- per control system 1600 5000 Distributed over several
- per AS 200 300 servers
Quantity values
(counters (CNT), runtimes (RT))
- per control system 800 3000 Distributed over several
- per AS 100 250 servers
Controllers
Short trend
- per control system 500 2000 Distributed over several
servers
Short trend
- per control system 500 2000 Distributed over several
servers
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 109
CEMAT Platform Architecture Guide
Curves
Number of curve frames per graphics 2 25
picture
Number of curves per curve frame 6 80
Number of curves per picture 12 80
Archives per Server/ Single Station 20 100
Archiving Values 2000 30000 Archive server necessary
Number of measured values per All Depends on the acquisition
measuring points on HD cycle, for recording longer
than 1 week
Number of measured values per 30 Time duration Depends on the acquisition
measuring point in main memory 10 minutes cycle
Alarms / messages
Configurable massages per server 20000 150000 Object dependent
Message classes 10 18
Message types 16
Message priorities 2 17
Process tags per message line 1 10
User text blocks per message line 4 10
Number of message archives 1 1
Number of current message archives 1000 2000
Number of long-term message archives 8 days 30 days
Message burst without message loss 10/sec. 100/sec.
Messages permanent 20/h 10/ sec.
Note: Some of the maximum values are significantly larger than the typical values and can
normally be "approached" when other requirements are reduced. The typical values apply in
combination and have been tested in this form.
110 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
AS response time
AS response time S5 300 ms 800 ms 1 cycle
AS response time S7 100 ms 300 ms 1 cycle
Curve output
Output/selection trend archive 2 sec 2 sec 6 curves
Output/selection long-term archive 10 sec Max. value depends on the
selection criterion
Memory Requirement
Message
Hard disc space RT
- Message without accompanying 172 byte
values and comments with 10-times compression
- Message with max.amount of 4012 byte
accompanying values and comments
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 111
CEMAT Platform Architecture Guide
8 Support
Helpline (365 days a year, 24 hours a day):
Tel.: +49 (0) 180 50 50 111
112 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Periodicals:
Process News online:
http://www.processnews.com
ProfiBus DP
http://www.automation.siemens.com/net/html_76/produkte/020_produkte.htm
CEMAT information
http://www.siemens.com/cemat
Design Criteria for Process Control and Electrical Equipment (PART IV) HOLCIM
02_System_Description_009.pdf in DOCU/Reference/System/ CEMAT
02_Preparations_009.pdf in DOCU/Engineering CEMAT
09_Engineering_Tools_009.pdf in DOCU/Engineering CEMAT
Object description in DOCU/Reference/Objects CEMAT
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 113
CEMAT Platform Architecture Guide
Appendix
114 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
CEMAT Platform Architecture Guide
A Appendix A
A.1 Module Description (Function Overview)
Input interface
Visualisation status
(interlocking conditions) ModulTag
(invisible)
C_FUNCTION TASK
- when to start
Description G-No./Task-No. To the Operator station
- when to stop
- which protection
etc.
Release Functions
Output interfaces
Release Functions
Release Annunciations Module flags for internal
connections
Process values
- Start/stop delay
- Limit values Periphery signals
etc. (Process image outputs)
Lamps, Contactors,
Relays
Commands (invisible)
115 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Each block has a list of input and output parameters, which can be connected either with a
signal (from the symbols file or an output of another block) or parameterized with a value.
Due to its utilization the inputs and outputs have different attributes which can be seen in the
object properties in tab "I/Os".
In Cemat we distinguish between different parameter types:
Input Interfaces
The so-called interface flags are used for starting, stopping, changing operation modes or
interlocking the blocks. They are mostly connected to an output of another Cemat block or to
some logic.
The interface flags are of type "Parameter". The linking if the interface flags can either be
done in the CFC or in the process object view in tab "Parameters".
New: With Cemat V8.0 the interlock interfaces (start interlock, operating interlock, protection
interlock etc.) and some of the block outputs (drive running, route selected etc.) are available
as structure inputs.
Instead of a binary connection, the link can be made via structure connection. Beside the
binary information the structure contains the signal status, which is displayed in the diagnosis
window. An additional advantage of the structure connection is that in the operation system
you can directly jump from one object faceplate to its predecessor or to the following object.
Using this method you can follow a missing interlocking condition very fast to its original
cause.
The binary interfaces for interlocking conditions can still be used, if someone doesn't want to
use the new functions (e. g. in case of a migration). It is also possible to use both inputs
(binary and structure) parallel.
Releases
Some functions of the Cemat blocks must be enabled or disabled according to the demand.
Some release functions can be carried out by the program others only from the Operator
Station (both is not possible).
The Release bits which can be connected in the CFC are of type "Parameter". The
connection can be programmed in the CFC or in the process object view in tab "Parameters".
Links
Each drive, annunciation block and measure must be connected to the group via the so-called
group link. The blocks can directly be connected to the group or indirectly via route module.
The links are of type "Parameter" and can be connected in the CFC or in the process object
view in tab "Parameters".
Process Values
Limit values, supervision or delay times are called the process values of the blocks. You can
retain the default values or if required you can adapt it according to the need of your
application. The adaptation can be carried out either in the CFC or from the Operator Station.
We recommend to adapt the values as far as possible during the engineering and to leave the
fine tuning for the commissioning.
Copyright © Siemens AG. All Rights Reserved. Version/ Date V1.6/ 2012-10-15 117
CEMAT Platform Architecture Guide
The process values are of type "Parameter". The parameterization can be carried out in the
CFC or in the process object view in tab "Parameters".
Output Interfaces
The most important information of the blocks are transferred to block outputs and therefore
available for the connection to other blocks.
New: Some of the outputs (drive running, route selected etc.) are additionally available as
structure output. See Input Interfaces.
A detailed functional description of the blocks you will find in the reference manual. There is a
separate chapter for each object type.
118 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The following standard signals are monitored for each unidirectional drive:
- Contactor feedback R in conjunction with the contactor output D
- Electrical availability K
- Overload T
- Local isolated U
- Local stop button S
If the drive is in automatic or in single-start mode and if the drive is in operation, any of the
above mentioned faults leads to an alarm message.
The drive can be configured as normal drive or warning drive. In case of a normal drive,
error messages are created. In case of a warning drive, warning messages are created.
Faceplate
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 119
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the drive
function block. More detailed information you will find in the object description of the block.
ModuleTag
C_DRV_1D MAIN_TAS
Unidirectional drive 1/23
Feedback ON 0 BO R EVS BO Running signal
Available 1 BO K LOCAL BO Drive in local mode
Overload 1 BO T D BO Contactor ON
Local switch Isolated 1 BO U
Local Stop 1 BO S
Local Start 0 BO G
Start interlock 1 BO EEVG
Operating interlock 1 BO EBVG
Protection interl. (allways active) 1 BO PINT1
Protection interl. (can be bypassed) 1 BO PINT2
Sporadic ON/OFF 1 BO ESPO
Process Feedback 1 BO PRFB
Enable local mode 0 BO ENLM
Disable local mode 0 BO DILM
Annunciation Release 0 BO EMFR
Type of drive (1 =Warming, 0 =Fail.) 0 BO WMOD
Command ON 0 BO EBFE
Command OFF 0 BO EBFA
Quick stop 0 BO QSTP
feedback time 4 I FEEDBTIM
start delay 0 I STARTDEL
stop delay 0 I STOPDEL
time for start up warning 10 I HORN_TIM
Group Stopped 0 BO GR_STP
Link to the Group 0 I GR_LINK1
The standard signals of the motor like Contactor ON, Contactor Feedback, etc. have to be
linked to the corresponding interfaces of the drive block.
If additional protections are available for the drive or for the equipment, those signals have to
be linked to an Annunciation block or a Process Feedback block in order to get an alarm. In
order to stop the drive in case of a fault an output of the annunciation block has to be
connected to the protection interlock of the drive:
- Protection interlock PINT1 effective in all modes
- Protection interlock PINT2 effective in all modes (can be by-passed in local mode)
Interlocks can be used in order to enable or disable the drive operation dependent on a
process condition, like "previous drive is running" or a process signal:
- Start interlock EEVG effective only in auto and in single-start mode
- Operating interlock EBVG effective only in auto and in single-start mode
- Sporadic ON/OFF ESPO only in auto mode
120 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The block icon of the unidirectional drive shows the following information:
The symbol of the equipment show grey for "Motor not running" and green for "Motor
running"
The Tagname is highlighted in case of an error (red), warning (yellow), not ready (violet)
An additional indication beside the tagname shows the operation mode:
White = Local mode
Blue = Single-start-mode
No indication = Automatic mode
A violet indication beside the tagname shows that the motor is not ready (he is in
sequence test mode).
A red indication beside the tagname shows "bad quality" for one of the motor signals (this
information is only available if driver blocks are used).
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 121
CEMAT Platform Architecture Guide
Additional Functions
Link to a measured value
A measured value like motor power or motor current can be linked to the drive block in order
to display the percentage value of the measure in the faceplate of the motor.
An additional button in the faceplate allows direct access to the faceplate of the measured
value.
SIMOCODE drives
In case SIMOCODE is used, the block C_SIMOS has to be added for the communication to
the SIMOCODE. An additional button in the drive faceplate opens the faceplate of the
C_SIMOS in order to display the SIMOCODE details.
The percentage value of current and power are directly displayed in the faceplate of the
motor.
Subcontrol Function
Sometimes function blocks and faceplates from sub suppliers are used, as e. g. for weigh
feeders, filter, grate cooler etc. In order to have the same philosophy for all kind of equipment
(block interfaces, summarizing indication in the group) a normal Cemat drive block can be
used in order to give a start command to the subcontrol function. The general fault of the
Subcontrol will be indicated in the diagnosis picture of the drive.
An additional button in the operator faceplate of the drive can be used to open another
faceplate for the display of the detail information for the Subcontrol.
122 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The following standard signals are monitored for each bi-directional drive:
- Contactor feedback RX in conjunction with the contactor output DX
- Contactor feedback RY in conjunction with the contactor output DY
- Electrical availability K
- Overload T
- Local isolated U
- Local stop button S
If the drive is in automatic or in single-start mode and if the drive is in operation, any of the
above mentioned faults leads to an alarm message.
The drive can be configured as normal drive or warning drive. In case of a normal drive,
error messages are created. In case of a warning drive warning messages are created.
Faceplate
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 123
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the drive
function block. More detailed information you will find in the object description of the block.
ModuleTag
C_DRV_1D MAIN_TAS
Unidirectional drive 1/23
Feedback Direction X 0 BO RX EVSX BO Running signal direction X
Feedback Direction Y 0 BO RY EVSY BO Running signal direction Y
Available 1 BO K LOCAL BO Drive in local mode
Overload 1 BO T DX BO Contactor direction X
Local switch Isolated 1 BO U DY BO Contactor direction Y
Local Stop 1 BO S
Local Start direction X 0 BO GX
Local Start direction Y 0 BO GY
Start interlock direction X 1 BO EEVGX
Operating interlock direction X 1 BO EBVGX
Start interlock direction Y 1 BO EEVGY
Operating interlock direction Y 1 BO EBVGY
Protection interl. (allways active) 1 BO PINT1
Protection interl. (can be bypassed) 1 BO PINT2
Sporadic ON/OFF 1 BO ESPO
Process Feedback 1 BO PRFB
Enable local mode 0 BO ENLM
Disable local mode 0 BO DILM
Annunciation Release 0 BO EMFR
Type of drive (1 =Warming, 0 =Fail.) 0 BO WMOD
Command ON direction X 0 BO EBFEX
Command ON direction Y 0 BO EBFEY
Command OFF 0 BO EBFA
Quick stop 0 BO QSTP
feedback time 4 I FEEDBTIM
start delay 0 I STARTDEL
stop delay 0 I STOPDEL
time for start up warning 10 I HORN_TIM
Monitoring for change direction 10 I CHMONTIM
Group stopped 0 BO GR_STP
Link to the group 0 I GR_LINK1
The standard signals of the motor like Contactor ON, Contactor Feedback, Limit switches,
etc. have to be linked to the corresponding interfaces of the drive block.
If additional protections are available for the drive or for the equipment, those signals have to
be linked to an Annunciation block or a Process Feedback block in order to get an alarm. In
order to stop the drive in case of a fault an output of the annunciation block has to be
connected to the protection interlock of the drive:
- Protection interlock PINT1 effective in all modes
- Protection interlock PINT2 effective in all modes (can be by-passed in local mode)
124 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Interlocks can be used in order to enable or disable the drive operation dependent on a
process condition, like "previous drive is running" or a process signal:
- Start interlock EEVGX effective only in auto and in single-start mode
- Operating interlock EBVGX effective only in auto and in single-start mode
- Start interlock EEVGY effective only in auto and in single-start mode
- Operating interlock EBVGY effective only in auto and in single-start mode
- Sporadic ON/OFF ESPO only in auto mode
The block icon of the bi-directional drive shows the following information:
The symbol of the equipment show grey for "Motor not running" and green for "Motor
running"
The Tagname is highlighted in case of an error (red), warning (yellow), not ready (violet)
An additional indication beside the tagname shows the operation mode:
White = Local mode
Blue = Single-start-mode
No indication = Automatic mode
A violet indication beside the tagname shows that the motor is not ready, he is in
sequence test mode.
A red indication beside the tagname shows "bad quality" for one of the motor signals (this
information is only available if driver blocks are used).
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 125
CEMAT Platform Architecture Guide
Additional Functions
Link to a measured value
A measured value like motor power or motor current can be linked to the drive block in order
to display the percentage value of the measure in the faceplate of the motor.
An additional button in the faceplate allows direct access to the faceplate of the measured
value.
SIMOCODE drives
In case SIMOCODE is used, the block C_SIMOS has to be added for the communication to
the SIMOCODE. An additional button in the drive faceplate opens the faceplate of the
C_SIMOS in order to display the SIMOCODE details.
The percentage value of current and power are directly displayed in the faceplate of the
motor.
Subcontrol Function
Sometimes function blocks and faceplates from sub suppliers are used, as e. g. for weigh
feeders, filter, grate cooler etc. In order to have the same philosophy for all kind of equipment
(block interfaces, summarizing indication in the group) a normal Cemat drive block can be
used in order to give a start command to the subcontrol function. The general fault of the
Subcontrol will be indicated in the diagnosis picture of the drive.
An additional button in the operator faceplate of the drive can be used to open another
faceplate for the display of the detail information for the Subcontrol.
126 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
For the "normal control" the start/stop can be carried out in three different operating modes:
- In the automatic mode the damper is opened/closed by a superordinated group module.
- The single-start mode allows individual open/close via operator faceplate of the damper.
- In the local mode the damper can be opened and closed by the locally installed
pushbuttons
S (stop button) and GX and GY (start buttons for direction X and Y).
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 127
CEMAT Platform Architecture Guide
Faceplate
Damper without and with Positioner function:
128 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Function block
The picture below shows the most important interfaces and process parameters of the drive
function block. More detailed information you will find in the object description of the block.
ModuleTag
C_DAMPER MAIN_TAS
Damper 1/23
Feedback Contactor direction X 0 BO RX KVSX BO logic signal Position X
Feedback Contactor direction Y 0 BO RY KVSY BO logic signal Position Y
Limit position X 0 BO ZX LOCAL BO Drive in local mode
Limit position Y 0 BO ZY DX BO Contactor Direction X
Internal Limit position X 0 BO X DY BO Contactor Direction Y
Internal Limit position Y 0 BO Y
Available 1 BO K
Overload 1 BO T
Local switch isolated 1 BO U
Local Stop 1 BO S
Local Start direction X 0 BO GX
Local Start direction Y 0 BO GY
Start interlock direction X 1 BO KEVX
Operating interlock direction X 1 BO KBVX
Protection interlock direction X 1 BO PINTX
Torque switch direction X 0 BO TX
Start interlock direction Y 1 BO KEVY
Operating interlock direction Y 1 BO KBVY
Protection interlock direction Y 1 BO PINTY
Torque switch direction Y 0 BO TY
Enable local mode 0 BO ENLM
Disable local mode 0 BO DILM
Annunciation Release 0 BO KMFR
Type of drive (1= warning, 0= Fail.) 0 BO WMOD
Command ON direction X 0 BO KEBX
Command ON direction Y 0 BO KEBY
Quick stop 0 BO QSTP
Feedback time 4 I FEEDBTIM
Limit switch delay time 2 I LSMONTIM
Run time supervision 90 I RTMONTIM
Wagging number 0 I WAGG_NO
time for start up warning 10 I HORN_TIM
Value position 0.0 R POS_IN
SCB 0.0 R SCB
SCE 100.0 R SCE
Unit %' SN UNIT
Group stopped 0 BO GR_STP
Link to the Group 0 I GR_LINK1
The standard signals of the motor like Contactor ON, Contactor Feedback, Limit switches,
etc. have to be linked to the corresponding interfaces of the drive block.
If additional protections are available for the damper or for the equipment, those signals
have to be linked to an Annunciation block in order to get an alarm. In order to stop the drive
in case of a fault an output of the annunciation block has to be connected to the protection
interlock of the drive:
- Protection interlock PINTX effective in all modes
- Protection interlock PINTY effective in all modes
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 129
CEMAT Platform Architecture Guide
Interlocks can be used in order to enable or disable the damper operation dependent on a
process condition, like "previous drive is running" or a process signal:
- Start interlock KEVX effective only in auto and in single-start mode
- Operating interlock KBVX effective only in auto and in single-start mode
- Start interlock KEVY effective only in auto and in single-start mode
- Operating interlock KBVY effective only in auto and in single-start mode
130 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Additional Functions
SIMOCODE drives
In case SIMOCODE is used, the block C_SIMOS has to be added for the communication to
the SIMOCODE. An additional button in the drive faceplate opens the faceplate of the
C_SIMOS in order to display the SIMOCODE details.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 131
CEMAT Platform Architecture Guide
Faceplate
132 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Function block
The picture below shows the most important interfaces and process parameters of the valve
function block. More detailed information you will find in the object description of the block.
ModuleTag
C_VALVE MAIN_TAS
Valve 1/23
Limit Position X (active) 0 BO X VVSX BO Limit Position X
Limit Position Y 0 BO Y VVSY BO Limit Position Y
Available 1 BO K LOCAL BO Valve in local mode
Local Switch isolated 1 BO U D BO Command on
Local Stop (Direction X) 1 BO S
Local Start (Direction Y) 0 BO G
Start interlock 1 BO VEVG
Operating interlock 1 BO VBVG
Protection interlock (always active) 1 BO PINT
Sporadic on/off 1 BO VSPO
Enable local mode 0 BO ENLM
Disable local mode 0 BO DILM
Annunciation Release 0 BO VMFR
Typ of drive (1= Warning, 0= Fail.) 0 BO WMOD
Command ON 0 BO VBFE
Command OFF 0 BO VBFA
Quick stop 0 BO QSTP
Run time supervision 10 I RTMONTIM
start delay 0 I STARTDEL
stop delay 0 I STOPDEL
time for start up warning 10 I HORN_TIM
Group stopped 0 BO GR_STP
Link to the Group 0 I GR_LINK1
The standard signals of the motor like ON command, Limit switches, etc. have to be linked
to the corresponding interfaces of the drive block.
If additional protections are available for the drive or for the equipment, those signals have to
be linked to an Annunciation block in order to get an alarm. In order to deactivate the valve in
case of a fault an output of the annunciation block has to be connected to the protection
interlock of the valve:
- Protection interlock PINT effective in all modes
Interlocks can be used in order to enable or disable the drive operation dependent on a
process condition, like "previous drive is running" or a process signal:
- Start interlock VEVG effective only in auto and in single-start mode
- Operating interlock VBVG effective only in auto and in single-start mode
- Sporadic ON/OFF ESPO only in auto mode
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 133
CEMAT Platform Architecture Guide
Additional Functions
SIMOCODE valves
In case SIMOCODE is used, the block C_SIMOS has to be added for the communication to
the SIMOCODE. An additional button in the valve faceplate opens the faceplate of the
C_SIMOS in order to display the SIMOCODE details.
134 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
SINA_GS block
Applications
The block is used to integrate a SINAMICS family unit into the PCS7 process
control system. It supports the standard functionality of a SINAMICS with respect to
control from a SIMATIC S7 and operation and monitoring from an operator station.
Communication between inverter and SIMATIC is via PROFIBUS DP.
Type / Number
FB624
The block number can be changed.
Function
The SINA_GS block supports the following functions:
Operation and monitoring of the drive in the "central control" (manual/auto) and "local
control" modes.
Specifying a normalized main setpoint, a additional setpoint and 3 freely selectable
setpoints.
Displaying the main actual value and the actual torque and current.
Monitoring the actual current or torque against definable limits.
Alarm message to PCS7
Detailed information about drive faults
Trend function
Simulation mode with additional inputs and outputs for connecting an external
simulation of the drive
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 135
CEMAT Platform Architecture Guide
Faceplate
Automatic mode
Manual mode
136 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
IMPORTANT
In general, no warranty can be given for changes of the block, because this is entirely the
responsibility of the user. It is always recommended to make a backup of the block before
proceeding.
Faceplate
Button "Curve" opens the curve dialog. There the values for Current and Power are displayed.
Button "Diagnosis" opens the diagnosis window which contains more information about the
status of the SIMOCODE.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 137
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the
C_SIMOS function block. More detailed information you will find in the object description of
the block.
ModuleTag
C_SIMOS MAIN_TAS
Valve 1/23
1 = Standard, 2 = with POWER 1 I BASICTYP I_PERC I Current in %
Input start address (process image) 0 I I_ADDR POWER R Power
Output start addres (process image) 0 I O_ADDR READY BO Communication OK
Start direction 1 1 BO START1 FAULT_SC BO General fault SIMOCODE
Start direcion 2 1 BO START2 EARTH_FT BO Earth fault SIMOCODE
reset SIMOCODE from external 0 BO RESET OV_FT BO Overload fault
Acknowledte from extern 0 BO ACK UNBALANC BO Unbalance
STALL_FT BO Motor stalled fault
WARN_SC BO General warning SIMOCODE
OV_WA BO Overload warning
OVASY_FL BO Overload + asymetrie fault
STAT_SC BY Status SIMOCODE for drived
INPUT1_O BO Basic input 1 of SIMOCODE
INPUT2_O BO Basic input 2 of SIMOCODE
INPUT3_O BO Basic input 3 of SIMOCODE
INPUT4_O BO Basic input 4 of SIMOCODE
FEED_ON1 BO Feedback ON direction 1
FEED_ON2 BO Feedback ON direction 2
The start address for Inputs and outputs has to be configured via Parameter I_ADDR and
O_ADDR.
138 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Starting a group
The group can be started via the Operator Faceplate or via the program. For the start via
program the group must be in "Standby mode". Standby mode must be enabled by the
operator.
With the group start a start-up warning is triggered. After the start-up warning has elapsed,
the group generates the ON-command to start the drives. The ON-command is limited by the
release time, i.e. the start process is aborted after the release time has elapsed.
If a drive is already running in local mode or in single-start mode a group start will switch it
automatically back into automatic mode. Running drives continue to run.
Stopping a group
The group can be stopped via Operator Faceplate or via program. Group stop via program
must not be enabled.
Immediate stop is possible via Operator Faceplate or via program. In this case the stop delay
of the drives is not considered. With an immediate stop all drives are switched to automatic
mode.
After the start-up warning is completed (horn time and waiting time have elapsed) the ON-
command is given to the drives.
- A release time can be configured, which is triggered after the start-up warning has elapsed.
Only within the release time the start command is given to the drives.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 139
CEMAT Platform Architecture Guide
Bypass Interlocks
During commissioning the interlocks (start interlock and operation interlock can be by-passed)
in order to test a group without the previous group being started. Bypass is indicated in the
block icon and in the faceplate.
Group not empty
When the group is completely started it is assumed that material is transported. This is
indicated in the faceplate with "Group not empty". The indication disappears automatically
after a normal group stop.
In case of an immediate stop or a stop by a fault or interlocking the indication "Group not
empty" remains in order to remind the operator that now route change is allowed. The
indication can be reset in the diagnosis window of the group.
Standby mode (starting the group via program)
If the standby function is enabled in the CFC (interface STANDBY = 1-Signal) the standby
mode can be activated from the diagnoses faceplate of the group by pressing the button
"Standby mode".
Faceplate
140 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Special Functions
Group Status call
The status call of the group can be used in order to list all existing faults, warnings or
interlocking conditions of the drives, measuring values and process signals assigned to this
group.
If there the group has routes, the status call of the group is related to the selected routes of
that group. The elements of the not selected route will not be displayed.
Acknowledgement mode
There are two modes for the acknowledgement of a fault in the PLC. By default the
acknowledgement is carried out for the complete PLC. If the acknowledgement shall be
carried out group-wise the setting in the system chart must be adapted and an additional
programming is required per Object.
Group-wise Acknowledgement
If a fault generates an alarm, the alarm appears in the alarm line. Pressing the acknowledge
button in the alarm line, only the alarm disappears.
In order to acknowledge the fault in the AS you have to open the group faceplate and press
button „GRP_ACK“. Only the modules belonging to this group will be acknowledged by this
button.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 141
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the group
function block. More detailed information you will find in the object description of the block.
ModuleTag
C_GROUP MAIN_TASK
Group 1/23
Start interlock 1 BO GEVG GBE BO Command ON
Operating interlock 1 BO GBVG GDA BO Continuous command OFF
Switch-off interlock 1 BO GAVG GRE BO Feedback ON
Quick stop 0 BO GQSP GRA BO Feedback OFF
Feedback ON 0 BO GREZ GQS BO Quickstop
Feedback OFF 1 BO GRAZ GLA BO Lamp start-up warning
Command ON 0 BO GEBG GHA BO start-up warning horn
Command OFF 0 BO GABG G_LINK I Link to the drives/routes
Feedback drives(s) in local mode 0 BO FB_L
Standby 0 BO STANDBY
Start up warning time 10 I HORN_TIM
Waiting time 15 I WAIT_TIM
Release time 300 I RELS_TIM
For the start of the drives, output signal GBE of the group is connected to the drive start
command. Interface GREZ must be used to transmit the information "all drives are running" to
the group.
For the stop of the drives, output signal GDA of the group is connected to the drive stop
command. Interface GRAZ must be used to transmit the information "all drives are stopped to
the group.
In addition to the Operator commands group start and stop can be carried out by program
using interfaces GEBG and GABG.
Interlocks can be used in order to enable or disable the group operation dependent on a
process condition, like "previous group is running" or a process signal:
- Start interlock GEVG effective only before the group start
- Operating interlock GBVG always effective
- Switch-off interlock GAVG effective during group stop
Through process parameters the following values can be configured on the CFC or online:
- Start-up warning time (s) timer for the Horn Output GHA
- Waiting time (s) after this timer has elapsed the group creates ON-command
- Release time (s) for the limitation of the ON-command
142 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 143
CEMAT Platform Architecture Guide
The route can be selected and deselected via the Operator faceplate or through the program,
e. g. by a process signal.
The route module generates operating messages for selection and de-selection.
144 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
Special Functions
Route Status call
The status call of the route can be used in order to list all existing faults, warnings or
interlocking conditions of the drives, measuring values and process signals assigned to this
route.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 145
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the route
function block. More detailed information you will find in the object description of the block.
ModuleTag
C_ROUTE MAIN_TAS
Route 1/23
Start interlock 1 BO WEVG WBE BO Command On
Operating interlock 1 BO WBVG WBA BO Command Off
Feedback ON 1 BO WREZ WRE BO Feedback On
Feedback OFF 1 BO WRAZ WRA BO Feedback Off
Preselection ON/OFF 0 BO WVWT WVE BO Route preselected
Preselection ON 0 BO WVWE WVW BO Route selected
Selection OFF 0 BO WVWA R_LINK I Link to the drives/annunciations
Preselection OFF 0 BO WVWL
Command ON 0 BO WEBW
Command OFF 0 BO WABW
Link to the Group 0 I G_LINK
In addition to the Operator commands selection and de-selection can be carried out by
program using interfaces WVWT, WVWE, WVWA and WVWL.
The group start command is connected to WEBW of the route. The selected route transmits
the start command via output WBE to the drives.
The group stop command is connected to WABW of the route. The selected route transmits
the start command via output WBA to the drives.
The feedback ON of the drives must be connected to the route. The selected route transmits
the feedback ON via output WRE to the group.
The feedback OFF of the drives must be connected to the route. The selected route
transmits the feedback OFF via output WRA to the group.
Interlocks can be used in order to enable or disable the route selection or operation
dependent on a process condition or a process signal:
- Start interlock WEVG effective only before the route selection
- Operating interlock WBVG always effective
146 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 147
CEMAT Platform Architecture Guide
Faceplate
148 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Function block
The picture below shows the most important interfaces and process parameters of the
selection block. More detailed information you will find in the object description of the block.
ModuleTag
C_SELECT MAIN_TAS
Selection 1/23
Selection interlock 1 BO AEVG AZE BO Selected
Deselection interlock 1 BO AAVG
Select 0 BO AEIN
Deselect 0 BO AAUS
In addition to the Operator commands selection and de-selection can be carried out by
program using interfaces AEIN and AAUS.
Interlocks can be used in order to enable or disable the route selection or operation
dependent on a process condition or a process signal:
- Selection Interlock AEVG can be used in order to inhibit selection
- De-selection Interlock AAVG can be used in order to inhibit de-selection
The block icon of the selection block shows the following information:
2nd column: D (white) = deselected
S (green) = selected
4th column: I (yellow) = interlock
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 149
CEMAT Platform Architecture Guide
Interlocks
The annunciation block can also be used in order to display missing interlocking conditions.
These may be process signals like level switches, pressures switches or even an internal
process condition like "no route selected".
In case of a process signal a message may be required but the group should not show the
summarizing fault and warning indications. The annunciation block must be configured
accordingly.
In case of an internal process condition you may not even want the message. The
annunciation block can be configured in a way that it only appears in the status call of the
group.
Alarm repetition
In case of very important process conditions the incoming alarm message can be repeated
after a certain time (if the problem is not yet solved) as a reminder for the operator.
Override function
If the override function is enabled by the Operator Faceplate, the input is not considered any
more. The simulation value is processed. The block icon shows orange color.
150 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
Function block
The picture below shows the most important interfaces and process parameters of the
annunciation block. More detailed information you will find in the object description of the
block.
ModuleTag
C_ANNUNC MAIN_TAS
Annunciation 1/23
Input Signal 0 BO MST0 MAU BO Output signal
Status on MST0 when Signal = OK 1 BO OKS AWA BO Annunciation Warning Active
Alarm interlock 1 BO MAMV
Alarm activation 1 BO MAAT
Annunciation release 1 BO MMFR
Fault interlock to group 0 BO MMZS
1 = Warning, 0 = Failure 0 BO WMOD
Active warning 0 BO AWAN
Simulation value from OS 1 BO SIM_VAL
Delay for incoming faults 0 I IN_DEL
Delay after dropout 0 I OUT_DEL
Delay between warning and alarm 0 I WARN_DEL
Annunciation repeat time 0 I REP_TIM
Group stopped 0 BO GR_STP
accessory group / route 0 I GR_LINK1
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 151
CEMAT Platform Architecture Guide
The process signal or interlocking condition must be linked to MST0. For NC signals OKS
must have "1-Signal".
In case the override function is enabled, the block reads the signal status from SIM_VAL.
The block icon of the annunciation block shows the following information:
Under normal conditions the symbol is invisible.
The Tagname is highlighted in case of an error (red), warning (yellow), not ready (violet)
A red indication beside the object shows a "B" for bad quality (in case driver blocks are
used)
An orange indication signalized that the override is activated (Simulation mode).
152 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 153
CEMAT Platform Architecture Guide
Faceplate
Function block
The picture below shows the most important interfaces and process parameters of the
process feedback block. More detailed information you will find in the object description of the
block.
ModuleTag
C_PROFB MAIN_TA
_TAS
Process Feedback 1/22
Input signal (HW speed monitor) 0 BO IN_SIG OUT_SIG BO Output signal for drives
Enable software speed monitor 0 BO EN_SSM FT_SIG BO Fault signal
Pulse for software speed monitor 0 BO PULS_SSM
Enable Annunciations 1 BO ENAL
Drive status for process feedback 16#0 W STAT_DRV
On delay for monitoring (start) 10 I ON_DLY
Off delay for monitoring (stop) 15 I OFF_DLY
Enable off delay monitoring 1 BO EN_OFFDM
tolerance value for speed monitor 50 I TOL_SSM
link to group or route 0 I GR_LINK1
154 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Using a Pulse
Receiving a pulse signal, the process signal must be linked to PULS_SSM. In this case
enable EN_SSM must be switched to 1-Signal.
The block icon of the Process Feedback block shows the following information:
Under normal conditions the symbol is invisible.
The Tagname is highlighted in case of an error (red), warning (yellow), not ready (violet)
A red indication beside the object shows a "B" for bad quality (in case driver blocks are
used)
An orange indication signalized that the override is activated (Simulation mode).
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 155
CEMAT Platform Architecture Guide
If no driver block is used: validation check of the read analogue value (QVZ, rated range,
overflow -> live zero)
The module live zero output is set to the 1-signal for an invalid measured value. A
measured value is invalid if the module does not exist (QVZ), or when the read measured
value has overshot or undershot (7FFF or 8000 hexadecimal).
Using driver block CH_AI, certain connections between driver block and measuring value
block are required.
ATTENTION: Using drivers no live zero monitoring is done. One can use the binary signal
QBAD from the driver block.
• The physical value is monitored for limit value violation. All violations are available as
module outputs for the user program.
HH Upper limit 2 leads to a fault message
H Upper limit 1 leads to a warning message
L Lower limit 1 leads to a warning message
LL Lower limit 2 leads to a fault message
SHH Upper switching limit 1 no alarm message
SH Upper switching limit 1 no alarm message
SL Lower switching limit 1 no alarm message
SLL Lower switching limit 2 no alarm message
• If the smoothing function is enabled the smoothing time can be set by the operator.
• If the hysteresis function is enabled, the hysteresis vale in % can be set by the operator.
• If the Spike suppression is enabled, the time can be set by the operator.
• Live zero delay can be set by the operator.
• Two arithmetic operations are possible for and can be enabled for further processing.
XE * XE
s q a r in g
SK E - SKA
r o o t e x t r a c ti o n X E * (S K E - S K A )
• If the gradient monitoring is enabled, the gradient values can be set by the operator. If
the gradient values are exceeded, the corresponding module outputs for the user program
are set to the 1-signal. No message generated by the measure block.
• If the override function is enabled by the Operator Faceplate, the input is not considered
any more. The simulation value is processed. The block icon shows orange color. The
simulation value can be modified from the faceplate.
During sequence-test mode all measure blocks are switched to the simulation mode.
• Through bypass-function the measuring value can be blocked. There are 2 solutions of
the bypass-function.
If the measuring value is bypassed, it can not be switched into simulation mode.
156 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
If an archive exists for the measure the "Curve" button can be used in order to show the
history of the measure.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 157
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the
measure block. More detailed information you will find in the object description of the block.
ModuleTag
C_MEASUR MAIN_TAS
Measured value 1/23
Block measuring channel 0 BO UGWA MV R Measured value
Set MV to scale beginning 0 BO USCB MV_PERC R Measured Value in %
Alarm interlock 1 BO UAMV HH BO Measured value > Upper limit 2
Annunciation release 1 BO UMFR H BO Measured value > Upper limit 1
Release squaring 0 BO REL_SQAR L BO Measured value < Lower limit 1
Release root extraction 0 BO REL_ROOT LL BO Measured value < Lower limit 2
Release smoothing 0 BO REL_SMOO ULZ BO Live Zero
Release gradient monitoring 0 BO REL_GRAD UGN BO Gradient negativ
Release spike suppression 0 BO REL_SPIKE UGP BO Gradient positiv
Upper limit 2 100.0 R VAL_HH USP BO Measured value blocked
Upper limit 1 100.0 R VAL_H SHH BO Measured value > Upper sw. limit 2
Lower limit 1 0 R VAL_L SH BO Measured value > Upper sw. limit 1
Lower limit 2 0 R VAL_LL SL BO Measured value < Lower sw. limit 1
Delay life zero (s) 3 I LZ_TIM SLL BO Measured value < Lower sw. limit 2
Spike suppression (s) 3 I SPIK_TIM
Hysteresis 0.0 R HYSTERES
Gradient positive 0.0 R GRAD_POS
Gradient negative 0.0 R GRAD_NEG
Gradient delay (s) 0 I GRAD_TIM
Smoothing time (s) 0 I SMOO_TIM
Upper switching limit 2 100.0 R VAL_SHH
Upper switching limit 1 100.0 R VAL_SH
Lower switching limit 1 0 R VAL_SL
Lower switching limit 2 0 R VAL_SLL
Scale beginning 0 R SCB
Scale end 100.0 R SCE
Unit %' SN UNIT
Type of imported value 77 I TYP
Input for physical value 0.0 R MV_PHYS
Input from analog input card 16#0 W MV_CARD
accessory group / route 0 I GR_LINK1
Whether the analogue value is read from Physical value or from an Analog input card is
decided by parameter TYP.
TYP = 77: read from Analog Input card via Interface MV_CARD (default)
TYP = 10: read physical value via Interface MV_PHYS
Scale beginning SCB, Scale end SCE and UNIT must be adapted according to the physical
range of the measure. The limit values must be modified accordingly.
The rest of the functions are optional and can be enabled/disabled depending on the
application.
158 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
The block icon of the measuring value block shows the following information:
Color indication shows the status of the measure
Measured value is ok black on grey
Measured value > UL2 white on red
Measured value > UL1 black on yellow
Measured value < LL1 black on yellow
Measured value < LL2 white on red
Measured value faulty (LZ) yellow on black
Gradient overshot white on violet
Measuring channel blocked white on blue
A red indication beside the object shows a "B" for bad quality (in case driver blocks are
used)
An orange indication signalized that the override is activated (Simulation mode).
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 159
CEMAT Platform Architecture Guide
160 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 161
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the
process feedback block. More detailed information you will find in the object description of the
block.
ModuleTag
CTRL_PID 100MS_TASK
PID Controller 1/23
Deadband Width 0.0 R DEADB_W LMN R Manipulated Variable
Proportional Gain 1.0 R GAIN ER R Control Difference (Control Error)
Reset Time (s) 10.0 R TN SP R Active Setpoint
Differential Time (s) 0.0 R TV
Lag Time Constant (s) 1.0 R TN_LAG
LMN Normalizing Range High Limit 100.0 R NM_LMNHR
LMN Normalizing Range Low Limit 0.0 R NM_LMNLR
Process Value (to AUX_PRO4 of Message) 0.0 R PV_IN
PV Normalizing Range High Limit 100.0 R NM_PVHR
PV Normalizing Range Low Limit 0.0 R NM_PVLR
Disturbance Value 0.0 R DISV
Control System Fault; 1 = external error 0 BO CSF
1 = set SP_OP equal PV_IN PV BO SP_TRK_ON
External Setpoint 0.0 R SP_EXT
High Limit for SP_EXT 100.0 R SPEXTHLM
Low Limit for SP_EXT 0.0 R SPEXTLIM
Linkable input to Select SP_EXT 0 BO SPEXON_L
High Limit Value for Manipulated Var. 100.0 R LMN_HLM
Low Limit Value for Manipulated Var. 0.0 R LMN_LIM
External tracking Value 0.0 R LMN_TRK
Select External Tracking Value (1 = Active) 0 BO LMN_SEL
Linkable input for Manual/Auto Mode 0 BO AUT_L
Feedb. of Manipulated Variable for OS 0.0 R LMNR_IN
From the block icon of the controller block you get the following information:
Control mode (M = Manual mode; A = Automatic mode)
Operationg mode (E = External; I = Internal)
Tracking (T = Tracking Setpoint or Tracking Output, dependent on the control mode)
Set Point Value
Process Value
Manipulated Value
162 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Recommendation:
If there is no need for a controller with 3 separate settings use the standard controller block
CTRL_PID because the C_PID3 needs more performance.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 163
CEMAT Platform Architecture Guide
164 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
With mouse click on the module symbol the Faceplate will be
open.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 165
CEMAT Platform Architecture Guide
166 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Diagnosis Dialog
With Mouse click on button „Diagnosis“, a dialog with all Status information and Parameter
values from the Storage instance will be shown. In addition the locked or simulation function
can be switched on or off...
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 167
CEMAT Platform Architecture Guide
168 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 169
CEMAT Platform Architecture Guide
170 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Function block
The picture below shows the most important interfaces and process parameters of the
Storage function block. More detailed information you will find in the object description of the
block.
ModuleTag
C_STORAG MAIN_TAS
Storage 1/23
1=normal, 2=multi, 3=stock pile, 4=tank 1 BO S_TYPE CHA_OUT STRUC CHAMBER OUT
APF data structure in use 0 BO APF_ACT PV_Out STRUC Process Value (Analog Output)
group is completely running 0 BO GROUP_ON PV_Stat STRUC Process Value (STATUS)
Storage locked 0 BO S_LOCK READY BO Storage ready to fill
interlock 1 BO S_INT HH BO overshoot Limit HH
charging is running 0 BO S_CHARG H BO overshoot Limit H
discharging is running 0 BO S_DISC L BO undershoot Limit L
homogenizing is running 0 BO S_HOMOG LL BO undershoot Limit LL
storage is empty 1 BO S_EMPTY SLZ BO Live zero
storage is full 1 BO S_FULL DEDU BO dedusting fault
dedusting is running 0 BO S_DEDU
different material 0 BO S_DIFFM
PV 0 STRUC PV
Value 0 REAL PV.Value
Signal Status 0 BYTE PV.ST
unit 0 STRINGUNIT
simulation value from OS 0 REAL SIM_VAL
HH limit 0 REAL VAL_HH
H limit 0 REAL VAL_H
L limit 0 REAL VAL_L
LL limit 0 REAL VAL_LL
time delay Live Zero 0 INT LZ_TIM
hysteresys 0 REAL HYSTERES
storage height 0 REAL HEIGHT
storage width 0 REAL WIDTH
storage length 0 REAL LENGTH
storage diameter 0 REAL DIAM
storage capacity 0 REAL CAPAC
storage hour to full or empty 0 REAL STORAH
The standard signals of the storage like PV, Unit, Group ON, Interlock, storage full/empty,
dedusting on, etc. have to be linked to the corresponding interfaces .
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 171
CEMAT Platform Architecture Guide
172 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 173
CEMAT Platform Architecture Guide
Faceplate
With mouse click on the module symbol the Faceplate will be open.
174 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
(9) Selected Chamber no., whose parameter and status are shown
(10) Open user faceplate
(11) Open Group Faceplate
(12) Actual level as % , m , Tons
(13) Measurement scale end
(14) Alarm level full
(15) Alarm level full l
(16) Material quantity charging
(17) Maximum amount of Chamber
(18) charged chamber no.
(19) Silo Information as in the Symbol:
- Charging on
- Storage full
- no dedusting
- Storage locked
- no original material
- Homogenization on
- Simulation on
- Storage empty
- discharging on-
(20) Material quantity discharging
(21) Warning level empty
(22) Alarm level empty
(23) Measurement scale begin
(24) Remaining time (h) till the Storage is full or empty.
(25) Close Dialog
(26) Help
(27) Limit Symbols
(28) Filling level Indication as bar
(29) Open Information- Dialog
(30) Open chamber Dialog
(31) Open Diagnosis Dialog
(32) Curve window with the measurement and the two alarm limits
(33) Operating devices of the curve window
(34) Actual charge Material
(35) Assigned Material
(36) Material quality 0 = "ok", 1 = worse "<", 2 = ">" better
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 175
CEMAT Platform Architecture Guide
- Diagnosis Dialog
With Mouse click on button „Diagnosis“, a dialog with all Status information and Parameter
values from the Storage instance will be shown.
176 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 177
CEMAT Platform Architecture Guide
(1) Multi chamber representation into dependence of the input parameter "SC_TYPE"
1 = 5 chamber Silo
2 = 8 chamber Silo
(2) Selection button to show the specific Chamber Information in the symbol and Faceplate.
(3) Actual charging material
(4) Silo Information as in the Symbol:
- charging on
- Storage full
- no dedusting
- Storage locked
- no original material
- Homogenization on
- Simulation on
- Storage empty
- discharging on-
(5) Actual discharging material
(6) Selected Chamber no., which is connected to the Input „AC_CHA_C“.
178 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 179
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the
Storage MA function block. More detailed information you will find in the object description of
the block.
ModuleTag
C_STO_MA MAIN_TAS
Storage 1/23
Visualisation Type 1, Type 2, Type 3; 1 BO SC_TYPE
max. number of chambers 0 BO AM_CHA PV_Out STRUC Process Value (Analog Output)
display chamber 0 BO CHA_DISP PV_Stat STRUC Process Value (STATUS)
actual charging chamber 0 BO AC_CHA_C HH BO overshoot Limit HH
actual discharging chamber 1 BO AC_CHA_D H BO overshoot Limit H
CHAMPER 1 0 BO CHA_I_1 L BO undershoot Limit L
CHAMPER 2 0 BO CHA_I_2 LL BO undershoot Limit LL
CHAMPER 3 0 BO CHA_I_3 SLZ BO Live zero
CHAMPER 4 1 BO CHA_I_4 DEDU BO dedusting fault
CHAMPER 5 1 BO CHA_I_5
CHAMPER 6 0 BO CHA_I_6
CHAMPER 7 0 BO CHA_I_7
CHAMPER 8 0 STRUC CHA_I_8
CHAMPER 9 0 REAL CHA_I_9
CHAMPER 10 0 BYTE CHA_I_10
The standard signals of the storage like PV, Unit, Group ON, Interlock, storage full/empty,
dedusting on, etc. have to be linked to the corresponding interfaces .
180 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 181
CEMAT Platform Architecture Guide
182 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 183
CEMAT Platform Architecture Guide
(10) The time response of the exit speed is defined the 6 areas in these. The active one Area
is green highlighted. This one becomes the height of the areas about the separate X values
"Speed" charged to definition and the polygon 1
184 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Parameter- Dialog
With mouse click on button "parameter" the following dialog will be open. All parameter values
can be modified. In addition it is possible to store or read the Parameter from a database.
These write and also the read operation is only possible with the user right “21” and Input
"Release" = "0", i.e. no Output values are calculated.
(9) Number of
interpolation points
defined in the CFC on
the X axis.
(10) Interpolation points of the 3 Y axes
(11) Speed Area active
(12) X values for speed Output (only ascending from 0 till max. possible)
(13) Maximum X value
(14) Run period of the auxiliary drive in seconds
(15) Stop period of the auxiliary drive in seconds
(16) Maximum speed per min
(17) Ramp calculation of base X to Y.
(18) Use main drive
(19) Close Dialog
(20) Speed set points in rpm
(21) Output "speed active" is shown green for the duration of the running time
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 185
CEMAT Platform Architecture Guide
186 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Storage- Dialog
This dialog shows only the individual parameters of the stored data sets (1). Editing is not
possible.
The individual data sets of the stored Module parameters can be read and displayed from the
user archives. Use the button set (2).
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 187
CEMAT Platform Architecture Guide
Operation/Alarm- Dialog
This dialog shows the Operator annunciations. Alarms are not caused.
188 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Curve- Dialog
This dialog shows the 4 Output values (Out1, Out2, Out3, speed) and the actual curve values,
if there is a definition for this Poly3 object in the curve archives.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 189
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the
Polygon3 function block. More detailed information you will find in the object description of the
block.
ModuleTag
C_POLY3 MAIN_TAS
Polygon 1/23
Number of interp. points 2>= Num <= 2 INT Num IN_I STRUC internal time
Release Polygon is active 0 BOOL Release Out1 STRUC Output Polygon1
Input 0 STRUC IN Out2 STRUC Output Polygon2
Value 0 REAL IN.Value Out3 STRUC Output Polygon3
Signal Status 0 BYTE IN.ST Speed STRUC Output Speed
Feedback Out 1 0 STRUC FB_Out1 Speed_ON STRUC Bool Signal Speed ON
Value 0 REAL FB_Out1.Value MD_ON STRUC Bool Signal Main drive ON
Signal Status 0 BYTE FB_Out1.ST Speed_No INT Speed area number
Feedback Out 2 0 STRUC FB_Out2 X_active BO IN is between X1 and XNum
Value 0 REAL FB_Out2.Value Complete BO Complete IN reached XNum
Signal Status 0 BYTE FB_Out2.ST
Feedback Out 3 0 STRUC FB_Out3
Value 0 REAL FB_Out3.Value
Signal Status 0 BYTE FB_Out3.ST
Feedback Speed 0 STRUC FB_Speed
Value 0 REAL FB_Speed.Value
Signal Status 0 BYTE FB_Speed.ST
IN_UNIT 0 INT IN_UNIT
Out1_UNIT 0 INT Out1_UNIT
Out2_UNIT 0 INT Out2_UNIT
Out3_UNIT 0 INT Out3_UNIT
X value 1 0 REAL X1
Interpolation point 1_1 0 REAL Y1_1
Interpolation point 1_2 0 REAL Y1_2
Interpolation point 1_3 0 REAL Y1_3
The standard signals of the storage like PV, Unit, Group ON, Interlock, storage full/empty,
dedusting on, etc. have to be linked to the corresponding interfaces .
190 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 191
CEMAT Platform Architecture Guide
Faceplate
Function block
The picture below shows the most important interfaces and process parameters of the
Runtime block. More detailed information you will find in the object description of the block.
ModuleTag
C_RUNNT MAIN_TAS
Running Time 1/23
Input signal 0 BO RTLS
Release for counting seconds 1 BO REL_RT
The block icon of the Runtime block shows the following information:
Runtime in hours
192 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 193
CEMAT Platform Architecture Guide
Function block
The picture below shows the most important interfaces and process parameters of the
Counter block. More detailed information you will find in the object description of the block.
ModuleTag
C_COUNT 100MS__TAS
Counter 1/23
Input for pulse signal P CNZS
Release for counting pulses 1 BO REL_PULS
selection pulse/value 0 BO MODE_V
New value overwrites the old one 0 BO NEW_VAL
Value (allready counted pulses) A VAL_CNT
Value of one Pulse 1.0 R PULS_VAL
Unit %' SN UNIT
The block icon of the Counter block shows the following information:
Counter value and unit
194 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Faceplate
The block has no operator interface.
Function block
The picture below shows the most important interfaces and process parameters of the
Adapter block. More detailed information you will find in the object description of the block.
ModuleTag
C_ADAPT MAIN_TAS
Adapter 1/23
Static fault signal 0 P FAULT
Fault not acknowledged 0 BO FT_NACK
Fault interlock to the group 0 BO AMZS
Link to the group 0 I GR_LINK1
Static fault and non-acknowledged fault are transmitted to the block via interfaces FAULT and
FT_NACK.
The Adapter block is linked to the group and passes this information (fault/no fault) to the
group.
Further information, such as drive running and type off fault must be provided in a
configuration file which has to be created for the non-CEMAT function block.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 195
CEMAT Platform Architecture Guide
B Appendix B
General notes
* All documentation will be in English
2 Project control
Monthly progress report x
Monthly progress claim x
3 Shipping
Preliminary shipping weights & x
dimensions
Packing list x
4 Client data
P&ID's x
Symbols & nomenclature standards x
Process control description, sequence / x
logic function description
Emergency & Shutdown cause & effect x
196 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
charts
Instrument Index x
I/O data file (MS Excel format - includes x
Tag No, I/O type, range, alarm limits, history
archive requirement, trend view requirement
- SIEMENS DATA FORMAT PREFERRED)
Electrical equipment interface drawings x
(MCC control diagrams etc)
Typical instrument loop drawings x
Interface specifications for 3rd party
equipment & systems -as listed
(System 1)
5 System Engineering
System architecture drawing x
I/O Rack / slot allocation & network x
address list
I/O card assignment & address list x
System loading calculation x
System bill of materials x
7 Hardware Design
Console layout drawings
Console wiring diagrams
Auxiliary console layout drawings
Auxiliary console wiring diagrams
Control room layout x
System, I/O, marshalling, interposing x
relay cabinet layouts
System, I/O, marshalling, interposing x
relay cabinet wiring diagrams
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 197
CEMAT Platform Architecture Guide
8 Testing
FAT procedure x
FAT report x
SAT procedure x
SAT report x
9 Final documentation
Standard hardware, operation & x
maintenance manuals
Standard system self documentation (I/O x
schedule, SFC / CFC charts etc)
System operating manual x
Hardware design documents x
Legend
w = weeks
after award
m = months
after award
<F = before
FAT
<S = before
SAT
198 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
C Appendix C
Step 4 -> Open the CEMAT V8 Configuration Excel Tool and move to the page
“Configuration”
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 199
CEMAT Platform Architecture Guide
Configuration Input
200 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Step 6 -> Open “License & AS Hardware” Page and select “HOLCIM 004”
then copy over the Values from Step 3 and give additional values if it is necessary.
At the end press “Calculate Server and ES License” and then “Return”.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 201
CEMAT Platform Architecture Guide
Step 7 -> Open Page “I/O System” and adjust the Settings.
If you want to use an other I/O module please change the code in column “D” or “K“
202 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Step 8-> Open Page “Communication” and write the values for switches and cable
depending your configuration.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 203
CEMAT Platform Architecture Guide
Step 9 -> Open Page “Engineering expanses” and adjust the values in all fields with gray
background.
204 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 205
CEMAT Platform Architecture Guide
Step 10 -> Open Page “Training” and adjust the values in all fields with gray background.
206 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Step 11 -> Open Page “Clock/Firewall” and adjust the values if necessary.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 207
CEMAT Platform Architecture Guide
Step 12 -> Open Page “UPS” and adjust the values if necessary.
208 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Step 13 -> Open Page “Cabinets” and adjust the values if necessary.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 209
CEMAT Platform Architecture Guide
Step 14 -> Open Page “Test&Simulation Station” and adjust the values if necessary.
210 Version/ Date V1.6/ 2012-10-15 Copyright © Siemens AG. All Rights Reserved.
Platform Architecture Guide CEMAT
Step 15 -> Press “create material list” and the list will be created for each of the Stations.
Copyright © Siemens AG. All Rights Reserved Version/ Date V1.6/ 2012-10-15 211