Sie sind auf Seite 1von 85

ONLINEPRACTICALSITEMANAGEMENTGUIDE

(e-PSMG)
CAWANGAN KEJURUTERAAN ELEKTRIK
ONLINE PRACTICAL SITE MANAGEMENT GUIDE
(e-PSMG)
Mission
 To equip site supervisory team with knowledge and tools to deliver
quality construction products by-
 Providing basic construction knowledge and tools that are
accessible online 24 x 7, comprising but not limited to-
o Specifications and Standards
o Manuals and guidelines
o Lessons Learned (Dos and Don’ts)
o Best Practices
 Establishing an online discussion forum to be moderated by SMEs

Expected Benefits
The E-PSMG is expected to bring the following benefits to the
department:

 It will help ensure quality and standards of supervision work are


maintained regardless of the nature and different levels of
complexities of the projects;
 It will improve productivity and efficiency;
 It will help nurture and develop human capital;
 It will help foster closer cooperation between different disciplines
and enable the creation of cross functional knowledge clusters;
 It will enable more effective utilisation of resources;
 It will promote long life learning and provide support to the
creation of new knowledge

2
ELECTRICAL SERVICES

SISTEM PEMASANGAN VOLTAN RENDAH (LOW VOLTAGE


INSTALLATION SYSTEM)

1. DB/SSB/MSB

 Kemasukan single core cable


 Mounting of wall mounted type Switchboard
 Mounting Height For Distribution Board
 Penggunaan Cable Lug dan Cable Sleeve bagi Pendawaian di dalam Papan
Suis / Papan Agihan

2. Switchboard equipment

 Copper Busbar - Arrangement & Phase Color Indicator


 Air Circuit Breaker (ACB)
 Current Transformer
 Moulded Case Circuit Breaker (MCCB) - Marking & External Accessories
 Surge Protection Devices (SPD)

3. Busduct
4. Sytems of Wiring

 No 'tee'/ 'loop-in-system'
 No reduction of strands-minimum 7 strands

5. Conduit wiring

 Pemasangan konduit GI jenis permukaan


 Pemasangan konduit GI jenis terbenam
 Pemasangan Boxes
 Accessories (Inspection elbow,Bracket,saddle, Tee)
 S/S/O including Switches & switch plate

6. Trunking

 Ceiling

7. Cable

 Underground cable
3
8. Cable Tray

 Pemasangan Cabble Tray (Thickness & Suspension system)


 Fire barrier

9. Cable Ladder

10. Luminaires installation

 Incandescent luminaires
 Spacer
 Suspension system (Ketebalan Galvanised Steel Wire yang digunakan)
 Termination of flexible conduit at fitting

11. Ceiling fans


12. Earthing
13. Bilik Riser
14. Lightning Protection & Earthing

 Installation of air termination system


 Installation of down conductor system
 Installation of earth termination system

15. Genset

 Susun Atur Bilik Janakuasa Tunggusedia


 Pemasangan Kabel Janakuasa Tunggusedia
 Pemasangan Sistem Pembumian Janakuasa Tunggu Sedia

16. Pengujian Litar Akhir

 Ujian Kefungsian RCCB

17. Pemasangan Gantungan Ceiling Speaker

4
DB/SSB/MSB

5
1.1 Kemasukan single core cable

Butiran Kerja

 Objektif : Kemasukan single core cable pada papan suis perlu


menggunakan plate of a non-ferrous material
 Keterangan : Untuk memastikan fenomena eddy current dan
hysterisis tidak berlaku
 Peralatan penyeliaan : T/B

Ilustrasi Gambar-gambar pemasangan

1.2 Mounting of wall mounted type Switchboard

Butiran Kerja

 Objektif - Pemasangan U atau C channel bagi memastikan wujud


ruang pengudaraan antara papan suis dan dinding.
 Keterangan - Perlu dipasang bagi papan suis jenis wall mounted
dan Papan Agihan
 Peralatan penyeliaan T/B

Ilustrasi

6
Metodologi
Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber


rujukan).

 Berpandukan kepada amalan kejuruteraan terbaik


 Borang JKR.PK(O).04-SKE.4C (Pin. 1/2009) - BORANG
PEMERIKSAAN PEMASANGAN PSU/PSK/FEEDER PILLAR

Gambar-gambar pemasangan

 The front cover of the switchboard shall be provided with grummets and
dust seal to exclude dust and dirt.
7
 Serrated star washers shall be fitted to ensure satisfactory earthing of the
front cover.

1.3 Mounting Height Bagi Papan Suis Agihan

Butiran Kerja

 Objektif : Ketinggian papan yang perlu dipasang bagi


memudahkan kerja-kerja penyenggaraan
 Keterangan :

⇒Ketinggian pada 1450mm apabila papan agihan berada di


dalam bilik suis

⇒Ketinggian pada 2050mm apabila papan agihan berada di


luar bilik suis

 Peralatan penyeliaan : Pita pengukur

Ilustrasi

Metodologi

 Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber


rujukan).

8
 L-S1; Section 9.10: Mounting heights list below shall be measured
from the underside of the fitting to the finished floor level. Unless
otherwise specified or directed on site by the S.O.’s
Representative, heights of fixing shall be as follows:-
Distribution boards (in service duct)……………………………..1450mm
Distribution boards (other than in service duct)……………….2050mm

 Borang JKR.PK(O).04-SKE.4D (Pin. 1/2009) - BORANG


PEMERIKSAAN PEMASANGAN PAPAN AGIHAN

Gambar-gambar pemasangan

1.4 Penggunaan Cable Lug dan Cable Sleeve bagi Pendawaian di


dalam Papan Suis / Papan Agihan

Butiran Kerja

 Objektif : Pengunaan kod warna bagi setiap kabel yang


digunakan untuk penyambungan dari busbar ke switchgears
 Keterangan :

1. Untuk mengenalpasti konduktor fasa dan konduktor neutral


setiap kabel yang digunakan untuk penyambungan dari busbar ke
switchgears
2. Setiap tamatan kabel perlu menggunakan cable lug untuk
tamatan yang lebih sempurna

9
 Peralatan penyeliaan : T/B

Rujukan

 L-S1; Section 2.3: Connections from busbars to the switchgears


shall be affected by means of copper conductors securely
clamped to the busbars and colour coded to identify the phase
and neutral conductors. Copper conductor either bare tinned
busbars or insulated cable shall be rated in accordance with the
current rating of the switchgear. Neutral conductor shall be of full
size as phase conductor. Coloured cable sleeve shall be shrouded
for cable end termination.

10
 [Borang JKR.PK(O).04-SKE.4D] - BORANG PEMERIKSAAN
PEMASANGAN PAPAN AGIHAN

Gambar-gambar pemasangan

11
Switchboard

12
2.1 Copper Busbar - Arrangement & Phase Color Indicator

Butiran Kerja

 Objektif : Kaedah susun atur busbar (horizontal & vertical) dan


pengunaan kod warna bagi setiap busbar dalam switchboard.
 Susun atur busbar mengikut turutan fasa di dalamKeterangan :
MSB
Semua busbar hendaklah ditanda menggunakan cat
mengikut warna fasa berkaitan.
 Peralatan penyeliaan : Tidak Berkenaan

Ilustrasi

Rujukan

 L-S1; Section 2.3: The main busbar shall be arranged in a


horizontal plane in the order red-yellow-blue-neutral from back to
front. On each panel connections should be red-yellow-blue-
neutral. Busbars shall be painted at appropriate points with
colours red, yellow, blue and black to denote the phases.

13
 Borang JKR.PK(O).04-SKE.4C (Pin. 1/2009) - BORANG
PEMERIKSAAN PEMASANGAN PSU/PSK/FEEDER PILLAR

2.2 Air Circuit Breaker (ACB)

Butiran Kerja

 Objektif : Visual inspection –marking on the ACB


 Keterangan : Memeriksa marking yang perlu ada pada ACB
 Peralatan penyeliaan : Tidak Berkenaan

Ilustasi dan Gambar Pemasangan

14
Methodologi

 Pemeriksaan secara visual dijalankan dengan memastikan setiap


pelabelan terdapat pada ACB yang dipasang

Rujukan

 L-S1; Section 4.1 : They shall be three or four poles type as


specified and shall comply fully with IEC 60947-1 and 60947-2.
They shall be ASTA or KEMA certified for minimum rupturing
capacity of 50 kA at 415 V for 1 s or
otherwise specified.
 Borang JKR.PK(O).04-SKE.4C (Pin. 1/2009) - BORANG
PEMERIKSAAN PEMASANGAN PSU/PSK/FEEDER PILLAR

2.3 CT Transformer

Butiran Kerja

 Objektif : Memastikan pengunaan jenis CT yang sesuai untuk


pengukuran/pelindungan
 CT untuk pengukuran – class 1, VA ≥ 15VACT
untukKeterangan : pelindungan
CT untuk pelindungan – class 10P10, VA ≥ 15VACT
 Peralatan penyeliaan : Tidak Berkenaan

Methodologi

Tiada

Rujukan

 L-S1; Section 6.2</u : ..They shall be adequately rated in VA to


carry the summation of all VA burdens of the
connected loads but in any case, the rating shall not be less than 15VA. Unless
otherwise specified, current transformers used for measuring andmetering shall be

15
of Class 1.0 accuracy and those used for protection shall be of Class 10P10
accuracy.

 Borang JKR.PK(O).04-SKE.4C (Pin. 1/2009) - BORANG


PEMERIKSAAN PEMASANGAN PSU/PSK/FEEDER PILLAR

Gambar-gambar Pemasangan

16
2.4Moulded Case Circuit Breaker (MCCB) - Marking & External

Butiran Kerja

 Objektif : 1. Mengenal pasti penandaan (marking) yang perlu ada


pada MCCB.
2. Keperluan pemasangan External Accessories untuk
MCCB
 Penandaan pada MCCB dibuat dengan jelas dan
tahanKeterangan : lasak.
External Accessories ; Insulation barrier and external
operating handle with padlocking facilities untuk MCCB yang perlu
dipasang mengikut keperluan.
 Peralatan penyeliaan : Tidak Berkenaan

Ilustrasi

Methodologi

 PENANDAAN MCCB :

Maklumat Yang Perlu Ada Pada Label mengikut Standard IEC 60947-2 clause 5
17
(a) The following data shall be marked on the circuit-breaker itself or on a name
plate or nameplates attached to the circuit-breaker, and located in a place such that
they are visible and legible when the circuit-breaker is installed.

Contoh marking :

(b) Marking on equipment not needed to be visible after mounting :

18
Rujukan

 L-S1; Section 4.2 : Panel mounting external operating handle with


padlocking facilities and door interlocking facilities to prevent the panel
door from being opened to access to the mccb in closed position shall be
provided.

 External Accessories :-

Insulation Barrier : The insulation barrier prevents accidental contacts and flash-
over between each phase and is highly recommended for the breakers especially
during installation of a switchboard.

 Borang JKR.PK(O).04-SKE.4C (Pin. 1/2009) - BORANG PEMERIKSAAN


PEMASANGAN PSU/PSK/FEEDER PILLAR

Gambar-gambar Pemasangan

19
2.5. Surge Protection Devices (SPD)

Butiran Kerja

 Objektif : Memastikan keperluan peralatan bagi pemasangan SPD dalam


switchboard
 Pemutus litar hendaklah dari jenis 4P MCCB atau Fuse l/dKeterangan :
neutral link
Compartment khas l/d tanda amaran
Kabel bumi ke MEB ≤ 1000mm
 Peralatan penyeliaan : Tidak Berkenaan

Ilustrasi dan Gambar Pemasangan

Rujukan

20
 L-S1; Section 7.0: The connecting leads shall be as short as
possible and not more than 1000 mm in length, and shall be
tightly bound together over throughout the whole length. Unless
otherwise specified, four-pole moulded case circuit breaker or
fuses of rating as recommended by the SPD manufacturer shall be
provided to enable full isolation of SPD from the system for
maintenance.
 Borang JKR.PK(O).04-SKE.4C (Pin. 1/2009) - BORANG
PEMERIKSAAN PEMASANGAN PSU/PSK/FEEDER PILLAR
 Classification of SPDs

21
Busduct

22
3.1 Busduct

Butiran Kerja

 Objektif - Memastikan pemasangan bus duct (Busbar Trunking) adalah


mengikut spesifikasi yang telah ditetapkan
 Keterangan - Perlu dipasang copper tape bersaiz 25mm X 3mm di luar
busduct

- Perlu guna hanger untuk mounting Bus duct hendaklah disokong


dengan jarak 3 meter untuk pemasangan menegak dan 1.5 meter untuk
pemasangan mendatar.

 Peralatan penyeliaan T/B

Ilustrasi

23
Metodologi
Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan).

LS 1- (8.1) Pre-Assembled, Totally Enclosed Type (Bus Duct System) :

1. Housing - galvanised sheet steel ≥ 1.5 mm thickness


2. IP 42 for indoor installation
3. IP 65 for outdoor installation
4. Current density of ≤ 1.5A/sq.mm
5. 25mm x 3mm earth continuity fitted to the external bus duct

Gambar-gambar pemasangan

24
System of Wiring

25
4.1 System of Wiring

Butiran Kerja

 Objektif - Memastikan pendawaian soket alur keluar dipasang secara Litar


Gelang (Ring Circuit atau Litar Jejari (Radial circuit)dan tiada pemasangan
tee or spur pada pendawaian
asal.
 Keterangan - Jenis pendawaian:
1. Ring Circuit (Maksimum luas lantai 100m persegi)
- Alat pemanas,pemanas air takungan lebih 15 liter dan
pemanas immersion tidak boleh disambung pada Ring Circuit
2. Radial circuit(Maksimum luas lantai 50m persegi)
 Peralatan penyeliaan T/B

Ilustrasi

26
Metodologi

Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan).

LS-1 Specification of Low Voltage Internal Electrical Installation

9.0: System of Wiring

 Comply with MS IEC 60364-5-52


 Wiring shall be on the ‘loop-in system’ and no ‘tee’ or joints are allowed
 Standard colour coded cable shall be used for 3 Ø circuit

9.1 Surface Wiring

 PVC/PVC cable of 300/500 V grade to MS 136 & 600/1000 V grade to MS


274
 The insulation shall be suitable for continuous operation at a max. cable
temp. of 70° C

9.2 : Concealed Wiring

 Cables used are similar to surface wiring


 Cables shall be concealed behind the plaster of walls & ceiling slab

9.3 : Conduit Wiring (Surface and Concealed)

 PVC insulated cable of 450/750 V grade to MS 136


 The insulation shall be suitable for continuous operation at a max. cable
temp. of 70° C

27
Conduit wiring

28
5.1 Pemasangan konduit GI jenis permukaan

Butiran Kerja

 Objektif : Memastikan pemasangan konduit GI mematuhi LS-1


 Keterangan : Cara pemasangan konduit GI jenis permukaan termasuk jarak
pemasangan saddles
 Peralatan Penyeliaan : Pita pengukur

Ilustrasi

Metodologi

1. Pelana besi atau `steel saddle' perlu dipasang pada jarak


setiap750mm.'Manakala dalam had jarak 300mm daripada setiap outlet
box, junction box dan device box.
2. Pemasangan konduit mestilah kemas dan teratur.
3. Laluan konduit mestilah selari dengan dinding dan tiang serta selaras (co-
ordinated) dengan servis lain.

29
Rujukan

 L-S1 Section 9.3 : Conduit Wiring (Surface and Concealed)

1. PVC insulated cable of 450/750 V grade to MS 136


2. The insulation shall be suitable for continuous operation at a max. cable
temp. of 70° C
3. Multi strand conductors with minimum seven (7) strands shall be used

 Borang JKR.PK(O).04-SKE.4A (Pin. 1/2005) - BORANG PEMERIKSAAN


PEMASANGAN/PENDAWAIAN KONDUIT/TRUNKING

5.2 Pemasangan konduit GI jenis terbenam

Butiran Kerja

 Objektif : Memastikan pemasangan konduit GI terbenam dalam dinding


mematuhi spesifikasi L-S1
 Keterangan :

1. Cara pemasangan konduit GI jenis terbenam dalam dinding lengkap


dengan cara lekat konduit ke dinding batu-bata.

2. Konduit GI jenis terbenam dalam tiang (column) dengan ikatan ke


'steel bar'.

 Peralatan Penyeliaan : Pita Pengukur

Metodologi

1. Konduit mestilah dilekatkan ke dinding bata dengan menggunakan paku


sebgai penyokong.
2. Bagi pemasangan konduit jenis terbenam dalam tiang, konduit mesti diikat
dengan dawai ke steel bar sebelum kerja-kerja konduit dilaksanakan.
3. Ruang dalam back box perlu diisi dengan foam' atau suratkhabar basah
sehinggaformwork' ditukar.

30
Rujukan

 L-S1 : Section 9.3


 Borang JKR.PK(O).04-SKE.4A (Pin. 1/2005) - BORANG PEMERIKSAAN
PEMASANGAN/PENDAWAIAN KONDUIT/TRUNKING

5.3 Pemasangan Boxes

Butiran Kerja

 Objektif : Memastikan pemasangan 'Boxes' mematuhi spesifikasi L-S1


 Keterangan : Cara pemasangan konduit masuk ke 'boxes' untuk suis dan
S/S/O
 Peralatan Penyeliaan : Callipher

Rujukan

 L-S1 Section 10.3 : Boxes For Switches, Switched Socket Outlets And Socket
Outlets

1. Comply with MS 589 and/or MS 616


2. Galvanised sheet steel with minimum thickness of 0.8mm
3. Brass screw earth terminal

31
Gambar-gambar Pemasangan

Surface Backbox (metal clad type) Conceal Backbox (galvanize sheet steel)

5.5 Accessories (Inspection elbow,Bracket,saddle, Tee)


From E-PSMG

Butiran Kerja

 Objektif : Memastikan ’accessories’ yang digunakan dalam sistem


pemasangan elektrik mengikut spesifikasi yang telah diluluskan oleh E-MAL.
 Keterangan : Perlu dipasang menggikut pepasangan yang dijalankan
 Peralatan penyeliaan : Tidak Berkenaan
Ilustrasi

32
Metodologi

 Sila rujuk Ilustrasi

Rujukan

 L-S1. Clause 10 : Wiring Accessories

Gambar-gambar pemasangan

33
5.5 S/S/O

Butiran Kerja

 Objektif : Memastikan pemasangan s/s/o di tapak bina


dilaksanakan dengan betul dan mengikut spesifikasi
 Keterangan : Perlu dipasang mengikut spesifikasi yang telah ditetapkan oleh
JKR
 Peralatan penyeliaan : Pita ukur,soket tester, test pen

Ilustrasi

34
Metodologi

 Sila rujuk Ilustrasi

Rujukan

L-S1: CLAUSE 10.3 BOXES FOR SWITCHES, SWITCHED SOCKET


OUTLETS AND SOCKET OUTLETS
Unless otherwise specified, boxes used for mounting switch plates,
switched socket outlet and socket outlets in concealed wiring, concealed
conduit wiring and surface metal conduit wiring shall be metalclad type
made of galvanised steel sheet, minimum 0.8 mm thick. Earth terminal
complete with brass screw shall be provided. Cable for bonding the box
to switch, switched socket outlet and socket outlet shall be the same size
as the circuit protective conductor. For surface wiring, with or without
rigid high impact PVC conduit or casing, moulded type boxes shall be
used
Generally the boxes shall comply with MS 589 and/or MS 616. Switch
plates, switched socket-outlet and socket-outlets shall be fixed to the
boxes by means of original flat base chrome screws.

Gambar-gambar Pemasangan

35
Trunking

36
6.1 Ceiling Trunking

Butiran Kerja

 Objektif : Pemasangan trunking mengikut spesifikasi yang ditetap kan oleh


JKR
 Keterangan : Perlu dipasang dengan kemas dan mengikut spesifikasi LS-1
 Peralatan penyeliaan : Pita penggukur, clipper

Ilustrasi

37
Metodologi

 Sila rujuk Ilustrasi

Rujukan

 Cable trunkings shall comply with IEC 61084. They shall be fabricated from
galvanised sheet steel and finished with two coats of standard orange
enamel. They shall be equipped with removable covers at suitable intervals.
They shall be supplied in lengths to suit the installation and shall have the
following minimum wall thickness: -( LS-1)

 Borang JKR.PK(O).04-SKE.4A (Pin. 1/2005) - BORANG PEMERIKSAAN


PEMASANGAN/PENDAWAIAN KONDUIT/TRUNKING

38
Gambar-gambar Pemasangan

39
Cable

40
7.1 Underground cable

Butiran Kerja

 Objektif :

⇒Memastikan pemasangan kabel bawah tanah mematuhi spesifikasi L-S3.


⇒Memastikan tiada kerosakan kepada kabel semasa kerja pemasangan.
⇒Mencegah kerosakan kabel bawah tanah yang berpunca dari kerja
pengorekan.

 Keterangan :

⇒Pegawai Penguasa (P.P) atau Wakil P.P perlu menjalankan standing


supervision bagi kerja ini. Pemasangan kabel bawah tanah tidak boleh dilakukan
tanpa kehadiran S.O. atau wakil S.O.

⇒Selepas kerja menanam kabel selesai, ujian perlu dilaksanakan bagi


memastikan kabel berada dalam keadaan baik. Ujian-ujian terdiri daripada ujian
keterusan, ujian fasa (phasing out) dan ujian penebatan di antara konduktor dengan
konduktor dan perisai menggunakan alat penguji penebatan dengan nilai 500V dc.

 Peralatan penyeliaan Pita ukur : untuk mengukur kedalaman lurang laluan


kabel.
 Alat-alat bagi pengujian penebatan, keterusan dan phasing.

Ilustrasi

41
42
Rujukan

 L-S3;Section 5.0:

Unless otherwise specified, cable trenches shali be 750mm deep. The


trenches shall be of sufficient width to enable provision of adequate spacing
betwee
cables but in any case shall not be less than 450 mm wide.

 L-S3:Section 8.1 :

The bottom of the trench sholl be covered with a layer of 75 mm of


clean sand. The cables shall then be laid on this bedding in an orderlv manner
without
overlapping and crossing each other.

 L-S3;Section 8.0 :

The minimum internal bending radius of the cable shall be not less than
12 times the overall diameter of the cable.

 L-S3;Section 8.0 :

For groups of more than one cables laid in the same trench, they shall
be spaced by the horizontal clearance between adjacent cables of at least twice the
overall diameter of the adjacent largest size cables. Unless otherwise permitted by
the
S.O.'s Representative no cable shall be laid and covered UD in the absence of the
S.O.'s

 Borang JKR.PK(O).04-SKE.3A (Pin. 1/2009) - BORANG PEMERIKSAAN KABEL


BAWAH TANAH

43
Cable Tray

44
8.1 Pemasangan cable tray
From E-PSMG

Butiran Kerja

 Objektif : Memastikan Pemasangan Mengikut Spesifikasi Yang Ditetapkan


seperti di dalam spesifikasi L-S1
 Keterangan : Pemasangan ‘Cable Tray’ dan aksesori yang mengikut
spesifikasi yang telah ditetapkan.
 Peralatan penyeliaan : Alat ‘Caliper’ digunakan untuk mengukur ketebalan
sesuatu ’Cable Tray’ .

Kaedah Pemasangan.

1. Pemasangan ‘Perforated Cable Tray dan aksesori’ pada permukaan dinding


hendaklah dipasang menggunakan ’ arm bracket’ pada jarak 600mm.
2. Pemasangan ‘Perforated Cable Tray’ secara tergantung juga perlu
menggunakan ‘Hanger’ pada jarak 600mm.
3. Ikatan kabel pada ‘Perforated Cable Tray’ perlu menggunakan ‘Fixing Clip and
cleats ’ bersama ‘Bolts’, ‘Washers’ dan ‘ Nuts’.
4. Ketebalan ’ Perforated Cable Tray’ jenis Galvanised:-

Lebar (mm) Ketebalan (mm)

≤300 mm 1.5 mm

> 300 mm 2.0 mm

Sekiranya ’Perforated Cable Tray’ jenis Hot dipped Galvanised digunakan


ketebalan yang ditetapkan ialah 2.5mm tanpa mengira lebar perforated cable tray.
5. ’Hanger’ dan ’Bracket’ yang digunakan perlulah menggunakan bahan yang
sama dengan jenis ’perforated Cable Tray’.
6. Copper Tape bersaiz 25mm x 3mm dipasang di atas ’Cable tray’ sepanjang
’Cable Tray’ tersebut.
7. Setiap laluan yang menembusi dinding atau lantai perlu diadakan penghadang
rintangan api dengan ketahanan 2 jam.

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan).

 LS 1- (9.7) Cable Trays


45
Gambar-gambar Pemasangan

 Copper tape sebagai kaedah konduktor pembumian

 Kabel diikat dengan menggunakan fixing cleats bersama bolt washer dan
nut.

8.2 Fire barrier

Butiran Kerja

 Objektif : Pemasangan fire barrier bagi mengelakkan kebakaran merebak ke


bilik atau tingkat yang lain.
 Keterangan ⇒Perlu dipasang sekiranya trunking @ ducting melalui dinding
atau slab.
⇒Bagi trunking yang melebihi 25 x 25 mm dan konduit yang saiz melebihi
32mm sahaja.
 Peralatan penyeliaan : T/B
46
Ilustrasi

 Ilustrasi 1 Ilustrasi 2

Metodologi

 Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan).

L-S1; Section 9.6 :

 Wherever the trunkin passes through a floor or a fire resistant wall, fire
resistant barrier shall be provided.
 All joint shall be bridged by ≥ 25mm x 3 mm tinned copper tap

Shall comply with IEC 61084 :

 Galvanised sheet steel with two coated of standard orange enamel

UBBL (Uniform Building by Laws) : 161(4)

Gambar-gambar pemasangan

 Pemasangan Fire Barrier di tapak bina

47
Cable ladder

48
9.1 Cable ladder

Butiran Kerja

 Objektif : Memastikan Pemasangan Mengikut Spesifikasi Yang Ditetapkan.


 Keterangan : Setiap aksesori tambahan pada pemasangan perlulah dari
jenis yang sama iaitu dari jenis ‘Hot Dipped Galvanised-HD’
 Peralatan penyeliaan : T/B

Ilustrasi

 Model 'Cable-Ladder'

Metodologi

 Kaedah Pemasangan – Cara menegak pada dinding ( width - 300mm)

1. Anak tangga atau “Rung’ hendaklah dipasang pada jarak 300mm.


2. Penambatan kabel perlu menggunakan ‘Cable Clamp’ atau ‘fixing clip’
bersama bolts, washers dan spring nuts . Penggunaan ‘cable tie’ adalah
dilarang.
3. Arm atau bracket cable ladder perlu dipasang pada jarak 600mm setiap
satu.
4. Dua atau lebih kabel yang dipasang di atas cable ladder perlulah dipasang
dalam keadaan selari. Jarak minimum antara satu kabel adalah separuh
daripada saiz keseluruhan setiap kabel (Rujuk Jadual 4A-Schedule of
installation Methods Of Cables).
5. Setiap laluan yang menembusi dinding atau lantai perlu diadakan
penghadang rintangan api(fire resisting barrier).
6. Perlu dipasang coper tape sebagai cpc di atas cable ladder.

49
Rujukan

Gambar-gambar pemasangan

50
Luminaires installation

51
10.1 Spacer For Luminaires

Butiran Kerja

 Objektif : Pemasangan Spacer perlu bagi memastikan wujud ruang


pengudaraan antara lampu dan siling mudah terbakar
 Keterangan : Perlu dipasang pada lampu jenis lekapan siling dan Ketebalan
Spacer – 10mm
 Peralatan penyeliaan : T/B

Ilustrasi

Metodologi

 Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan)

 L-S1 : Section 11.4 : Where fluorescent luminaires are to be surface


mounted on the underside of the softboard or other type of ceilings which
is combustible, suitable spacers shall be inserted between the base of the
luminaires and the ceiling such that a minimum clearance of 10mm exists
between the luminaires and the ceiling.

Gambar-gambar pemasangan

52
10.2 Suspension system

Butiran Kerja

 Objektif - Pemasangan sistem penggantungan yang berasingan untuk


kelengkapan lampu termasuk control gear (jika berasingan).
 Keterangan - Perlu dipasang pada semua kelengkapan lampu dan/atau
control gear, bukannya hanya dipasang di atas siling.
- Sistem ini perlu bagi menampung berat kelengkapan lampu
termasuk control gear (jika berasingan).
- Saiz minimum bagi dawai penggantung adalah 22 SWG steel
wire (0.71mm).
 Peralatan penyeliaan - T/B

Ilustrasi

53
Metodologi

Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan).

L-S1 : Section 11.4 : The luminaires shall not sit on the ceiling structure but shall
be securely suspended from the floor slabs or beams of roof trusses by means of
suspension rods, brass chains or G.S. wires as specified or as directed by the
S.O.’s Representative.

Surat Arahan Pengarah CKE rujukan (51) dlm PKR(L)2/2/44-Jilid 4 bertarikh 7


Mei 2007.

Gambar-gambar pemasangan

10.3 Termination of flexible conduit at fitting

Butiran Kerja

 Objektif :

⇒Pemasangan flexible metallic conduit pada semua peralatan adalah


untuk memudahkan kerja-kerja penyenggaraan dan bagi melindungi peralatan
daripada getaran.

54
⇒Perlu ada penamatan yang sempurna pada lampu dan juga junction
box.

 Keterangan:

⇒Flexible metallic conduit perlu dipasang pada peralatan dengan


panjang tidak melebihi 400mm.
⇒Perlu ada adaptor pada setiap hujung flexible metallic conduit sebagai
penamatan penyambungan.
⇒Penyambungan pada junction box perlu menggunakan die-cast cone-
shaped metal cover.

 Peralatan penyeliaan : T/B

Ilustrasi

Metodologi

 Sila rujuk ilustrasi

Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan).

L-S1 : Section 9.3 :

 Conduit for lighting point shall be terminated in a junction box complete


with die-cast cone-shaped metal cover so that downdrop to luminaire shall
be carried out through flexible steel conduit up to the luminaire. Ceiling fan
points shall be run in the similar way.Flexible conduit shall be used for
termination to equipment, which are subjected to movement or vibration.
However, the length of this flexible conduit shall not exceed 400mm unless
approved by the S.O.’s Representative.

55
Gambar-gambar pemasangan

56
Ceiling Fans

57
11.1 Ceiling Fans – Safety wire rope & rod must ensure

come from same manufacturer

Butiran Kerja

 Objektif
o Pemasangan wire rope adalah bertujuan memegang kipas daripada
terjatuh jika rod kipas rosak atau tercabut. Rod dan kipas juga perlu
dibuat dari kilang yang sama.
 Keterangan
o Perlu dipasang pada semua rod kipas.
 Peralatan penyeliaan
o T/B

Ilustrasi

Metodologi

 Sila rujuk ilustrasi


Rujukan (Sila sertakan klausa/ayat yang terbabit dari sumber rujukan).

 L-S1 : Section 12 : Ceiling fans shall be provided with a supplementary


independent suspension system so that in the event of failure of the rod
suspension system, the fan motor will be safely suspended by this
supplementary independent suspension system from the fan hook and

58
electricity supply to the ceiling fan shall be disconnected.
Design and construction of the supplementary independent suspension
system and disconnection of electricity supply shall be subject to the JKR
approval. These features must be assembled in the manufacturer’s factory.
 Arahan Teknik 1/2008 (USPM)

Gambar-gambar pemasangan

Wayar keselamatan di ikat dengan ketat dan sempurna pada shaft motor tanpa
ditegangkan.

Lilit Wayar Keselamatan ke Cangkuk Siling sebanyak 2 kali tanpa ditegangkan.

Ikat dengan ketat Wayar Keselamatan (dengan Spring Washer) pada paip Down
Rod.

59
Earthing

60
12.1 Earthing

Butiran Kerja

 Objektif : Memastikan pemasangan 'Earthing' di tapak bina adalah seperti


dinyatakan pada lukisan dan spesifikasi L-S1
 Keterangan :

1. Saiz Switchboard Earthing Bar (SEB) seperti di dalam lukisan


2. Saiz Protective Conductor (PC) seperti didalam lukisan.
3. Saiz Main Earthing Bar(MEB) seperti di dalam lukisan/spesifikasi L-S1
4. Kedudukan Main Earthig Bar(MEB) dalam bilik suis seperti di dalam
lukisan/spec. L-S1.
5. Kedudukan dan pemasangan Current & Potential test prob.
6. Memastikan test prob dan Main Earthing Bar tidak bersambung.
7. Menentukan jarak Earth Chamber yang betul
8. Menentukan kaedah joint menggunakan EWC.
9. Memastikan saiz kedalaman copper tape yang menyambungkan dua earth
chamber
10.Memastikan ada lebel di pasang di dalam earth chamber.
11.Memastikan penutup earth chamber sama aras dengan aras tanah

 Peralatan penyeliaan : Caliper

Ilustrasi

61
Metodologi

 Sila rujuk ilustrasi

Rujukan

L-S1, Section 13 : Earthing

 Comply with Peraturan-peraturan Elektrik 1994 and MS IEC 60364


62
 The min cross sectional area of the protective conductors shall be in
accordance with the following tables/clause in the MS IEC 60364-5-
54 :-

1. Earthing Conductors (Table 54.2 – except for solid earthing)


2. CPCs (Table 54.3 – need not exceed 75 mm2)
3. Bonding Conductors (Clause 544)

 Main Earthing Terminals/Bars mounted on porcelain insulators shall be


provided at a position near to the switchboard
 RCCBs shall be provided with minimum cross-sectional area 16 mm2 PVC
insulated copper conductor cable as earth conductor, one set of earth
electrodes, inspection chambers and removable covers
 Borang JKR.PK(O).04-SKE.3B (Pin. 1/2009) - BORANG PEMERIKSAAN
PEMASANGAN ELEKTROD BUMI
 Dimension of Main Earthing Bars (MEB) and Earthing Conductors (EC)

Gambar-gambar pemasangan

Main Switch Board Main Earthing Bar

Earth Chamber yang digunapakai


63
Bilik riser

64
Bilik riser

Butiran Kerja

 Objektif :

• Menyediakan bilik untuk menempatkan servis-servis elektrikal yang berkaitan


berdasarkan keperluan-keperluan beban
• Memastikan keluasan ruang bilik yang disediakan adalah bersesuaian supaya
kerja-kerja senggaraan dapat dilaksanakan.

 Keterangan:

1. BILIK SESALUR LV & SSB SERTA BILIK SESALUR PA/CCTV/MATV

Perlu terdapat sekurang-kurangnya 1 Bilik Sesalur di setiap tingkat bagi


pembinaan bangunan satu (1) tingkat dan ke atas Bilik tambahan perlu disediakan
sekiranya jarak melebihi 80 meter .

Keperluan bilik juga dikehendaki disediakan secara individu ataupun bergabung


dengan servis elektrikal yang lain
Saiz bilik juga berbeza bergantung kepada kerumitan projek (complexity of the
projects)
Bilik hendaklah dinamakan dan dilabelkan dengan tanda-tanda amaran yang
berkaitan

2. BILIK SESALUR BILIK SESALUR TELEFON, IT & IT EQUIPMENTRACK

Perlu terdapat sekurang-kurangnya 1 telecommunication closet(tempat


penyimpanan alatan telekomunikasi) di setiap tingkat bagi pembinaan bangunan
satu (1) tingkat dan ke atas
Tempat penyimpanan tambahan perlu disediakan sekiranya :
Keluasan lantai melebihi 1000 m2 (meter persegi)
Jarak closet ke ruang kerja adalah melebihi 90 meter
Bilik hendaklah dinamakan dan dilabelkan dengan tanda-tanda amaran yang
berkaitan

 LV RISER ROOM

65
 IT RISER ROOM

 Keluasan Bilik Server berbanding jumlah Ruang Kerja (Workstation)

66
Metodologi

 Sila rujuk ilustrasi

Rujukan

 PPE- Peraturan 38 : Bilik suis hendaklah dinamakan dan ditanda dengan


“DILARANG MASUK”, “BAHAYA” dan “DILARANG MEROKOK”
 Borang JKR.PK(O).04- SKE.4B (Pin. 1/2009) - BORANG PEMERIKSAAN BILIK
SUIS / MESIN ELEKTRIK

67
Lightning Protection &
Earthing

68
14.1 Installation of air termination system

Butiran Kerja

 Objektif : Memintas panahan kilat (intercept lightning flashes)


 Keterangan
o Perlu dipasang pada bangunan yang ingin dilindungi menggunakan
25mm x 3mm copper tape sebagai komponen pengalir.
o Dipasang dengan mana-mana kombinasi samada rods, catenary wires
dan/atau meshed conductor.
o Komponen air termination hendaklah dipasang dibahagian penjuru,
bahagian terdedah dan disisi/pinggir terutamanya diaras atas bagi
mana-mana permukaan bangunan.

 Peralatan penyeliaan.

Ilustrasi

 Tiada

Metodologi

 Sila Rujuk Ilustrasi

Rujukan

 IEC 62305-3; 5.2.2 : Air-termination components installed on a structure


shall be located at corners, exposed points and edges (especially on the
upper level of any facades) in accordance with one or more of the following
methods - i.e protection angle method, rolling sphere method and/or mesh
method.
 Borang JKR.PK(O).04-SKE.3B (Pin. 1/2009) - BORANG PEMERIKSAAN
PEMASANGAN ELEKTROD BUMI

14.2 Installation of down conductor system

Butiran Kerja

 Objektif : Mengalirkan arus kilat daripada air-termination system ke bumi


dengan selamat
 Keterangan
69
oMerupakan sambungan terus dari air-termination system ke bumi
dengan menggunakan 25mm x 3mm copper tape sebagai komponen
pengalir.
o Dipasang lurus dan menegak bagi mengujudkan laluan mudah bagi
arus kilat mengalir ke bumi.
 Peralatan penyeliaan

Ilustrasi

Metodologi

 Sila rujuk ilustrasi

Rujukan

 IEC 62305-3; 5.2.2 : Air-termination components installed on a structure


shall be located at corners, exposed points and edges (especially on the
upper level of any facades) in accordance with one or more of the following
methods - i.e protection angle method, rolling sphere method and/or mesh
method.
 Borang JKR.PK(O).04-SKE.3B (Pin. 1/2009) - BORANG PEMERIKSAAN
PEMASANGAN ELEKTROD BUMI

70
Genset

71
15.1 Susun Atur Bilik Janakuasa Tunggusedia

Butiran Kerja

 Objektif : Memastikan sususnatur barang-barang di dalam bilik Janakuasa


Tunggusedia bersesuaian untuk tujuan kerja-kerja selenggara,
pengudaraan, memudahkan operasi dan janakuasa tunggusedia statik.

 Ruang dalaman yang luas sekurang-kurangya 1 meter atau


1.5Keterangan : meter antara dinding bilik ke janakuasa tunggusedia
bersesuaian mengikut kuasa KVA janakuasa dan tiada halangan untuk
pengudaraan
Bilik janakuasa mestilah mempunya 3 free wall kerana ketika janakuasa
berfungsi, bunyi bising dan asap akan berlaku.
Pintu yang dipasang jenis Double Leaf Door (Acoustic Door ) penyerap
bunyi, bukaan pintu keluar bangunan, saiz pintu boleh memuatkan
janakuasa tunggusedia untuk masuk (loading).
Mempunyai soket alur keluar 13A untuk penyelenggaraan.
Sistem pemadam api jenis Fire Fighting jenis Co2 atau Clean Agent
Sistem pengudaran dan penyejukan menggunakan kipas pelawas .

 Peralatan penyeliaan : Tidak Berkenaan

Ilustrasi

72
1.0 Susunatur Barang-barang keperluan didalam bilik Janakuasa Tunggusedia

2.0 Saiz Bilik Janakuasa Tunggusedia yang bersesuaian 6000 × 5500 , Door:
2000(H) × 2000(W),

3.0 Keperluan Dinding Bilik Janakuasa Tunggusedia adalah jenis berlapis dua

4.0 Pengudaraan Maksimum

73
Methodologi

 Sila Rujuk Ilustrasi

Rujukan

1. LS-5 dan LS-6


2. Panduan Teknik Chapter 2 dan Chapter 9
3.Kit Selia

Gambar-gambar Pemasangan

74
15.2 Pemasangan Kabel Janakuasa Tunggusedia

Butiran Kerja

 Objektif : Memastikan pemasangan kabel Janakuasa Tunggusedia


bersesuaian , kemas dan selamat
 Pemasangan kabel antara MSB(E) keKeterangan : AMF.
Pemasangan kabel antara AMF ke Janakuasa Tunggusedia.
Jenis kabel yang digunakan adalah Fire Rated Cable.
Pemasangan ini menggunakan Cable Tray.
 Peralatan penyeliaan : Tidak Berkenaan

Ilustrasi

Jenis-jenis kabel keluaran yang sesuai:

• Mineral Insulated Copper Cable (MICC) – mahal dan tidak mudah lentur
• Fire Rated Cable (FRC) – harganya lebih murah dan mudah lentur

75
Ciri-ciri kabel ialah tahan suhu yang tinggi kerana risiko kebakaran adalah tinggi
dan diluluskan oleh pihak Bomba
Saiz cable tray yang mempunyai kelegaan yang sesuai. Pemasangan juga kemas.

Methodologi

MINERAL-INSULATED CABLES

1.Mineral-insulated cables shall be manufactured complying with IEC 60702, IEC


60331 and BS 6387 Category C, W and Z for electrical circuit integrity in case of
fire.
The cables shall have been tested to comply with IEC 60332-1 and 60332-3 for
flame retardance, and IEC 61034 for smoke obscuration.

2.The cables shall be halogen free with low organic content and do not release any
corrosive emission when subject to fire conforming to IEC 60754-2. The cables
shall be able to withstand a short circuit temperature of 280 0C for 5 s. For general
lighting and power points final circuits, unless otherwise specified, cables of 600V
insulation grade may be used.

3.For main circuits and major power points, the cables used shall be of 1000 volt
insulation grade. They shall be installed strictly in accordance with the
manufacturer's
recommendation and instruction. The mineral-insulated cables shall be as
specified, either:

(a) mineral-insulated copper sheathed copper conductor (MICC) cables comprise


of pressure packed magnesium oxide insulation contained within a solid drawn
ductile
seamless copper sheath with solid high conductivity copper conductors; or

76
(b) mineral-insulated mineral sheathed copper conductor (FR) cables comprise of
multi stranded high conductivity copper conductors wrapped with layers of glass
mica
composite tape flame barrier and be insulated with a non-melt cross linked mineral
insulation and mineral sheathed.

4.Cables installed on walls shall be fixed by means of copper clips or copper


saddles at appropriate spacing. The clips or saddles shall be secured by means of
brass
screws. Where cables are installed on cable trays, they shall be clipped at
appropriate spacing by means of copper saddles. The saddles shall be secured by
means of brass bolts
and nuts. Where single core cables are used on multi-phase distribution work, the
cables shall be laid on their phase groups whether flat or trefoil.

5. Adequate bonding shall be provided where cables break formation to enter


terminating positions. Minimum bending radius shall be not less than six times the
cable diameter and saddle spacing not more than 60 times the cable diameter or
500 mm whichever is less.

6.Connection to motors, generators, transformers and other similar equipment


shallbe by one of the two methods listed below: -

(a) The cable shall be clipped at the appropriate spacing up to a point adjacent to
the equipment and an unsupported antivibration loop shall be left in the cable.

(b) The cable shall be glanded into a suitable terminal box adjacent to the
equipment and connection to the equipment being effected by means of
mechanically protected flexible
cable of adequate cross sectional area.

6.For mineral-insulated copper sheathed copper conductor (MICC) cables,


termination shall be of cold seal type. Silicon rubber sleeve insulation shall be used
to
replace copper sheath stripped off near the termination for temperature not
exceeding 1500C. For temperature exceeding 150 0C, varnished glass sleeve
insulation shall be used.
Insulation and continuity tests shall be carried out before and after the cable
isterminated. The insulation test reading shall be `infinity'. A blow lamp may be
used for drying out cable ends.

For mineral-insulated mineral sheathed copper conductor (FR) cables, termination


shall be metal gland or close fitting metal bush of crimping type. All other
77
necessary accessories such as tap-off units, joint boxes including termination kits
etc

CABLE TRAYS
1.Cable trays shall be fabricated from perforated galvanised sheet steel complete
with all necessary bends, tee pieces, adaptors and other accessories.

2.The minimum thickness of the sheet steel shall be 1.5 mm for cable trays with
widths up to and including 300 mm and 2.0 mm for cable trays with width
exceeding 300 mm.

3.However minimum thickness for the sheet steel of the perforated hot dipped
galvanised cable trays shall be 2.5 mm.

4.Cable trays may either be suspended from floor slabs by hangers or mounted on
walls or vertical structure by brackets at 600 mm intervals.

5. All supports, hangers, bracket and structure for the perforated hot dipped
galvanised cable trays shall also be of hot dipped galvanised type. Fixing clips and
cleats for cables on trays shall be installed by means of bolts,washers and nuts. All
tees, intersection units, adaptor units etc.

Rujukan

1. LS-5
2. Panduan Teknik Chapter 6 dan Chapter 9
3.Kit Selia
Gambar-gambar Pemasangan

78
15.3 Pemasangan Sistem Pembumian Janakuasa Tunggu Sedia

Butiran Kerja

 Objektif : Memastikan pemasangan sistem pembumian Janakuasa Tunggu


Sedia bersesuaian dengan fungsi Janakuasa.
 Menggunakan copper tape sebagai komponenKeterangan : pengalir.
Menggunakan konsep Centralize Earthing daripada Main
Earthing Bar ke concreate earth chamber.
 Menggunakan pvc black cable sebagai neutral cable daripada
Janakuasa Tunggu Sedia ke Earth Chamber.
 Peralatan penyeliaan : Tidak Berkenaan

Ilustrasi

FIRE BARRIER

Table 4: Dimension of Main Earthing Bars and Earthing Conductors


Extracted from L-S1, Earthing Section 13

Cabling
1 Always use flexible cables for inter connecting the PCC3100 / PCC3200 controls
with the switchgear andother equipments.

2 Power cabling between alternator and control panel and control panel and change
over switch to mains should be done with recommended cable sizes.
79
3 While terminating cables avoid any tension on the bolts / busbars.

4 While terminating R.Y.B. phase notations should be maintained in the alternator


and control panel for easy maintenance.

5 Crimped cables should be connected to alternator and control panel through


cable glands.

6 Overheating due to loose thumbing / undersize cables causes most of electrical


failures, hence ensure that correct size of cables and thimbles is used.

7 For AMF application, use 8/10 core 2.5 sq. mm armoured copper cable for
control cabling.

8 Typical cable sizes for 415 V application are provided in Table M.7. The sizes
given are indicative, please refer to cable manufacturers for details.

9 For HT installations, kindly contact OEM’s for details on sizing.

10 Care to be taken, that weights of cables should not fall on alternator / base rail.
It is recommended to support output cables on separate structure on ground.

11 External wirings, when provided for remote voltage / excitation monitoring /


droop CT etc. shall be screenedsheathed type. Maximum length of such wiring
shall not exceed 5 meters.

80
Rujukan

1. LS-5
2. Panduan Teknik Chapter 6 dan Chapter 9
3.Kit Selia

Gambar-gambar pemasangan

81
Pengujian Litar Akhir

82
16.1 Ujian Kefungsian RCCB

Butiran Kerja

 Objektif : Bagi menentukan masa RCCB berfungsi mengikut kepekaan yang


ditetapkan
 Keterangan : Ujian-ujian yang perlu dilaksanakan:

1. 50% TRIPPING CURRENT - TIDAK TRIP


2. 100 % TRIPPING CURRENT - TRIP < 200 mS
3. 500 % TRIPPING CURRENT - TRIP < 40 mS

 Peralatan Pengujian : Alat Uji RCD

Methodologi dan Ilustrasi

83
Rujukan

 L-S1; Section 16.2 : TEST AND TEST CERTIFICATES- After the installation
work has been completed and before Certificate of Practical Completion is
issued, the whole electrical installation covered under this part of the
Contract shall be tested as prescribed in Electricity Regulations 1994 and
MS IEC 364-6-61 and any other tests deem necessary by the S.O.'s
Representative.
 Borang JKR.PK(O).04-SKE.5B Pin.1/2009 - BORANG PEMERIKSAAN
KEFUNGSIAN KOMPONEN ELEKTRIK
 Borang JKR.PK(O).04-SKE.5A Pin.1/2005 - BORANG PEMERIKSAAN UJIAN-
UJIAN ELEKTRIKAL
 FORM NO : JKR.RCCB - Record of RCCB Test

84
17.1 Pemasangan Gantungan Ceiling Speaker

Butiran Kerja

 Objektif : Memberi penerangan berkaitan kaedah gantungan ceiling


speaker yang betul dengan menggunakan 1.6mm dia. Low carbon
galvanized steel wire untuk memastikan ceiling speaker tidak jatuh dan
untuk mengelakkan siling daripada melendut(sagging).
 Keterangan : Perlu dipasang bagi semua pemasangan ceiling speaker
 Peralatan Penyeliaan : Pita Pengukur

Ilustrasi

Metodologi

To attach, tie both end of 1.6mm dia. Low carbon galvanized steel wire around the
speaker steel wire hook, and secure soffit cleat or wire hanger on the RC
Beam/Slab. Sila rujuk perkara 2. Ilustrasi.

Rujukan

Perlu dibacakan bersama-sama dengan Garis Panduan


Bahan(CKE.GP.01.00.2010), Panduan Penggantungan: Fluorescent Luminaires,
Downlight dan Speaker. Ruj. No (25)dlm.JKR(PE)2/7/4 bertarikh 12hb Oktober
2010.
85