Inverter
2100 H, 3000 H, 4000 H, 4600 H
2 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Contents
Contents
1 Introduction 5
1.1 PLATINUM H 5
1.2 About this manual 5
1.3 Symbols used 5
1.4 Symbols on product and packaging 6
2 Safety 7
2.1 Intended usage 7
2.2 Improper usage 7
2.3 Personnel requirements 7
2.4 General safety instructions 7
3 Installation 8
3.1 Scope of delivery 8
3.2 Unpacking 8
3.3 Assembly 9
3.4 Connection 12
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 3
Contents
7 Web server 58
7.1 Connection between inverter and computer 58
7.2 Starting the web server 61
7.3 Menu tree 62
7.4 Home 63
7.5 Statistics 66
7.6 Setup 67
7.7 Event Log 75
7.8 Status 76
7.9 Help 78
7.10 Logout 78
10 Technical data 86
12 Disposal 89
4 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Introduction
1 Introduction
1.1 PLATINUM H
Inverters in the PLATINUM H series are single-phase feed-in inverters for different
power ranges; see “Technical data” on page 86.
Inverters in the PLATINUM H series are equipped with an integrated web server, which
allows data to be viewed and evaluated via a network or via the internet.
Up to 30 PLATINUM H inverters can be connected to form a single inverter system via
the CAN network.
Additional documents
The following additional documents are available in the download area of our website
www.platinum-nes.com:
▪▪ Detailed installation and user guide
▪▪ Information on fault current protection devices
▪▪ Detailed list of events for detecting/eliminating faults
▪▪ Overview of country and grid codes
▪▪ Declaration of conformity and certificates
▪▪ Manufacturer’s warranty
Notes give tips on how to work easily and safely or contain further
information.
WARNING WORD
Type, source and consequence of the hazard!
ff Measures to avoid the hazard.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 5
Introduction
Disposal
▪▪ Do not dispose of PLATINUM inverters in household
waste.
▪▪ Packaging and replaced parts are to be disposed of in
accordance with the regulations of the country in which the
inverter was installed.
6 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Safety
2 Safety
2.1 Intended usage
▪▪ Inverters are to be used solely for the purpose of feeding photovoltaically generated
solar energy into the public grid.
▪▪ All other usage does not comply with the regulations.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 7
Installation
3 Installation
3.1 Scope of delivery
▪▪ Inverter
▪▪ Wall bracket
▪▪ Brief guide
▪▪ Installation materials
▪▪ Grounding kit
3.2 Unpacking
CAUTION
Risk of injury!
ff Wear safety shoes when unpacking the inverter and during
installation.
ff Ensure that the inverter is positioned securely.
8 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Installation
3.3 Assembly
3.3.1 Safety instructions
WARNING
Injury may result if the inverter falls!
ff Use fixing materials suited to the assembly wall and the weight of the
inverter.
ff Wear safety shoes during assembly and disassembly.
ff Ensure that the inverter is positioned securely.
CAUTION
Damage to the inverter due to excessive buildup of dust.
ff Avoid excessive build-up of dust.
ff Avoid build-up of dust with electrically conductive dust particles.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 9
Installation
4 5
10 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Installation
Anti-theft protection
Two clamps are included in the scope of
delivery, with the aid of which the inverter
can be protected against theft.
A padlock is not included in the scope of
delivery.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 11
Installation
3.4 Connection
3.4.1 Preparatory work
12 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Installation
CAN
Network cable
▪▪ CAN: cross-section 0.21 mm2, max. 100 m
▪▪ Ethernet: CAT 5 shielded twisted-pair cable with pre-assembled RJ45 plugs
Connect
10
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 13
Installation
11
12
14 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Installation
14 and H
–– Outgoing line: right-hand terminals
L and H
9. At the master inverter, connect the
plug of the Ethernet cable with the lug
facing towards the rear into the socket
(15).
Termination
Termination via an internal terminating resistor ensures correct operation of the
network. This is done by means of a jumper, which lies across the CAN terminal block
and short-circuits two pins.
No jumper is fitted at the factory, so the terminating resistance is not activated.
The terminating jumper is included with the supplied installation materials.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 15
Installation
DANGER
Risk of death due to high AC voltage!
ff Switch off the mains voltage supply (AC side) before connecting the
inverter (safety device).
ff Make sure that the central isolation device can be accessed freely.
ff Only connect the inverter to TN or TT networks (see IEC 60364-1)
with 230 V.
ff Observe max. fuse protection permitted on the AC voltage side; see
“Technical data” on page 86.
ff Establish the AC voltage connection with a circuit breaker.
PLATINUM recommends a type C miniature circuit breaker.
ff If an external residual current protective device is required, PLATINUM
recommends using a residual current protective device (RCD) of
type A.
CAUTION
Destruction of the inverter!
ff Never connect inverters between two phases.
ff Never mix up the phases with PE or N.
ff If several inverters are connected, distribute them across the three phases so
that the differences in feed-in power between the phases do not exceed the
maximum permitted unbalanced load of the grid operator.
16 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Installation
1. Protect the AC voltage connection lines with appropriate fuses; see “Technical data”
on page 86.
2. Strip 18 mm of insulation from the AC voltage connection lines and add wire-end
sleeves.
Connect
The AC connection screw fitting does not have a seal. One of the sup-
plied seals must be used to ensure that the requirements for safety class
IP65 are met.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 17
Installation
Terminal Assignment
GND Protective ground conductor
N Neutral conductor
L Feed-in phase
WARNING
Risk of electric shock and damage to the inverter.
ff Only install the grounding strap on grounded PV modules.
18 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Installation
GND/PE
2 -NEG
Ungrounded Grounded
1 Terminal 2 Terminal
N5
WARNING
Risk of electric shock and damage to the inverter.
ff Only install the grounding jumper on grounded PV modules.
Ungrounded Grounded
1 Terminal 2 Terminal
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 19
Installation
Swap over the internal cables if the PV modules are positively grounded
WARNING
Risk of electric shock and damage to the inverter.
ff Only swap over the internal cables if the PV modules are positively
grounded.
At the factory, black cables are assigned to the connections N1 to N4 and red cables to
the connections P1 to P4. In the case of negatively earthed PV modules, this assign-
ment needs to be swapped over.
This concludes the work inside the inverter. The lower cover can be closed again.
20 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Installation
DANGER
Risk of death due to high DC voltage! A voltage is present at the PV
modules when it is bright.
ff Before connecting the inverter, check whether voltage is applied to
the generator’s DC voltage connection.
ff Before connecting the inverter, check whether the polarity of the DC
voltage is correct.
ff If voltage is applied, wear insulating protective clothing and face
protection.
ff Ensure that the cable plug has engaged completely with the socket.
ff Detach the DC voltage cable only if the inverter is not in operation.
ff Make sure that the DC isolator or a central isolation device can be
accessed freely.
WARNING
Risk of electric shock and damage to the inverter and/or PV plant!
ff Use only the original DC voltage Multi-Contact MC4 cable plug.
ff Only connect PV modules that meet the requirements of IEC 61730
class A.
ff Ensure that the max. DC voltage permitted is not exceeded.
ff Ensure that the max. direct current permitted per string is not
exceeded.
ff Make sure that the lower cover is closed before making the DC
voltage connection.
If more than one string is connected, make sure that the quantity and
type of solar modules and the voltage of strings to be connected in
parallel are the same.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 21
Installation
Fit protective caps to plug connectors that are not used on the inverter.
22 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Placing into operation
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 23
Placing into operation
Text entry
1. If the required input field is highlighted yellow (e.g. Customer name), press the
(OK) key to open the on-screen keypad.
2. Use the arrow keys / and / to select the required letter or number field.
3. Press the (OK) key several times as required until the correct character is dis-
played in the text window (top row) (this works in a similar way to the buttons on a
mobile phone).
4. Repeat steps 1 and 2 for the remaining characters.
5. Once the entry is complete, press the OK key on the on-screen keypad to close the
keypad.
A maximum of 19 characters can be displayed in the text window.
24 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Placing into operation
Text can be easily entered at the PC keyboard via the integrated web
server.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 25
Placing into operation
4.3.1 Overview
The Installation Menu contains the following menu items:
▪▪ Start installation
▪▪ Language
▪▪ Date *
▪▪ Time *
▪▪ Bus ID (RS485, can be skipped)
▪▪ Configure as master
▪▪ Country setting/grid code **
▪▪ Screen lock
▪▪ Customer name
▪▪ Site
▪▪ Message 1 / Message 2
▪▪ Owner password
* Changing the date and time can cause saved data to be overwritten or
lead to gaps in data logging.
During initial operation, the date and time must be entered completely
and correctly once.
** The country setting can only be changed for the first 5 hours after
feed-in starts. After this, the menu is no longer accessible for the owner.
26 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Placing into operation
Changing the date and time can cause saved data to be overwritten or
lead to gaps in data logging.
During initial operation, the date and time must be entered completely
and correctly once.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 27
Placing into operation
4.3.6 Master/Slave
▪▪ When multiple inverters that are networked with each other via the CAN network are
installed, one inverter can be configured as the master and the others as slaves. For
this to be possible, all inverters in the network must be switched on.
▪▪ The master inverter automatically transfers the setting values to the other inverters
via the CAN network.
▪▪ A CAN network can comprise one master and up to 29 slaves.
28 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Placing into operation
CAUTION
No inverter operation, or malfunction of the inverter!
ff Make sure that the selected country is actually correct for the installation site.
Otherwise it may be impossible to operate the inverter, or its operation may
contravene local and national regulations because incorrect threshold values are
used.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 29
Placing into operation
30 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Placing into operation
CAUTION
Risk of unauthorised manipulation of the inverter!
ff Do not leave the owner password in its default setting – make sure you change
it to a different 4-digit value.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 31
Placing into operation
Repeat the network scan after every test step until the number of
detected inverters matches the actual number present in the network.
32 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Operation of the inverter
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 33
Operation of the inverter
▪▪ The start screen is always displayed if no button has been pressed for 1 minute.
▪▪ If a screen saver is activated (blank screen), any button can be pressed to display the
start screen.
34 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Operation of the inverter
▪▪ The values displayed by the inverter may differ from those displayed
on calibrated electricity meters.
▪▪ The operation displays Month and Year show the same values relating
to the affected period.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 35
Operation of the inverter
Status displays and operating modes are also indicated by the LEDs.
36 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Operation of the inverter
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 37
Menu on the inverter
3. Use the navigation keys to select the required menu and confirm by pressing .
38 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Setup General setup Language, date and time, password, CO2 rate,
yield rate, yield currency
Network setup IP address, subnet mask, gateway, master,
setting
Inverter setup Model, serial number, SW version numbers, HW
version numbers etc.
Plant setup Company/customer name, site, date of install-
ation, maintenance date, area of responsibility,
device name, message, apparent power of plant
Grid configuration Country, country code etc.
Event Log
Statistics Inverter
System
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 39
Menu on the inverter
Menu settings can also be input via the web server; see chapter 7.
40 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
Input parameters ▪▪ Values from the PV modules to the inverter:
current, voltage and power
Output parameters ▪▪ Feed-in values from the inverter to the grid:
current, voltage and power
Inverter, peak power value ▪▪ Highest power value attained on this day
Energy today ▪▪ Total energy yield during the course of the day
Temperature ▪▪ Temperature inside the inverter
Insulation resistance ▪▪ Safe insulation value for the avoidance of injuries and
plant damage
Operating hours ▪▪ Total running time of the inverter since it was first
taken into operation
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 41
Menu on the inverter
Parameters Meaning
Plant mode Operating mode is displayed. For details of possible
operating modes, see section 5.2.6.
Plant status (faults) Plant status is displayed. For details of possible
statuses, see section 5.2.6.
Number of inverters Total number of inverters in the plant
Number of active inverters Total number of active inverters in the plant
Number of inverter alarms Number of event alarms in the plant
Number of inverter Number of event warnings in the plant
warnings
Input current Total current from the PV modules to the inverters
Input power Total power from the PV modules to the inverters
Output current Total grid feed-in current from all active inverters
Output voltage Total grid feed-in voltage from all active inverters
Output power Total grid feed-in power from all active inverters
Energy today Total energy production of the plant today
42 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
Language ▪▪ The preferred language is defined during installation.
Date and time ▪▪ The date and time are set during the installation.
Password ▪▪ Owner password; factory setting: 0003
CO2 rate ▪▪ Avoided CO2 emissions, based on 0.7 kg/kWh
Yield rate ▪▪ Feed-in rebate in the relevant country
Yield currency ▪▪ Currency in the relevant country (3 characters)
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 43
Menu on the inverter
Parameters Meaning
IP address ▪▪ Unique network address for the inverter
Subnet mask ▪▪ Sub-network address; first part of the IP address
Gateway ▪▪ Network transmission to a different network
Master setting ▪▪ If multiple inverters are connected to each other, one
of the inverters must be configured as the master
and all the others as slaves
You will need to have these data available for service situations.
Parameters Meaning
Model ▪▪ Inverter model
Serial number ▪▪ Unique identification for every inverter, also to be
found on the type plate
Part number ▪▪ Identification for every inverter hardware
configuration within PLATINUM
Version ▪▪ Unique version name for tracking the development of
different inverter versions within PLATINUM
GUI software part no. ▪▪ GUI = Graphical User Interface
▪▪ The GUI enables interaction with the inverter via the
display.
GUI software version ▪▪ Version of the GUI software
GUI hardware part ▪▪ Identification for the GUI card hardware
number
44 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
GUI hardware version ▪▪ Version number of the GUI hardware
SW1 part number ▪▪ Part number of the DSP1 software
▪▪ (DSP1 = Digital Signal Processing)
▪▪ The DSP microprocessor is used to control the
energy conversion in the inverter.
SW1 version ▪▪ Version number of the DSP software
Part number of the control ▪▪ Part number of the DSP card
board
Version of the control ▪▪ Version designation for the DSP control hardware
board
Part number of the main ▪▪ Identification for the main board; all of the
board components and subsystems of the inverter are
mounted on the main board.
Version of the main board ▪▪ Unique version number for tracking the development
of the different main board versions
SW2 part number ▪▪ Part number of the DSP2 software
SW2 version ▪▪ Version number of the DSP2 software
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 45
Menu on the inverter
Parameters Meaning
Company/customer name ▪▪ Name of the operator/customer
Site/site name ▪▪ Site (description)
Installation date ▪▪ Date of initial operation
Service date ▪▪ Date of last service
Area of responsibility ▪▪ Field for messages from the service personnel
Device name ▪▪ The inverter is displayed with this name in the list of
inverters linked to the master device
Message ▪▪ Extra field for additional messages
Plant apparent power ▪▪ The product of voltage times current for the entire
PV plant [kVA]
46 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
These parameters can be changed with the owner password for a period
of 5 hours after feed-in to the grid starts.
Please contact the Service department if you need to make changes
after this.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 47
Menu on the inverter
48 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
Name ▪▪ Name of the grid standard for power derating
Enable ▪▪ Enables or disables power derating
Start frequency ▪▪ Frequency at which power derating starts
Isolating frequency ▪▪ Frequency at which power derating ends and the inverter
is isolated from the grid
Slope ▪▪ Slope of the effective power curve in %/Hz
Recovery rate ▪▪ Recovery rate of the inverter in %/min
Parameters Meaning
Name ▪▪ Name of the grid standard for reactive power
Method ▪▪ Method for feeding in reactive power:
–– Deactivated
–– CosPhi(P), based on characteristic curve
–– CosPhi (fixed)
PF Setpt ▪▪ Fixed power factor value,
Only for CosPhi (fixed) method
Number of points ▪▪ Number of XY points used for the characteristic curve,
with a max. of 8 points each,
Only for CosPhi(P) method
PntX1 – PntX8 ▪▪ X-point: Defines the percentage of the effective power
Only for CosPhi(P) method
Automatic adjustment based on the grid code
PntY1 – PntY8 ▪▪ Y-point: Defines the CosPhi setting for each device
Only for CosPhi(P) method
Automatic adjustment based on the grid code
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 49
Menu on the inverter
Parameters Meaning
Name ▪▪ Name of the grid standard for power balancing
Enable ▪▪ Enables or disables power balancing
Imbalance limits ▪▪ Balancing of the power per phase: Maximum permitted
imbalance limits in VA
Parameters Meaning
Name ▪▪ Profile name of the effective power settings
Enable – fixed ▪▪ Enable/disable fixed effective power limit
Eff. power setpt. ▪▪ Fixed effective power limit in W
Parameters Meaning
Name ▪▪ Name of the grid connection standard
VAC min. connection ▪▪ Minimum voltage for renewed grid connection
VAC max. connection ▪▪ Maximum voltage for renewed grid connection
Connection min. ▪▪ Minimum frequency for renewed grid connection
frequency
Connection max. ▪▪ Maximum frequency for renewed grid connection
frequency
50 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
Delete Energy Log ▪▪ Deletes the entries in the energy log and the
cumulative values of the inverter
Delete Data Log ▪▪ Deletes the 15-minute average power values of the
inverter
Reset Web Administrator ▪▪ Resets the administrator password to "Admin"
Account
Self-test ▪▪ Starts the self-test (Italy only)
Self-test result ▪▪ Displays the results of the last self-test (Italy only)
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 51
Menu on the inverter
Parameters Meaning
Delete Energy Log ▪▪ Deletes the entries in the energy log and the
cumulative values of the plant
Delete Data Log ▪▪ Deletes the 15-minute average power values of the
plant
Reset Total Number of ▪▪ Updates the total number of inverters when inverters
Inverters are added or removed
Re-create Plant Energy ▪▪ Re-creates the energy log of the plant based on
Log the energy logs of the inverters that are currently
connected and being operated in the system. This
process may take several minutes. It requires that all
of the inverters in the plant are in operation.
52 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
User name ▪▪ E-mail user name
Password ▪▪ User password for the mail server
Sender e-mail address ▪▪ Valid e-mail address – required in order to send
notifications
Receiver Email 1 ▪▪ Address for the notification to recipient 1
Receiver Email 2 ▪▪ Address for the notification to recipient 2
SMTP server ▪▪ Simple Mail Transfer Protocol server for the sending
of e-mails
SMTP-Port 1 ▪▪ Number of the SMTP port of the SMTP server
Default setting: 25
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 53
Menu on the inverter
Please note
An ISP can change the SMTP IP address without prior notification.
tt If e-mail protocols suddenly cease, check whether the IP address has been changed.
Parameters Meaning
Notification time ▪▪ Time for sending the e-mail with production data
(hours)
Notification time ▪▪ Time for sending the e-mail with production data
(minutes)
Time interval ▪▪ Interval between two notifications in minutes
Send production on ▪▪ Sends the energy yield data to e-mail 1 at the
e-mail 1 indicated time
Send mode on e-mail 1 ▪▪ Sends the operating mode changes to e-mail 1 (sent
immediately)
Send alarm on e-mail 1 ▪▪ Sends a warning or alarm to e-mail 1 (sent
immediately)
Send production on ▪▪ Sends the energy yield data to e-mail 1 at the
e-mail 2 indicated time
Send mode on e-mail 2 ▪▪ Sends the operating mode changes to e-mail 1 (sent
immediately)
Send alarm on e-mail 2 ▪▪ Sends a warning or alarm to e-mail 1 (sent
immediately)
54 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
FTP server IP ▪▪ IP address of the FTP server
User name ▪▪ User name for the FTP server
Password ▪▪ Password for the FTP server
SMTP port 2 ▪▪ The number of the SMTP port of the SMTP server
for uploading e-mails to the portal
Default setting: 25
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 55
Menu on the inverter
This menu shows information about the events that have been logged by the inverter.
The events are listed in descending order.
The possible alarm messages are listed in section “Event Log” on page 75.
56 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Menu on the inverter
Parameters Meaning
Energy ▪▪ Total energy yield of the inverter in kWh
Yield ▪▪ Earnings for the energy fed in by the inverter, e.g. in euro
Avoided CO2 ▪▪ CO2 emissions avoided by the inverter in comparison to fossil
emissions fuels in kg
Peak power ▪▪ Highest instantaneous power of the inverter in W
Parameters Meaning
Energy ▪▪ Total energy yield of the plant in kWh
Yield ▪▪ Earnings for the energy fed in by the plant, e.g. in euro
Avoided CO2 ▪▪ CO2 emissions avoided by the plant in comparison to fossil fuels
emissions in kg
Peak power ▪▪ Highest instantaneous power of the plant in W
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 57
Web server
7 Web server
The inverter has an internal web server, which supplies detailed information about
operation, warnings/alarms and the energy feed-in.
Ethernet
CAN
IP addresses
The IP addresses of the computer and inverter must be in the same area, i.e. the first
eight digits of the IP addresses must be identical. If necessary, one of the IP addresses
has to be changed (see below).
Example
IP address of the inverter: 192.168.10.x,
IP address of the computer: 192.168.10.y
Here, x and y must be different numbers between 1 and 254.
58 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
CAN Ethernet
1. Connect the (master) inverter and the router/switch to each other using a CAT5
Ethernet cable.
2. Under Setup –> Network Setup enter the IP address 000.000.000.000 and press
(OK) to confirm.
The router/switch assigns the network parameters automatically to the inverter. The
inverter performs a restart.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 59
Web server
It should be possible to reach the web server of the inverter with these settings.
60 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
2. Enter the user name and password and press Sign in to confirm.
The home screen is displayed, see page 63.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 61
Web server
Help
Logout
62 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
7.4 Home
Statistics Help
Setup Logout
Event Log
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 63
Web server
Selection
In the area at the top right, either the entire plant or an individual inverter can be selec-
ted.
1. Move the mouse over the light-
coloured field with the plant or inverter
name.
A list of the inverters in the plant is
displayed.
2. Select an inverter.
The system status, production status
and operating hours of the selected
inverter are displayed.
64 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
Detailed values are displayed if you hover with the mouse over the
graphics.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 65
Web server
English French
German Italian
Spanish
7.5 Statistics
66 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
Detailed values are displayed if you hover with the mouse over the
graphics.
7.6 Setup
The Setup menu contains the following submenus:
▪▪ GS Power Plant Information
▪▪ General setup
▪▪ Alarm setup
▪▪ Network
▪▪ User account
7.6.1 Navigation
The Setup menu contains the following navigation icons:
Icon Meaning
Save changes
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 67
Web server
This menu allows you to provide a plant description that suits your own requirements.
You will need to have these data available for service situations.
▪▪ Data displayed in black can be edited.
▪▪ Data that are greyed out are defaulted by the system and cannot be
edited.
68 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 69
Web server
The addresses for automatic notification via e‑mail are set up in this menu.
70 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
Setup –> Alarm Setup –> Inverter Alarms –> Energy Production
The recipients and timings for automatic transmission of energy production are selected
in this menu.
In this menu, e-mail recipients are selected for automatic notification about operating
modes and alarms.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 71
Web server
CAUTION
No connection between the inverter and the network/internet!
ff Do not make any changes to the network data unless the network is being
reconfigured.
72 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
User account
The upper part of this menu shows the current user with his/her access authorisation
level.
Change password
In this area, the password can be changed for the user displayed above.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 73
Web server
Edit account
After pressing the button Edit account, you will see the list of users created on this
web server:
In the default setting, three users with different access authorisation levels are set up.
The user name and password are identical in the default setting.
A maximum of 10 users can be maintained.
CAUTION
Risk of unauthorised access to the web server!
ff Change all passwords during configuration of the system. Do not use standard
passwords.
74 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
For all inverters connected to the PC/internet, the current events are displayed in
chronological (descending) sequence.
Navigation
Via calendar Select the required day in the calendar.
The events for this day are displayed in chronological (descending)
sequence.
Scroll Via the buttons
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 75
Web server
7.8 Status
The Status menu contains the following submenus:
▪▪ Alarm
▪▪ Overview
▪▪ Plant
This screen shows all potential warnings and alarms that can occur on an individual
inverter or on the overall plant.
If an alarm is active for the selected inverter or for the entire plant, it is marked with a
yellow warning triangle.
76 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Web server
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 77
Web server
This menu shows the operating mode, status and some of the feed-in data for the
individual inverters in the plant.
7.9 Help
This menu displays contact information.
7.10 Logout
This menu is used to exit the web server.
The login screen is displayed again.
78 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Maintenance and cleaning
DANGER
Risk of death due to high DC and AC voltages!
ff Wear insulating protective clothing and face protection.
ff Maintenance and cleaning is to be performed only by trained
specialist personnel.
The trained specialist personnel must be granted permission by the
energy provider responsible.
Before every maintenance or cleaning task:
ff Switch off mains voltage supply (safety device).
ff Set the switch knob of the DC isolator to 0.
ff Wait at least 60 minutes until the capacitors are discharged.
ff Make sure that no voltage is applied to the DC cables.
8.1 Maintenance
Have the inverter serviced at least once a year by the PLATINUM Service
department or by a service partner who is authorised by PLATINUM.
8.2 Cleaning
CAUTION
Destruction of the inverter!
ff The inverters must not be cleaned with a steam cleaner.
To ensure effective cooling, regularly clean the cooling element on the rear of the
inverter. Suitable tools for this:
▪▪ Vacuum cleaner
▪▪ Soft brush
▪▪ Compressed air
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 79
Faults and troubleshooting
80 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Faults and troubleshooting
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 81
Faults and troubleshooting
82 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Faults and troubleshooting
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 83
Faults and troubleshooting
84 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Faults and troubleshooting
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 85
Technical data
10 Technical data
Input variables 2100 H 3000 H 4000 H 4600 H
Max. PV power 2,350 Wp 3,450 Wp 4,450 Wp 5,150 Wp
Max. DC power (cos ϕ = 1) 2,100 W 3,000 W 4,000 W 4,600 W
MPPT voltage range 230 V – 480 V
Max. input voltage 600 V
Max. MPPT input current 9.5 A 13.5 A 18.0 A 21.0 A
Number of string inputs 3
Number of MPP trackers 1
Short circuit current 14.2 A 20.2 A 27.0 A 31.5 A
Output variables 2100 H 3000 H 4000 H 4600 H
Nominal power (cos ϕ = 1) 2,000 W 2,900 W 3,800 W 4,400 W
Nominal current 9.0 A 13.0 A 17.0 A 20.0 A
(16.0 A *) (16.0 A *)
Max. apparent power 2,000 VA 2,900 VA 3,800 VA 4,400 VA
Max. AC current 10.5 A 15.2 A 19.7 A 23.0 A
Fuse protection on the AC side 13 A 20 A 25 A 25 A
Min. start power 7W
Network voltage / frequency 230 V (+/– 20%) / 50 Hz (+/– 5%)
Feed-in/monitoring phases 1 feed-in phase / 1 monitoring phase
Max. permitted grid impedance n/a n/a 446 mW 379 mW
Zmax
Standby consumption <1 W
Short-circuit strength Yes
Power factor (cos ϕ) 0.9 ind. ... 0.9 cap.
Max. short circuit current 45.0 A
Max. switch-on current 20 A (max. duration 5 ms)
Efficiency 2100 H 3000 H 4000 H 4600 H
Max. efficiency 96.9 % 97.0 % 97.2 % 97.3 %
Euro efficiency 96.0% 96.2 % 96.6 % 96.9 %
Type name 2100 H 3000 H 4000 H 4600 H
86 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Technical data
Interfaces ... H
DC isolation device Optional switch integrated in device for
isolation from generator field
DC connection DC connector, Multi-Contact MC4
AC connection Screw-type terminals
Network Ethernet / CAN
Ambient conditions ... H
Operating temperature –25 °C to +65 °C
Max. temperature for rated power 45 °C
Storage temperature –30 °C to +80 °C
Rel. Humidity 4% to 99%
Max. operating altitude 2000 m
Protection class IP66 in accordance with DIN EN 60529
Level of contamination II, external and internal use possible
Inverter data ... H
Weight
▪▪ 2100 H, 3000 H 19 kg
▪▪ 4000 H, 4600 H 21 kg
Dimensions (H x W x D) 610 x 353 x 154 mm
Overvoltage category DC side: II
AC side: III
Reverse voltage protection (DC) Yes
Ground fault monitoring DC side: insulation test
AC side: AFI
Protection class / overvoltage I / III
protection
Optical display Full graphic LCD, 170 x 76 pixels
Integrated datalogger ▪▪ Storage capacity sufficient for operating
time of 20 years
▪▪ Integrated web server
Switching concept HF transformer with electric isolation
Cooling concept Convection cooling
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 87
Taking out of operation
WARNING
Injury may result if the inverter falls!
ff Get a second person to help with assembly and disassembly.
ff Wear safety shoes during assembly and disassembly.
ff Ensure that the inverter is positioned securely.
The procedure for taking inverters out of operation is the reverse of that
for installation and assembly.
88 Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
Disposal
12 Disposal
▪▪ Packaging and replaced parts are to be disposed of in accordance with
the regulations of the country in which the inverter was installed.
▪▪ Do not dispose of PLATINUM inverters in household waste.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H 89