SECTION 15060

HANGERS AND SUPPORTS

Display hidden notes to specifier. (Don't know how? Click Here)


Copyright 2010 - 2011 ARCAT, Inc. - All rights reserved

PART 1 GENERAL
1.1 SECTION INCLUDES

A. Portable, non-penetrating rooftop supports for the following:


1. HVAC Equipment supports and platforms.
2. Electrical and Telecommunications Equipment supports and platforms.
3. Crossover Ramps.
4. Pipe supports.
5. Conduit supports.
6. Duct and equipment supports.
7. Accessories.

B. Permanent Structural Steel Equipment Platforms.

1.2 RELATED SECTIONS

A. Section 07700 - Roof and Deck Insulation.

B. Section 07700 - Membrane Roofing.

C. Section 07721 - Roof Walkway and Safety Rail.

D. Section 15070 - Mechanical Sound, Vibration and Seismic Control

E. Section 15700 - HVAC Equipment

F. Section 15820 - Duct Accessories

G. Section 16050 - Basic Electrical Materials and Methods

H. Section 16070 - Hangers and Supports

I. Section 16130 - Raceway and Boxes

J. Section 16133 - Cable Trays

1.3 REFERENCES

15060-1
A. ASTM A 36 - Standard Specification for Carbon Structural Steel.

B. ASTM A 123 - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings


on Iron and Steel Products.

C. ASTM A 153 - Standard Specification for Zinc Coating (Hot-Dip) on Iron and
Steel Hardware.

D. ASTM A 167 - Standard Specification for Stainless and Heat-Resisting


Chromium-Nickel Steel Plate, Sheet, and Strip.

E. ASTM A 501 - Standard Specification for Hot-Formed Welded and Seamless


Carbon Steel Structural Tubing.

F. ASTM A 570 - Standard Specification for Steel, Sheet and Strip, Carbon, Hot-
Rolled, Structural Quality.

G. ASTM A 572 - Standard Specification for High-Strength Low-Alloy


Columbium-Vanadium Structural Steel

H. ASTM A 653 - Standard Specification for Steel Sheet, Zinc-Coated


(Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

1.4 DESIGN / PERFORMANCE REQUIREMENTS

A. Performance Requirements: Provide portable, non-penetrating, equipment


support platforms, duct supports, crossover ramps, pipe and conduit supports which
have been manufactured, fabricated and installed to withstand loads, and to
maintain performance criteria without defects, damage or failure.

B. Design platform assemblies and attachments to resist the following loads:


1. Floor Live and dead loads with 1/180 of span maximum deflection.
2. Live Loads: As indicated on Drawings.
3. Dead Loads: Actual weight of materials incorporated into Work.

C. Wind Load: As calculated in accordance with applicable code.

D. Seismic Loads: As calculated in accordance with applicable code.

E. Design supports to limit pipe and/or conduit deflection to L/240, not to exceed
10 feet (3 m) on center.

1.5 SYSTEM DESCRIPTION

A. Design Requirements:
1. Prefabricated, engineered support systems designed specifically for
use on roofing without adhesive, roof penetrations, flashings or damage to
roofing system.
2. Prefabricated, watertight mechanically anchored, engineered support
systems designed specifically for use on roofing.

1.6 SUBMITTALS

15060-2
A. Submit under provisions of Section 01300.

B. Product Data: Manufacturer's data sheets on each product to be used,


including:
1. Preparation instructions and recommendations.
2. Storage and handling requirements and recommendations.
3. Installation methods.

C. Shop Drawings: Indicate layout, base mounting details, support components


and methods of installation.

D. Verification Samples: Two samples, full size base and frame and fastener
sections minimum size 12 inches (301 mm) long, representing actual product and
finish.

E. Manufacturer's Certificates: Certify products meet or exceed specified


requirements.

1.7 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in the manufacturing of


pipe support systems and rooftop equipment support platforms.

B. Installer Qualifications: Company approved by manufacturer and with not less


than 5 years of experience in installation of pipe support systems.

C. Pre-Installation Meeting: After approval of submittals, but before beginning


installation, conduct a meeting at project site attended by Architect, Contractor,
installers of roofing, and mechanical and electrical piping and equipment to be
installed in support system.
1. Purpose of meeting is to describe in detail the installation process and
to establish agreement, coordination, and responsibilities.
2. Prepare detailed meeting report and distribute copies to Architect and
all attendees.

1.8 DELIVERY, STORAGE, AND HANDLING

A. Store products in manufacturer's unopened packaging until ready for


installation.

B. Store materials in a dry, weathertight location.

1.9 COORDINATION

A. Coordinate Work with other operations and installation of adjacent materials


to avoid damage to installed insulation and membrane materials.

PART 2 PRODUCTS
2.1 MANUFACTURERS

A. Acceptable Manufacturer: Advanced Support Products, Inc., which is located


at: 24227 FM 2978 Rd. ; Tomball, TX 77375; Toll Free Tel: 888-626-3153; Email:
request info (leah@aspbase.com); Web: www.aspbase.com

15060-3
B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of


Section 01600.

2.2 MATERIALS - GENERAL

A. Non-Penetrating Base Material: Injected molded polypropylene with molded


insert for square tubing and two threaded rod couplings molded in.

B. Steel Frames:
1. Steel channel frame section, galvanized conforming to ASTM A 653.
2. Steel beams shall conform to ASTM A 572, grade 50.
3. Steel plates and angles shall conform to ASTM A 36.
4. Hollow Structural Sections: Steel tubing conforming to ASTM A 501.

C. Grating: 1 inch (25.5 mm) by 3/16 inch (4.8 mm) bar grating, 19-W-4 carbon
steel, ends capped with 1 inch (25.5 mm) 1/4 inch (6.4 mm) steel flat bar, welded,
hot-dipped uniform zinc coating after fabrication.

D. Handrail Framing: 1-1/2 inch (38 mm) schedule 40 pipe, welded, hot-dipped
uniform zinc coating after fabrication.

E. Hangers: Clevis and/or Band type as per pipe requirements.

F. Accessories: Cadmium plated threaded rods, clamps, nuts, bolts and


washers.

G. Rollers: Non-Binding Heavy-Duty SBR Rubber.

2.3 EQUIPMENT SUPPORTS

A. Non-Penetrating Roof Equipment Support System: Engineered prefabricated


support system custom designed by Advanced Support Products to be installed on
roof without adhesives, roof penetrations, flashings or damage to roofing system.
1. Base: Injected molded polypropylene, 3 inches (76 mm) high by 17
inches (432 mm) in diameter, designed for weight disbursement, with molded
insert for square tubing and two threaded rod couplings molded in for support
of structural steel frame.
2. Design to fit the roof slope as required.

B. Mechanically Fastened Steel Base System: Engineered prefabricated support


system custom designed by Advanced Support Products to be mechanically
fastened to comply with design/performance requirements.
1. Base shall consist of a 12 inches (305 mm) square galvanized steel
plate, 1/4 inch (6.4 mm) thick, with four holes for approved anchoring with
galvanized square tubing welded to plate as receiver for support of structural
steel frame with the opening covered.
2. Design to fit the roof slope as required.
3. Coordinate flashing and waterproofing of the support with Section
07700 Membrane Roofing.

2.4 EQUIPMENT PLATFORMS

15060-4
A. Equipment Platform: Equipment platform to support telecommunications
equipment, generators, HVAC equipment or miscellaneous equipment use
equipment platform, custom designed by Advanced Support Products for either
rooftop or land site applications. Equipment platforms shall be constructed as
follows:
1. Non-Penetrating Roof Equipment Support System:
a. Design to support frame, utilize base with no roof penetrations.
b. Frame fabricated of steel angle or channel and square tubing or
strut as required to suit design loads.
c. Deck fabricated of steel grating attached with hardware,
provided.
d. Handrails fabricated of 1-1/2 inch (38 mm) galvanized steel pipe,
as required.
e. Design to include the number and spacing of bases required to
support the weight of the equipment and load requirements.
2. Mechanically Fastened Steel Base System:
a. Design to support frame, utilizing 12 inch (305 mm) square
galvanized steel plate, 1/4 inch (6.4 mm) thick, with four holes for
anchoring to roof system.
b. Frame fabricated of steel I-beam or channel, connections
conforming to the AISC Manual of Steel Construction.
c. Deck fabricated of steel grating, attached with hardware,
provided.
d. Handrails made fabricated of 1-1/2 inch (38 mm) pipe, as
required.
e. Equipment platform designed to support weight of the equipment
based on load requirements.

2.5 PIPE AND DUCT SUPPORTS:

A. Conduit or Pipe Up to 1/2 inch (12.5 mm) Diameter: Model # SS1000B Pipe
Support with Strut Bar. Use with circular base with double sided strut inserted into
center cavity. Use strut clamps to secure pipe.

B. Conduit or Pipe Up to up to 8 inch (203 mm) Diameter Without Height


Adjustment: Model # SS1000 Pipe Support. Use with circular base with 12 gauge
framing channel, 18 inches long, attached directly to base using 1/2 inch (12.5 mm)
bolts. Strut clamps may be used as option for securing pipe.

C. Conduit or Pipe Up to up to 8 inch (203 mm) Diameter With Height


Adjustment: Model # SS1000A Adjustable Pipe Support. Use with circular base with
12 gauge framing channel, 18 inches long and attached to circular base using 1/2
inch (12.5 mm) threaded rods, 12 inches (305 mm) long, with washers and nuts.
Height of channel can be adjusted along the length of the threaded rods. Strut
clamps are recommended to hold piping or conduit in place.

D. Water or Gas Piping Up to 8 inch (203 mm) Diameter With Roller Support:
Model # SS1000R Pipe Support with Roller. Use with circular base with SBR heavy-
duty rubber roller assembly attached directly to base with 1/2 inch (12.5 mm) bolts.

E. Water or Gas Piping Up to 8 inch Diameter With Roller Support and Height
Adjustment: Model # SS1000RA Pipe Support with Adjustable Roller. Use with
circular base with SBR heavy-duty rubber roller assembly attached to circular base

15060-5
using 1/2 inch (12.5 mm) threaded rods, 12 inches (305 mm) long, with washers and
nuts. Height of roller assembly can be adjusted along the length of the 1/2 inch (12.5
mm) threaded rods.

F. Piping in Multiple Runs:


1. Cross Brace Bridge Model SS2000/36. Fabricated of two circular bases
and framing channel 36 inches long attached directly to the bases using 1/2
inch (12.5 mm) bolts or 1/2 inch (12.5 mm) threaded rods with washers and
nuts, 12 inches (305 mm) long, Height of framing channel can be adjusted
along the length of the 1/2 inch (12.5 mm) threaded rod. Use with strut clamps
or roller accessories as required.
2. Cross Brace Bridge Model SS2000/48. Fabricated of two circular bases
and framing channel 48 inches (1219 mm) long attached directly to the bases
using 1/2 inch (12.5 mm) bolts or 1/2 inch (12.5 mm) threaded rods with
washers and nuts, 12 inches (305 mm) long, Height of framing channel can
be adjusted along the length of the 1/2 inch (12.5 mm) threaded rod. Use with
strut clamps or roller accessories as required.
3. Cross Brace Bridge Model SS2000/60. Fabricated of two circular bases
and framing channel 60 inches (1524 mm) long attached directly to the bases
using 1/2 inch (12.5 mm) bolts or 1/2 inch (12.5 mm) threaded rods with
washers and nuts, 12 inches l(12.5 mm) long, Height of framing channel can
be adjusted along the length of the 1/2 inch (12.5 mm) threaded rod. Use with
strut clamps or roller accessories as required.

G. Conduit or Pipe Up to up to 4 inch (102 mm) Diameter When Height


Adjustment or Pipe Suspension is Required:
1. Model # SS1000H Hanging Pipe Support for single pipe. Use with
circular base with 12 gauge framing channel, 18 inches (457 mm) long,
attached to base using 1/2 inch (12.5 mm) threaded rods, 12 inches (305 mm)
long, with one hanger attached to channel using 1/2 inch (12.5 mm) threaded
rod to suspend piping at heights beginning at 3 inches (76 mm). Height of
channel can be adjusted along the length of the threaded rods. Height of
hanger can be adjusted along the length of the threaded rod.
2. SS1000T Hanging Pipe Support Tee for two pipes. Use with circular
base with 12 gauge framing channel formed to make a "T" shape with two
hangers attached to channel using 1/2 inch (12.5 mm) threaded rods on each
side of the "T" to suspend piping at heights beginning at 3 inches (76 mm).
Height of hanger can be adjusted along the length of the threaded rods.

H. Piping in Multiple Runs Up to 12 inch (305 mm) Diameter When Height


Adjustment or Pipe Suspension is Required:
1. SS4000P Adjustable Support Bridge is made of four circular bases and
12 gauge framing channel formed to make one "H" shaped support with
crossbar.
2. SS6000P Adjustable Support Bridge is made of six circular bases and
12 gauge framing channel formed to make two "H" shaped supports with
crossbar.
3. SS8000P Adjustable Support Bridge is made of eight circular bases
and 12 gauge framing channel formed to make three "H" shaped supports
with crossbar.
4. Crossbar height is adjustable: Provide in the following length:
a. 18 inches (457 mm).
b. 24 inches (610 mm).

15060-6
c. 36 inches (914 mm).
d. 48 inches (1219 mm).
5. Use with strut clamps or roller accessories.
6. Use with hanger supports to suspend water or gas piping at various
heights.
a. Hanger supports attached to support frame using 1/2 inch (12.5
mm) threaded rods. Hangers offer complete height adjustments along
the length of threaded rods.

I. HVAC Duct and Cable Tray Supports: use Model # SS2000D Duct Support.
Use with two circular bases with 12 gauge framing channel formed to make an "H"
shaped support. Framing channel is adjustable in both height and width.

J. Light Weight HVAC Equipment Supports:


1. Model #SS1000EC Equipment Support Corner used with one circular
base and 12 gauge Unistrut P9000 and P9200 with 6 inch (152 mm)
galvanized steel support bracket formed for a corner.
2. Model #SS1000E Equipment Support Stand. SS1000E is one circular
base and 12 gauge Unistrut P9000 and P9200 with 6 inch (152 mm)
galvanized steel support bracket.

K. Heavier HVAC Equipment Supports: Provide equipment platform designed by


to support the weight of the equipment and load requirements indicated on the
Drawings.
1. Equipment platform consists of circular bases supporting a structural
steel frame
2. Equipment platform consists of galvanized steel plates, with four holes
for approved anchoring and supporting a structural steel frame.

2.6 FABRICATION

A. Fit and shop assemble in largest practical sections, for delivery to site and
field bolted assembly.

B. Fabricate components with joints tightly fitted and secured.

C. Supply components required for anchorage of fabrications.

PART 3 EXECUTION
3.1 EXAMINATION

A. Do not begin installation until substrates have been properly prepared.

B. Verify that roof surface is smooth and clean.

C. If substrate preparation is the responsibility of another installer, notify


Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

A. Clean surfaces thoroughly prior to installation.

15060-7
B. Clean surfaces to receive supports removing any loose gravel and any
foreign matter.

C. Prepare surfaces using the methods recommended by the manufacturer for


achieving the best result for the substrate under the project conditions.

3.3 INSTALLATION

A. Install in accordance with manufacturer's instructions and approved shop


drawings.

B. Allow for erection loads, and for sufficient temporary bracing to maintain
fabrications safe, plumb, and in alignment until completion of erection and
installation of permanent bracing.

C. Non-Penetrating Supports:
1. Accurately locate and align pre-fabricated supports.
2. Isolation pads are not required under circular bases.
3. Should the roofing manufacturer require a separation sheet between
the roof and the support system, place a separation sheet or protective pad
conforming to the existing roof manufacturer's system under circular bases.
Do not adhere bases to the roof system.

D. Mechanical Supports:
1. Accurately locate and align pre-fabricated supports.
2. Coordinate flashing and waterproofing of the support with Section
07700 Membrane Roofing.

E. If required, insert frame structures into circular bases as indicated by


manufacturer's instructions.

F. Adjust height of each strut or channel and hanger or roller to its required
height and tighten with nut, but do not over-tighten. Check each support for equal
weight disbursement. Correct if necessary.

G. After erection, touch up abrasions to match shop finishes.

H. Remove any unused materials and packaging from job site.

3.4 FIELD QUALITY CONTROL

A. Underlayment manufacturers representative to verify that installation of


underlayment and perimeter isolation barrier is in conformance to the manufacturer's
recommendations as required under warrantee provisions.

3.5 PROTECTION

A. Protect installed products until completion of project.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION

15060-8
SECTION 15076

PIPING AND VALVE IDENTIFICATION

Display hidden notes to specifier. (Don't know how? Click Here)


Copyright 2003 - 2008 ARCAT, Inc. - All rights reserved

15060-9
PART 4 GENERAL
4.1 SECTION INCLUDES

A. Pipe markers.

B. Stencils.

C. Valve tags.

D. Valve chart frames.

E. Engraved acrylic plastic nameplates.

4.2 RELATED SECTIONS

A. Section 09900 - Paints and Coatings: Identification painting.

4.3 REFERENCES

A. ASME (ANSI) A13.1 - Scheme for the Identification of Piping Systems.

B. IIAR Bulletin 114 - Ammonia Refrigeration and Piping System Components


Identification; International Institute of Ammonia Refrigeration.

C. NFPA 99C - Gas and Vacuum Systems.

4.4 SYSTEM DESCRIPTION

A. Color Coding and Nomenclature for Building Piping: Conform to ASME


(ANSI) A13.1.

B. Color Coding and Nomenclature for Medical Gas Piping: Conform to NFPA
99C.

C. Color Coding and Nomenclature for Pulp and Paper Processing Materials
Piping: Conform to OSHA.

D. Color Coding and Nomenclature for Ammonia Refrigerant Piping: Conform


IIAR Bulletin 14.

4.5 SUBMITTALS

A. Submit under provisions of Section 01300.

B. Submit list of wording, symbols, letter size, and color coding for piping
identification.

C. Submit list of wording, symbols, letter size, and color coding for valve
identification.

D. Product Data: Provide manufacturers catalog literature for each product


specified.

15060-10
E. Samples: Submit two labels, indicating type and quality of products to be
installed.

F. Manufacturer's Installation Instructions: Indicate special procedures, and


installation.

PART 5 PRODUCTS
5.1 MANUFACTURERS

A. Acceptable Manufacturer: Seton Identification Products, which is located at:


20 Thompson Rd. ; Branford, CT 06405-2842; Toll Free Tel: 800-243-6624; Tel: 203-
488-8059; Email: request info (aecinfo@seton.com); Web: www.seton.com

5.2 MANUFACTURED UNITS

A. Pipe Markers for Indoor Use: Seton Setmark; snap-around type plastic
markers with direction-of-flow arrows for pipe sizes to 5-7/8 inches diameter, strap-
around type with nylon ties for pipe sizes 6 inches diameter and larger.

B. Pipe Markers for Indoor Use: Seton Opti-Code; media indicator on pressure-
sensitive vinyl sheet. Use with "on-a-roll tape"to conform with ASME A13.1 to
provide direction of flow.

C. Pipe Markers for Indoor Use: Seton Seton-Code; media indicator on


pressure-sensitive vinyl sheet, with detachable direction-of-flow arrows.

D. Pipe Markers for Indoor Use: Roll-form pipe markers; media indicator with
direct-of-flow arrows on pressure-sensitive vinyl tape roll.

E. Pipe Markers for Harsh Environments: Seton Xtreme-Code; media indicator


on pressure-sensitive over-laminated polyester sheet.

F. Pipe Markers for Harsh Environments: Seton Ultra-Mark; media indicator and
direction-of-flow arrows on weather-resistant pressure-sensitive polyester sheet.

G. Pipe Markers for Outdoor Use: Seton Weather-Code; media indicator and
detachable direction-of-flow arrows on weather-resistant pressure-sensitive vinyl
sheet; service temperature -40 degrees F to 175 degrees F.

H. Pulp and Paper Processing Materials Pipe Markers: Conforming to OSHA,


and 29 CFR 1910.261; media indicator with direction-of-flow arrows on vinyl roll.

I. Ammonia Refrigeration Piping Markers: Conforming to IIAR requirements;


media indicator with direction-of-flow arrows on vinyl roll.

J. Medical Gas Pipe Markers: Conforming to NFPA 99C and CGA C-9; media
indicator on vinyl tape roll.

K. Medical Gas Pipe Markers: Conforming to NFPA 99C and CGA C-9; media
indicator on pressure-sensitive vinyl sheet.

L. Direction-Of-Flow Arrows: Seton Arrows-On-A-Roll; direction-of-flow arrows


on pressure-sensitive vinyl tape roll.

15060-11
M. Pipe Stencils: Factory-cut stencils with media indicator and direction-of-flow
arrows.

N. Valve Tags:
1. Media and identification number imprinted on tag.
2. Tag material: Plastic.
3. Tag material: Brass.
4. Tag material: Aluminum.
5. Tag material: Stainless steel.

O. Valve Tag Securing Devices:


1. Provide one securing device for each tag in accepted schedule.
2. Device type: Number 6 brass bead chain.
3. Device type: Number 6 nickel-plated steel bead chain.
4. Device type: Number 16 brass jack chain.
5. Device type: Number 16 zinc-plated steel jack chain.
6. Device type: Brass "S" hook.

P. Valve Chart Frame:


1. Size: For included 8-1/2 inches by 11 inches chart.
2. Materials: Aluminum frame, plastic window.

Q. Engraved Acrylic Plastic Name Plates:


1. Materials: 1/16 inch multi-layered acrylic plastic.
2. Colors: Brown, yellow, green, blue, black, red, white, and orange as
selected.

PART 6 EXECUTION
6.1 PREPARATION

A. Degrease and clean surfaces to receive identification materials.

B. Prepare surfaces in accordance with Section 09900 for stencil painting.

6.2 INSTALLATION

A. Install pipe markers in accordance with accepted shop drawings and


manufacturer's instructions.

B. Install valve tags in accordance with accepted shop drawings and


manufacturer's instructions.

END OF SECTION

15060-12
SECTION 15080

DUCT AND PLENUM INSULATION

Display hidden notes to specifier. (Don't know how? Click Here)


Copyright 2009 - 2011 ARCAT, Inc. - All rights reserved

PART 7 GENERAL
7.1 SECTION INCLUDES

A. Duct insulation to achieve a 2-hour fire-resistive ventilation duct assembly.

B. Plenum insulation to achieve a non-combustible rating for combustible


materials in an air plenum.

C. Duct insulation to achieve zero clearance to combustibles and a 2-hour fire-


resistive rated duct enclosure on commercial kitchen grease duct exhaust and
hazardous exhaust duct systems.

7.2 RELATED SECTIONS

A. Section 07210 - Building Insulation: Thermal insulation, both fire rated and
unrated.

7.3 REFERENCES

A. The following published specifications, standards, or tests that apply to single


layer, fire - resistive rated ventilation air duct (VAD) insulation:
1. International Organization for Standardization, Fire resistance tests
ventilation air ducts (ISO 6944).
2. International Code Council (ICC).
3. International Building Code (IBC).
4. International Mechanical Code (IMC).
5. ASTM C 411 - Standard Test Method for Hot-Surface Performance of
High-Temperature Thermal Insulation.
6. ASTM E 84 - Standard Test Method for Surface Burning Characteristics
of Building Materials.
7. ASTM E 119 - Standard Test Method for Fire Tests of Building

15060-13
Construction Materials.
8. ASTM E 814 - Standard Test Method for Fire Tests of Through-
Penetration Fire Stops.

B. The following published specifications, standards, tests, or recommended


methods of trade, industry, or governmental organizations apply to single layer
noncombustible fire rated plenum insulation:
1. UL 1887 - Visible Flame and Smoke Characteristics for Plastic Pipe.
2. ASTM E 84/UL 723 - Surface Burning Characteristics.
3. ASTM E 136 - Non-combustibility.

C. The following published specifications, standards, or tests that apply to zero


clearance two layer fire rated systems of grease duct insulation and hazardous
exhaust duct insulation:
1. NFPA 96.
2. International Code Council Evaluation Service (ICCES).
3. 1997 ICBO Uniform Mechanical Code (ICBO UMC).
4. 1997 Uniform Building Code (UBC).
5. 2006 International Mechanical Code (IMC).
6. 2006 Uniform Mechanical Code (IAPMO UMC).
7. ASTM E 2336 - Standard Test Methods for Fire Resistance Rated
Grease Duct Enclosures.
8. ASTM E 84 - Standard Test Method for Surface Burning Characteristics
of Building Materials.
9. ASTM E 119 - Standard Test Methods for Fire Tests of Building
Construction and Materials.
10. ASTM E 136 - Standard Test Method for Noncombustiblity.
11. ASTM E 518 - Standard Test for Durability.
12. ASTM E 814 - Standard Test Method for Fire Tests of Through-
Penetration Fire Stops

7.4 SYSTEM DESCRIPTION

A. A lightweight, non-asbestos, bio-soluble, high temperature, inorganic, foil


encapsulated insulation blanket. The duct wrap system shall be a tested and listed
system evaluated for a 2-hour fire resistance rating on a ventilation air duct
assembly. Testing shall be conducted by a nationally recognized testing laboratory.
1. Performance Requirements:
a. Single Layer System for two hour fire rating.
b. 2-hour fire resistive enclosure assembly tested per ISO 6944.
c. Firestop tested per ASTM E 814, 2 Hour F and T Ratings.
d. Meets 25/50 Flame and Smoke Ratings per ASTM E 84.

B. A lightweight, non-asbestos, bio-soluble, high temperature, inorganic, foil


encapsulated insulation blanket. The plenum insulation system shall be tested and
listed to provide a non combustible rating for combustible items located in air
plenums.
1. Performance Requirements:
a. Single Layer System of 1/2 inch (13 mm) thick material.
b. Meets UL 1887 test criteria for visible flame and smoke
characteristics.

15060-14
c. Meets 25/50 Flame and Smoke Ratings per ASTM E 84.
d. Insulation and combustible item must be tested as an assembly.

C. A lightweight, non-asbestos, bio-soluble, high temperature, inorganic, foil


encapsulated insulation blanket. The blanket material must capable of performing at
2000 degree F (1093 degree C) matching the internal and external fire test
temperature for grease ducts. The duct wrap system shall be a tested and listed
system evaluated for reduced clearances to combustibles as an alternative to a
grease duct, with a two-hour fire rated shaft enclosure. Testing shall be conducted
at a nationally recognized testing laboratory.
1. Performance Requirements:
a. Two-layer system of 1-1/2 inch (38 mm) 6 pcf (96 kg/m3)
material.
b. Zero clearance to combustibles across the entire surface of the
blanket material per internal fire tests of ASTM E 2336.
c. 2-hour fire resistive enclosure assembly per ASTM E 119.
d. Firestop tested per ASTM E 814, 2 Hour F and T Ratings.
e. Meets 25/50 flame and smoke ratings per ASTM E 84.

7.5 SUBMITTALS

A. Submit under provisions of Section 01300.

B. Product Data: Manufacturer's data sheets on each product to be used,


including:
1. Preparation instructions and recommendations.
2. Storage and handling requirements and recommendations.
3. Installation methods.

C. Submit certification and installation documentation showing system


performance and Code compliance.

7.6 QUALITY ASSURANCE

A. Manufacturer Qualifications: Manufacturer capable of providing field service


representation during installation.

B. Fabricator Qualifications: Fabrication performed in quality controlled


manufacturing environment by experienced fabricators with references indicating
multiple satisfactory experiences fabricating high temperature insulation blanket as
required for this project.

C. Installer Qualifications: Installer experienced in performing work of this section


who has specialized in installation of work similar to that required for this project.

D. Mock-Up: Provide a mock-up for evaluation of surface preparation


techniques and application workmanship.
1. Finish areas designated by Architect.
2. Do not proceed with remaining work until workmanship, color, and
sheen are approved by Architect.
3. Refinish mock-up area as required to produce acceptable work.

15060-15
E. Preinstallation Meetings: Conduct preinstallation meeting to verify project
requirements, manufacturer's installation instructions and manufacturer's warranty
requirements. Comply with Division 01 Project Management and Coordination
(Project Meetings).

7.7 DELIVERY, STORAGE, AND HANDLING

A. Deliver materials in original unopened packages, clearly marked with


manufacturer's name, product designation, manufacturer's lot numbers and
appropriate third party classification listings.

B. Store in a covered dry environment.

C. Store and dispose of solvent-based materials, and materials used with


solvent-based materials, in accordance with requirements of local authorities having
jurisdiction.

7.8 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation)


within limits recommended by manufacturer for optimum results. Do not install
products under environmental conditions outside manufacturer's absolute limits.

PART 8 PRODUCTS
8.1 MANUFACTURERS

A. Acceptable Manufacturer: Unifrax I LLC, which is located at: 2351 Whirlpool


St. ; Niagara Falls, NY 14305-2413; Tel: 716-278-3800; Email: request info
(info@unifrax.com); Web:
www.unifrax.com/web/UnifraxHome3.nsf/AllDocuments/B4E2717A9E597B8C85256
A6500703A65?OpenDocument

B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of


Section 01600.

8.2 DUCT INSULATION FOR FIRE RATED VENTILATION AIR DUCTS (VAD)

A. Product: FyreWrap Elite 1.5 Duct Insulation by Unifrax I LLC, Niagara Falls,
NY:
1. Nominal 1.5 inch (38 mm) thick foil encapsulated blanket material at 6
PCF to provide 2-hour fire resistive enclosure assembly per ISO 6944.
2. An inorganic, flexible, non-asbestos, bio-soluble high temperature, foil
encapsulated blanket material.
3. Blanket insulation must maintain a 2012 degree F (1100 degree C)
operating temperature
4. Blanket fiber materials must be tested per EU regulatory requirements,
Directive 97/69/EC for bio-solubility, and verified by an independent
laboratory.
5. Provide Firestop sealants, tape, insulation pins, clips, banding and
other components to ensure the installed system complies with the complete
tested two-hour fire rated VAD assembly.

15060-16
8.3 PLENUM INSULATION FOR NONCOMBUSTIBLE FIRE RATED PLENUM

A. Product: FyreWrap 0.5 Plenum Insulation by Unifrax I LLC, Niagara Falls, NY:
1. Nominal 0.5 inches (12 mm) thick foil encapsulated blanket material to
provide non combustible rating.
2. An inorganic, flexible, non-asbestos, bio-soluble high temperature, foil
encapsulated blanket material.
3. Blanket insulation must maintain a 2012 degree F (1100 degree C)
operating temperature
4. Blanket fiber materials must be tested per EU regulatory requirements,
Directive 97/69/EC for bio-solubility, and verified by an independent
laboratory.

8.4 DUCT INSULATION FOR ZERO CLEARANCE APPLIED FIREPROOFING FOR


FIRE-RATED GREASE DUCTS

A. Product: FyreWrap Elite 1.5 Duct Insulation by Unifrax I LLC, Niagara Falls,
NY:
1. Nominal 1.5 inch (38 mm) thick foil encapsulated blanket material at 6
PCF to provide 2-hour fire resistive enclosure assembly per ASTM E 2336.
2. A lightweight, flexible, inorganic, non-asbestos, bio-soluble, high
temperature, foil encapsulated blanket wrap.
3. Flexible, fully encapsulated blanket material, two-layer system to
provide 2-hour fire resistive enclosure assembly per ASTM E 2336.
4. Blanket insulation must maintain a 2012 degree F (1100 degree C)
operating temperature.
5. Blanket fiber materials must be tested per EU regulatory requirements,
Directive 97/69/EC for bio-solubility, and verified by an independent
laboratory.
6. Provide field fabricated or prefabricated fire rated access doors (for
cleanout as required) to maintain 2-hour rating and required clearance.
7. Provide Firestop sealants, tape, insulation pins, clips, banding and
other components as per manufacturer's instructions to provide fully
functioning zero clearance to combustibles grease duct system.

8.5 ACCESS DOORS

A. Access Door: Field fabricated 16 gauge steel.


1. Threaded Rods: 1/4 inch (6 mm) diameter.
2. Gasket: 1/2 inch (13 mm) Unfaced FyreWrap or ceramic fiber blanket.

B. Access Door: Ductmate Ultimate prefabricated 16 gauge steel.

C. Access Door: Ductmate F2 prefabricated 16 gauge steel.

PART 9 EXECUTION
9.1 EXAMINATION

A. Do not begin installation until substrates have been properly prepared.

B. If substrate preparation is the responsibility of another installer, notify

15060-17
Architect of unsatisfactory preparation before proceeding.

9.2 PREPARATION

A. Inspect and verify that all surfaces are smooth, dry, clean and free from dust,
debris, or other loose materials. Surfaces must be dry before the application of
insulation materials.

B. Clean surfaces thoroughly prior to installation.

C. Prepare surfaces using the methods recommended by the manufacturer for


achieving the best result for the substrate under the project conditions.

9.3 INSTALLATION

A. Duct Insulation (HVAC Ducts):


1. Single-Layer System: Apply single layer encapsulated insulation
directly to duct surface.
2. Install with minimum 3 inch (76mm) material joint overlap.
3. Seal cut edges with aluminum foil tape
4. Attachment for duct widths of 24 inches (610 mm) or less:
a. Temporarily secure duct insulation with 1 inch (25.4 mm) wide
filament tape located 1-1/2 inches (38 mm) from blanket edge and on
10-1/2 inch (267 mm) centers.
b. Permanently attach blanket with carbon steel or stainless steel
banding located 1-1/2 inches (38 mm) from blanket edge and on 10-1/2
inch (267 mm) centers.
c. Tighten steel bands to secure insulation firmly without damaging
blanket.
5. Attachment for duct widths greater than 24 inches (610 mm):
a. Weld 12 gauge steel insulation pins to underside of horizontal
runs and backside of vertical runs in rows spaced maximum 10 1/2
inches (267 mm) on center along duct length, 6 inches - 12 inches (152
- 305 mm) from duct edges.
b. Space pins 12 inches (305 mm) on center across duct width.
c. Impale insulation over pins and hold in place with 2-1/2 inch (64
mm) square galvanized steel speed clips (washers).
d. Turn down or cut off exposed pin ends.

B. Plenum Insulation:
1. Apply single layer encapsulated insulation directly to surface of
combustible item.
2. Cut insulation lengths to wrap around combustible item providing 1 inch
(25.4 mm) longitudinal overlap.
3. Seal cut edges with aluminum foil tape.
4. Provide 1 inch (25.4 mm) perimeter overlap with adjacent insulation
blanket.
5. Temporarily secure plenum insulation with 1 inch (25.4 mm) wide
filament tape, located 1/2 inch (12.7 mm) from blanket edge and on 11 inch
(280 mm) centers.
6. Permanently attach insulation with steel tie wire or banding on
maximum 11 inch centers (279 mm).

15060-18
7. Tighten wire or banding to secure insulation firmly without damaging
blanket.

C. Duct Insulation (Grease and Hazardous Exhaust Ducts):


1. Two-Layer System: Apply two-layers of encapsulated insulation
directly on duct surface.
2. Install first layer with transverse material compression joints. Install first
layer longitudinal joints with minimum 3 inch (76mm) material joint overlaps.
3. Install second layer with minimum 3 inch (76mm) material joint
overlaps, offset minimum of 12 inches (305mm) from first layer joints.
4. Seal cut edges with aluminum foil tape.
5. Transverse material joints may be installed using any of the following
techniques:
a. Telescope overlap - insulation installed by leaving one edge
exposed and overlapping other edge with adjacent blanket.
b. Checkerboard overlap - overlap both edges of alternating
blanket, leaving both edges of others exposed.
c. Butt Joint & collar - cover blanket butt edges with 6 inch
(152mm) blanket collar centered on material joint.
6. Banding for duct widths 24 inches (610 mm) or less:
a. Temporarily secure insulation with filament tape.
b. Place carbon steel or stainless steel bands (minimum 1/2 inch
(12.7 mm) wide, nominal 0.015 inch (0.4 mm) thick) 1-1/2 inches (38
mm) from edge of overlap joints.
c. Place bands at maximum 10-1/2 inches (267 mm) on center in
field between overlaps.
d. Tighten steel bands to secure insulation firmly without damaging
blanket.
7. Pins and Banding for duct widths greater than 24 inches (610 mm) up
through 48 inches (1220 mm):
a. Weld 12 gauge steel insulation pins to underside of horizontal
runs and backside of vertical runs in rows spaced maximum 10-1/2
inches (267 mm) on center along duct length.
b. Space pins 12 inches (305 mm) on center across duct width and
1-1/2 inches (38 mm) from duct edges.
c. Impale insulation over pins and hold in place with 2-1/2 inch (64
mm) square galvanized steel speed clips (washers).
d. Secure insulation to duct with filament tape as needed.
e. Turn down or cut off exposed pin ends.
f. Locate carbon steel or stainless steel bands (minimum 1/2 inch
(12.7 mm) wide, nominal 0.015 inch (0.4 mm) thick) 1-1/2 inches (38
mm) from edge of overlap joints.
g. Space remaining bands at midpoint between overlap joints or at
10-1/2 inches (267 mm) oc. Tighten steel bands to secure insulation
firmly without damaging blanket.
8. Pins for ducts wider than 48 inches (1220 mm):
a. Weld 12 gauge steel insulation pins on all sides of duct in rows
spaced maximum 10 1/2 inches (267 mm) on center along duct length.
b. Space pins 8 inches (203 mm) on center around duct and 5
inches (127 mm) from duct edges. Center insulation overlaps on pins.
c. Impale insulation over pins and hold in place with 2-1/2 inch (64

15060-19
mm) square galvanized steel speed clips (washers).
d. Turn down or cut off exposed pin ends.
9. Vertical Ductwork: Apply insulation in continuous length parallel to
vertical length of duct with overlaps minimum of 6 inches (152 mm) from duct
corners. Space pins 8 inches (203 mm) on center at centerline of vertically
oriented overlaps and on maximum 12 inch (305 mm) columns.

9.4 ACCESS DOORS

A. Field-Fabricated:
1. Cut and remove installed insulation to dimension 2 inches (51 mm)
larger than opening.
2. Seal cut edges of remaining insulation with aluminum foil tape.
3. Cut access opening in duct.
4. 1/4 inch (6.4 mm) diameter threaded rod to corners of opening.
5. Cover rods with hollow steel tubes.
6. Cut 16 gauge cover plate with dimensions 2 inches (51 mm) larger
than opening.
7. Drill holes in cover plate to match rod pattern.
8. Place 1/2 inch (12.7 mm) ceramic fiber or unfaced FyreWrap blanket
gasket between duct and access door cover.
9. Install cover over rods.
10. Single Layer: Weld 4 steel insulation pins to outside of door panel, 1
inch (25.4 mm) from corners.
11. Double Layer: Weld 5 steel insulation pins to outside of door panel, 1
inch (25.4 mm) from corners.
12. Cut first insulation piece to size of access door, seal cut edges with
aluminum foil tape and install over pins within cutout area.
13. Cut second insulation piece with dimensions 2 inches (51 mm) larger
than first piece, seal cut edges with aluminum foil tape and install over pins.
14. Cut third insulation piece (for 2-Layer grease duct systems only) with
dimensions 2 inches (51 mm) larger than second piece, seal cut edges with
aluminum foil tape and install over pins.
15. Place washers on pins and bend over excess pin lengths.
16. Place washers on threaded rods and secure with nuts.
B. Pre-fabricated: Ductmate Industries - Ultimate and F-2 access door to be
prefabricated from 16 gauge steel and installed as one unit.

9.5 MAINTENANCE

A. Cut banding or insulation washers on damaged blanket areas and remove.

B. Cut and remove damaged blanket.

C. Cut new blanket piece with exact dimensions as that removed and install on
ductwork in same configuration as previously used in compliance with required
material overlaps and attachment methods.

D. Ensure same minimum overlap is created.

E. Replace permanent attachment.

15060-20
9.6 FIELD QUALITY CONTROL

A. Have manufacturer of products supplied under this Section review Work


involved in handling, installation/application and protection of its products, and
submit written reports in acceptable format to verify compliance of Work with
Contract.

B. Schedule site visits to review Work as installation is about to begin.

9.7 PROTECTION

A. Protect installed products until completion of project.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION

SECTION 15080

15060-21
FIRE RATED DUCT INSULATION

Display hidden notes to specifier. (Don't know how? Click Here)


Copyright 2009 - 2009 ARCAT, Inc. - All rights reserved

PART 10 GENERAL
10.1 SECTION INCLUDES
A. Rated Duct Wraps.

10.2 RELATED SECTIONS


A. Section 04200 - Unit Masonry.

B. Section 07840 - Firestopping.

C. Section 09260 - Gypsum Wallboard Assemblies.

D. Section 15810 - Ducts.

E. Section 15820 - Duct Accessories.

10.3 REFERENCES
A. ASTM C 518 - Standard Test Method for Steady-State Thermal Transmission
Properties by Means of the Heat Flow Meter Apparatus.

B. ASTM C 1338 - Fungi Resistance of Insulation Materials and Facings


Standard.

C. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of


Building Materials.

D. ASTM E 119 (UL 263) - Standard Test Methods for Fire Tests of Building
Construction and Materials.

E. ASTM E 136 - Standard Test Method for Behavior of Materials in a Vertical


Tube Furnace at 750C.

F. ASTM E 814 - Fire Tests of Through-Penetration Fire Stops Standard.

G. ASTM E 2336 - Standard Test Methods for Fire Resistive Grease Duct
Enclosure Systems.

H. International Code Congress (ICC):


1. ternational Building Code (IBC).
2. International Mechanical Code (IMC)

15060-22
3. International Residential Code (IRC).

I. ISO 6944: Fire Resistive Tests - Ventilation Ducts; 1985.

J. NFPA 96 - Standard for Ventilation Control and Fire Protection of Commercial


Cooking Operations.

10.4 PERFORMANCE REQUIREMENTS


A. Listing Agency: Provide products that are listed by at least one the following:
1. Underwriters Laboratories Inc. (UL), in "Fire Resistance Directory"
category XHEZ or XHBN as appropriate.
2. Omega Point Laboratories (OPL), in "Directory of Listed Products,
Through Penetration Fire Resistance Directory."
3. Any other qualified independent testing and inspection agency that
conducts periodic follow-up inspections and is acceptable to authorities
having jurisdiction.

B. Furnish products identical to those tested for classification by listing agency.

C. Mark product packing with classification marking of listing agency.

D. Firestopping Exposed to View: Provide products with flame spread index of


less than 25 and smoke developed index of less than 450, when tested in
accordance with ASTM E 84.

E. Firestopping Exposed to View, Traffic, Moisture, or Physical Damage:


Provide products that after curing do not deteriorate when exposed to those
conditions during and after construction.

F. Materials: Use only products specifically listed for use in listed systems.

G. Compatibility: Provide products that are compatible with each other, with the
substrates forming openings, and with the items, if any, penetrating the firestopping,
under the conditions represented by this project, based on testing and field
performance demonstrated by manufacturer.

H. Firestopping material must be asbestos-free and capable of maintaining an


effective barrier against flame, smoke and gases in compliance with the
requirements of ASTM and UL standards cited in this section.

I. Firestopping materials must meet and be acceptable for use by all building
codes and NFPA codes cited in this section.

J. Materials must be suitable for the firestopping of penetrations made by steel,


glass, plastic and insulated pipe.

K. Firestop Listings: The following is only a partial list of ASTM E 814 tested
through-penetration designs. Consult with the manufacturer for more information.
1. UL: W-L-7180, W-J-7104, C-AJ-7096, F-C-7054.
2. Omega Point Laboratories: 3MU/PH 120-14 (FS 559 W), 3MU/PV 120-
03 (FS 560 F), 3MU/PV 120-04 (FS 561 F), 3MU/PH 120-20 (FS 572 W),
3MU/PH 120-07 (FS 578 F), 3MU/PH 120-29 (FS 579 W).

15060-23
L. Fire Rating: All duct wraps must be One (1) hour rated, but in no case less
than the rating of any time-rated assemblies which are penetrated.

M. Fire Rating: All duct wraps must be Two (2) hour rated, but in no case less
than the rating of any time-rated assemblies which are penetrated.

10.5 SUBMITTALS
A. Submit under provisions of Section 01300.

B. Shop Drawings: For each different firestopping configuration, provide the


following:
1. Listing agency's detailed drawing showing opening, penetrating items,
and firestopping materials, identified with listing agency's name and number
or designation, fire rating achieved, and date of listing.
2. Identify which rated assembly each system is to be used in.
3. Any installation instructions that are not included on the detailed
drawing.
4. For proposed systems that do not conform strictly to the listing, submit
listing agency's drawing marked to show modifications and stamped approved
by firestop system manufacturer's fire protection engineer.
5. Submit listing agency's test report showing compliance with
requirements, based on testing of current products.

C. Product Certificates: Submit certificates signed by firestop system


manufacturer certifying that materials furnished comply with requirements.

D. Product Data: Manufacturer's data sheets on each material to be used in


firestop system systems, including:
1. Product characteristics and Material Safety Data Sheets.
2. Listing numbers of systems in which each product is to be used.
3. Preparation instructions and recommendations.
4. Storage and handling requirements and recommendations.
5. Installation methods.

E. Installer's Qualification Documentation.

F. Verification Samples: For each finish product specified, two samples


representing actual product, color, and patterns.

10.6 QUALITY ASSURANCE


A. General: All through-penetration firestop systems shall be installed with
approved methods using materials that have been tested and classified to produce
an approved assembly.

B. Manufacturer Qualifications: All primary products specified in this section will


be supplied by a single manufacturer with a minimum of ten (10) years experience.

C. Installer Qualifications: Firm must be qualified by having experience, staff,


and training to install the specified products, and meets the following criteria:
1. Contractor is a 3M Master Contractor.

15060-24
2. Contractor is a Certified 3M Trained contractor.
3. Contractor is acceptable to or licensed by manufacturer.
4. Contractor is acceptable to or licensed by authority having jurisdiction.
5. Contractor has completed the manufacturer's certified product
installation training.
6. Contractor must provide a list of completed projects as evidence of
experience; include project name and address, Owner's name and address,
and Architect's name and phone number.

D. Codes: Where manufacturer's application procedures are in conflict with


those of the code authority having jurisdiction, the more strict guidelines will prevail.

10.7 DELIVERY, STORAGE, AND HANDLING


A. Deliver and store products until ready for installation in manufacturer's original
unopened packaging, legibly marked with manufacturer's name and product
identification, date of manufacture, lot number, shelf life, listing agency's
classification marking, curing time, and mixing instructions if applicable.

B. Store and handle in such a manner as to prevent deterioration or damage due


to moisture, temperature changes, contaminants, and other causes; follow
manufacturer's instructions.

C. Store and dispose of hazardous materials, and materials contaminated by


hazardous materials, in accordance with requirements of local authorities having
jurisdiction.

10.8 PROJECT CONDITIONS


A. Coordinate construction and cutting of openings so that each particular
firestop system may be installed in accordance with its listing, including sizing,
sleeves, and penetrating items.

B. Maintain environmental conditions (temperature, humidity, and ventilation)


within limits recommended by manufacturer for optimum results. Do not install
firestopping under environmental conditions outside manufacturer's absolute limits.

C. Provide ventilation as required by firestopping manufacturer, including


mechanical ventilation if required.

10.9 WARRANTY
A. At project closeout, provide to Owner or Owners Representative an executed
copy of the manufacturer's standard limited warranty against manufacturing defect,
outlining its terms, conditions, and exclusions from coverage.

PART 11 PRODUCTS
11.1 MANUFACTURERS
A. Acceptable Manufacturer: 3M Fire Protection Products, which is located at:
3M Center Bldg. 223-2N-21 ; St. Paul, MN 55144-1000; Toll Free Tel: 800-328-1687;
Email: jemannix@mmm.com; Web: www.3m.com/firestop

15060-25
B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of


Section 01600.

11.2 SCOPE/APPLICATION
A. Provide fire protection to grease and air ducts as a shaft alternative.

B. Provide installed firestopping that limits the spread of fire¸ heat¸ smoke¸ and
gasses through otherwise unprotected openings in rated assemblies¸ including
walls¸ partitions¸ floors¸ roof/ceilings¸ etc.

11.3 FIRE RATED DUCT WRAP INSULATION


A. 3M Fire Barrier Duct Wrap 615+: Lightweight¸ non-asbestos¸ high
temperature¸ bio-soluble¸ calcium-magnesium-silicate (CMS) non-woven blanket¸
encapsulated in a scrim-reinforced foil¸ blanket thickness of 1.5 inches (38mm) for
ventilation and grease duct applications.
1. Color: White blanket, aluminum foil encapsulated.
2. Weight: 0.9 psf (4.38 kg/m2).
3. Density: 6 pcf nominal.
4. Thermal Conductivity (k-value) at 500 Degrees F (260 Degrees C)
(ÅSTM C411, ÅSTM C518): 0.48 Btu/(ft2 x h x F) (0.07 W/(m x K)).
5. R-Value per ÅSTM C 518 at ambient (77 F/ 25 C): at least 6.3 (F-ft2-
hr / Btu)
6. Service range up to 2000 degree F (1093 degree C)
7. Fire Resistance: For use in 1 hour fire resistant systems.
8. Fire Resistance: For use in 2 hour fire resistant systems.
9. Product complies with ÅSTM E 2336 test standard.
10. Product complies with ISO 6944 test standard.
11. Through-penetration per ÅSTM E 814 (UL 1479)
12. Non-combustible per ASTM E 136
11.4 RELATED DUCT WRAP PRODUCTS
A. Firestop Tapes:
1. High performance filament tape, 3M No. 898 1 inch (25mm) wide.
2. FSK Facing Tape with aluminum foil¸ fiberglass scrim¸ kraft paper
backing: nominal 3 inches (76mm) or 4 inches (102mm) wide (for sealing cut
blanket edges and seams)¸ 3M No. 3320.

B. Banding Material: Stainless or carbon steel banding: 1/2 inch (13mm) wide X
0.015 inch (0.4mm) thick¸ as stated in duct wrap Design Listing.

C. Insulation pins and clips:


1. Copper-coated steel pins¸ 12 gauge with a minimum length of 4 inches
(102mm) with square galvanized steel speed clips: 2.5 inch (64mm). .
2. 12 gauge insulated cup head steel pins.

D. Through-penetration firestop materials:

15060-26
1. Packing materials: Pieces of 3M Fire Barrier Duct Wrap¸ or 4 pcf
mineral wool.
2. Sealants: 3M Fire Barrier: 1000 NS non-slump silicone sealant¸ 1003
SL self-leveling silicone sealant¸ 2000+ premium non-slump silicone sealant¸
or CP 25WB+ premium intumescent latex caulk¸ as stated in firestop Design
Listing.

PART 12 EXECUTION
A. Do not begin installation until substrates have been properly prepared.

B. Conduct tests according to manufacturer's written recommendations to verify


that substrates are free of oil, grease, rolling compounds, incompatible primers,
loose mill scale, dirt and other foreign substances capable of impairing bond of
firestopping.

C. Verify that items penetrating fire rated assemblies are securely attached,
including sleeves, supports, hangers, and clips.

D. Verify that openings and adjacent areas are not obstructed by construction
that would interfere with installation of firestopping, including ducts, piping,
equipment, and other suspended construction.

E. Verify that environmental conditions are safe and suitable for installation of
firestopping.

F. If substrate preparation is the responsibility of another installer, notify


Architect of unsatisfactory preparation before proceeding.

12.2 PREPARATION
A. Prepare substrates in accordance with manufacturer's instructions and
recommendations.

B. Install masking and temporary coverings as required to prevent contamination


or defacement of adjacent surfaces due to firestopping installation.

12.3 INSTALLATION - GENERAL


A. Install in strict accordance with manufacturer's detailed installation
instructions and procedures.

B. Install so that openings are completely filled and material is securely adhered.

C. Where firestopping surface will be exposed to view, finish to a smooth,


uniform surface flush with adjacent surfaces.

D. After installation is complete, remove combustible forming materials and


accessories that are not part of the listed system.

E. Repair or replace defective installations to comply with requirements.

F. At each through penetration, attach identification labels on both sides in


location where label will be visible to anyone seeking to remove penetrating items or

15060-27
firestopping.

G. Clean firestop materials off surfaces adjacent to openings as work


progresses, using methods and cleaning materials approved in writing by firestop
system manufacturer and which will not damage the surfaces being cleaned.

H. Notify authority having jurisdiction when firestopping installation is ready for


inspection; obtain advance approval of anticipated inspection dates and phasing, if
any, required to allow subsequent construction to proceed.

I. Do not cover firestopping with other construction until approval of authority


having jurisdiction has been received.

12.4 FIRE RATED DUCT WRAP INSULATION (1 AND 2 HR. ENCLOSURES)


A. Kitchen Exhaust Grease Ducts: Install fire resistive duct wrap insulation in
direct contact with ductwork to Manufacturer's instructions and referenced
standards, to applicable Omega Point Laboratories design numbers, including listed
penetration firestop system.
1. For kitchen exhaust grease ducts, regardless of fire rating, provide two
layers of 3M Fire Barrier Duct Wrap 615+ per layer with 3 inch (76mm)
overlaps.

B. Kitchen Exhaust Ductwork: Overlap perimeter and longitudinal joints 3 inches


(76mm) or 3 inches (76mm) on both layers. If required, tape seams using minimum
3 inch (76mm) wide aluminium foil adhesive tape.

C. Ventilation Air Ducts (1 and 2 hr. Enclosure): Install fire resistive duct wrap
insulation in direct contact with ductwork to Manufacturer's instructions and
referenced standards, including Listed penetration firestop system.
1. Apply fire resistive duct wrap insulation continuously to ductwork as
indicated on Drawings. For ventilation air ducts, provide one layer of 3M Fire
Barrier Duct Wrap 615+ with 3 inch (76mm) overlaps for 1 and 2 hour
applications. Observe requirements for additional duct wrap material required
at firestop, when required.

D. Ventilation Ductwork (1 and 2 hr. applications): overlap perimeter and


longitudinal joints 3 inches (76mm). If required, tape seams using minimum 3 inch
(76mm) wide aluminium foil adhesive tape.

E. Filament tape may be used as a temporary securing measure during


application of duct wrap. Finish installation using 1/2 inch (13mm) wide by 0.015
inch (0.4mm) steel banding on exterior layer of wrap. Spacing 10.5 inches (267mm)
on center and within 1.5 inches (39mm) of all overlapped seams. Consult individual
listings for approved banding type.

F. Duct Widths Greater than 24 Inches (610mm): Weld insulation pins to bottom
of horizontal ducts on a 12 inch (305mm) by 10.5 inch (267mm) maximum grid
spacing. Welded insulation pins to one of the wider sides of all vertical ducts on a
12 inch (305mm) by 10.5 inch (267mm) maximum grid spacing. Impale duct wrap
insulation over pins and secure with speed clips.

G. Duct Access Doors: Install duct wrap to Manufacturer's instructions and


procedures.

15060-28
H. Firestopping At Fire Separations:
1. Firestop all wrapped ductwork penetrating fire rated concrete floors,
gypsum board, block and concrete wall assemblies and gypsum board
shaftwall assemblies using UL and/or Omega Point Laboratories firestop
system Listings appropriate for the applicable duct wrap system .
2. Kitchen exhaust grease ducts: Fire resistive duct wrap insulation to be
continuous through wall or floor penetrations. Minimum 0.5 inch (13mm),
maximum 4.5 inch (114mm) clearance permitted between outer layer of duct
wrap insulation and edge of opening. Fill annular space between edge of
opening and wrapped duct with pieces of 3M duct wrap insulation or mineral
wool insulation firmly packed into opening. Compress to percentage stated
and minimum depth stated in firestop listing. Recess packing material below
surface on both sides of walls or top side only for floors to depth stated in
firestop listing. Seal over packing material using 3M firestop sealant to depth
stated in firestop listing, flush with top side of floor and both sides of wall
surfaces.
3. Ventilation ducts: Fire resistive insulation may pass continuously
through fire rated wall or floor penetrations or may tightly butt to both sides of
fire rated separations. Minimum 1 inch (25mm), maximum 3 inch (76mm)
clearance permitted around unwrapped duct in opening or from edge of
opening to outer layer of duct wrap. Consult individual Listed firestop systems
for specific requirements.
a. Option A: Terminate wrap at fire separation. Fill space around
unwrapped duct where it passes through a fire rated wall or floor with
pieces of 3M duct wrap insulation or mineral wool insulation firmly
packed into opening. Compress to the percentage stated in the firestop
listing to full depth of floor or wall. Recess packing on both sides of
walls or top side of floor to depth stated in firestop listing. Seal over
packing material using 3M firestop sealant to depth stated in firestop
listing, flush with top side of floor and both sides of wall surfaces.
Tightly butt fire resistive duct wrap insulation to each side of wall or
floor assembly and seal interface with a continuous bead of 3M firestop
sealant.
b. Option B: Wrap continuous through fire separation. Fill space
around continuously wrapped duct where it passes through fire rated
wall or floor with pieces of 3M duct wrap insulation or mineral wool
insulation firmly packed into opening and compress to the percentage
stated in the firestop listing to a minimum depth of 4". Recess packing
material below surface on both sides of wall or top side of floor to depth
stated in firestop listing. Seal over packing material using 3M firestop
sealant to depth stated in firestop listing, flush with top side of floor and
both sides of wall surfaces.

I. Where kitchen exhaust hoods are located within a fire rated area or zone,
begin application of duct wrap insulation inside fire rated area 6 inches (152mm)
from face of fire rated wall or ceiling assembly for non-combustible fire separations,
and 18 inches (457mm) from face of wall or ceiling surface inside fire rated area for
combustible fire separations, or as indicated on the Drawings. Apply two layers of
duct wrap continuously to ductwork through fire separation for distance indicated on
the Drawings.

12.5 FIELD QUALITY CONTROL


A. Owner will engage an independent testing agency to inspect installed

15060-29
firestopping and to prepare reports indicating whether the installed work complies
with the contract documents.

B. Notify testing agency at least 7 days prior to date when firestopping


installation will be ready for inspection; obtain advance approval of general schedule
and phasing, if any, required to allow subsequent construction to proceed.

12.6 CLEANING AND PROTECTION


A. Remove left over material and debris from Work area. Use necessary means
to protect film before, during, and after installation.

B. Touch-up, repair or replace damaged products before Substantial Completion.

C. Install identification Labels for Through Penetration Systems: Pressure


sensitive self-adhesive vinyl labels, preprinted with the following information:
1. The words "Warning - Through Penetration Firestop System - Do not
Disturb. Notify Building Management of Any Damage."
2. Listing agency's system number or designation.
3. System manufacturer's name, address, and phone number.
4. Installer's name, address, and phone number.
5. General contractor's name, address, and phone number (if applicable).
6. Date of installation.

END OF SECTION

SECTION 15410

PLUMBING FIXTURES

Display hidden notes to specifier. (Don't know how? Click Here)


Copyright 2010 - 2011 ARCAT, Inc. - All rights reserved

PART 13 GENERAL
13.1 SECTION INCLUDES
A. Plumbing fixtures and trim including the following:
1. Pedestal sinks.
2. Drop-in sinks.
3. Undermount sinks.
4. Wall mounted sinks.

15060-30
5. Toilets.
6. Bidets.
7. Urinals.

13.2 RELATED SECTIONS


A. Section 15050 - Basic Mechanical Materials and Methods.

B. Section 15400 - Plumbing Fixtures and Equipment.

13.3 REFERENCES
A. American National Standards Institute (ANSI):
1. ANSI A 117.1 - Accessible and Usable Buildings and Facilities
2. ANSI A112.19.2 - Standard for vitreous china plumbing fixtures and
hydraulic requirements for water closets and urinals.
3. ANSI A112.19.6 - Hydraulic Performance Requirements for Water
Closets and Urinals.

13.4 SUBMITTALS
A. Submit under provisions of Section 01300.

B. Product Data: Manufacturer's data sheets on each product to be used,


including:
1. Preparation instructions and recommendations.
2. Storage and handling requirements and recommendations.
3. Installation methods.
4. Cleaning and maintenance instructions.

C. Shop Drawings: Provide shop drawings indicating details of construction and


installation.

D. Selection Samples: For each finish product specified, two complete sets of
color chips representing manufacturer's full range of available colors and patterns.

E. Verification Samples: For each finish product specified, two samples,


minimum size 6 inches (150 mm) square, representing actual product, color, and
patterns.

13.5 QUALITY ASSURANCE


A. Mock-Up: Provide a mock-up for evaluation of surface preparation techniques
and application workmanship.
1. Finish areas designated by Architect.
2. Do not proceed with remaining work until workmanship, color, and
sheen are approved by Architect.
3. Refinish mock-up area as required to produce acceptable work.

13.6 DELIVERY, STORAGE AND HANDLING


A. Deliver, store and handle materials and products in strict compliance with

15060-31
manufacturer's instructions and recommendations and industry standards. Store
materials within absolute limits for temperature and humidity recommended by the
manufacturer. Protect from damage.

B. Store products in manufacturer's labeled packaging until ready for installation.

13.7 PROJECT CONDITIONS


A. Maintain environmental conditions (temperature, humidity, and ventilation)
within limits recommended by manufacturer for optimum results. Do not install
products under environmental conditions outside manufacturer's absolute limits.

13.8 SEQUENCING AND SCHEDULING


A. Conference: Convene a pre-installation conference to establish procedures to
maintain optimum working conditions and to coordinate this work with related and
adjacent work.

13.9 WARRANTY
A. Manufacturer's standard limited warranty for materials and workmanship.
1. Warranty Period: 1 year for parts and fittings.
2. Warranty Period: 5 years for vitreous china.

PART 14 PRODUCTS
14.1 MANUFACTURERS
A. Acceptable Manufacturer: Contrac, which is located at: 5970 Chedworth Way,
Unit A ; Mississauga, ON; Canada L5R 3V5; Toll Free Tel: 888-256-7551; Tel: 905-
507-2005; Email: request info (contrac@foremostgroups.com); Web:
contrac.ca/index.php
1. Email: customerservice@foremostgroups.com.
2. Web: contrac.ca/index.php.
3. Address: 5970 Chedworth Way, Unit A; Mississauga, ON; Canada L5R
3V5. ASD. Toll Free Tel: 888-256-7551. Tel: 905-507-2005. Fax: 905-507-
2006.
4. Address: 906 Murray Road East Hanover, NJ 07936. ASD. Toll Free:
800-443-1410 Tel: 973-428-0400.

B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of


Section 01600.

14.2 PEDESTAL SINKS


A. Pedestal Sinks: Caprice - Square Pedestal Lavatory as manufactured by
Contrac.
1. Sink: Model 4343DMX - Basin with 4 inch (102 mm) Faucet Center.
2. Sink: Model 4383DMX - Basin with 8 inch (203 mm) Faucet Center.
3. Pedestal: Model 4344DMX - Pedestal leg.
4. Description: Square pedestal basin with rear overflow hole; template

15060-32
supplied, faucet and pop-up not included.
5. Mounting: Mounting hardware supplied with unit.
6. Materials: Vitreous china.
7. Finish: Soft White.
8. Finish: Bone.
9. Finish: Biscuit.

B. Pedestal Sinks: Carley - Round Pedestal Lavatory as manufactured by


Contrac.
1. Sink: Model 5343DMX - Basin with 4 inch (102 mm) Faucet Center.
2. Sink: Model 5383DMX - Basin with 8 inch (203 mm) Faucet Center.
3. Pedestal: Model 5344DMX - Pedestal leg.
4. Description: Round pedestal basin with rear overflow hole; template
supplied, faucet and pop-up not included.
5. Mounting: Mounting hardware supplied with unit.
6. Materials: Vitreous china.
7. Finish: Soft White.

14.3 DROP-IN SINKS


A. Drop-In Sinks: Catalina - Oval Drop-In Sink as manufactured by Contrac.
1. Model: 4110BGW - Single Hole for Faucet.
2. Model: 4140BGW - 4 inch (102 mm) Faucet Center.
3. Model: 4180BGW - 8 inch (203 mm) Faucet Center.
4. Description: Oval drop-in basin with front overflow hole; template
supplied, faucet and pop-up not included.
5. Materials: Vitreous china.
6. Finish: Soft White.
7. Finish: Bone.
8. Finish: Biscuit.

B. Drop-In Sinks: Cailyn - Round Drop-In Sink as manufactured by Contrac.


1. Model: 4110BRW - Single Hole for Faucet.
2. Model: 4140BRW - 4 inch (102 mm) Faucet Center.
3. Model: 4180BRW - 8 inch (203 mm) Faucet Center.
4. Description: Round drop-in basin with front overflow hole; template
supplied, faucet and pop-up not included.
5. Materials: Vitreous china.
6. Finish: Soft White.

C. Drop-In Sinks: Curtis - Semi-Oval Drop-In Sink as manufactured by Contrac.


1. Model: 4140BEW - 4 inch (102 mm) Faucet Center.
2. Description: Semi-oval drop-in basin with front overflow hole; template
supplied, faucet and pop-up not included.
3. Materials: Vitreous china.
4. Finish: Soft White.

14.4 UNDERMOUNT SINKS

15060-33
A. Undermount Sinks: Connor - 17 inch (432 mm) Oval Undermount Sink as
manufactured by Contrac.
1. Model: 4210CFY.
2. Description: Oval basin with front overflow hole; template supplied,
faucet and pop-up not included.
3. Mounting: Mounting kit supplied with unit.
4. Materials: Vitreous china.
5. Finish: Soft White.

B. Undermount Sinks: Calvin - 19-1/4 inch (489 mm) Oval Undermount Sink as
manufactured by Contrac.
1. Model: 4220CFY.
2. Description: Oval basin with front overflow hole; template supplied,
faucet and pop-up not included.
3. Mounting: Mounting kit supplied with unit.
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Materials: Vitreous china.
7. Finish: Soft White.
8. Finish: Bone.
9. Finish: Biscuit.

C. Undermount Sinks: Camden - 16 inch (406 mm) Square Undermount Sink as


manufactured by Contrac.
1. Model: 4210CHY.
2. Description: Square basin with front overflow hole; template supplied,
faucet and pop-up not included.
3. Mounting: Mounting kit supplied with unit.
4. Materials: Vitreous china.
5. Finish: Soft White.

D. Undermount Sinks: Catena - 20 inch (208 mm) Rectangular Undermount Sink


as manufactured by Contrac.
1. Model: 4210CIY.
2. Description: Rectangular basin with front overflow hole; template
supplied, faucet and pop-up not included.
3. Mounting: Mounting kit supplied with unit.
4. Materials: Vitreous china.
5. Finish: Soft White.

E. Undermount Sinks: Cachet - 21.5 inches (546 mm) Rectangular Undermount


Sink as manufactured by Contrac.
1. Model: 4220CIY.
2. Description: Rectangular basin with front overflow hole; template
supplied, faucet and pop-up not included.
3. Mounting: Mounting kit supplied with unit.
4. Materials: Vitreous china.
5. Finish: Soft White.

14.5 WALL MOUNTED SINKS

15060-34
A. Wall Mounted Sinks: Chelsea - Wall Mounted Sink as manufactured by
Contrac.
1. Model: 4640BHW - Basin with 4 inch (102 mm) Faucet Center.
2. Description: Wall mount basin with front overflow hole; faucet and pop-
up not included.
3. Mounting: Mounting hardware supplied with unit.
4. Mounting: Mounting hardware supplied with unit, with metal support
legs by others.
5. Materials: Vitreous china.
6. Finish: Soft White.

B. Wall Mounted Sinks: Carmin - Wall Mounted Sink as manufactured by


Contrac.
1. Model: 4640BHZ - Basin with 4 inch (102 mm) Faucet Center.
2. Description: Wall mount basin with backsplash ledge and rear overflow
hole; template supplied, faucet and pop-up not included.
3. Mounting: Mounting hardware supplied with unit.
4. Mounting: Mounting hardware supplied with unit, with concealed arm
carrier by others.
5. Materials: Vitreous china.
6. Finish: Soft White.

C. Wall Mounted Sinks: Cambridge - Wall Mounted Sink as manufactured by


Contrac.
1. Basin: Model 4640CHZ - Basin with 4 inch (102 mm) Faucet Center.
2. Shroud: Model 4644CHZ - Shroud.
3. Description: Wall mount basin with lower shroud and rear overflow
hole; template supplied, faucet and pop-up not included.
4. Mounting: Mounting hardware supplied with unit.
5. Mounting: Mounting hardware supplied with unit, with concealed arm
carrier by others.
6. Materials: Vitreous china.
7. Finish: Soft White.

D. Wall Mounted Sinks: Cassidy - Semi-Recessed Sink as manufactured by


Contrac.
1. Model: 4343DGX - Basin with 4 inch (102 mm) Faucet Center.
2. Description: Lavatory for wall secured vanity or cabinet with rear
overflow hole; template supplied, faucet and pop-up not included.
3. Mounting: Mounting hardware supplied with unit, 9-1/4 inch (235 mm)
front overhang.
4. Materials: Vitreous china.
5. Finish: Soft White.

14.6 TOILETS
A. Toilets: Carlin - 2 piece 6L Toilet as manufactured by Contrac.
1. Bowl: Model 4722BFT; toilet seat not included.
a. Description: Round front bowl.
b. Height: 15.5 inches (394 mm).

15060-35
2. Tank: Model 4721BFT-L - Lined, Locking Tank
a. Locking: Allen key locking mechanism.
b. Rough-In: 12 inches (305 mm).
3. Tank: Model 4721BFT - Lined Tank.
a. Maximum Performance: 500 g (17.6 oz).
b. Rough-In: 12 inches (305 mm).
4. Tank: Model 4721BFTU - Unlined Tank.
a. Maximum Performance: 500 g (17.6 oz).
b. Rough-In: 12 inches (305 mm).
5. Tank: Model 4721BFTU-RH - Unlined Tank, right hand lever.
a. Maximum Performance: 500 g (17.6 oz).
b. Rough-In: 12 inches (305 mm).
6. Tank: Model 4700BFTU - Unlined Tank.
a. Maximum Performance: 800 g (28.2 oz).
b. Rough-In: 10 inches (254 mm).
7. Tank: Model 4724BFTU - Unlined Tank.
a. Maximum Performance: 800 g (28.2 oz).
b. Rough-In: 14 inches (356 mm).
8. Materials: Vitreous china.
9. Finish: Soft White.
10. Finish: Bone.
11. Finish: Biscuit.
12. Water Usage: Low consumption, 6.0 Lpf/1.6 gpf.
13. Flushing: Siphon jet flush action.
14. Operation: Chrome trip lever.
15. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
16. Water Surface: 8-7/8 inches x 10-7/8 inches (225 mm x 275 mm).

B. Toilets: Carlin - 2 piece 4.8L HET Toilet as manufactured by Contrac.


1. Bowl: Model 4722BFV; toilet seat not included.
a. Description: Round front bowl.
b. Height: 15.5 inches (394 mm).
2. Tank: Model 4721BFT-L - Lined, Locking Tank.
a. Locking: Allen key locking mechanism.
b. Rough-In: 12 inches (305 mm).
3. Tank: Model 4721BFV - Lined Tank.
a. Rough-In: 12 inches (305 mm).
4. Tank: Model 4721BFVU - Unlined Tank.
a. Rough-In: 12 inches (305 mm).
5. Tank: Model 4721BFVU-RH - Unlined Tank, right hand lever.
a. Rough-In: 12 inches (305 mm).
6. Tank: Model 4724BFVU - Unlined Tank.
a. Rough-In: 14 inches (356 mm).
7. Materials: Vitreous china.
8. Finish: Soft White.
9. Finish: Bone.
10. Finish: Biscuit.

15060-36
11. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
12. Flushing: Siphon jet flush action.
13. Maximum Performance: 800 g (28.2 oz).
14. Operation: Chrome trip lever.
15. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.

C. Toilets: Cody - 2 piece 4.8L HET Toilet as manufactured by Contrac.


1. Bowl: Model 4722BEV; toilet seat not included.
a. Description: Round bowl.
b. Height: 15.5 inches (394 mm).
2. Tank: Model 4721BFT-L - Lined, Locking Tank
a. Locking: Allen key locking mechanism.
b. Rough-In: 12 inches (305 mm).
3. Tank: Model 4721BFV - Lined Tank.
a. Rough-In: 12 inches (305 mm).
4. Tank: Model 4721BFVU - Unlined Tank.
a. Rough-In: 12 inches (305 mm).
5. Tank: Model 4721BFVU-RH - Unlined Tank, right hand lever.
a. Rough-In: 12 inches (305 mm).
6. Tank: Model 4724BFVU - Unlined Tank.
a. Rough-In: 14 inches (356 mm).
7. Materials: Vitreous china.
8. Finish: Soft White.
9. Finish: Bone.
10. Finish: Biscuit.
11. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
12. Flushing: Siphon jet flush action.
13. Maximum Performance: 600 g (21.2 oz).
14. Operation: Chrome trip lever.
15. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
D. Toilets: Cody - 2 piece 6L Toilet as manufactured by Contrac.
1. Bowl: Model 4722BET; toilet seat not included.
a. Description: Elongated bowl.
b. Height: 15.5 inches (394 mm).
2. Tank: Model 4721BFT-L - Lined, Locking Tank
a. Locking: Allen key locking mechanism.
b. Rough-In: 12 inches (305 mm).
3. Tank: Model 4721BFV - Lined Tank.
a. Rough-In: 12 inches (305 mm).
4. Tank: Model 4721BFVU - Unlined Tank.
a. Rough-In: 12 inches (305 mm).
5. Tank: Model 4721BFVU-RH - Unlined Tank, right hand lever.
a. Rough-In: 12 inches (305 mm).
6. Materials: Vitreous china.
7. Finish: Soft White.
8. Finish: Bone.

15060-37
9. Finish: Biscuit.
10. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
11. Flushing: Siphon jet flush action, 100 percent factory flush tested.
12. Maximum Performance: 600 g (21.2 oz).
13. Operation: Chrome trip lever.
14. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
15. Water Surface: 8-1/2 inches x 6-1/2 inches (218 mm x 165 mm).

E. Toilets: Crista - 2 piece 4.8L HET Toilet as manufactured by Contrac.


1. Bowl: Model 4722BHV; toilet seat not included.
a. Description: Elongated bowl.
b. Height: 17 inches (432 mm).
2. Tank: Model 4721BFT-L - Lined, Locking Tank
a. Locking: Allen key locking mechanism.
b. Rough-In: 12 inches (305 mm).
3. Tank: Model 4721BFV - Lined Tank.
a. Rough-In: 12 inches (305 mm).
4. Tank: Model 4721BFVU - Unlined Tank.
a. Rough-In: 12 inches (305 mm).
5. Tank: Model 4721BFVU-RH - Unlined Tank, right hand lever.
a. Rough-In: 12 inches (305 mm).
6. Materials: Vitreous china.
7. Finish: Soft White.
8. Finish: Bone.
9. Finish: Biscuit.
10. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
11. Flushing: Siphon jet flush action.
12. Maximum Performance: 1000 g (35.3 oz).
13. Operation: Chrome trip lever.
14. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
15. Water Surface: 8-1/2 inches x 6-1/2 inches (218 mm x 165 mm).
F. Toilets: Crista - 2 piece 6L Toilet as manufactured by Contrac.
1. Bowl: Model 4722BIT; toilet seat not included.
a. Description: Rounded front bowl.
b. Height: 17 inches (432 mm).
2. Tank: Model 4721BFT-L - Lined, Locking Tank
a. Locking: Allen key locking mechanism.
b. Rough-In: 12 inches (305 mm).
3. Tank: Model 4721BFV - Lined Tank.
a. Rough-In: 12 inches (305 mm).
4. Tank: Model 4721BFVU - Unlined Tank.
a. Rough-In: 12 inches (305 mm).
5. Tank: Model 4721BFVU-RH - Unlined Tank, right hand lever.
a. Rough-In: 12 inches (305 mm).
6. Materials: Vitreous china.
7. Finish: Soft White.

15060-38
8. Finish: Bone.
9. Finish: Biscuit.
10. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
11. Flushing: Siphon jet flush action.
12. Maximum Performance: 600 g (21.2 oz).
13. Operation: Chrome trip lever.
14. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
15. Water Surface: 9-1/2 inches x 6-1/4 inches (240 mm x 160 mm).

G. Toilets: Carson - 2 piece 6/3L Dual Flush Toilet as manufactured by Contrac.


1. Tank and Bowl: Model 4720BFW - Lined Tank and Bowl Combo.
a. Description: Round front bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
2. Tank and Bowl: Model 4720BFWU - Unlined Tank and Bowl Combo.
a. Description: Round front bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
3. Tank and Bowl: Model 4720BFWU-RH - Unlined Tank and Bowl
Combo, right hand lever.
a. Description: Round front bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Rough-In: 12 inches (305 mm).
7. Water Usage: High Efficiency (HET), dual flush; 6.0 Lpf/1.6 gpf - 3.0
Lpf/0.8 gpf.
8. Flushing: Siphon jet flush action.
9. Maximum Performance: 800 g (28.2 oz).
10. Operation: Top push actuator.
11. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
12. Water Surface: 8-7/8 inches x 6-1/4 inches (225 mm x 160 mm).
H. Toilets: Camri - 2 piece 6/3L Dual Flush Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 4720BEW - Lined Tank and Bowl Combo.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
2. Tank and Bowl: Model 4720BEWU - Unlined Tank and Bowl Combo.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
3. Tank and Bowl: Model 4720BEWU-RH - Unlined Tank and Bowl
Combo, right hand lever.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Rough-In: 12 inches (305 mm).
7. Water Usage: High Efficiency (HET), dual flush; 6.0 Lpf/1.6 gpf - 3.0
Lpf/0.8 gpf.
8. Flushing: Siphon jet flush action, 100 percent factory flush tested.

15060-39
9. Maximum Performance: 800 g (28.2 oz).
10. Operation: Top push actuator.
11. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
12. Water Surface: 8 inches x 6 inches (205 mm x 150 mm).

I. Toilets: Cullen - 2 piece 6/3L Dual Flush Toilet as manufactured by Contrac.


1. Tank and Bowl: Model 4720BIW - Lined Tank and Bowl Combo.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 17 inches (432 mm).
2. Tank and Bowl: Model 4720BIWU - Unlined Tank and Bowl Combo.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 17 inches (432 mm).
3. Tank and Bowl: Model 4720BIWU-RH - Unlined Tank and Bowl Combo,
right hand lever.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 17 inches (432 mm).
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Rough-In: 12 inches (305 mm).
7. Water Usage: High Efficiency (HET), dual flush; 6.0 Lpf/1.6 gpf - 3.0
Lpf/0.8 gpf.
8. Flushing: Siphon jet flush action.
9. Maximum Performance: 800 g (28.2 oz).
10. Operation: Top push actuator.
11. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
12. Water Surface: 9-1/2 inches x 6-1/2 inches (240 mm x 165 mm).
J. Toilets: Cadell - 2 piece 3.8L HET Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5730BFVU - Unlined Tank and Bowl Combo.
a. Description: Regular round bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
2. Tank and Bowl: Model 5730BFVU-RH - Unlined Tank and Bowl Combo.
a. Description: Regular rounded bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
3. Materials: Vitreous china.
4. Finish: Soft White.
5. Rough-In: 12 inches (305 mm).
6. Water Usage: High Efficiency (HET), 3.8 Lpf/1.0 gpf.
7. Flushing: Siphon jet flush action.
8. Maximum Performance: 500 g (17.6 oz).
9. Operation: Tank lever actuator.
10. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
11. Water Surface: 9-1/2 inches x 6-1/2 inches (240 mm x 165 mm).
K. Toilets: Cato - 2 piece 3.8L HET Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5730BEVU - Unlined Tank and Bowl Combo.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).

15060-40
2. Tank and Bowl: Model 5730BEVU-RH - Unlined Tank and Bowl Combo,
right hand lever.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15.5 inches (394 mm).
3. Materials: Vitreous china.
4. Finish: Soft White.
5. Rough-In: 12 inches (305 mm).
6. Water Usage: High Efficiency (HET), 3.8 Lpf/1.0 gpf.
7. Flushing: Siphon jet flush action.
8. Maximum Performance: 500 g (17.6 oz).
9. Operation: Tank lever actuator.
10. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
11. Water Surface: 8 inches x 6 inches (205 mm x 150 mm).
L. Toilets: Clancy - 2 piece 3.8L HET Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5730BEVU - Unlined Tank and Bowl Combo.
a. Description: Regular round bowl; toilet seat not included.
b. Bowl Height: 17 inches (432 mm).
2. Tank and Bowl: Model 5730BEVU-RH - Unlined Tank and Bowl Combo,
right hand lever.
a. Description: Regular round bowl; toilet seat not included.
b. Bowl Height: 17 inches (394 mm).
3. Materials: Vitreous china.
4. Finish: Soft White.
5. Rough-In: 12 inches (305 mm).
6. Water Usage: High Efficiency (HET), 3.8 Lpf/1.0 gpf.
7. Flushing: Siphon jet flush action.
8. Maximum Performance: 600 g (21.2 oz).
9. Operation: Tank lever actuator.
10. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
11. Water Surface: 8-5/8 inches x 6-1/4 inches (220 mm x 160 mm).
M. Toilets: Case - 2 piece 3.8L HET Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5730BOVU - Unlined Tank and Bowl Combo.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 17 inches (432 mm).
2. Tank and Bowl: Model 5730BOVU-RH - Unlined Tank and Bowl
Combo, right hand lever.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 17 inches (394 mm).
3. Materials: Vitreous china.
4. Finish: Soft White.
5. Rough-In: 12 inches (305 mm).
6. Water Usage: High Efficiency (HET), 3.8 Lpf/1.0 gpf.
7. Flushing: Siphon jet flush action.
8. Maximum Performance: 500 g (17.6 oz).
9. Operation: Tank lever actuator.
10. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.

15060-41
11. Water Surface: 8-5/8 inches x 6-5/8 inches (220 mm x 170 mm).

N. Toilets: Chloe - 1 piece 6L Toilet as manufactured by Contrac.


1. Tank and Bowl: Model 5710BFT - Lined Tank; 1-piece.
a. Description: Rounded front bowl; toilet seat not included.
b. Bowl Height: 15-7/8 inches (403 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Finish: Bone.
5. Finish: Biscuit.
6. Rough-In: 12 inches (305 mm).
7. Water Usage: Low consumption, 6.0 Lpf/1.6 gpf.
8. Flushing: Siphon jet flush action, 100 percent factory flush tested.
9. Maximum Performance: 600 g (21.2 oz).
10. Operation: Tank lever actuator.
11. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
12. Water Surface: 7-7/8 inches x 6 inches (200 mm x 150 mm).
O. Toilets: Chloe - 1 piece 4.8L HET Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 4710BFV - Lined Tank; 1-piece.
a. Description: Regular round bowl; toilet seat not included.
b. Bowl Height: 15-3/4 inches (400 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Finish: Bone.
5. Finish: Biscuit.
6. Rough-In: 12 inches (305 mm).
7. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
8. Flushing: Siphon jet flush action, 100 percent factory flush tested.
9. Maximum Performance: 800 g (28.2 oz).
10. Operation: Tank lever actuator.
11. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
12. Water Surface: 8-1/4 inches x 6 inches (209 mm x 150 mm).
P. Toilets: Caden - 1 piece 6L Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5710BET - Lined Tank; 1-piece.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15-3/4 inches (400 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Finish: Bone.
5. Finish: Biscuit.
6. Rough-In: 12 inches (305 mm).
7. Water Usage: Low consumption, 6.0 Lpf/1.6 gpf.
8. Flushing: Siphon jet flush action, 100 percent factory flush tested.
9. Maximum Performance: 600 g (21.2 oz).
10. Operation: Tank lever actuator.

15060-42
11. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
12. Water Surface: 10-7/8 inches x 8-1/4 inches (275 mm x 210 mm).

Q. Toilets: Caden - 1 piece 4.8L HET Toilet as manufactured by Contrac.


1. Tank and Bowl: Model 4710BEV - Lined Tank; 1-piece.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15-3/4 inches (400 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Finish: Bone.
5. Finish: Biscuit.
6. Rough-In: 12 inches (305 mm).
7. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
8. Flushing: Siphon jet flush action, 100 percent factory flush tested.
9. Maximum Performance: 800 g (28.2 oz).
10. Operation: Tank lever actuator.
11. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
12. Water Surface: 9 inches x 6-1/4 inches (230 mm x 160 mm).
R. Toilets: Claire - 1 piece 6/3L Dual Flush Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5710BFWU - Unlined Tank; 1-piece.
a. Description: Regular round bowl; toilet seat not included.
b. Bowl Height: 15-1/2 inches (394 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Rough-In: 12 inches (305 mm).
5. Water Usage: High Efficiency (HET), dual flush; 6.0 Lpf/1.6 gpf - 3.0
Lpf/0.8 gpf.
6. Flushing: Siphon jet flush action.
7. Maximum Performance: 800 g (28.2 oz).
8. Operation: Top push actuator.
9. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
10. Water Surface: 8-1/4 inches x 6-1/8 inches (210 mm x 155 mm).
S. Toilets: Canby - 1 piece 6/3L Dual Flush Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5710BEWU - Unlined Tank; 1-piece.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15-3/4 inches (400 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Rough-In: 12 inches (305 mm).
5. Water Usage: High Efficiency (HET), dual flush; 6.0 Lpf/1.6 gpf - 3.0
Lpf/0.8 gpf.
6. Flushing: Siphon jet flush action.
7. Maximum Performance: 800 g (28.2 oz).
8. Operation: Top push actuator.
9. Trapway: 1-3/4 inches (44 mm) fully glazed ball pass trapway.
10. Water Surface: 8-7/8 inches x 6-1/2 inches (225 mm x 165 mm).

15060-43
T. Toilets: Cosby - 1 piece 4.8L HET Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 5710BFVU - Unlined Tank; 1-piece.
a. Description: Regular round bowl; toilet seat not included.
b. Bowl Height: 15-3/4 inches (400 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Rough-In: 12 inches (305 mm).
5. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
6. Flushing: Siphon jet flush action.
7. Maximum Performance: 800 g (28.2 oz).
8. Operation: Tank lever actuator.
9. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
10. Water Surface: 8-1/4 inches x 6-1/4 inches (210 mm x 160 mm).
U. Toilets: Captiva - 1 piece 4.8L HET Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 4710BIV - Unlined Tank; 1-piece.
a. Description: Regular round bowl; toilet seat not included.
b. Bowl Height: 15-3/4 inches (400 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Rough-In: 12 inches (305 mm).
5. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
6. Flushing: Siphon jet flush action.
7. Maximum Performance: 800 g (28.2 oz).
8. Operation: Top push actuator.
9. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
10. Water Surface: 8-5/8 inches x 6 inches (220 mm x 150 mm).
V. Toilets: Colter - Elongated Toilet as manufactured by Contrac.
1. Bowl: Model 4762BEX - Top Inlet.
2. Bowl: Model 4762BEU - Rear Inlet.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 15-1/8 inches (384 mm).
3. Mounting: Commercial floor mount.
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Rough-In: 10 inches (254 mm).
7. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
8. Water Usage: Provide optional Flushometer accessory.
a. High Efficiency (HET), 4.8 Lpf/1.28 gpf.
b. Flushometer, 6 Lpf/1.6 gpf.
9. Flushing: Siphon jet flush action.
10. Maximum Performance: 800 g (28.2 oz).
11. Operation: Manual flush valve actuator.
12. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
13. Water Surface: 10-5/8 inches x 7-1/4 inches (270 mm x 185 mm).

15060-44
W. Toilets: Clay - Elongated Toilet as manufactured by Contrac.
1. Bowl: Model 4762BOX - Top Inlet.
2. Bowl: Model 4762BOU - Rear Inlet.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 16-5/8 inches (422 mm).
3. Mounting: Commercial floor mount.
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Rough-In: 10 inches (254 mm).
7. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
8. Water Usage: Provide optional Flushometer accessory.
a. High Efficiency (HET), 4.8 Lpf/1.28 gpf.
b. Flushometer, 6 Lpf/1.6 gpf.
9. Flushing: Siphon jet flush action.
10. Maximum Performance: 800 g (28.2 oz).
11. Operation: Manual flush valve actuator.
12. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
13. Water Surface: 9-7/8 inches x 6-5/8 inches (250 mm x 170 mm).
X. Toilets: Clark - Elongated 4.8L Flushometer Toilet as manufactured by
Contrac.
1. Bowl: Model 4762CEX - Top Inlet.
2. Bowl: Model 4762CEU - Rear Inlet.
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: Variable.
3. Mounting: Commercial wall mount.
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Water Usage: High Efficiency (HET), 4.8 Lpf/1.28 gpf.
7. Water Usage: Provide optional Flushometer accessory.
a. High Efficiency (HET), 4.8 Lpf/1.28 gpf.
b. Flushometer, 6 Lpf/1.6 gpf.
8. Flushing: Siphon jet flush action.
9. Maximum Performance: 800 g (28.2 oz).
10. Operation: Manual flush valve actuator.
11. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
12. Water Surface: 10-1/4 inches x 8-5/8 inches (260 mm x 220 mm).
Y. Toilets: Cleo - 2 piece 3.8L HET Toilet as manufactured by Contrac.
1. Bowl: Model 5722BOY; toilet seat not included.
a. Description: Elongated bowl.
b. Bowl Height: 17 inches (432 mm).
2. Tank: Model 5721BOY - Unlined Tank.
3. Materials: Vitreous china.
4. Finish: Soft White.
5. Rough-In: 12 inches (305 mm).
6. Water Usage: High Efficiency (HET), 3.8 Lpf/1.0 gpf.

15060-45
7. Flushing: Siphon jet flush action with pressure assist technology.
8. Maximum Performance: 1000 g (35.3 oz).
9. Operation: Tank lever actuator.
10. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
11. Water Surface: 8 inches x 6-1/2 inches (203 mm x 165 mm).

Z. Toilets: Chane - 2 piece 3.8L HET Toilet as manufactured by Contrac.


1. Bowl: Model 5722BMY; toilet seat not included.
a. Description: Elongated bowl.
b. Bowl Height: 17 inches (432 mm).
2. Tank: Model 5721BOY - Unlined Tank.
3. Wall Connection: Rear outlet.
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Water Usage: High Efficiency (HET), 3.8 Lpf/1.0 gpf.
7. Flushing: Siphon jet flush action with pressure assist technology.
8. Maximum Performance: 1000 g (35.3 oz).
9. Operation: Tank lever actuator.
10. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
11. Water Surface: 11-5/8 inches x 7-7/8 inches (295 mm x 198 mm).
AA. Toilets: Caledon - 2 piece Kindergarten Toilet as manufactured by Contrac.
1. Tank and Bowl: Model 4760BKT - Lined Tank and Bowl Combo
a. Description: Elongated bowl; toilet seat not included.
b. Bowl Height: 11 inches (432 mm).
2. Materials: Vitreous china.
3. Finish: Soft White.
4. Water Usage: Low consumption, 6.0 Lpf/1.6 gpf.
5. Flushing: Siphon jet flush action.
6. Operation: Tank lever actuator.
7. Trapway: 2 inches (50 mm) fully glazed ball pass trapway.
8. Water Surface: 9-1/4 inches x 8-1/4 inches (235 mm x 210 mm).

14.7 BIDETS
A. Bidets: Cale - 4 Hole Bidet as manufactured by Contrac.
1. Model: 4830BLX.
2. Bowl Height: 15.5 inches (394 mm).
3. Mounting: Fits deck mounted fitting.
4. Description: Vertical cleansing spray with flushing rim and integral
overflow; with 3 faucet holes 8 inches (203 mm) on center and 1 small hole
for pop-up rod, faucet and pop-up not included.
5. Materials: Vitreous china.
6. Finish: Soft White.
7. Finish: Bone.
8. Finish: Biscuit.

14.8 URINALS

15060-46
A. Urinals: Calder - Wall Mount Urinal as manufactured by Contrac.
1. Model: 4810BEX - Top Inlet.
2. Model: 4810BEY - Rear Inlet.
3. Water Usage: High Efficiency, 1.9 Lpf/0.5 gpf.
4. Mounting: Mounting hardware supplied with unit.
5. Materials: Vitreous china.
6. Finish: Soft White.
7. Flushing: Washout flush action with flushing rim.
8. Inlet Spud: 3/4 inches (19 mm).
9. Outlet Spud: With 1.5 inch (38 mm) tubing tailpiece.
10. Drain: With integral strainer.
11. Accessory: Provide optional Flushometer.
B. Urinals: Carlo - Wall Mount Urinal as manufactured by Contrac.
1. Model: 4810BHX - Top Inlet.
2. Model: 4810BHY - Rear Inlet.
3. Water Usage: High Efficiency, 1.9 Lpf/0.5 gpf.
4. Mounting: Mounting hardware supplied with unit.
5. Materials: Vitreous china.
6. Finish: Soft White.
7. Flushing: Washout flush action with flushing rim.
8. Inlet Spud: 3/4 inches (19 mm).
9. Outlet Connection: Threaded 2 inches (51 mm) inside, National Pipe
Taper Fuel (NPTF).
10. Drain: With integral strainer.
11. Accessory: Provide optional Flushometer.
C. Urinals: Carlton - Wall Mount Urinal as manufactured by Contrac.
1. Model: 4810BFX - Top Inlet.
2. Water Usage: High Efficiency, 1.9 Lpf/0.5 gpf.
3. Mounting: Mounting hardware supplied with unit.
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Flushing: Washout flush action with flushing rim.
7. Top Inlet Spud: 3/4 inches (19 mm).
8. Outlet Connection: Threaded 2 inches (51 mm) inside, National Pipe
Taper Fuel (NPTF).
9. Drain: With integral strainer.
10. Accessory: Provide optional Flushometer.
D. Urinals: Canata - Wall Mount Urinal as manufactured by Contrac.
1. Model: 4810BMX - Top Inlet.
2. Water Usage: High Efficiency, 1.9 Lpf/0.5 gpf.
3. Mounting: Mounting hardware supplied with unit; elongated rim projects
13-7/8 inches (352 mm) from wall.
4. Materials: Vitreous china.
5. Finish: Soft White.
6. Flushing: Siphon jet flush action with flushing rim.

15060-47
7. Top Inlet Spud: 3/4 inches (19 mm).
8. Outlet Connection: Threaded 2 inches (51 mm) inside, National Pipe
Taper Fuel (NPTF).
9. Drain: With integral strainer.
10. Accessory: Provide optional Flushometer.
PART 15 EXECUTION
15.1 PREPARATION
A. Do not proceed with installation until substrates have been properly prepared
and deviations from manufacturer's recommended tolerances are corrected.
Commencement of installation constitutes acceptance of conditions.

B. Prepare substrates using the methods recommended by the manufacturer for


achieving the best result for the substrate under the project conditions.

C. If preparation is the responsibility of another installer, notify Architect in writing


of deviations from manufacturer's recommended installation tolerances and
conditions.

15.2 INSTALLATION
A. Install in accordance with manufacturer's written instructions and
recommendations.

15.3 CLEANING AND PROTECTION


A. Protect installed products until completion of project.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION