Open circuit and short circuit test of a 400 kVA, 200/400 V, 50 Hz, single phase
1 transformer gave the following test results. 4
OC test: 200 V, 1 A, 100 W (carried on L.V. side)
SC test: 15 V, 10 A, 85 W (carried on HV side)
i) Draw equivalent circuit as referred to L.V. Side
ii) Determine efficiency at full load and half the full load at 0.8 power factor.
2 The maximum efficiency of a 500 kVA, 3300/500 V, 50 Hz single phase
transformer is 97 % and occurs at 3/4 full load unity power factor. If the 4
impedance is 10%, calculate the regulation at full load 0.8 pf lagging.
Draw the phasor diagrams and connection schemes for each of the four phasor
3 groups pertaining to 3 phase transformer. 4