ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1

DATA :

1. Load on each Jacking Pad = 50 T


2. Total no. of Jacking Pad = 4
3. S.B.C of Soil = 15 T/sq.m AT 1.5m DEPTH AS PER GEOTECHNICAL REPORT
4. Sa = 0.3 g
5. Size of Footing = 4.7 m x 5.2 m
6. Load on each Wheel = 40 T

MATERIAL SPECIFICATION :

Concrete Grade : M - 20 N/mm2


Reinforcement Grade : Fe - 415 N/mm2

DESIGN CALCULATION :

Total load on Jacking Pad = 50 x 4


= 200 T

Self weight of Footing = 4.7 x 5.2 x 1.8 x 2.5


= 109.98 T

Total Load on Footing = 309.98 T

Footing area required = 309.98


15
= 20.67 M2

Footing area provided = 24.44 M2

DESIGN OF HORIZONTAL SEISMIC COEFFICIENT :-

From IS 1893- Part 1

Z x I x Sa
Ah =
2x Rxg

Z = Zone Factor = 0.1 For zone II


I = Importance Factor = 1.5
R = Response Reduction Factor = 3
Sa/g = Average Responce Acceleration
Coefficient for rock or soil sites = 0.3

0.1 X 1.5
Ah = X 2.99
2 X 3

Ah = 0.075

Base Shear = Vb = Ah x W

= 0.075 x 200 = 14.97 T


2

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1

Base shear will act CG of Transformer. Moment due to base shear create Up and Down force on Foundation
as shown :-

14.97 T
4.45 m

2.225 m
1.726 m
Rolling Center

Up and Down force on Footing = 14.97 x 2.225


2.00 x 1.726

= + 9.65 T

9.65 T 9.65 T

14.97 T
0.3 m

1.5 m W

4.7 m x 5.2 m

Moment at Footing level = 14.97 x 1.8


5.2

= 5.18 T.m/M
3

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1
Pmax = 309.98 T 5.18 X 6
+
4.7 m x 5.2 m 5.2 x 4.7 x 4.7

Pmax = 12.95 T / m2 < S.B.C = 15 T/sq.m

Pmin = 309.98 T 5.18 X 6


-
4.7 m x 5.2 m 5.2 x 4.7 x 4.7

Pmin = 12.41 T / m2

Y
4.7 m

3.15 m

5.2 m 0.775 5.442 m

Bending moment at sect. Y-Y = 12.95 x 0.775 x 0.775


2

= 3.89 T.m

Mu = Q x b x d x d

d= 3.890 x 107 x 1.5


2.760 x 1000

d= 145.41 mm

D= 145.41 + 50
D= 195.41 mm

Provided depth of Footing = D = 400 mm d = 350 mm

Mu
Ast Required in mm2 = Ast =
4

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1
Ast Required in mm2 = Ast =
0.87 x fy x 0.8 x d

= 3.890 x 107 x 1.5


0.87 x 415 x 0.8 x 350

= 577.22 mm2

Ast (min) = 0.12


x 1000 X 350
100

= 420 mm2

Provide 10 Tor at 100 mm c/c Bothways

0.12
Reinforcement in Block Pedestal = x 1000 X 1350
100

= 1620 mm2

Provide 16 Tor at 125 mm c/c Bothways

LOADING / DESIGN DETAILS OF FOOTING FOR RADIATOR HEADER SUPPORT (F1) :

Load = 6000 KG

Pedestal size = 350 x 350 mm

Footing size = 1000 x 1000 mm


= 1.00 M2

Bearing Stress = 6
1.00

= 6.00 T / m2
< 15 T / m2

1.0 M

0.35

1.0 M
0.35

0.325
5

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1

Bending moment = 6 x 0.325 x 0.325


2

= 0.32 T.m

Mu = Q x b x d x d

d= 0.317 x 107 x 1.5


2.760 x 1000

d= 41.50 mm

D= 41.50 + 50
D= 91.50 mm

Provide Depth = D = 250 mm

Mu
Ast Required in mm2 = Ast =
0.87 x fy x 0.8 x d

= 0.317 x 107 x 1.5


0.87 x 415 x 0.8 x 200

= 82.28 mm2

0.12
Ast (min) = x 1000 x 200
100 0

= 240 mm2

PEDESTAL DESIGN :

0.4
Min Reinforcement = x 350 x 350
100

= 490 mm2

Provide 8 Tor at 200 c/c rings

DESIGN OF FAN MTG. BRACKET SUPPORT (PD2) :

Load = 500 KG

Pedestal size = 350 x 350 mm

Footing size = 600 x 600 mm


6

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1
= 0.36 M2

Bearing Stress = 0.5


0.36

= 1.39 T / m2
< 15 T / m2

DESIGN OF MARSHALLING KIOSK MIN FOUNDATION (PD3) :

Load = 1000 KG

Pedestal size = 750 x 1650 mm

Footing size = 1050 x 1950 mm


= 2.05 M2

Bearing Stress = 1
2.05

= 0.5 T / m2
< 15 T / m2

750 mm 750 mm
300

1650 mm 12 Tor @ 100 c/c


500

200

1050 x 1950 mm

8 Tor @ 200 c/c (B/W)

Self weight of Footing = 0.75 x 1.65 x 0.8


= 0.99 T

Load = 1T

Total Load = 1.99 T

Footing size Provided = 1050 x 1950 mm

Bending moment = 0.49 x 0.15 x 0.15


2
7

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1
= ### Very less

0.12
Min Rienfocement = x 1000 X 150
100

= 180 mm2

Provide 8 Tor @ 200 c/c Bothway

PEDESTAL REINFORCEMENT :

0.12
Min Rienfocement = x 1000 x 800
100

= 960 mm2

Provide 12 Tor @ 100 c/c Bothway

DESIGN OF FOOTING FOR TRANSFORMER :

4.1 m

500

8.425 m

3.032 m

Total Load = 159 T

Self weight of Footing = 4.1 x 8.425 x 0.4 x 2.5


= 34.54 T

Self weight of Walls = 0.5 x 1.4 x 8.425 x 2 x 2.5


= 29.49 T

Total Load = 223.03 T


8

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1
Assuming 5% Earthquake Load = 223.03 x 0.05
= 11.15 T

Moment @ Footing level


= 11.1515 x 1.5
= 16.73 T.m

Pmax = 223.03 T 16.73 X 6


+
4.1 m x 8.425 m 8.425 x 4.1 x 4.1

Pmax = 7.17 T / m2 < S.B.C = 15 T/sq.m

Pmin = 223.03 T 16.73 X 6


-
4.1 m x 8.425 m 8.425 x 4.1 x 4.1

Pmin = 5.75 T / m2

Max Moment = B.M = wxl2


8

= 7.17 x 3.032 x 3.032


8
= 8.23 T.m

Mu 8.234 x 107 x 1.5


=
bxdxd 1000 x 350 x 350

= ###

pt % = 0.295

Ast = 0.295 x 1000 x 350


100

= 1032.5 mm2

Provide 16 Tor @ 175 mm c/c Top and Bottom (B/W)

DESIGN OF WALL FOR TRANSFORMER :

Load on each Wheel = 40 T

Assuming 5% earthquake load


= 80 x 0.05
9

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1
= 4 T

Moment at Base = 4 x 1.4


= 5.6 T.m

Mu 5.600 x 107 x 1.5


=
bxdxd 1000 x 450 x 450

= ###

pt % = 0.117

Ast = 0.117 x 1000 x 450


100

= 526.5 mm2

Provide 10 Tor at 120 mm c/c Each face

Provide 8 Tor at 200 mm c/c in Horizontal direction

DESIGN OF R.C.C SLAB AT ROAD :

Depth of R.C.C Slab = 150 mm

Dead Load of Slab = 0.15 x 2.5


= ###

Live Load = 0.5 T/sq.m

Total load on Slab = ###

Max Moment = B.M = wxl2


8

= 0.9 x 2.682 x 2.682


8
= 0.79 T.m

d= 0.79 x 107 x 1.5


2.760 x 1000

d= 65.39 mm

D= 65.39 + 20
D= 85.39 mm

Provide Depth = D = 150 mm


10

ADVANCE CONSULTING ENGINEERING PVT. LTD.


PROJECT : 220/66/11 Kv SUBSTATION AT BEGUR DATE : 31.01.06
BY : ASHWINI
SUBJECT : DESIGN OF 100 mvA AUTO TRANSFORMER
REV. R1
Mu
Ast Required in mm2 = Ast =
0.87 x fy x 0.8 x d

= 0.79 x 107 x 1.5


0.87 x 415 x 0.8 x 130

= 314.29 mm2

Provide 10 Tor @ 175 mm c/c Top and Bottom