IDD
INTELLIGENT DIAGNOSTIC DEVICE
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery

IDD
For Bushings
Tap Current Measurement - Online

Bushings are monitored from the


test tap in sets of three.
A

. B

C . C

.
1
IA C

.
1
IB C

.
1
C 2 IC
C IDD
I
2

C 2
Tap Current Measurement - Online

A Bushing Sensor is used to take


the current measurement.
Tap Current Measurement - Online

Three Bushing Sensors are used for


each bushing set.
Tap Current Measurement - Online

The three phases produce three tap


currents, all with similar magnitudes and
120º from the other two.

IA

IB

IC
Reference Phase

There isn't a reference voltage available,


as with off-line testing. Instead, the
center phase is used as a reference.

IA Reference Phase

IB

IC
Reference Phase

 Phase A is approximately 120º from the reference.


 Phase C is approximately 240º from the reference.

0º Reference Phase

IA
120º Φ γ

IB

IC
240º
Current and Capacitance

Voltage
 Xc  Reactance
Current

1
Xc  f  Frequency
2fC
C  Capacitance
Current and Capacitance

Voltage 1

Current 2fC

As the Bushing Tap Current Increases h


Capacitance Increases h
Changes in Capacitance

Changes in Capacitance are manifested as


a change in Tap Current magnitude with
respect to the other two vectors.

IA

IB

IC
Changes in Capacitance

For example, the change below indicates


a Phase A Capacitance increase.

IA

IB

IC
Changes in Power Factor

Changes in Power Factor are manifested


as a change in vector direction with
respect to the other two vectors.

IA

Φ
IB

IC
Changes in Power Factor

The Power Factor change shown below


is in Phase A.

IA

Φ
IB

IC
Changes in Power Factor

The change shown below is in Phase C.

IA

IB

IC
Changes in Power Factor

i
A decrease in the Phase A or C
Bushing Tap Current Angle
indicates an increase h in Power
Factor in Phase A or C.
Changes in Power Factor

For example, the change below


indicates a Phase A Power Factor
increase.

IA

Φ
IB

IC
Changes in Power Factor

How is a change in Power Factor of the


Reference Bushing determined?
Remember, the Reference Bushing is
always 0o.

IA

IB

IC
Changes in Power Factor

An increase h in the Phase A and C


Bushing Tap Current Angles
indicates an increase h in Power
Factor in Phase B
Changes in Power Factor

For example, the change below indicates


that the Phase A and Phase C angles are
increasing in the same direction.

IA

Φ γ

IB

IC
Changes in Power Factor

What this really means is that Phase A and


C are stationary, but that the Phase B angle
decreased.

IA

IB

IC
Changes in Power Factor

The Reference Bushing (Phase B) is


always considered to be 0o.

IA
Reference Phase

IB

IC
Changes in Power Factor

The Phase A and C angles have only appeared


to increase. The decrease in Phase B has
created that effect.

IA

Φ γ
IB

IC
Changes in Power Factor

The angle change described below would


indicate a Power Factor increase in Phase B.

IA

IB

IC
Off-Line/On-Line Comparison

Off-Line Monitoring takes absolute measurements


 An applied voltage is used as a reference and
synchronized with the current measurement

On-Line Monitoring takes relative measurements


 A reference phase is used in order to
calculate Power Factor and Capacitance
 There is an evaluation of the relationship
between real and reactive components
 There are three trend cycles used to evaluate
the data:
 Daily (24 Hrs),
 Weekly (168 Hrs)
 Monthly (672 Hrs)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery

IDD
General Overview
Current IDD Offering

One IDD can support :

 Standard IDD:
 Six Bushings (2 Bushing sets)
 IDD with Bushing Expansion Card Option Installed:
 Twelve Bushings (4 Bushing Sets)
(Second Data Acquisition Card required for Sets 3
and 4)
Recommended IDD Installation

Doble recommends that one IDD be installed per apparatus

“Apparatus” as defined as:


 One three phase transformer (or circuit breaker)
 A bank of three single phase transformers (or circuit breakers)

Voltage across
different apparatus
during faults may
damage the IDD
IDD System Connections
IDD Local Access

• Connection via RS-232.


• For configuration of the
IDD.
• For retrieving,
Laptop
acknowledging and
resetting Alerts
• Viewing data and features
• Access via a PC using a
standard web browser like
Internet Explorer or
Netscape. No special
software application is
required.