Sie sind auf Seite 1von 84

Page 1 of 84 Transmission Lines Prof. Nazar M.

Karyar Tuesday, September 16, 2014

Transmission Tower and conductor

The transmission tower or pylon is one of the most important accessories of a


transmission line. As the whole load of the line and accessories are taken by the towers
so its design is crucial. For construction of a transmission line the type and numbers of
transmission towers required depends on many factors. Transmission tower is designed
to carry the whole load of phase and grounding conductors in normal and abnormal
conditions. The design requirements in icy, non-icy, coastal areas, cyclone prone areas
and heavily air polluted areas are different. Due to the deposition of ice on conductor
the weight of line is increased considerably resulting in heavy load on the tower. In the
cyclone prone areas the conductors and towers experience severe wind loading. In such
situations if these factors are not properly taken care of, then the conductor may snap
and the tower may collapse. In the design process all these factors are taken care of.
Climatic condition plays an important role in tower and line design. For the purpose,
climatic load data is collected. The tower foundation type depends on the soil. Also
seismic data of the concerned region is collected for tower design. The tower types
generally used are Lattice structure, Guyed V, Tubular pole type etc. We have already
discussed about the conductor types used in transmission lines.

Insulators

Insulators for use in transmission lines can be categorized different ways. The main
function of insulator is undoubtedly to insulate the live conductor from the metallic
tower at ground potential but the important thing is that the insulator should be able to
carry the load/tension in the transmission line. At angle towers or at dead end the
insulators should be able to carry large tensional force. The insulators used
for transmission lines are mainly of porcelain or composite
polymer types. Traditionally porcelain insulators are used for both
transmission and distribution purposes.
In the coastal areas the climatic condition also influences the selection of
materials . In the coastal areas salt deposits on the insulator
surface, that results in increased leakage current on the insulator
surface. Similar situation arises where lots of suspended chemical
particles are present in the atmosphere. While designing the
transmission tower and selecting the conductor all these factors
are taken into account.
We will devote one article about insulators.

Damping devices

Due to wind and ice, the transmission lines swing under different
modes. The transmission lines may vibrate in three major ways.
Page 2 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

 Galloping : Due to the deposit of ice above conductor


surface, the conductor cross section resembles an aerofoil.
The wind flowing across the conductor (aerofoil) results in
Galloping of conductor. Galloping is the oscillation of the
conductor at high amplitude and low frequency. The
conductor may oscillate in vertical or horizontal plane.
Generally the conductor oscillates in vertical plane. The
amplitude of the oscillation may be more than a meter with
frequency upto 3 Hz. Due to galloping the clearance between
the conductors may reduce very much to initiate flashover.
Structural damage may also happen due to conductor
gallopping. Anti-gallopping devices may be fitted to reduce
the affect of gallopping.
 Aeolian vibration : When wind flows across the line steadily
then vortices are formed in the back side of conductor which
is the cause of aeolian vibration. Here the amplitude is in
milimeter or centimeter and frequency may be upto 150 Hz.
Over a long time the aeolian vibration may cause damage to
the strands of wire. Stockbridge Dampers in the shape of
dumbbell with midpoint clamped to the line are used for
damping the Aeolian vibration. As shown in the figure they
are fitted at a position most effective in damping the
vibration. In any conductor the dampers are used at both the
ends of the span. Dampers are used both in the phase and
ground conductors
 Wake induced vibration: Wake induced vibration takes place
in bundled conductors. The aerodynamic forces in the
downstraem of conductor gives rise to this form of
oscillation. It has amplitude in centimeters. The oscillation
is reduced by keeping the spacing of bundled conductors
large enough.

Earthing System

Every electrical system is equipped with a earthing system. The


ground wires (also called shield wire) run above the phase
conductors and protect the line from direct lightning strokes as
the lightning strikes first the ground conductor due to its position.
The foot of the transmission towers are properly earthed so that
the potential gradient near the tower remains within the limit and
protects the human beings and animals around the tower in
faulted condition.
Page 3 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

High Voltage Insulator

Introduction
The purpose of the insulator or insulation is to insulate the electrically
charged part of any equipment or machine from another charged part or
uncharged metal part. At lower utilization voltage the insulation also
completely covers the live conductor and acts as a barrier and keeps the
live conductors unreachable from human being or animals. In case of
the high voltage overhead transmission and distribution the
transmission towers or poles support the lines, and insulators are used
to insulate the live conductor from the transmission towers.
The insulators used in transmission and distribution system are also
required to carry large tensional or compressive load.

Here our brief discussion will be restricted to high voltage insulators


used in transmission lines and substations.

The HV/EHV insulators are broadly divided into two types based on the
material used. One is ceramic and the other is polymer (composite)
insulator. In Fig-A is shown the sketch of a porcelain disc insulator unit
and in Fig-B is shown a glass disc insulator.

Traditionally ceramic insulators of porcelain are used in both


transmission and distribution lines.
Now polymer or composite insulators are increasingly used in high
voltage transmission systems. The polymer insulators have a fibre rod
surrounded by outer sheath of some polymer. Due to the hydrophobic
nature of the polymer insulator surface, dry areas are formed between
wet areas resulting in discontinuities in wet creepage path. This
phenomenon helps improve the performance of the polymer insulator in
polluted and coastal areas. The polymer insulators has one great
advantage that it is quite lighter in comparison to porcelain insulators.
It is reported that the polymeric insulator surface degrade faster in
comparison to porcelain insulator. One important disadvantage with
porcelain insulator is that the porcelain insulators can bear large
compressive force but less tensional force. The porcelain insulators
surface is hydrophilic in nature, which means affinity for water. Polymer
insulators age faster than ceramic insulators.
Page 4 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Below are few definitions in relation to insulator that one should know
which are required here to understand some concepts.

Creepage Length -The creepage length is the shortest distance between


two metallic end fittings of insulator along the surface of insulator . In
the string of insulators for creepage length calculation the metallic
portion between two consecutive insulator discs is not taken into
account.
The corrugation below the insulator is for the purpose of obtaining
longer creepage path between the pin and cap. The corrugation
increases the creepage length so consequently increasing resistance to
the insulator leakage current. The leakage current that flows through
the surface of insulators should be as little as possible.
The creepage distance required in clean air may be 15 mm per kiloVolt
(line voltage). In the polluted air depending on the level of pollution of
air the required creepage distance increases.

Flashover distance - It is the shortest distance through air between the


electrodes of the insulator. For a pin type insulator shown in Fig-C the
double headed red arrow line is flashover distance.

Flashover voltage - The voltage at which the air around insulator breaks
down and flashover takes place shorting the insulator.

Puncture voltage - The voltage at which the insulator breaks down


and current flows through the inside of insulator.
Page 5 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

An insulator may fail due to excessive electrical stress, excessive


thermal and mechanical stress or degradation due to environmental
chemical action of surface of the insulator. The electrical failure can
happen between conductor and earth through air or through the volume
of insulating material. In one case due to excessive electric stress the
insulator may fail when a flashover takes place through the air between
the conductor and tower. In other case the insulator may be punctured
through the volume. The insulating materials say porcelain has high
dielectric strength in comparison to air. The insulators are designed so
that it will flashover before it gets punctured. Failure due to flashover is
generally temporary and self restoring. But failure due to insulation
puncture is permanent and the insulator is damaged and required to be
replaced. An insulator which have internal defects like voids and
impurities, reduces the electrical strength of the insulator.
The flashover may results in damage of insulator glaze which can be
repaired. In polluted regions contaminants deposit on the surface of the
insulator that results in reduction of the flashover voltage of the
insulator in wet condition. For example if the power frequency flashover
voltage of a 33 kV pin insulator is 95 kV in dry then in wet condition the
flashover voltage may be reduced to below 80 kV. Insulators are
designed to withstand flashover voltage. In this example you can
observe that even in the wet condition the flashover voltage (80 kV) is
more than twice the insulator working voltage (33 kV).

The other important electrical parameters of insulator are


Electromechanical failing load, lightning withstand voltage
and switching impulse withstand voltage etc.. HV Line insulator
requirement is based upon the creepage length. The switching impulse
withstand voltage is particularly more important in case of Extra High
Voltage (more than 300 kV) and Ultra High Voltage lines.

Insulators of different design are available for different applications


Page 6 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

some cases are outlined below.

Suspension Insulator
The suspension insulators are used to support conductors in high
voltage transmission lines. The suspension insulators string used in
transmission lines are obtained by joining several disc insulator units.
according to the type of hardware fittings, usually two varieties of disc
insulators are used in HV transmission line. These are cap and pin type
and ball and socket type. A porcelain cap and pin disc insulator is shown
in Fig-A. Also in Fig-B is shown a glass disc insulator. In the porcelain
insulator the somewhat umbrella like upper part called skirt is glazed
and smoothened so that when it rains the dust and salt deposited on it
are easily washed away. The contaminants cannot easily penetrate the
glazed surface. When it rains the lower corrugated part does not wet
and remains dry. This dry portion is the effective creepage length in wet
condition.
In the transmission line a string of disc insulators are formed by fitting
the pin of one disc to the cap of next disc. Simply by adding more
numbers of discs in the string the insulator string is used for higher
voltage. Moreover when one disc is damaged only that particular disc is
replaced not the whole string.

Pin Type Insulator


The pin type insulators are suitable for use in low and high voltage
distribution systems. Actually in distribution lines you will hardly find
any other type of insulators. Pin type insulators are not usually used
above 33 kV as the insulator size will become large and costly and
unfeasible. See the figure-C for a pin type insulator.

Post Insulator
The post type insulators are mostly used in high and extra high voltage
substations. In the substation Post type insulators are used for
supporting equipments and Bus conductors. See Figure-D for a post type
insulator.
Page 7 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The post insulator is manufactured as single unit from porcelain or


composite material. The post insulators are also required to have
sufficient bending strength and torsional strength. Both porcelain and
polymeric post type insulators are used in practice.

8 comments Links to this post


Labels: Power System

Transmission Tower Types

In the last article we discussed about the transmission line main accessories. Now we will discuss
about transmission tower or pylon types. The transmission tower is an important accessory and
the performance of the transmission line depends very much on the design of the transmission
tower. The electric transmission towers or pylons can be classified several ways. Here we will
try to classify it broadly. The most obvious and visible tower types are

 Lattice structure
 Tubular pole structure

Varieties of tower types are used in practice. Traditionally self supporting lattice structures are
used for electricity transmission line towers (see Fig-A). You will mostly find the use of self
supporting type lattice structures for transmission lines in most of the power companies .
The lattice structures can be erected easily in very inaccessible locations as
the tower members can be easily transported. Lattice structures are
light and cost effective. The main disadvantage of lattice structure is
that it requires more ROW (Right Of Way). Right Of Way is the stretch of
land acquired along the route length of line keeping the towers in the
middle of ROW width. See Fig-D where the width of ROW is shown by
double headed arrow. The ROW width is as per the standard set by Local
authority or government agency. Clearly ROW is more for higher voltage
Page 8 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

line.
In the sketch of a single circuit lattice tower (Fig-A), two numbers of
ground conductors are used. Theta is the shield angle. For reliably
protecting the conductors from lightening this angle θ should be less
than 30 degrees. In the Fig-A the phase conductors used are bundled
type (twin conductor).

In many cases due to public resentment the use of lattice structures has been restricted. So
alternative transmission structures are adopted by some power companies.

Steel tubular pole structures have been used quite successfully by some power companies for
high and extra high tension transmission lines. The installation of these structures are costly
but requires less time. See the sketch of a tubular steel pole structure (Fig-B). The tubular
structure can be a single tubular form or H-form. Like Lattice tower it can also be designed for
carrying two or more circuits. A lattice tower with double circuit is shown in Figure-D. More
transmission companies are considering the use of this type of tower especially in populated
areas.
Page 9 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The lattice guyed-V transmission towers has also been used by the transmission companies in
cases where more space is available.. These are simple, easy and cheaper to install. The guyed
towers also require less time for installation. The main disadvantage is that these towers require
more space due to presence of guy wires. See the sketch of the tower (Fig-C). This tower uses
two string insulators per phase arranged in V form.
Page 10 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Another classification is from the point of view of materials used. The transmission towers are
usually made from steel and galvanized steels. Aluminium is also used as construction material
for transmission lines. In many countries wooden transmission towers are also
used for HV/EHV transmission, if plenty of wood of considerable length(or height)
is available at reasonable cost. The wooden towers are mainly single pole or H-
frame type.
Page 11 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Even concrete poles/towers are used by transmission companies of


some countries for HV/EHV power transmission.

Angle Towers
Another main classification is from the point of view of functioning of tower. That means
whether the tower is suspension type, angle type or dead end type. Depending on the deviation
angle of the line the respective tower is chosen. The suspension type of towers only carry the
load of the conductor in normal situation. However suspension towers are usually designed to
work satisfactorily for very small angular deviationn of line. The standard code of practice of
different countries has specified the maximum deviation angle for use of suspension towers. The
angle towers are used when the line route deviates more than this specified maximum angle.
The angle towers can again be sub grouped for different ranges of angular deviation. So the
towers can be categorized as small angle, medium angle or large angle towers. The towers used
at the termination point of line are dead end towers and are designed to carry large unbalanced
load. The dead end towers are the strongest and heavy. In practice large angle towers are
designed so that they can be used as dead end towers. Doing so will eliminate the need for
designing one more tower type that is dead end. The angle towers use tension
insulator strings. See the picture below.
Page 12 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The numbers of transmission towers required to be erected per kilometer depends on the
topography of the line route. So the span length of the line depends on the topography. For a
particular conductor, the span should be such so that under highest temperature the line
maintains minimum clearance (as per local standard) to ground or other nearby objects.

Obviously more towers are required to be erected per kilometer in hilly or other difficult
terrain. When the path of line deviates more often from the straight route then the line requires
more towers per kilometer. Angle towers are used whenever the line route such deviates so that
the suspension tower cannot be used.

From the above discussion it is clear that the choice of transmission tower types depends upon
several factors. Also you must have observed that when the tower carries only one circuit then
the phase conductors are usually arranged horizontally(or triangular form). In this
arrangement more Right Of Way is required but the tower height will be less, resulting in
saving in tower materials so tower cost is reduced. When the transmission tower carries two or
more circuits, then the phase conductors are usually arranged vertical (See above photograph
and Fig-D sketch). In this configuration the requirement of Right Of Way is less but tower
height is more. Usually this is the choice in double or multi-circuit case. Sometimes double
circuits are also arranged horizontally and single circuit vertically according to the availability
of Right Of Way and optimized total cost.

Tower Foundation
The type of tower foundation depends on the soil type where the tower is to be erected. Some
common foundation types are for dry soil, wet soil, rocky soil, sandy soil and submerged type.
In most cases existing standard design can be adopted to reduce the overall cost of tower
installation. In the earth quake prone areas, data pertaining to seismic
activity of the area is very important for consideration in foundation.
Page 13 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The foundation cost on river bank or river bed is much more than on
plain land.

The design of transmission tower and line is complex which need to


consider loading under different conditions. Several softwares are
available in the market for the analysis and design purpose.

Transmission Line Parameters: Capacitance and


Conductance

Capacitance
The last article was about line resistance and inductance. Now we will
discuss about line capacitance and conductance. We already said that
leakage current flows between transmission lines and ground and also
between phase conductors. Leakage current flows to ground through
the surface of insulator. This leakage current depends upon the
suspended particles in the air which deposit on the insulator surface. It
depends on the atmospheric condition. The other leakage current flows
between the phase conductors due to the occurrence of corona. This
leakage current also depends upon the atmospheric condition and the
extent of ionization of air between the conductors due to corona effect.
Both these two are quite unpredictable and no reliable formula exist to
tackle these leakage currents. Luckily these two types of leakage
currents are negligibly small and their ignorance has not proved to
influence much the power system analysis for line voltage and current
relationships. Here we will ignore the leakage currents so we will not
show the leakage resistance. Inverse of this leakage resistance is called
line conductance.

Here rest of the article is about line capacitance. Like previous article on
inductance here also I am not going to derive the formulas for
capacitance for different line configurations rather to develop some
concepts.

As the flow of line current is associated with inductance similarly the


voltage difference between two points is associated with capacitance.
Inductance is associated with magnetic field and capacitance is
associated with electric field.

The voltage difference between the phase conductors gives rise to


electric field between the conductors ( see Fig-A). The two conductors
are just like parallel plates and the air in between the conductors is
dielectric. So this arrangement of conductors gives rise to capacitance
between the conductors. The value of capacitance depends on the
configuration of conductors. We will discuss few configurations and the
corresponding capacitance value.
Page 14 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

 Here in Fig-A is shown the single phase line conductors. In the


figure is shown the cross section view of the conductors. See the
Electric lines of force representing Electric field. The lines of force
start from one conductor and terminate on other. In the diagram it
is assumed that there is no other charged body, even the ground
(which is at potential zero) is assumed to be far away and has no
influence on line capacitance. In this situation,

Let the capacitance between the two lines each of radius r is C


Farad per meter of line length. Then,

.k
C = -----------
ln(D/r)

( ln is for natural logarithm )


k is the permittivity of air.

Note: In this article capacitance is always per meter of line


length. So the unit is F/m .

One important thing is that here the actual radius r is used in the
formula. Compare with inductance
formula where we used the equivalent radius r' which is 0.7788
times the actual radius r.

In the last article, inductance was found for each line individually.
Here also capacitance between line to
neutral is desired for per phase analysis of power system.
Page 15 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

It is important to think that the line to line capacitance is


equivalent to two capacitance each of value
2C, one between line-1 and neutral(N) and other between
neutral(N) and line-2. See Fig-B.

Note: Capacitance in series behaves similar to resistance in


parallel. Also capacitance in parallel behaves
similar to resistance in series. When two capacitors are
connected in parallel their equivalent is
sum of the two capacitances.

So the line to neutral capacitance Cn is two times C.

Cn = 2k / ln (D/r)

 Now let us consider our favorite case of three phase circuit(see


Fig-C) where the phase conductors (a, b and c) occupy the corners
of equilateral triangle. The conductors are equidistant from each
other. If Cn is the capacitance from line to neutral N (per phase
capacitance). Note that point N is imaginary not physical.

Cn = 2k / ln (D/r)
Page 16 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

 The general form (Fig-D) of capacitance between one phase and


neutral for a three phase line is

Cn = 2k / ln
(GMD/GMR)

GMD is Geometric Mean Distance and GMR is Geometric Mean


Radius of the particular
configuration. GMR used for calculation of capacitance is slightly
different from GMR used for
inductance as mentioned below. It is also assumed that the phase
lines are transposed

In actual practice in most of the cases you will find that the three
phase conductors are arranged
horizontally or nearly vertically as per the tower design. Only in
few situations you will find the
conductors are placed nearly equidistant from each other. Hence
calculation of GMD and GMR are
important.
Page 17 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Here in Fig-D the three phase conductors are arbitrarily placed. Let
the distance between the phase
conductors are D12, D23 and D31 . The distances are between the
centers of bundled twin conductors.
Similar to inductance, transposing the conductors
the capacitance between any two phases is made
equal. Or the capacitance between any phase and neutral point are
made same. The above
equation is actually derived considering transposed lines.

here, GMD = ∛(D12 D23 D31)


In fig-D ACSR twin bundled conductors are used for which GMR is
calculated as below.

 In case of bundled conductors, the GMR for commonly used


bundles are as below

For twin conductor bundle


GMR=[(r.d)(r.d)]1/4
= √(r . d)
For triple conductor bundle
GMR=[(r . d . d)(r . d .
d)(r . d . d)]1/9
= ∛(r.d2)
For quad conductor bundle
GMR = 1.09 ∜(r.d ) 3
Page 18 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Note: In case of inductance r' is used. But here the actual radius r
is used in GMR calculation

In all the above formulas r is the actual radius of circular


conductor. But usually ACSR conductors are
used. For ACSR conductor in place of r put the value of Ds as
supplied by the manufacturer. In Fig-D
two ACSR conductors per bundle(twin) are used in each phase a,
b and c.

So for Fig-D, GMR =√(r . d)


 In Fig-E is shown a three phase line (in power sector a three
phase line is usually simply called as single circuit line. If the
tower is carrying two numbers of such three phase lines then it is
called double circuit line). The line is assumed as transposed. Here
each phase conductor is comprised of four numbers of
conductors(quad conductor). The conductors within a bundle are
arranged in a square of side d.

Here,
GMD = ∛(D . D . 2D)
GMR = 1.09 ∜(r.d3)
As already said If ACSR stranded conductors are used (instead
of circular one as shown) so Ds as
per the manufacturer's data is used in place of r. Ds is the
equivalent radius of stranded conductor.
The values of GMD and GMR are put on the above equation to
find line to neutral capacitance.

 So far we only considered one three phase circuit (single circuit).


An example of double circuit will be considered exclusively in next
article for both inductance and capacitance calculation.

Earth being at zero potential influences the electric field. Some electric
lines of force originating from conductors terminate on earth surface at
90 degrees. The presence of earth is tackled by considering imaginary
image conductors placed below the earth, just like image of real
conductors. However the influence of earth on the capacitance of line is
small in comparison to the line to line capacitance. So the influence of
earth is neglected in many cases. We discuss it here.

When the line parameters for all the three phase conductors are nearly
equal, then the line voltages at the other end of the line are more or less
Page 19 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

balanced. Of course the balanced three phase system can be solved by


considering any one phase and neutral. This is called per phase analysis.
It should be remembered that here neutral does not mean the
requirement of a neutral conductor for transmission. Although the above
general formula for capacitance derived considering transposed lines,
but it is often used for non-transposed lines to get approximate values

Labels: Power System

Transmission Line Model: Short and Medium lines

In last few articles we discussed some basic design aspects of electric


transmission lines. Sometimes the discussion about a certain part was
very brief considering that the same can be elaborated more somewhere
else. Effort is made to flash the important points or parts of the subject.

In the previous 3/4 articles we developed some concepts on AC


transmission line parameters and discussed how the line parameters
can be calculated under different configuration of phase conductors. The
behavior of transmission lines and its voltage and current under normal
and abnormal conditions depends on these parameters. For carrying out
system studies the proper modelling of transmission lines is very
important. Here in this article we discuss the transmission line modeling
. Transmission lines are also called as power lines. Transmission line
theory is important for both power and electronics or communication
engineering. But here our discussion is mainly from the power
engineering point of view.

The transmission lines are mainly classified as short, medium or long


lines. The classification is based upon the accuracy of the model and
simplicity. While the short line model is quite simple, the long line model
is somewhat complex and the medium line is in-between the two. At
power frequency of 60 or 50 Hz, the lines of length below 80 km are
treated as short lines and the length of line exceeding 80 km but less
than 250 km can be modeled as medium lines and as the length of lines
exceed 250 km it is long line.

For short and medium length lines the parameters are lumped. This
simplifies the model and gives quite accurate result. In case of the long
transmission lines the line parameters are considered as distributed
along the length of the line. The aim of the transmission line model is
that it should be simple and the analysis of the model should bear
desired accuracy. Of course you can apply the long line theory for power
lines of length below 80 km. Doing so one can achieve somewhat more
accurate result (which may not be desired) while making the model or
Page 20 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

calculation more complex.

Here in this article we will discuss short and medium length lines only
and long line is the topic of the next article.

Before proceeding further, as we already discussed in our previous


articles there are four line parameters, these are line resistance R ,
inductance L, leakage conductance G and line to neutral capacitance C
per meter length of line. Here instead of using the symbol Cn as the
capacitance between line and neutral we will adopt C.

Here we will use these.


z = Series impedance per meter length = R + j ωL Ω / meter (ω = 2
π f where f is the frequency)

y = Shunt admittance per meter length = G + j ωC S / meter

Ω symbol is for Ohm, the unit of impedance


S symbol is for siemens, the unit of admittance. mho or
inverted Ohm symbol is also used for
admittance

As already discussed in our previous article G arises due to leakage


currents and is ignored in transmission line modelling.

so, y = j ωC S / meter

If, Z is the total lumped line impedance and Y is the total admittance
between the line and neutral, then we get Z and Y by multiplying per
meter values with the total length of the line. Then
Z = z .l Ω
Y = y .l S

where l is the total length of the line in meter.

Short Lines
As already said the lines of below 80 km length can be modeled as short
lines. The transmission line is a three phase system and here assumed
as balanced due to transposition and balanced load at receiving end. The
analysis adopted here can be applied to unbalanced non-transposed
systems for obtaining result with reasonable accuracy. For the balanced
three phase line we are only required to analyze one phase. The return
path is imaginary neutral.
In Fig-A is shown a short transmission line. The resistance and
inductance are lumped together which is the transmission line serie
impedance Z. Further for short line here the capacitance of the line is
ignored so the admittance is ignored.
Page 21 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

As shown the sending end and receiving end voltages are Vs and Vr
respectively and the sending end and receiving end currents are Is and
Ir respectively.

From the diagram it is clear that both sending and receiving end current
are the same
Is = Ir
According to Kirchhoff's voltage law,
Vs = Vr + Z Ir

Z = R + j XL
R is the total line resistance and XL is the total line inductance, both are
lumped.

Those who are familiar with two port network analysis, the above can
be represented in terms of ABCD parameters. In this form the supply
side voltage and current is represented in terms of receving side voltage
and current as below

Vs = A Vr + B Ir
Is = C Vr + D Ir
In the above formulas A and D are dimension less. Dimension of B is
Ohm and that of C is Siemens.

The parameters satisfy the condition AD-BC =1

In transmission line problem this representation is sometimes found


suitable. Usually the receiving side voltage and current requirement are
given and it is required to find the supply side voltage and current.

For the above short line equations we get


A = 1, B=Z, C=0, D=1

clearly it satisfies the condition AD-BC=1

Voltage Regulation
The performance of a transmission line is determined by a term called
voltage regulation. Voltage regulation is defined as the percentage
Page 22 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

change in voltage at the receiving end from No load to Full load with
sending end voltage held constant.

or means the values or magnitudes of voltages without


sign . So the subtraction is the simple subtraction and not the phasor
subtraction. The voltage regulation is desired to be small or zero.
Integrated Grids has set standards for voltage variation say ±5%
or ±7% depending on voltage levels.

The relationship Vs = Vr + Z Ir between the sending end and receiving


end voltages can also be illustrated by a phasor diagram shown in Fig-B.
In Fig-B(i) we have considered an inductive load. So the receiving end
current Ir lags the receiving end voltage Vr by a phase angle
φ(determined by load). In Fig-B(ii) is considered a capacitive load. Here
current Ir leads the voltage Vr by an angle φ.

In both the diagrams Vr and Z Ir are added as per the rule of phasor
addition. Z is the line impedance as discussed above.

Z Ir = (R+j XL ) Ir = R Ir +j XL Ir

The main difference between the above two is that in case of lagging
load the receiving end voltage is less than the sending end voltage. But
Page 23 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

in case of leading load the receiving end voltage can even become more
than the sending end voltage depending on the lead phase angle φ .
Which is due to the fact that the load is capacitive. In our case Fig-B (ii),
for the chosen phase angle the receiving end voltage is more than the
sending end voltage. Actually the industrial loads are mostly inductive.
The inductive loads consume reactive power. Capacitors which generate
reactive power are connected at the load end or at substations to supply
reactive power. At sub-transmission and distribution levels where
voltage drop is a problem, capacitors can improve the voltage profile
and power factor at the receiving end. The capacitive load helps in
improving the receiving end voltage regulation and power factor. For
only voltage regulation purpose usually tap changer of transformer is
utilized. By tap changing the transformer turns ratio is changed, so
adjusting the secondary voltage.

Another common definition which sometimes may be useful for


evaluation of transmission line performance is the transmission
efficiency of the line. The transmission efficiency is defined as the ratio
of power delivered at receiving end to the power supplied at sending
end.

If η is the transmission efficiency then,

cos φ is the power factor at the receiving end, or power factor of load
but cos φs is the power factor at the sending end (due to both load and
transmission line).
Using the above formula it is easy to find the transmission efficiency of
short and medium lines. For short line the angle φs is clearly visible
from the phasor diagram (angle between Vs and Is (or Ir)). But in case
of medium line little more effort is required.

Medium Lines
The medium length lines are categorized as transmission lines of more
than 80 km and less than 250 km length. The medium length lines can
be modeled two ways. These are nominal π and nomial T (Fig-C), so
named due to the arrangement of elements. Due to the length of the
line admittance Y is no more neglected. Of course in both the π and
nomial T representations lumped elements are used. In the nominal π
representation the total admittance due to line capacitance is equally
divided into two halves and each half connected at both sending and
receiving ends. In the nominal T representation the admittance is
connected at the center of line and line impedance is divided into two
equal parts and each part is connected on both sides in series (Fig-C).
Page 24 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

It can be shown that for the π representation the sending end voltage
and current can be written in terms of receiving end voltage and current
as shown below.

From above two expressions ABCD parameters can be easily identified.


Also you should verify the condition AD-BC=1.

For T representation also applying KCL and KVL we can obtain the
similar expression for Vs and Is.

At no load putting Ir = 0 we obtain Vr NL = Vs / A, .


Page 25 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Analysis of short and medium lines helps us gain important concepts of


transmission lines. It is useful for long line analysis.

15 comments Links to this post


Labels: Power System

Influence of Earth on Capacitance Calculation

In last article we discussed the technique for calculation of inductance


and capacitance of double circuit transmission line, which can be easily
applied for multi circuit lines. Of course before proceeding further I
strongly recommend to go through those articles. I also advise to have a
look at the two articles on calculation of line inductance and capacitance
in general. Moreover as this article uses basic formulas of logarithm so
we have tabulated few useful formulas at the bottom.

In the above three articles we developed some basic concepts. In the


previous articles we neglected the influence of earth on capacitance
calculation of transmission lines. But this is not true for Extra High
voltage (EHV) and Ultra High Voltage (UHV) lines. For example for
transmission lines above 200 kV voltage level the clearance distance
between phases is quite comparable with the clearance between phase
and ground. And electric field is considerably influenced by the presence
of earth. This situation requires the consideration of influence of earth
on calculation of line capacitance.

Here I will derive the formulas for calculation of transmission line


capacitance.

Let us consider a charged line of circular cross section conductor as


shown in Fig A. When this object is far removed from earth its electric
field will be as shown in Fig-A(i), radial lines of force. In Fig-A(ii) is
shown how the electric field is disturbed in the presence of Earth. This
field pattern above ground can be obtained by replacing the ground and
placing an imaginary oppositely charged similar conductor same
distance below the ground line. Here it is imagined that the ground level
as a mirror. This is called image charge (see Fig-A (iii)). Now the
problem is reduced to a pair of opposite charges.
Page 26 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Let us consider Fig-B where there are two very long line conductors of
charge +q and -q coulmb per meter length of the conductor. From the
basics it can be shown that the potential at a point P is vp
Then,
Page 27 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The above equation can also be written as

The above equation can be imagined as the potential ( vp) at the point '
p ' is composed of two components one due to positive charge +q and
other due to negative charge -q. These two are respectively first and
second terms in the above equation.

Generalizing it we can say that the total potential at a point p due to


several charges is equal to the sum of the potential due to all the
individual charges.

Here next we will consider our favorite and practical case of the three
phase line. Let us assume that the three phase conductors are placed in
a general arbitrary form as shown in Fig -C. Now imagining the ground
level as mirror we get the image charges which are -ve of actual charges
on conductors as shown. Now the ground line can be removed. In the
figure all the distances between the conductors and/or image are
illustrated.
Page 28 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

As illustrated in above case we will obtain the voltage difference


between the conductors a and its image a' . For this we have to find the
potential at the surface of a and a'. Let the potential at a is va and the
potential at a' is va'.

As already said the potential at the surface of conductor a is the simple


algebraic sum of the potential due to charges on all the conductors
including this particular conductor a. Similarly we can find the potential
at the surface of a'.

This way we get,

Now Vaa' = va-va'

So from the above two equations

Or in compact form we can write as


Page 29 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

As already said the phase conductors are transposed. So for ⅓ rd of


distance the conductor of phase-a will take the position of phase-b and
conductor of phase-b will take that of c . So for all the three positions
we will calculate the voltage for ' a ' phase and take the average. As
already said in last articles by transposition, the capacitance between
any of the three conductors and neutral are made equal. If C denotes
capacitance then after transposition we get

Of course here we will concentrate on calculation of capacitance (Can)


between phase-a and neutral.

Due to transposition when the phase a conductors will take position of b


as shown above and of course b will take position of c and c will take
that of a. (You can think cyclically).

Similarly when phase-a conductor occupies the other position .

Let us call the average voltage between conductor a and image


conductor a' be va-a'
Then,

Combining above three we get the value of va-a'


But we require the voltage from neutral (n) to phase-a conductor (see Fig-D), that is van
Page 30 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

From Fig-D it is clear that,

Hence we get

Simplifying we get

or,

but the charges of three phases sum up to zero,

So,

by rearranging the terms (see the properties of logarithm below at the end) we finally get
Page 31 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

We know that the capacitance between phase a and neutral


Can is,

So finally we get

From the above derived formula of capacitance Can we observe that due
to the consideration of influence of earth the denominator second term
comes into picture and the capacitance Can is more than what we would
have got if earth influence was ignored.

Logarithm Formulas Table

Here ln means natural logarithm. Natural logarithm is the logarithm


when the base is e. The value of e is approximately 2.718.

0 comments Links to this post


Labels: Power System

Double Circuit Inductance and Capacitance

Introduction
In last two articles we developed some useful concepts on transmission
line inductance and capacitance. There we discussed the formulas used
for calculation of inductance and capacitance of transmission lines for
different arrangement of conductors. I advise you to go through those
two topics in archive (above links) before proceeding further. In those
Page 32 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

two articles our discussion was restricted to single phase or one three
phase line (single circuit line). Here we will calculate the inductance
and capacitance of double circuit line which you can extend to multi-
circuits.

Double circuit GMD and GMR


In high voltage transmission system you will often find transmission
towers carrying two or more circuits. In fact numerous multi-circuit
lines are already in use. The conductors of circuits are arranged in
different configuration depending on the tower types used. We will
calculate inductance for a double circuit line using the formula.

Although the two circuits are in parallel, the inductance of double circuit
can not be found by imagining two inductances(for two circuits) in
parallel. Actually this is true only when the magnetic field of one circuit
does not link with other circuit conductors. Hence that is the case when
each circuit runs on separate tower and the separation between them is
such so that there is negligible or no magnetic field interaction between
the circuits.

Due to the closeness of the circuits being on the same tower, the
magnetic and electric field interaction of one circuit on the other
requires modified calculation of GMD and GMR.

See the Figure-A below for a double circuit arrangement on a self


supporting lattice tower. Here we have chosen the conductors arranged
vertically which will simplify our calculation and we will derive the
inductance for this arrangement where the phase conductors are also
assumed as transposed. As we discuss the topic you will realize that the
method can be applied to other arrangements or multi-circuits also.
Page 33 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

In the figure one circuit phase conductors are a-b-c and other circuit
phase conductors are a'-b'-c'. As shown here the phase conductors are
single rounded conductors.

In the last two articles we have already discussed bundled conductors


for inductance and capacitance calculation. Here the double circuit is
treated very similar to single circuit or a three phase line with bundled
conductors. The conductors a-a' are imagined as bundle conductor for
phase A, similarly b-b' and c-c' are imagined as bundle conductors for
phases B and C. Of course here the bundle sub-conductors are far away
and not bunched unlike the case of twin, triple or quad conductors
bundles.
Page 34 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Now we are ready to apply the general formula for calculating


Geometric Mean Distance(GMD). For calculating GMD all the distances
between the phase conductors are identified. In Fig-A(ii) all the
distances between the phases are shown. For example a-b, a-c, a-c', a-
b', c-b', c-a' etc.. There are 12 possible distances between conductors of
phases as shown. It should be noted that for calculation of GMD the
distances a-a', b-b' and c-c' are not taken.

GMD = (Dab . Dab' . Dbc . Dbc' . Dca . Dca' . Da'b . Da'b' . Db'c . Db'c' .
Dc'a . Dc'a') 1/12

Clearly there are 12 distances and so 12th root of the product of twelve
distances are taken.

By rearranging the terms you can also write GMD as below.

GMD = (DAB . DBC . DCA.)1/3


Where DAB = (Dab . Dab' . Da'b . Da'b')1/4
similarly DBC and DCA.

In our example

GMD = (6 . 10 . 6 . 10 . 12 . 8 . 10 . 6 .
10 . 6 . 8 . 12)1/12 meter
= 8.37 meter.

Now let us calculate the Geometric Mean Radius (GMR)

For GMR calculation the method is just similar to bundle conductors. Of


course for inductance calculation we require r' and for capacitance r. As
already said in previous articles the equivalent radius r' =0.7788r .
Here let us first calculate the GMR of each phase separately for
inductance.

GMRa = √(Daa' . r')

GMRb = √(Dbb' . r')

GMRc = √(Dcc' . r')


Page 35 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Daa' is the distance between the conductors a and a'.


Similarly for Dbb' and Dcc'

As the phases are transposed so,


GMRL = (GMRa . GMRb . GMRc)1/3
Note: Daa' Dbb' and Dcc' were not used in GMD calculation but used
in GMRL calculation.
Subscript L is used for GMR of inductance calculation and subscript C for
capacitance.

Putting the values of GMD and GMRL in the equation

L = 2 * 10 -7
ln ( GMD/GMRL )
we obtain inductance per meter per phase

In above calculation for GMRL the conductor is circular of radius r. But in


actual practice ACSR conductors are mostly used, so for inductance
calculation r' is replaced by Ds as supplied by the manufacturer of ACSR
conductor.
For capacitance calculation the radius of conductor is used
in GMRC formula whether it is one circular conductor or ACSR conductor,
for calculation of capacitance,

GMRa = √(Daa' . r)
GMRb = √(Dbb' . r)
GMRc = √(Dcc' . r)

GMRC = (GMRa . GMRb . GMRc)1/3


putting the value of GMRC in the equation,
Cn = 2k / ln (GMD/ GMRc)
We obtain the value of capacitance ( Cn ) per meter
between phase and neutral .
k is the permittivity of air and GMD is already calculated
for inductance.

Now you can put the numerical values to get a feel of the Cn so obtained.
Page 36 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Long Transmission Line

In the last article we discussed short and medium length lines. Now is
the time for long transmission lines. For long transmission lines if we
apply the formula for medium length line we will get large error. The
error becomes larger with longer transmission lines and the method is
useless. So for long lines it becomes important to represent accurately.
Hence the long transmission lines are represented by distributed
parameters.

Long Line Model


For medium length line we lumped the line impedance at one place. This
line impedance which is actually distributed throughout the length of
line will be represented here as distributed. The capacitive current
between the line conductors flows throughout the length of line. Which
necessitates for distributing the line to line capacitance throughout the
length of the line. But for a balanced three phase system we analyse
per phase analysis. Which necessitates for consideration of phase to
neutral capacitance, Both line inductance and capacitance for several
configurations are illustrated in previous articles. The equivalent long
line representation is shown in Fig-A.

In the diagram the distributed capacitance also automatically requires


that the line impedance also distributed. It should be clear from the
above figure that in general throughout the length of the line the
voltage and current values may vary.
Page 37 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

What is the voltage and current at a distance x from the receiving end.
See Fig-B Let the voltage and current at a distance x from receiving end
are V(x) and I(x) respectively. It should be noted that V(x) and I(x) are
phasors.

Let Zc = √(Z/Y)
and γ =√(ZY)

As Z and Y are complex numbers so in general Zc and γ are complex


numbers. Zc is called the characteristics impedance and γ is the
propagation constant. Zc is commonly called surge impedance in power
sector.

Formula for calculation of Z and Y are already discussed in previous


articles.
Z is the series impedance per unit length ( impedance per kilometer or
meter)
Y is the shunt Admittance per unit length

Using differential calculus and solving the resulting differential


equations it can be shown that,
Page 38 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The above formula can be rearranged and written in several ways.


Rearranging the terms and using the formulas of complex hyperbolic,
the above formulas for V(x) and I(x) can be written in the form

To find the voltage Vs and current Is at the sending end, we just have to
put l (length of line) in place of x in the above formulas. So at the
sending end

If you compare the above equations relating sending and receiving end
voltage and current with the corresponding equations discussed in last
article for medium length lines then we can easily find ABCD
parameters. These are

You can argue that the long transmission line can also be represented
by a nominal ∏ circuit. Yes a long line can be represented by an
equivalent ∏ circuit. It should be remembered that in case of medium
length line it is called Nominal ∏. Here it is called equivalent ∏. This
equivalent ∏ is only a convient representation of the actual long line
analysis. But Nominal ∏ is an approximation for medium lines. For load
flow study and other system studies this equivalent representation is
very helpful without sacrificing any accuracy. In Fig-C is shown the
equivalent ∏ representation of any line of length l according to long line
theory.
Page 39 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

It is left as an exercise for you to find Z' and Y' by comparing with
Medium length line.

Surge Impedance loading


In all the above formulas we used two parameters Zc and γ. These two
parameters are very important. Of course these two parameters are
derived from our transmission line parameters Z and Y. The
characteristics of the long line depends upon these two parameters.

As already said Zc and γ are complex numbers.

Let us consider a case when the load impedance is just equal to the
characteristics impedance Zc then, the receiving end voltage Vr =Ir Zc

substituting in above equations we get

and

let, γ = α+j β

Dividing V(x) by I(x) we get

From the above equation it is easy to interpret that the impedance as


seen at any point of the line is the same as the load impedance that is
Zc , the characteristics impedance. Moreover from the above equations
of V(x) and I(x) it is clear that
Page 40 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The magnitude of voltage is

Clearly the magnitude of the voltage increases with x. But our x


increases from receiving end to sending end. So the voltage increases
exponentially from receiving end to sending end.

At the sending end the voltage is

The other term is the phasor and only provides phase shift
between the voltages at receiving end and at a point x distance from the
receiving end. Similar argument can be made for equation of current
I(x).

In the above formula of Zc and γ we put Z(series impedance) and


Y(shunt admittance). (recall that Z and Y are the values per unit line
length)

Loss Less Line


What will happen for a loss less line. For loss less line R=0 and G=0.
So our above equations reduces to

Observe that for loss less line, Zc becomes a pure resistance. We also
know that γ = α+j β, for this loss less situation we get
Page 41 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Now our previous voltage and current equations for surge impedance
loading reduces to

As in case of lossy line here also at any distance x from receiving end
the ratio of voltage and current is always same that is Zc, the surge
impedance of the line. Using the complex algebra you are sure that the
magnitude of V(x) is Vr and I(x) is Ir. Which means that for loss less
line the voltage and current at any distance x from the receiving end is
same. It also implies voltage at sending end is same as voltage at
receiving end which is same as voltage at any intermediate point. So Vs
= V(x) = Vr. At Surge Impedance Loading the reactive power generated
by the line capacitance is equal to the reactive power absorbed by the
line inductance for every unit length of line. In Power industry it is said
that the voltage profile is flat. So we conclude that for a lossless line the
voltage magnitude is same throughout the length of line. As in case of
lossy line the term is the phasor responsible for phase shift. It is
simply giving phase shift to the voltage wave along the length of line.
The phase angle between sending and receiving end voltage is . It is
clear that if the distance between the sending and receiving end is more
then the phase difference between the voltage phasors at both the ends
of the line will be more.

In previous articles we already discussed that in case of transmission


line how and when we can ignore the line resistance R and leakage
conductance G. At least for rough estimate of the load carrying
capability of transmission line we can presume it lossless. The surge
impedance loading is the ideal loading of the line, which is desired
keeping in view of the optimised (flat for lossless ideal case) voltage
profile of the line.

For Loss less line the surge impedance loading (SIL) is

Where

It should be recalled that Zc is pure resistance for lossless line.

Vr and Vl are the receiving end phase and line voltage respectively.
Page 42 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Approximate SIL for few nominal voltages

 132/138 kV - 50 MW
 230 kV - 150 MW
 345 kV - 400 MW
 400 kV - 500 MW
 500 kV - 900 MW
 765 kV - 2090 MW

Above values of SIL is true for both 50 Hz and 60 Hz systems.

Line Loadability
System planners usually use line loadabilty curve for deciding loading
capability of the line. See Fig-D. The relationship between SIL and
length in km shown in Fig-D is almost same for all voltage levels.

What is the capacity of the transmission line or how much power it can
carry. The power that a transmission line can carry are based on three
factors. These are

 Thermal Limit
 Voltage Drop Limit
 Stability Limit
Page 43 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Due to the current flow heat is generated in the line and the line length
changes which gives rise to more sag. Sometimes heating of the line is
enough that, later cooling of the line due to less load or environment
factors does not make the line regain its actual length. The sagging
become permanent. Due to this the minimum clearance of the line to
ground decreases which may violates the standard set by the local
authority. Also if the load is very high the conductor may be damaged
due to excessive heat. All transmission lines has thermal limits. But the
thing is that only short lines can approach this limit. Voltage drop and
stability limits situation usually do not arise here due to short length.
Lines less than 80 km length falls in this category.

For medium length line the loading is mainly limited by allowable


voltage drop (usually between 5 to 10 % as set in grid standard). For
medium length line the steady state stability limit situation usually does
not arises due to lesser length(discussed below). But the length is
enough so that the medium length line can encounter the voltage drop
limit before reaching thermal limit. By reactive compensation the
voltage drop limit can be increased. Lines exceeding 80 km and less
than 250 km long belong to this category.

For long line(above 250 km) we have shown that effort is made to
operate the line with surge impedance loading. So for long lines the
voltage profile may be made more or less flat with SIL loading. If the
loading of line exceeds above SIL then the voltage at receiving end is
less than sending end. If the loading of the line is less than SIL then the
voltage at receiving end is more than sending end. This phenomenon is
called Ferranti effect. For very lightly loaded or open long lines the
voltage at receiving end may become very high. To avoid this situation
Reactors are used at receiving end.

In both lossy and lossless lines it is clear that phase difference between
sending and receiving end voltage arises. This angle is called power
angle. The power that flows from sending to receiving end depends
upon this angle and the magnitude of Vs and Vr. (The magnitude of a
phasor V is represented as |V| )

The simplified formula for this power (P) transmitted is

X is the equivalent series reactance(ignoring resistance) of the line.

To increase the power to be transmitted, this power angle δ may


increase up to 90 degrees. Increasing slightly further, the line becomes
unstable and lose synchronism. It is a good practice to operate the lines
with sending and receiving ends phase differnce angle (power angle)
less than 30 degrees. Doing so, if in emergency load generation
disbalance in adjacent areas occurse this line can take more load by
Page 44 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

increasing this power angle, so avoiding instability. So operating below


30 degrees we keep more than 60 degree angle margin. From the above
formula you can say that if X is made smaller and smaller for any fixed
small δ ( small sin δ imply small δ) then more power can be
transmitted. Hence it is clear that small line reactance X is desired. This
small reactance which cannot be made arbitrarily small by line design,
definitely limit the power transmission in line. This loading limit for
transmission line is quite less than thermal limit. So the long lines
cannot approach thermal limit, before that other limits come to
action. This small power angle corresponds to quite lesser load carrying
capacity in comparison to thermal limit. Effort is made by power
companies to push the limit towards thermal limit by employing reactive
compensation so reducing effective series X further.

Complex Power and Power Triangle

Introduction

In the last article we discussed the basics of Electrical Power and


related terminologies. Here we will develop the concept of Complex
Power and Power Triangle. These two are very important concepts used
frequently by power engineers. As this article requires the knowledge of
previous article so it is advised to at least have a look at the last article.

From the previous article the following points are clear.

 The instantaneous power p is composed of real power and reactive


power.
 The time average value of instantaneous power is the real power
(true power) is |V | | I | cos φ
 The instantaneous reactive power oscillates about the horizontal
axis, so its average value is zero
 The maximum value of the reactive power is |V | | I | sin φ

It should be remembered that real power is the average value and the
reactive power is maximum value.

Complex Power
In power system analysis the concept of Complex Power is frequently
used to calculate the real and reactive power.

This is a very simple and important representation of real and reactive


power when voltage and current phasors are known. Complex Power is
defined as the product of Voltage phasor and conjugate of current
phasor. See Fig-A
Page 45 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Let voltage across a load is represented by phasor V and current


through the load is I.

If S is the complex power then,

S = V . I*
V is the phasor representation of voltage and I* is the conjugate of
current phasor.

So if V is the reference phasor then V can be written as |V| ∠0.


(Usually one phasor is taken reference which makes zero degrees with
real axis. It eliminates the necessity of introducing a non zero phase
angle for voltage)

Let current lags voltage by an angle φ, so I = | I | ∠-φ


(current phasor makes -φ degrees with real axis)

I*= | I | ∠φ
So,
S = |V| | I | ∠(0+φ) = |V| | I | ∠φ

(For multiplication of phasors we have considered polar form to


facilitate calculation)

Writting the above formula for S in rectangular form we get

S = |V| | I | cos φ + j |V| | I |


sin φ
The real part of complex power S is |V| | I | cos φ which is the
real power or average power and the imaginary part |V| | I | sin φ is
the reactive power.
Page 46 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

So, S=P+jQ

Where P = |V| | I | cos φ and Q = |V|


| I | sin φ
It should be noted that S is considered here as a complex number. The
real part P is average power which is the average value, where as
imaginary part is reactive power which is a maximum value. So I do not
want to discuss further and call S as phasor. If you like more trouble I
also advise you to read my article about phasor or some other articles
on phasor and complex numbers.

Returning to our main point, from the above formula it is sure that P is
always more than zero. Q is positive when φ is positive or current lags
voltage by φ degrees. This is the case of inductive load. We previously
said that inductance and capacitance do not consume power. The power
system engineers often say about reactive power consumption and
generation. It is said that inductive loads consume reactive power and
capacitors produce reactive power. This incorrect terminology creates
confusion.

The fact is that most of the loads are inductive and they unnecessarily
draw more current from source. Although in each cycle both inductance
and capacitance draw power from the source and return same amount
of power to the source but the behavior of inductance and capacitance
are opposing to each other. When capacitors are connected in parallel to
inductive load the power requirement of inductive load is supplied by
capacitor in half cycle and in next half cycle the reverse happens.
Depending upon the values of capacitor this power requirement of
inductance in the load may be fully or partially satisfied. If partially
satisfied the rest will be drawn from the distant source. By properly
selecting the capacitance the maximum value of reactive power (Q)
drawn from the distant source (or returned to the distant source) is
reduced. This reduction in reactive power results in reduction of line
current so the reduction of losses in transmission line and improvement
in voltage at load end.

Power Triangle
Returning to the complex power formula, P, Q and S are represented in
a power triangle as shown in figure below.
Page 47 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

S is the hypotenuse of the triangle, known as Apparent Power. The value


of apparent power is |V|| I |

or |S| = |V|| I |
It is measured in VoltAmp or VA.

P is measured in watt and Q is measured in VoltAmp-Reactive or VAR. In


power systems instead of these smaller units larger units like Megawatt,
MVAR and MVA is used.

The ratio of real power and apparent power is the power factor of the
load.

power factor = Cos φ = |P| / |S|

= |P| / √(P 2+Q 2)

The reactive power Q and apparent power S are also important in power
system analysis. As just shown above the control of reactive power is
important to maintain the voltage within the allowed limits. Apparent
power is important for rating the electrical equipment or machines.

Total Power of Parallel Circuits


In real world the loads are usually connected in parallel. Here we will
show the total power consumed by parallel branches. See Figure-C. It
has two branches.
Page 48 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

First we have to draw the individual power triangles for each branch.
Next the power triangles are arranged back to back keeping real power
in positive x direction as shown. The total power consumed is obtained
by connecting starting point O to the tip of last triangle. This is actually
the result of addition of complex numbers.

If S1 = P1 +j Q1
S2 = P2 +j Q2

Then, S = S1+ S2

or S = (P1+ P2 ) + j (Q1+ Q2 )

P = P1+ P2
Q = Q1+ Q2
Page 49 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

S1 P1 , Q1 and φ 1 correspond to branch1 and S2 P2 , Q2


In the above diagram
and φ 2 correspond to branch2.
S, P, Q and φ correspond to total power consumption as seen by the
generator

0 comments Links to this post


Labels: Basics

Instantaneous, Average, Real and Reactive Power

Forward

We discussed and developed some important concepts of transmission


lines in last few articles. Last time we discussed about long transmission
lines. Here we discuss a simple but important basic concept Electric
Power. This will refresh our knowledge before we move further.

Electric Power has same meaning as mechanical power but here the
power or energy that we are concerned is in Electrical form. We often
encounter terms like instantaneous, average, total, real, reactive,
apparent and complex power or simply power. What they mean? how
are they related ? That we will discuss here and in next article.

DC Circuit
As long as our analysis is restricted to Direct Current(DC) circuit the
power consumed by the resistance load is the product of voltage across
the resistance and current flowing through the resistance. It is really
simple.

P=V.I

The power consumed by the load is the product of voltage across the
load and current drawn by the load (Fig-A). Or the Power supplied by
Page 50 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

the DC source (battery/cell) is the product of voltage across the cell and
current supplied by the cell. Both are equal in our example
figure(considering ideal battery of zero internal resistance). The law of
energy conservation implies power supplied by the source must be same
as power consumed by the circuit. In DC circuit case instantaneous
power is same as average power.

AC Circuit
In AC circuit analysis, what is this power that we talk about. The main
problem is that the AC voltage and current varies sinusoidally with time.
Moreover the presence of circuit reactive elements like Inductor and
capacitor shift the current wave with respect to voltage wave (angle of
phase difference).

Power is rate at which energy is consumed by load or produced by


generator. Whether it is DC circuit or AC circuit, the value of
instantaneous power is obtained by multiplying instantaneous voltage
with instantaneous current. If at any instant of time t the voltage and
current values are represented by sine functions as

v = Vm sin ωt

i = Im sin (ωt-φ)

Vm and Im are the maximum values of the sinusoidal voltage and


current. Here ω=2 π f
f is the frequency and ω is the angular frequency of rotating voltage or
current phasors. It should be clear that for a power system f is usually
50 or 60 Hz
φ is the phase difference between the voltage and current.

As we said the instantaneous power is the product of instantaneous


voltage and current, if we name instantaneous power as p then
Page 51 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

p = v.i = Vm sin ωt . Im sin (ωt-φ)


or p = Vm Im sin ωt sin (ωt-φ)

Applying trigonometric formula 2.sin A.sin B = cos(A-B) - cos (A+B) we


get

It can be written as

This is the equation of instantaneous power

In the Fig-C is drawn all the three waves corresponding to v, i and p.


Graphically also we can get the value of instantaneous power (p) at any
instant of time t by simply multiplying the value of current i and voltage
v at that particular instant t. (You can verify that in the diagram p is
negative when either v or i is negative otherwise p is positive. See the
points where p is zero). In the graph we have shown horizontal axis as
angle φ instead of time t for easy visualization. It should be clear that
both way it is correct.
Page 52 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Clearly the instantaneous power p is composed of two terms. The first


term is constant because for a given load the phase angle φ is fixed. It
does not change unless the load is changed. The second term is
varying with time sinusoidally due to the presence of the term cos (2ωt-
φ). Look that the instantaneous power frequency is twice the frequency
of voltage or current.

So the instantaneous power in a single phase circuit varies sinusoidally.

The instantaneous power, p = constant term + sinusoidal oscillating


term.

In one complete period the average of oscillating term is zero.

Then what is the average power within a given time, say one Time
Period of the wave?

It is the constant term.

Here is another way to think about the average power.


Page 53 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Just observe that the instantaneous power is negative for a small time.
For any time interval you just find the total +ve area A+ (above
horizontal-axis (blue line) and below p curve) and total -ve area A-
(below horizontal axis and above p curve). The net area is obtained by
subtracting A- from A+. By dividing this net area ( by the time interval
Ti we get the average power(P). You can do this using calculus. What
you will ultimately get is only the first term in the above formula for
instantaneous power p.

In still another way it is easier to realize that the formula for


instantaneous power p has a constant term (Vm.Im / 2) cos φ and the
other sinusoidal term (Vm.Im / 2) cos (2 wt - φ). Actually p is the
oscillating power which oscillates about the average constant term
(Vm.Im / 2) cos φ .

So the average power is

The above formula can be written as

Or,

here,

V and I are the phasor representation of RMS values* of voltage and


current sinusoids. The symbols |V| and |I| are the magnitudes of
phasors V and I. (See at the buttom for definition of RMS value).

This above formula is your favorite formula for useful power that we are
most concerned about. This average power formula is used to find the
power consumed by the load. The monthly electric energy bill at home is
based on this power. The engineers and technicians in power or
electrical industry simply use the term power instead of average power.
So whenever we simply call power it means average power.

Of course the instantaneous power is oscillating in nature. As we


already said it does not oscillates about the horizontal-axis rather about
the average power P (cyan color horizontal line).
Page 54 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

P will be zero when cos φ =0 or φ = 90 degree, that is when the phase


angle between voltage and current waves is 90 degrees. It is only when
the load is pure inductive or capacitive. In this case the second term
only remains in the instantaneous power formula.

From the above figure for some time the power becomes negative that
means the load supply energy to source for this period. This is due to
the presence of reactive element in load.

The above formula for instantaneous power can be written in another


form. This form actually is an attempt to distinguish the oscillating
reactive power from the instantaneous power formula. Rearranging the
terms in equation for instantaneous power above we get

p = |V| | I | cos φ (1-cow2ωt) - |V|


| I | sin φ sin2ωt
In this equation the first term |V| | I | cos φ (1-cow2ωt) is oscillatory
whose average value is |V| | I | cos φ. We already talked about this
average power.

The second term |V| | I | sin φ sin2ωt which is also oscillatory but with
zero average value. The maximum value of this term is |V| | I | sin φ.
This is the so called Reactive power. So Reactive power is the maximum
value of a oscillatory power that is repeatedly drawn from the source
and again returned to the source within each cycle. So the average of
this reactive power is zero.

The average power P is called as Real Power. It is also sometimes called


active power.

Real power = P = |V| | I | cos φ


It is usually written as P = VI cos φ. But it should be remembered that V
and I are the rms values of voltage and current. For example when we
say single phase 220 volt AC it means the rms value of voltage is 220
volts ( it is not maximum value of voltage sinusoid)

Reactive power = Q = |V| | I | sin


φ
Real power is measured in Watt and the reactive power is measured in
VAR (VoltAmpereReactive). In power sector these units are too small so
real power is measured in Megawatt (MW) and reactive power in
Megavar (MVAR). The letter R at the end denotes reactive power.

Many times students and practicing engineers are confused about the
average power (often simply called power). They think that what they
Page 55 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

get by multiplying RMS voltage and RMS current is RMS power. No that
is wrong. There is no RMS power. RMS power has no meaning or not
defined. (Also see definition of RMS value, below at the end). It is
average power or real power or true power.

Power In Three phase Balanced System

Let us consider a three phase balanced system. A three phase balanced


system is analysed considering only one phase and neutral return. This
is called per phase analysis. So the above analysis for single phase is
true for balanced three phase case. Let the total power here is Pt. Then
we get total three phase power as thrice of single phase case.

Pt = 3 |V| | I | cos φ
It should be remembered that |V| and | I | are the per phase values.
and φ is the phase angle of load in per phase analysis.

The above formula for balanced three phase system can be written as

Pt = √3 |Vl| | Il | cos φ

In the above formula Vl and Il are line voltage and current (Fig-D). This
equation is independent of type of three phase load connection i.e delta
or star connected load. You have to know the line voltage, line current
and phase angle φ as above. This form is very convenient and used
often in power calculation.

There is one main difference between the single phase and total three
phase power. The instantaneous single phase power is pulsating. In the
balanced three phase case, each phase instantaneous power is pulsating
but the three pulsating power waves are 120 degrees displaced from
Page 56 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

each other. At any instant of time the total of these three instantaneous
power waves is a constant which is 3 |V| | I | cos φ. So the total power
consumed in three phase balanced system is not pulsating. Non-
pulsating power also imply the desired non-pulsating torque in case of
three phase rotating machines. In large 3-phase motors this is really
desired.

*RMS value of AC Sinusoids

The value of AC voltage or current that produces the same heating (or
same energy) that is produced if DC voltage or current numerically
equal to RMS value of AC is applied instead of AC. This concept helps
make the formula for power similar for both DC and AC circuits.

Autotransformer

Introduction

Previously we already discussed basics of single phase transformer and


three phase transformer. We also discussed about three phase
transformer connections or Vector Groups. Now, here we will discuss
about auto-transformers. Auto transformers have several applications.
But first we will develop some basic concepts of autotransformer.
Before proceeding further one should have some basic knowledge of
transformer.

Auto transformers can be made in two ways. In one way it can be


realized by additively connecting the primary and secondary windings of
the two winding transformer. In other way the autotransformers can be
thought of built as a single unit with one continuous winding. We will
start from first approach and move to second.

Single Phase Autotransformer


Let us first consider a normal single phase two winding transformer. The
schematic diagram of a transformer is shown in Fig-A(i). We will obtain
an autotransformer from this usual transformer.

Let the primary side and secondary side voltage ratings are respectively
V1, I1 and V2, I2 respectively. Number of turns in primary and secondary
side are N1 and N2 respectively. Now let us connect the transformers as
shown in Fig-A(ii) with additive polarity. For the analysis purpose for
better visibility we rearrange the windings in Fig-A(ii) as shown in Fig-
B. Of course here we have shown a load connected across secondary
Page 57 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

For the purpose of simplifying the analysis the transformer is considered


as ideal. (In case of power transformer the ideal transformer analysis
gives quite accurate result). The autotransformer analysis can be very
simple if you recall two important concepts of a transformer.

 The voltage developed in the windings are dependent on the flux


linkages. The windings are wound on the same magnetic core so
they link the same flux. Hence

V1 / N1= V2 / N2

So whenever voltage V1 exist across primary winding, then


voltage V2 will be induced across the
secondary winding irrespective of changes in connections.

 Similarly the magnetic circuit demands that mmf should be


balanced. It implies the primary side ampere turn should equal the
secondary side ampere turn. Hence

I1 . N1= I2 . N2

It means current I2 that flows in secondary winding is associated with


current I1 in primary winding according to above mmf balance formula.
Page 58 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

In Fig-B the primary of autotransformer is taken across both the


windings where as secondary is across N2 winding.
The autotransformer is so loaded that the secondary current is I1+I2 . It
makes the current flowing in the windings as I1 and I2 which are the
rated values.
using KCL and KVL if the primary side voltage and current of the auto
transformer is Vp and Ip and secondary side voltage and current of the
auto transformer is Vs and Is then,

Vp = V1+V2
Ip = I1
Vs = V2
Is = I1+I2.

Now the capacity of the autotransformer is (V1+V2).I1 or (I1+I2).V2

Using the voltage ratio and mmf balance formula it is quite easy to show
that the autotransformer capacity formula can be simplified as

The capacity of autotransformer = Sa = (V1 + V2).I1 = (I1 +


I2).V2 = V1 I1 (1 + N2 / N1)
= V2 I2 (1 + N2 /
N1)

Where as the capacity of our original transformer = S


=V1 I1 = V2 I2

So, Sa = S(1 + N2 / N1)

But (1 + N2 /N1) is always greater than 1.


Hence by forming an autotransformer the capacity of the resulting
autotransformer is always more than the original isolated winding type
transformer. In the so formed autotransformer it should be remembered
that the voltage and current through the windings remains as before i.e
the rated values. From the above formula it is clear that larger value of
N2/N1 gives larger capacity of the autotransformer.
Page 59 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

In this case the voltage ratio of autotransformer = (V1+V2)/ V2=


V1 / V2 +1 = (N1 / N2 ) + 1

Hence Vp / Vs = (N1 / N2 ) +1 =
(N1 / N2 ) +1

From this formula it is clear that if N2 /N1 is made large to increase the
capacity then the voltage ratio between primary and secondary of
autotransformer approaches 1. For this reason auto transformers are
advantageous for use in power network when the voltage ratio between
both sides is near unity. It is used in grid substations as interconnecting
transformers (ICT). The autotransformers are used to interconnect two
different voltage levels. For example interconnection of 400kV and
220kV, 735kV and 345kV and 765kV and 400kV etc.. The voltage ratio
should be less than 3:1 for more advantageous use.

Again look at the formula,


I1 . N1= I2 . N2

As we said N2 /N1 should be large for adavantageous use.

To achieve it, N2 should be much greater than N1

It implies that I2 will be much less than I1

The current I2 flows in the common winding of the autotransformer.


Hence the auto transformer can be designed with N2 number of turns
made of conductor of smaller cross section area, so resulting in a big
saving.The autotransformers are cheaper and lighter in comparison to
two winding transformers.

Just looking at the sketch you may think that instead of connecting two
windings in additive ways. Why should not it be made of single winding
and one terminal brought out from the middle as per requirement. Yes
this is true and the autotransformer can be thought of made of a single
winding having a part of winding common to primary and secondary .

Sometimes this method is used to obtain a variable secondary


voltage. This case it is so designed that the middle contact can smoothly
slides over the coil. It is commonly used in the academic electrical
laboratories. This is usually called as Variac(Fig-C) or Dimmerstat. There
are some other terminologies adopted by different manufacturers. In
this design it is not possible to adopt conductors of two different cross
sectional area as in case of ICT where turns ratio is fixed(due to fixed
voltage ratio) between primary and secondary.

Autotransformers are also used for voltage regulation in distribution


networks, for starting of induction motors and as lighting dimmers.
Autotransformers are also used in electric traction.
Page 60 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

One main disadvantage about autotransformer is that the primary and


secondary are electrically connected. So the electrical disturbance i.e
high voltage transients from one side can be easily transmitted to the
other side.
The other disadvantage is that the impedance of the autotransformer is
considerably low, so the short circuit current will be more. More over an
open circuit in common winding results in full primary side voltage
across the load which is harmful.

But in several cases the advantages outweigh the disadvantages.

Three Phase Autotransformer


First thing is that the theory of single phase autotransformer is the basis
of three phase autotransformer. Three single phase autotransfor bank
can be used for forming a three phase transformer or a single unit three
phase autotransformer can be built. The three phase autotransformers
(see Fig-D) are connected in star-star(Wye-Wye). If the
autotransformers are connected as Delta-Delta, then phase difference
between primary and secondary exist which is not desired (See Vector
Groups).
Page 61 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

In three phase Y-Y connected power autotransformers an additional


delta connected winding is used to take care of zero sequence currents
(for unbalanced systems), and third harmonic currents.

Although we discussed here is for one particular case still we revealed


the general approach. If you wish to connect load across the other
winding, then you can proceed in a similar way.

Moreover the above analysis is for step down case. You can easily
analyze for step up case by interchanging the position of source and
load. In this case the direction of I1+I2 is reversed so also the directions
of I1 and I2. It should be recalled again that the change of direction of
current in series winding is associated with change of direction of
current in common winding to satisfy mmf balance.

Substation Planning and Siting

We have already discussed in brief about different types of electrical


substations. Now we will discuss about the main factors influencing
selection of substation. The discussion is mainly for transmission
substation which requires many factors to be considered before
selecting the site, size etc. The smaller or distribution substation has
fewer requirements so only some of the points are required to be
considered.

A substation is like a junction point in a power system. Many


transmission lines at different voltage levels terminate at a substation.
Page 62 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Shut down of the substation means shutdown of all the lines


terminating at the substation. Clearly a substation is a very important
unit of power system.

A transmission substation may be comprised of one or more of the


following main sections depending on its size and importance. These are
Switchyards, Control rooms, Office building and Colony for employees.
See the figure at the bottom. The substation planning requires several
factors to be considered. A substation which is not properly planned or
Ill designed may face several problems, in particular if future expansion
or renovation of the switchyard is required. Proper design of substation
also enables it to operate in normal state for maximum possible time so
avoiding overloading to the maximum. It is true that many substations
undergo expansion and renovation with time. So for substation planning
future expansion must be considered.

There are several factors that need to be considered for deciding for a
substation. Some of these requirements are actually the purpose of the
substation while the others are the requirements to fulfill the purpose.

Some important primary factors in the design of substation are


operational flexibility, supply reliability, secutity and short circuit
withstand capability etc.

One important factor to be considered first is the site selection.


Substation design and some equipment selection depends on site
selection. Hence it has a bigger influence on the cost of substation. The
orientation of the lines to be terminated at the substation also decides
the substation orientation and equipment arrangement.

The site should be near the load center keeping in view the future load
growth.
Page 63 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Some general factors to be considered are listed. It should be


remembered that some of the factors are actually interdependent.

 Access road to the site for smooth movement of construction


machines, equipments and transformers. Good Roadways to
construction site and shorter distance to rail head are desired.
 The site should be chosen to avoid soil filling, earth removal etc.
The requirement of soil filling and earth removal takes time and
increases total cost of substation
 Historical data of worst flood is taken into account to avoid water
logging of the substation in case of possibility of flood. Flood
plains and wetlands are avoided.
 Atmospheric conditions like salt and suspended chemical
contaminants influence selection of equipments and maintenance
requirements.
 Interference with communication signals. The construction
company have to take permission from the appropriate authority.
 Electric and magnetic field strength are of particular concern
especially for Ultra High Voltage (UHV) systems at 765 kV,1200 kV
or above. Research organisations has shown the impact of strong
Electric/magnetic fields due to UHV substations and lines on
human health. Such new concerns are also required to be
addressed properly
 Forest land, sanctuaries and national parks are avoided. Almost all
governments has laid stringent rules to comply for approval of
forest land and wild life sanctuary. The usual process takes time to
get approval from the concerned authorities. This process delays
the construction activities.
 Approval is also required from aviation authority. Substation
should be away from airport and defence establishments.
 Water supply and sewage system are the two most important
facilities to be given due consideration.

Some other factors related to the general public:

 The substation should be located far from the crowded places.


Efforts are always made to locate transmission substations
outside the city areas.
 The locals should be made aware of the upcoming substation. To
avoid public resentment it is better to involve the local people in
the process. If required they should be educated and trained.
Many times the local people also plays an important role to check
vandalism and theft.
 Heritage sites and tourist spots are avoided.
 Electric substation is a source of noise. While charged
transformers, reactors and EHV lines are sources of continuous
hissing noise, operation of different equipment also emit sudden
noise. The design should be adopted to tackle the issues by
complying to the standards set by the appropriate authority for
reduction of noise pollution and avoid public resentments.
 Landscaping should be done to keep the substation out of direct
view of common people.
Page 64 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Finally it is safety of man and machine. The safety of the personnel


involved both in construction phase, operational safety and safety of
public is to be followed as per the safety rules and regulations framed
by international bodies and local authorities. These rules are not to be
compromised. Moreover the manufacturer instruction manuals, safety
procedures and other documents for equipment and machines are to be
referred.

A substation should have adequate arrangement of fire fighting system.


It is the ultimate safety measure of any substation. The fire fighting
system should be suitable for dealing with fire due to electrical arc.
Usually costly equipments like transformer should have Nitrogen gas
or high speed water jet as fire fighting system.

In the figure below is a conceptual substation


Page 65 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The substation has 400 kV, 220 kV and 33 kV switchyards. Here some of
the equipments/parts are identified. There are two 400/220 kV, 315
MVA Inter Connecting Transformers (ICT). One 220/33 kV, 100 MVA
step down transformer is used for feeding the distribution network. The
double arrow-head lines represent control and data channels between
switchyard equipments and control room.

Substation Bus Schemes

Introduction:
Page 66 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

We already mentioned the different types of substations. Before more


in-depth discussion about each type of substation it is better to know
few common essential features of a substation. Here we discuss about
the bus schemes commonly implemented in an electrical substation. The
Bus scheme is the arrangement of overhead bus bar and associated
switching equipments in a substation. The operational flexibility and
reliability of the substation greatly depends upon the bus scheme.

Here I reiterate that the electric substation is a junction point where


usually more than two transmission lines terminate. Actually in most of
EHV and HV substations more than half a dozen of lines terminate. In
many large transmission substations the total numbers of lines
terminating exceeds one or two dozens. In this scenario obviously the
first requirement is avoidance of total shutdown of the substation for
the purpose of maintenance of some equipment(s) or due to fault
somewhere. Total shutdown of substation means complete shutdown of
all the lines connected to this particular substation. So the switching
scheme is adopted depending upon the importance of the substation,
reliability requirement, flexibility and future expansion etc.. Of course
substation construction and operational cost is also to be considered.
Clearly a EHV or UHV transmission substation where large numbers of
important lines terminate is extremely important and the substation
should be designed to avoid total failure and interruption of minimum
numbers of circuits.

There are mainly six bus schemes. these are:

 Single Bus
 Main Bus and Transfer Bus
 Double Bus Double Breaker
 Double Bus Single Breaker
 Ring Bus
 Breaker and Half

Before we proceed further I would like to discuss in brief about the


Circuit Breaker and Isolator. It will be helpful for novices. See the figure
below where two buses are connected by circuit breakers and isolators
as shown. A circuit breaker is a device whose main purpose is to break
the circuit carrying load current or fault current. As the breaker is
opened then current is interrupted in the circuit. But it is not safe to
work with opened breaker as one or both sides of the breaker terminals
may be still energised. The breaker is then isolated from the rest of the
circuit by opening the isolators on both sides of breaker. The isolators
are used to isolate the breaker or circuit. It should be remembered that
the isolators are never opened or closed to interrupt or make the circuit.
That means when the circuit is to be made on, first the isolators on both
sides of a breaker are closed then breaker is closed to allow current
flow. When the circuit is to be made off or interrupted, first the breaker
is opened(tripped), hence load current is interrupted. Then to isolate
the breaker, isolators are opened. Isolators are designed to interrupt
small current. Breakers are designed to interrupt large load current and
Page 67 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

heavy fault current. Both breaker and isolator carry load current in
normal state.

Single Bus
As the name indicate the substation with this configuration has a single
bus (Fig-B). All the circuits are connected to this bus. A fault on the bus
or between the bus and a breaker results in the outage of the entire bus
or substation. Failure of any breaker also results in outage of the entire
bus. Maintenance of any circuit breaker requires shutdown of the
corresponding circuit/line and maintenance of bus requires complete
shutdown of the bus. A bypass switch across the breaker should be used
for maintenance of the corresponding breaker. This case the protection
system is disabled.

Single Bus configuration is the simplest and least cost of all


configurations. The system can be easily expanded. This configuration
requires less area. The reliability of this system being low, it is not to be
implemented in the substation where high reliability is expected. Large
substations usually do not utilize this scheme. By sectionalising of the
bus the reliability and availability of the single bus system can be
improved.
Page 68 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

Main Bus and Transfer Bus


In this scheme one more bus is added. See Figure-C how
the equipments are arranged and circuits are connected between main
and transfer bus. In this arrangement one more breaker may be used,
known as tie circuit breaker. No circuit is associated with this tie
breaker.

When the tie CB is not present, for maintenance of a circuit breaker, the
transfer bus is energized by closing the isolator switches to transfer
bus. Then the breaker to undergo maintenance is opened and isolated
(opening isolators on both sides of CB) for maintenance. In this
arrangement there is no protection for the circuits. The circuits can be
protected from outside the substation.

When the tie breaker is present, for maintenance of a breaker the


Page 69 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

transfer bus is energised by closing the tie breaker. Then the isolator
near the transfer bus of the breaker of circuit to be maintained is closed.
Now the breaker to be maintained is opened. Then corresponding
isolators on both sides of breaker are opened. The breaker is removed
for maintenance. The circuit is transferred to transfer bus. Remember
that the isolator to the transfer bus corresponding to the breaker not to
be maintained remain open. Here the tie breaker protects the circuit in
place of removed breaker. In this scheme the relay setting is quite
complex due to the requirement of the tie breaker to handle each
situation for maintenance of any of the other breakers. This scheme is
somewhat more costly than the single bus scheme but is more reliable.
The scheme can be easily expanded. The switching procedure is
complicated for maintenance of any circuit breaker. Failure of a breaker
or fault on the bus results in outage of complete substation.

Double Bus Double Breaker


In this scheme there are two buses and two circuit breakers per circuit
are used (See Fig-D). In normal state both the buses are energised. Any
circuit breaker can be removed for maintenance without interruption of
the corresponding circuit. Also the failure of one of the two buses does
not interrupt any circuit as all the circuits can be fed from the remaining
bus and isolating the failed bus. By shifting circuit from one bus to other
the loading on the buses can be balanced.
The substation with this configuration requires twice as much
equipments as single bus scheme. This scheme has high reliability. But
due to more equipments this scheme is costly and requires more space.
This scheme is usually used at EHV transmission substation or
generating station where high reliability is required.

Double Bus Single Breaker


This scheme is shown in Fig-E. This scheme has two buses. Each circuit
Page 70 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

has one breaker and connected to both buses by isolators as shown.


There is one tie breaker between two buses. The tie breaker is normally
closed. For the tie breaker in closed position the circuit can be
connected to either of the buses by closing the corresponding switch. It
is clear that fault on one bus requires isolation of the bus and the
circuits are fed from the other bus.

From the figure you can guess that the configuration has some
improvement over the single bus system. This arrangement has more
flexibility in operation than the single bus scheme. This scheme is
costlier and requires more space than the single bus scheme. Many EHV
transmission substations use this scheme with an additional transfer
bus.

Ring Bus
The Ring Bus configuration is shown in Fig-F. The breakers are so
connected and forms a ring. There are isolators on both sides of each
breaker. Circuits terminate between the breakers. The number of
breakers is same as the numbers of circuits. Each of the circuits in ring
bus system is fed from both sides. Any of the breaker can be opened and
isolated for maintenance without interrupting any of the circuits. A fault
on any of the circuit is isolated by tripping of two breakers on both sides
of the circuit. By tripping the two breakers only the faulted circuit is
isolated and all other circuits continue to operate in open ring state.
This scheme has good operational flexibility and high reliability. The
main disadvantage is that when a fault happens and the ring is split and
may result into two isolated sections. Each of these two sections may
not have the proper combination of source and load circuits. To avoid
this as far as possible the source and load circuits should be connected
side by side (see figure). The ring bus scheme can be expanded to
accommodate more circuits. The ring bus scheme is not suitable for
more than 6 circuits (although possible). When expansion of the
substation is required to accommodate more circuits, the ring bus
Page 71 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

scheme can be easily expanded to One and Half Breaker(See below and
compare) scheme. The scheme is required to be planned properly to
avoid difficulties in future expansion.

Breaker and Half

The Breaker and Half scheme has two main buses (Fig G). Both the
buses are normally energised. Three breakers are connected between
the buses. The circuits are terminated between the breakers as shown.
In this bus configuration for two circuits three numbers of breakers are
required. Hence it is called one and half scheme. It is something like,
for controlling one circuit we require one full and a half breakers. The
middle breaker is shared by both the circuits. Like the ring bus scheme
here also each circuit is fed from both the buses.

Any of the breakers can be opened and removed for maintenance


purposes without interrupting supply to any of the circuits. Also one of
the two buses can be removed for maintenance without interruption of
the service to any of the circuits. If fault happens on a bus it is isolated
without interruption of supply to any of the circuits. If the middle circuit
breaker fails then the breakers adjacent to the buses are tripped so
interrupting both the circuits. But if a breaker adjacent to the bus fails
then the tripping of middle breaker does not interrupt power supply to
circuit associated with healthy breaker. Only the circuit associated with
failed breaker is interrupted.
Page 72 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

This configuration is very flexible and highly reliable. The relaying of the
scheme is complicated as the middle breaker is associated with both the
circuits. This scheme is economical in comparison to Double Bus Double
Breaker scheme. This scheme also require more space in comparison to
other schemes to accommodate more equipments.

In one substation you can find two or more schemes implemented as


per the requirement. In most of the modern substations it is usual to
add one transfer bus in most of the schemes above. Which enhances the
availability and maintainability of the system and operational flexibility

Circuit Breaker

In last article we discussed common bus schemes used in substations.


We felt the importance of the circuit breaker. Here we will discuss more
about the circuit breakers. Although here the primary concern is about
the breakers used in HV, EHV or UHV substations the basic is still
applicable to low voltage breaker. Also Switchgear is a very common
term often used by power system engineers. Switchgear includes circuit
breaker, protective devices, and also measuring and control devices.

The main function of the circuit breaker is to break and make the circuit.
So theoretically a circuit breaker is a switch. The breaker is rated so that
is should be capable to make, carry and break load current during
normal operation and interrupt large fault current in abnormal
conditions.

Circuit breaker is the main equipment for controlling power flow and
safety of other equipments and personnel. The different associated
Page 73 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

elements and basic functioning of the circuit breaker is illustrated in the


simplified Figure-A. The breaker can be operated by a trained substation
personnel by pressing the button at the control room. But during the
fault condition it trips automatically.

When fault in the line takes place the large fault current is associated
with the increase of secondary current in current transformer (CT). This
will actuate the relay and relay contact closes. Now as the tripping
circuit of the breaker is complete the trip coil is energised. The
energised trip coil initiates breaker mechanism for moving the circuit
breaker moving contact away from fixed contact. The Arc formed
between the moving contact and fixed contact is extinguished by
breaker arc extinguishing mechanism. The breaker is open. From the
figure it is clear that the breaker trip circuit can be closed by closing of
either of the contacts C1 or C2. While C1 is for manual closing by
pressing the button at the control panel, the C2 is closed automatically
by breaker relay for abnormal over current condition sensed by CT.
These two contacts in parallel fulfil the logic OR function. Applying same
reasoning it is easy to think that the breaker can be logically
conditioned for tripping on other abnormal conditions.

The trip circuit is supplied with DC battery source. Independent AC


source may be used for trip circuit. It should be noted that for high
voltage breaker the fault sensing device is outside the circuit breaker
Page 74 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

where as in case of low voltage breaker the sensing device is


accommodated within the breaker enclosure.

During separation of moving contact from fixed contact electric arc is


produced between the contacts. Extinguishing of the arc is the most
important part of breaker functioning, which greatly influences the
breaker design. Actually in low and medium voltage case, the arc
extinction is not of much problem. The arc extinguishing is a difficult
task in HV and EHV or UHV circuit and is the primary concern for breaker
design. The energy stored in the line/circuit inductance is dissipated in
the arc and the arc is required to be extinguished reliably.

From the above discussion it is observed that the circuit breaker


functioning is comprised of three main components.

 Sensing and tripping circuit


 Operating mechanism
 Arc interruption

The breakers can be classified several ways. The most important


classification is the medium used for arc interruption.

For low and medium voltage use, air is mainly used as the medium for
arc extinction (In past, oil was also used for 430/220 volt system). In
HV, EHV and UHV substations oil and gas is used as arc quenching
medium (In the past Air Blast breakers were also often used for
HV/EHV/UHV application). Like low voltage system, Oil Circuit breakers
are also becoming obsolete for higher voltage use. Vacuum is also used
for arc quenching. Vacuum circuit breakers are usually used for
breakers in the range of 3 kV to 38 kV. In modern EHV and UHV
substations SF6 gas breakers have replaced the Oil circuit breakers
and Air Blast circuit breakers. But one can still find Oil Breakers and Air
Blast Breakers in many old substations.

SF6 is a superior gas having good dielectric strength and arc quenching
ability which has proved to be a better medium for arc quenching in the
breaker. An UHV SF6 Circuit Breaker is displayed below.
Page 75 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

The circuit breakers are also available as single tank type or separate
tank type. In case of separate tank type, each phase has a separate
tank. For EHV application separate tank type breakers are preferred.

The circuit breakers can also be classified from the point of view of
operating mechanism. The operating mechanism of the circuit breaker
may be hydraulic, pneumatic or motor operated types.

The circuit breakers are also classified as live tank type or dead tank
type. In case of live tank type breaker the enclosure of the breaker is at
line potential. In the dead tank type breaker the enclosure of the
breaker is at ground potential. The dead tank type breaker requires
additional oil/gas for insulation from the grounded enclosure. Live tank
type breaker requires less oil or gas.

More on Circuit Breaker is discussed in subsequent articles.

Arcing in Circuit Breaker

Electric Arc
For interrupting power supply to a part of a network or circuit, or to
clear a fault, circuit breakers are employed. On receipt of trip signal the
circuit breaker operating mechanism operates to separate moving
contact from the fixed contact (Fig-A). As the moving contact starts
moving away from the fixed contact, the contact area of the tips of both
moving contact and fixed contact reduces. But the same current now
Page 76 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

passes through this reduced contact area. The current density of the
contact area increases very much. This situation makes the areas of the
tips in contact very hot, may be several thousand degrees celsius. Now
as the contacts just separate these hot spots becomes source of
electron emission. High energy electrons are emitted from the separated
contact tips. This is called thermionic emission.

The other main cause of electron emission is field emission. As the


movable contact moves away from the fixed contact voltage difference
between the two electrodes (fixed and moving contacts) exist (Fig-B).
Which gives rise to an electric field between the electrodes.

Electric Field = V / d

Where V is the potential difference between the electrodes and d is the


separation between the two.
Page 77 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

So from the above formula it is clear that just after separation when the
movable contact has not moved much away, then d is small so the
electric field strength is very high (order of several kV per millimetre).
High electric field gives rise to emission of high energy electrons from
the contact surface. The high speed electrons emitted bombard the
molecule or atoms of the medium and dislodge electrons from the
atoms. This is secondary emission.

The high energy electrons so emitted ionise the gas or oil used as
medium. Arc plasma is formed between the fixed and moving
contacts. The current continues to flow through the arc plasma between
the contacts (see Fig-A).

It is clear that just separating the contacts does not automatically break
the circuit and flow of current does not stop. The arc is required to be
extinguished. More importantly the dielectric strength of the medium
between the fixed and moving contacts should be restored quickly,
otherwise arc may re-strike between the contacts. This is the job of the
arc interruption chamber of the circuit breaker.

Several techniques are employed for the arc extinction. The arc can be
extinguished by increasing the resistance of the arc path. This is
achieved by lengthening the arc or splitting the arc using one of the
techniques and by reducing the diameter of the arc by cooling. By
increasing the resistance the voltage drop across the arc increases. It
achieves such a value that the supply voltage cannot sustain the voltage
drop across the arc and the arc is extinguished.
Also in AC circuit the current varies sinusoidally so the arc is
extinguished at next current zero. Although the arc is extinguished but
the medium is having enough ionised particles. Hence to stop the re-
striking of arc due to Transient Restriking Voltage the space between
the separated contacts should rapidly regain dielectric strength. This
can be done by blowing gas or air at high speed to the region between
the contacts in Gas or Air Blast breaker. In case of oil circuit breaker
rapid flow of oil to the contact region helps regain high dielectric
strength. Regaining dielectric strength is the result of recombination of
ions and electrons.

The working principles of some breakers will be discussed later.

Transmission Line Parameters Resistance and Inductance

The transmission lines are modeled by means of the parameters


resistance, inductance, capacitance and conductance. Resistance and
inductance together is called transmission line impedance. Also
capacitance and conductance in parallel is called admittance Here we
Page 78 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

are not going to derive the formulas rather to develop some concepts
about the transmission line parameters. It will help us understand the
transmission line modelling and in analyzing the power system. In this
article we will discuss about the line resistance and inductance. In the
next article we will discuss about line capacitance and conductance.

Resistance
The conductors of the transmission lines have small resistance. For
short lines, resistance plays an important role. As the line current
increases so do the ohmic loss (I2R loss). When the current exceed a
certain value the heat generated due to ohmic loss starts to melt the
conductor and the conductor becomes longer that results in more sag.
The current at which this condition of conductor is irreversible is called
thermal limit of conductor. Short overhead lines should be operated well
within this limit.

The resistance R of a conductor of length 'l' and cross section 'a' is


given by the formula

l
R = ρ ----
a

Here ρ is the resistivity of the conductor material which is a


constant.

Transmission lines usually use ACSR conductors with spirally twisted


strands. So the actual length of the conductor is about 2 % more than
the ACSR conductor length. So from the above formula, the resistance of
the line is proportionately 2% more than the conductor length. Another
important factor is that when the frequency of current increases the
current density increases towards the surface of conductor and current
density at the center of conductor is less. That means more current
flows towards the surface of conductor and less towards the center.
This is well known skin effect. Even at power frequency (60/50 Hz) due
to this skin effect the effective cross sectional area of conductor is less.
Again from the above equation it is clear that the conductor resistance
is more for higher frequency. So AC resistance of conductor is more than
the DC resistance. Temperature is another factor that influences the
resistance of conductor. The resistance varies linearly with temperature.
The manufacturers specify the resistance of the conductor and one
should use the manufacturers data.

Inductance
For medium and long distance lines the line inductance (reactance) is
more dominant than resistance. The value of current that flows in a
conductor is associated with another parameter, inductance. We know
that a magnetic field is associated with a current carrying conductor. In
AC transmission line this current varies sinusoidally, so the associated
Page 79 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

magnetic field which is proportional to the current also varies


sinusoidally. This varying magnetic field induces an emf (or induced
voltage) in the conductor. This emf(or voltage) opposes the current flow
in the line. This emf is equivalently shown by a parameter known as
inductance. The inductance value depends upon the relative
configuration between the conductor and magnetic field. Inductance in
simple language is the flux linking with the conductor divided by the
current flowing in the conductor. In the calculation of inductance the
flux inside and outside of the conductor are both taken care of. The
inductance so obtained is total inductance. Now onwards if not
exclusively mentioned then inductance means total inductance due to
conductor internal and external flux linkages. The symbol L is used
universally to represent inductance. L is measured in Henry (H). It is
usually expressed in smaller unit, milli Henry(mH). Manufactures
usually specify inductance value per kilometer or mile.

It should be noted that, in all the formulas below inductance L is in


Henry per unit length and not simply Henry. Here few cases are
depicted.

 For a single phase line see the fig-A. The conductor inductance is

L = 2 * 10-7 ln ( D/r1' )

Here D is the distance between the centers of conductors.

r1' = r1 * e-(1/4) = 0.7788 r1


r1 is the actual radius of the conductor.

For a single phase line the return path also has inductance say L'. If the
return conductor is of radius r2, then

L' = 2 * 10-7 ln ( D/r2' )


Therefore the total inductance of single phase circuit is Lt = L+L'
rearranging we get

Lt = 4 * 10 -7
ln [D / √ (r1'. r2')]
Page 80 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

 For three phase circuit whose three circular conductors are at the
corners of equilateral triangle(Fig-B(i)) then the above formula for
single phase case is applied here. In this case inductance per
phase L is as below:

If the Denominator is renamed as Ds, then

L = 2 * 10-7 ln ( D / Ds )
Here Ds = r'

As already said r' is 0.7788 times the actual radius(r) of


conductor.
Page 81 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

 For three phase circuit whose three circular conductors are


arbitrarily placed (Fig-B(ii)) and the conductors are transposed
then,

L = 2 * 10-7 ln [ ∛(D1 .
D2 . D3) / Ds ]

Beginning from the single phase line, it is observed that all the three
equations for inductance of a phase conductor are similar.
Remember that this formula for three phase line is not valid for non-
transposed lines.

Observing the formula for single phase and three phase lines we can
generalize the formula for inductance of a phase line as in the form

L = 2 * 10-7 ln ( D / Ds )
Where
D = Geometric Mean Distance (GMD)
Ds= Geometric Mean Radius (GMR)

In single phase case GMD is simply the distance between the centers of
two conductors.
Page 82 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

In three phase case for conductors equidistant from each other GMD is
the distance between any two phase conductors.
In the three phase case, for line conductors arbitrarily placed GMD
= ∛(D1D2D3 )

In all the three cases Ds = r'.

 From above we can conclude that GMD is like equivalent distance


between conductors. When two or more conductors per phase are
used as in bundled conductors then GMD is required to be
computed. Here distances from each conductor in one phase to
each conductor in other phase is calculated. If for example in a
single phase line there are 4 conductors in one phase and 3
conductors in other phase (Fig-C) then we will have 12 numbers of
distances between the conductors. I have shown four distances
only.

GMD = [D1 . D2 ........ D12] 1/12

so here GMD is the 12th root of product of 12 numbers


of distances.

 GMR is calculated for each phase separately. Each of the phases


may have different GMR values depending upon the conductor size
and arrangement. GMR is to be calculated when each phase is
comprised of more than one conductor per phase as in the
example above. For GMR calculation when two or more
conductors per phase are used, first product of all the groups
(one group for each conductor)are found where each group is
product of possible distances from one conductor to other
conductors including r' of that conductor. In the above example
case GMR for line with 3 conductors per phase is

GMR =
[(r1'.D12.D13)(r2'.D23.D21)(r3'.D31.D32)]1/9
It should be noted that D12 = D21, D13 = D31 and D23 =
D32
Page 83 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

 Below is the formula to calculate GMR for the bundled conductors


(see Fig-D)

For three conductors per phase (triple conductor)


GMR = ∛(Ds *d )
2

For four conductors per phase (quad conductor)


GMR = 1.09 ∜(Ds *d 3)

How to calculate GMD of three phase line with bundled conductors? For
an example see Fig-E where three phase bundles (triple conductror) are
placed horizontally on transmission towers. In this case the distance
between the conductors (D) is taken as distance between the centers of
bundled conductors.

So, GMD = ∛(D.D.2D)


You can also calculate considering the distance from each bundled
conductors of one phase to other conductors of two other phases. But
the GMD calculated does not vary significantly from our simple form
above. This is due to the fact that D is quite larger than d.
Page 84 of 84 Transmission Lines Prof. Nazar M. Karyar Tuesday, September 16, 2014

 For ACSR conductors GMR is specified by the manufacturer.If this


GMR is called Ds. For example if two such ACSR conductors(twin
conductor) are used in a bundle for each phase. The GMR of the
phase conductor arrangement is calculated imagining that the
supplied GMR (or Ds) as the equivalent radius of ACSR conductor.

Hence if d is the distance between the centers of the two ACSR


conductors, similar to the formulas in
Fig-D,

GMR= [(Ds.d).(Ds.d)]1/4 =√(Ds . d)


 We will discuss Inductance and capacitance for double circuit after
discussing line capacitance in next article.

Usually it is not always possible to arrange the phase lines equilaterally


on the towers. To make the inductance and capacitance of all the three
phases nearly equal, the conductors are transposed. Which means the
conductors exchange the position after 1/3 rd of line length. By
transposing the inductance and capacitance of all the three phase lines
are made nearly equal. This helps balancing the three phase voltages at
the receiving end of the line. Although the above formulas are derived
considering transposition, the same formulas are also used for non-
transposed cases to get approximate values.

Transmission line capacitance and conductance

Das könnte Ihnen auch gefallen