1 Job Name :- Villa Job No:- 01 Estimated for Local Time (GMT)
2 Location :- Nagpur Floor :- Ground (Bedroom 1) Peak Month June Sun Time 3.00 pm
3 Space used for:- Residential Space
Wheather
Area in Height
O
F DBT O
F WBT % RH O
F DP GR/LB
Conditions
4 Size Mts Mts CU.Fts
SQ.Fts in FT BTU/ HR
5 5.2 4.2 234.9984 13.8 3242.978 Outside 110 80 40 81 160
6 Description AREA TEMP DIFF. U FACTOR #VALUE! Inside Room 75 62 50 55 65
7 SOLAR GAIN - GLASS Differences 35 XXX XXX XXX 95
Range of
8 SQ.FT Deg (F) U Value BTU/ HR Coil
DBT
Latitude 21.10N 19.4 BYPASS 0.1
9 NE Glass 15 14 1 210 (Outdoor
Factor
)
10 SE Glass 15 14 1 210 OUTSIDE AIR
No of
11 E Glass 0 3 Cfm/Person 20 60
People
VENTILA
12 W Glass 0 TION Sq. Ft. 234.9984 Cfm/Sq.ft 0.33 77.549472
13 Sky light 0 CFM VENTILATION 77.549472
14 SOLAR & TRANS. GAIN - WALLS & ROOF Swinging / Revolving Doors
15 SQ.FT ETD+D.B.T. outdoor U Value
16 NE Wall 175 16 22.9 0.33 2246.475 People 3 Cfm/Person 20 60
17 SE Wall 220 15 22.9 0.33 2751.54 INFILTRA Open Doors
18 E Wall 0 TION Doors X Cfm/Door =
19 W Wall 0 Exhaust Fans
20 Wall 0 Crack Feet X Cfm/Ft. =
21 Roof-Sun 0 CFM INFILTRATION
22 Roof-Shaded 0 CFM OUTDOOR AIR THRU APPARATUS 77.549472
23 TRANS. GAIN- EXCEPT WALLS & ROOF
APPARATUS DEWPOINT
24 SQ.FT 0F U Value
25 All Glass 0 Effective Room
Effective Heat 20458.4983
26 Partitions 317 30 0.37 3518.7 Sensible Heat
Sensible Factor 0.7648409288
27 Ceiling 235 30 0.4 2820 (ESHF) Effective Room Total
26748.6971
28 Floor 0 Heat
29 INFILTRATION & OUTSIDE AIR ADP Indicated ADP = _0F Selected ADP = _0F 50
30 Infiltration 77.549472 Cfm 35 TD 0.98 2659.94689 DEHUMIDIFIED AIR QUANTITY
31 Outside Air 77.549472 Cfm 3.5 TD*BF 0.98 265.994689 TEMP. 1- BF X (TRM
0.9 75 50 22.5
RISE -TADP)
32 INTERNAL HEAT
Sensible Heat Gain
33 People No. People 3 240 720 DEHUM. ERSH = 20458.4983
From People 841.9135103052
CFM
34 Power H.P./KW 0 1.08 X 0F T Rise 24.3
35 Lights Watts/ SFT 4 234.998 3.4 3195.97824
RSH = 18598.6348
36 Appliances, Etc. 0 0 OUTLET
TEMP. 20.4545454545
37 Additional Heat Gains 0 DIFF.
1.08 X CFMDA 909.26659
38 ROOM SENSIBLE HEAT 18598.6348
39
SAFETY RSH = 18598.6348
DUCT HEAT DUCT LEAK SUPPLY
FAN + H.P. FACTOR 10 % = 1859.86348 CFM
841.9135103052
40 GAIN LOSS 1.08 X 0F(RM-OUTLET) 22.090909
0.1

41 EFFECTIVE ROOM SENSIBLE HEAT 20458.4983 BYPASS CFMSA 841.9135 CFMDA 841.914 0
42 LATENT HEAT CFM
43 Infiltration CFM 77.549 95 gr/lb 0.68 5009.69589 RESULTING ENT &LVG CONDITIONS AT APPARATUS

44 Outside Air CFM 77.549 9.5 gr/lb*BF 0.68 500.969589


EDB TRM____0F+(CFMOA/*CFM)X(TOA____0F-TRM____0F)=TEDB____0F
Latent Heat Gain
45 People No. People 3 160 480
From People
46 Steam lb/hr 0
LDB TADP____0F+ _____BF X (TEDB____0F-TADP____0F)=TLDB____0F
47 Appliances, Etc. 0
48 ROOM LATENT HEAT 5990.66548 FROM PSYCHOMETRIC CHART: TEWB_______0F, TLWB______0F
49 SAFETY NOTES
DUCT HEAT DUCT LEAK
FAN + H.P. FACTOR 5% = 299.533274
50 GAIN LOSS TR 1 ROOM TR 2.82463803
0.05
51 EFFECTIVE ROOM LATENT HEAT 6290.19875 CFM 400 ROOM CFM 1129.85521
52 EFFECTIVE ROOM TOTAL HEAT 26748.6971
53 OUTSIDE AIR HEAT 7146.95934
54 TEMP DIFF. 1-BF
Sensible CFM 77.549 1.08 2638.23304
55 35 0.9
56 GR/LB DIFF. 1-BF
Latent CFM 77.549 0.68 4508.7263
57 95 0.9

58 TONS 2.82463803 GRAND TOTAL HEAT 33895.6564


Mohammed Ehtesham Uddin Jamal Mohammed Ehtesham Uddin Jamal

A B C D E F G H I J K L M N O P
1 Job Name :- Villa Job No:- 01 Estimated for Local Time (GMT)
2 Location :- Nagpur Floor :- Ground (Bedroom 1) Peak Month June Sun Time 3.00 pm
3 Space used for:- Residential Space
Wheather
Area in Height
O
F DBT O
F WBT % RH O
F DP GR/LB
Conditions
4 Size Mts Mts CU.Fts
SQ.Fts in FT BTU/ HR
5 5.2 4.2 234.9984 13.8 3242.978 Outside 110 80 40 81 160
6 Description AREA TEMP DIFF. U FACTOR #VALUE! Inside Room 75 62 50 55 65
7 SOLAR GAIN - GLASS Differences 35 XXX XXX XXX 95
Range of
8 SQ.FT Deg (F) U Value BTU/ HR Coil
DBT
Latitude 21.10N 19.4 BYPASS 0.1
9 NE Glass 15 14 1 210 (Outdoor
Factor
)
10 SE Glass 15 14 1 210 OUTSIDE AIR
No of
11 E Glass 0 3 Cfm/Person 20 60
People
VENTILA
12 W Glass 0 TION Sq. Ft. 234.9984 Cfm/Sq.ft 0.33 77.549472
13 Sky light 0 CFM VENTILATION 77.549472
14 SOLAR & TRANS. GAIN - WALLS & ROOF Swinging / Revolving Doors
15 SQ.FT ETD+D.B.T. outdoor U Value
16 NE Wall 175 16 22.9 0.33 2246.475 People 3 Cfm/Person 20 60
17 SE Wall 220 15 22.9 0.33 2751.54 INFILTRA Open Doors
18 E Wall 0 TION Doors X Cfm/Door =
19 W Wall 0 Exhaust Fans
20 Wall 0 Crack Feet X Cfm/Ft. =
21 Roof-Sun 0 CFM INFILTRATION
22 Roof-Shaded 0 CFM OUTDOOR AIR THRU APPARATUS 77.549472
23 TRANS. GAIN- EXCEPT WALLS & ROOF
APPARATUS DEWPOINT
24 SQ.FT 0F U Value
25 All Glass 0 Effective Room
Effective Heat 20458.4983
26 Partitions 317 30 0.37 3518.7 Sensible Heat
Sensible Factor 0.7648409288
27 Ceiling 235 30 0.4 2820 (ESHF) Effective Room Total
26748.6971
28 Floor 0 Heat
29 INFILTRATION & OUTSIDE AIR ADP Indicated ADP = _0F Selected ADP = _0F 50
30 Infiltration 77.549472 Cfm 35 TD 0.98 2659.94689 DEHUMIDIFIED AIR QUANTITY
31 Outside Air 77.549472 Cfm 3.5 TD*BF 0.98 265.994689 TEMP. 1- BF X (TRM
0.9 75 50 22.5
RISE -TADP)
32 INTERNAL HEAT
Sensible Heat Gain
33 People No. People 3 240 720 DEHUM. ERSH = 20458.4983
From People 841.9135103052
CFM
34 Power H.P./KW 0 1.08 X 0F T Rise 24.3
35 Lights Watts/ SFT 4 234.998 3.4 3195.97824
RSH = 18598.6348
36 Appliances, Etc. 0 0 OUTLET
TEMP. 20.4545454545
37 Additional Heat Gains 0 DIFF.
1.08 X CFMDA 909.26659
38 ROOM SENSIBLE HEAT 18598.6348
39
SAFETY RSH = 18598.6348
DUCT HEAT DUCT LEAK SUPPLY
FAN + H.P. FACTOR 10 % = 1859.86348 CFM
841.9135103052
40 GAIN LOSS 1.08 X 0F(RM-OUTLET) 22.090909
0.1

41 EFFECTIVE ROOM SENSIBLE HEAT 20458.4983 BYPASS CFMSA 841.9135 CFMDA 841.914 0
42 LATENT HEAT CFM
43 Infiltration CFM 77.549 95 gr/lb 0.68 5009.69589 RESULTING ENT &LVG CONDITIONS AT APPARATUS

44 Outside Air CFM 77.549 9.5 gr/lb*BF 0.68 500.969589


EDB TRM____0F+(CFMOA/*CFM)X(TOA____0F-TRM____0F)=TEDB____0F
Latent Heat Gain
45 People No. People 3 160 480
From People
46 Steam lb/hr 0
LDB TADP____0F+ _____BF X (TEDB____0F-TADP____0F)=TLDB____0F
47 Appliances, Etc. 0
48 ROOM LATENT HEAT 5990.66548 FROM PSYCHOMETRIC CHART: TEWB_______0F, TLWB______0F
49 SAFETY NOTES
DUCT HEAT DUCT LEAK
FAN + H.P. FACTOR 5% = 299.533274
50 GAIN LOSS TR 1 ROOM TR 2.82463803
0.05
51 EFFECTIVE ROOM LATENT HEAT 6290.19875 CFM 400 ROOM CFM 1129.85521
52 EFFECTIVE ROOM TOTAL HEAT 26748.6971
53 OUTSIDE AIR HEAT 7146.95934
54 TEMP DIFF. 1-BF
Sensible CFM 77.549 1.08 2638.23304
55 35 0.9
56 GR/LB DIFF. 1-BF
Latent CFM 77.549 0.68 4508.7263
57 95 0.9

58 TONS 2.82463803 GRAND TOTAL HEAT 33895.6564


Mohammed Ehtesham Uddin Jamal Mohammed Ehtesham Uddin Jamal

A B C D E F G H I J K L M N O P
1 Job Name :- Villa Job No:- 01 Estimated for Local Time (GMT)
2 Location :- Nagpur Floor :- Ground (Bedroom 1) Peak Month June Sun Time 3.00 pm
3 Space used for:- Residential Space
Wheather
Area in Height
O
F DBT O
F WBT % RH O
F DP GR/LB
Conditions
4 Size Mts Mts CU.Fts
SQ.Fts in FT BTU/ HR
5 4.2 3.2 144.6144 13.8 1995.679 Outside 110 80 40 81 160
6 Description AREA TEMP DIFF. U FACTOR #VALUE! Inside Room 75 62 50 55 65
7 SOLAR GAIN - GLASS Differences 35 XXX XXX XXX 95
Range of
8 SQ.FT Deg (F) U Value BTU/ HR Coil
DBT
Latitude 21.10N 19.4 BYPASS 0.1
9 NE Glass 0 (Outdoor
Factor
)
10 SE Glass 15 14 1 210 OUTSIDE AIR
No of
11 E Glass 0 2 Cfm/Person 25 50
People
VENTILA
12 W Glass 0 TION Sq. Ft. 144.6144 Cfm/Sq.ft 2 289.2288
13 Sky light 0 CFM VENTILATION 289.2288
14 SOLAR & TRANS. GAIN - WALLS & ROOF Swinging / Revolving Doors
15 SQ.FT ETD+D.B.T. outdoor U Value
16 NE Wall 0 People 2 Cfm/Person 25 50
17 SE Wall 130 15 22.9 0.33 1625.91 INFILTRA Open Doors
18 E Wall 0 TION Doors X Cfm/Door =
19 W Wall 0 Exhaust Fans
20 Wall 0 Crack Feet X Cfm/Ft. =
21 Roof-Sun 0 CFM INFILTRATION
22 Roof-Shaded 0 CFM OUTDOOR AIR THRU APPARATUS 289.2288
23 TRANS. GAIN- EXCEPT WALLS & ROOF
APPARATUS DEWPOINT
24 SQ.FT 0F U Value
25 All Glass 0 Effective Room
Effective Heat 30211.8349
26 Partitions 335.56 30 0.37 3724.716 Sensible Heat
Sensible Factor 0.5785207191
27 Ceiling 144.61 30 0.4 1735.32 (ESHF) Effective Room Total
52222.5634
28 Floor 0 Heat
29 INFILTRATION & OUTSIDE AIR ADP Indicated ADP = _0F Selected ADP = _0F 34
30 Infiltration 289.2288 Cfm 35 TD 0.98 9920.54784 DEHUMIDIFIED AIR QUANTITY
31 Outside Air 289.2288 Cfm 3.5 TD*BF 0.98 992.054784 TEMP. 1- BF X (TRM
0.9 75 34 36.9
RISE -TADP)
32 INTERNAL HEAT
Sensible Heat Gain
33 People No. People 2 245 490 DEHUM. ERSH = 30211.8349
From People 758.1008458898
CFM
34 Power H.P./KW 2000 3.4 6800 1.08 X 0F T Rise 39.852
35 Lights Watts/ SFT 4 144.614 3.4 1966.75584
RSH = 27465.3045
36 Appliances, Etc. 0 0 OUTLET
TEMP. 33.5454545455
37 Additional Heat Gains 0 DIFF.
1.08 X CFMDA 818.74891
38 ROOM SENSIBLE HEAT 27465.3045
39
SAFETY RSH = 27465.3045
DUCT HEAT DUCT LEAK SUPPLY
FAN + H.P. FACTOR 10 % = 2746.53045 CFM
758.1008458898
40 GAIN LOSS 1.08 X 0F(RM-OUTLET) 36.229091
0.1

41 EFFECTIVE ROOM SENSIBLE HEAT 30211.8349 BYPASS CFMSA 758.1008 CFMDA 758.101 0
42 LATENT HEAT CFM
43 Infiltration CFM 289.23 95 gr/lb 0.68 18684.1805 RESULTING ENT &LVG CONDITIONS AT APPARATUS

44 Outside Air CFM 289.23 9.5 gr/lb*BF 0.68 1868.41805


EDB TRM____0F+(CFMOA/*CFM)X(TOA____0F-TRM____0F)=TEDB____0F
Latent Heat Gain
45 People No. People 2 205 410
From People
46 Steam lb/hr 0
LDB TADP____0F+ _____BF X (TEDB____0F-TADP____0F)=TLDB____0F
47 Appliances, Etc. 0
48 ROOM LATENT HEAT 20962.5985 FROM PSYCHOMETRIC CHART: TEWB_______0F, TLWB______0F
49 SAFETY NOTES
DUCT HEAT DUCT LEAK
FAN + H.P. FACTOR 5% = 1048.12993
50 GAIN LOSS TR 1 ROOM TR 6.57315746
0.05
51 EFFECTIVE ROOM LATENT HEAT 22010.7285 CFM 400 ROOM CFM 2629.26299
52 EFFECTIVE ROOM TOTAL HEAT 52222.5634
53 OUTSIDE AIR HEAT 26655.3262
54 TEMP DIFF. 1-BF
Sensible CFM 289.23 1.08 9839.56378
55 35 0.9
56 GR/LB DIFF. 1-BF
Latent CFM 289.23 0.68 16815.7624
57 95 0.9

58 TONS 6.57315746 GRAND TOTAL HEAT 78877.8896