Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
3.1 65 NB RMT 75
3.2 32 NB RMT 45
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40
4.2 50 NB RMT 50
4.3 32 NB RMT 65
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10
considered in the scope.
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20
12.2 TYPE B Nos 20
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290
18.2 200mm, perforated tray. RMT 35
18.3 300 mm perforated tray. RMT 50
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900
19.2 Panel to Roof exhaust fans RMT 600
19.3 Control cabling for sensors. RMT 1500
19.4 From panel to VRF ODU RMT 100
19.5 Starter panel to Secondary Scavenger Fan RMT 80
19.6 Starter panel to Water pump RMT 80
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
28.1 28 HP Nos. 1
(Necessary combination to submitted by the contractor / supplier) (With Multi kits
wherever required)
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70
shall fire retardant UL standard approved. Size 150 NB
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1
Commissioning of the system (28 HP)
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
41.1 65 NB RMT 40
41.2 25 NB RMT 25
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2
42.2 500 CFM @ 20 mm Static Nos 2
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
2393929 66694 21545361 600246 2437510 48,000 21937590 432000 2512900 50,750 22616100
58989 31386 471912 251088 96000 48,000 768000 384000 89976 43,863 719808
263 145 19725 10875 410 120 30750 9000 254 116 19050
150 83 6750 3735 150 120 6750 5400 141 87 6345
838 504 33520 20160 750 120 30000 4800 710 479 28400
533 334 26650 16700 470 120 23500 6000 452 319 22600
450 207 29250 13455 290 120 18850 7800 331 239 21515
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
1004 339 200800 67800 1590 290 318000 58000 1404 265 280800
888 305 44400 15250 1430 290 71500 14500 1268 265 63400
490 128 171500 44800 270 150 94500 52500 434 140 151900
9831 2672 98310 26720 29250 1,800 292500 18000 18850 1,450 188500
6017 1976 120340 39520 750 230 15000 4600 9295 1,160 185900
6017 1976 120340 39520 8580 750 171600 15000 13650 1,740 273000
4464 760 8928 1520 8250 750 16500 1500 9750 1,160 19500
880 102 264000 30600 690 160 207000 48000 1121 140 336300
1993 653 39860 13060 1800 230 36000 4600 6760 1,160 135200
1993 653 39860 13060 1800 230 36000 4600 6760 1,160 135200
3810 236 1714500 106200 3380 750 1521000 337500 3250 725 1462500
121890 27464 731340 164784 114940 8,250 689640 49500 123500 10,875 741000
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
312638 26680 312638 26680 45290 2,250 45290 2250 366600 14500 366600
1028542 38448 1028542 38448 151610 3,750 151610 3750 1105000 51890 1105000
158 100 4740 3000 210 150 6300 4500 306 94 9180
145 100 36250 25000 280 190 70000 47500 373 102 93250
355 100 159750 45000 350 190 157500 85500 445 109 200250
287 100 10045 3500 420 190 14700 6650 520 119 18200
308 142 15400 7100 710 190 35500 9500 715 123 35750
680 150 27200 6000 620 190 24800 7600 605 145 24200
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
6760 3924 13520 7848 4000 800 8000 1600 42,943 9,212 85886
9292 3924 9292 3924 17600 800 17600 800 36,595 1,755 36595
9292 1178 46460 5890 5600 800 28000 4000 10,010 1,755 50050
1488 1570 13392 14130 5600 800 50400 7200 4,550 877 40950
17206 3139 154854 28251 28800 1,280 259200 11520 16,359 2,105 147231
5163 2355 7,362 2,632
7756 3139 31024 12556 24000 1,280 96000 5120 36,808 5,264 147232
54900 4500 109800 9000 51290 2,910 102580 5820 55,250 4,386 110500
545639 16478 545639 16478 534800 9,000 534800 9000 494,000 7,250.00 494000
25151 4395 75453 13185 45360 2,160 136080 6480 39390 1,233 118170
30559 4395 152795 21975 45920 2,160 229600 10800 34580 1,204 172900
31787 4395 95361 13185 47040 2,160 141120 6480 34710 1,204 104130
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
33016 4395 132064 17580 51920 2,160 207680 8640 34970 1204 139880
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
1098 601 109800 60100 1350 230 135000 23000 1326 131 132600
243 53 17010 3710 170 120 11900 8400 507 218 35490
1230 1178 18450 17670 300 100 4500 1500 390 145 5850
9141 5003 9141 5003 5250 750 5250 750 5,850 2,175.00 5850
18128 3532 36256 7064 16380 1,800 32760 3600 15,925 2,900.00 31850
608 203 31616 10556 660 270 34320 14040 663 261.00 34476
263 154 10520 6160 470 120 18800 4800 254 116 10160
150 83 3750 2075 140 120 3500 3000 141 87.00 3525
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
25606 6279 51212 12558 20090 1,800 40180 3600 22,536 2,175.00 45072
18806 5493 37612 10986 14840 1,800 29680 3600 16,644 2,175.00 33288
608 203 36480 12180 660 270 39600 16200 663 250.00 39780
1107 236 37638 8024 680 150 23120 5100 845 218.00 28730
78645 7847 157290 15694 65470 3,750 130940 7500 73,442 3,625.00 146884
75306 7847 150612 15694 62320 3,750 124640 7500 69,911 3,625.00 139822
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
456750 2570035 52,480 23130315 472320 2342267 41,595 21080403 374355 2425000
350904 90572 47,340 724576 378720 64888 36,396 519104 291168 75000
19160 686 649 27440 25960 807 395 32280 15800 1500
15950 439 406 21950 20300 503 247 25150 12350 1200
15535 281 260 18265 16900 315 321 20475 20865 900
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
53000 1479 216 295800 43200 1484 210 296800 42000 2225
13250 1325 216 66250 10800 1357 196 67850 9800 2050
49000 271 227 94850 79450 278 182 97300 63700 510
14500 17200 1,961 172000 19610 31860 1,329 318600 13290 21000
23200 16409 1,488 328180 29760 64578 3,680 1291560 73600 8500
34800 14027 1,488 280540 29760 9884 845 197680 16900 8500
2320 5616 1,488 11232 2976 4582 1,119 9164 2238 7500
42000 686 227 205800 68100 704 196 211200 58800 1300
23200 13037 1,623 260740 32460 2678 195 53560 3900 5500
23200 16297 1,623 325940 32460 4029 195 80580 3900 5500
326250 3957 744 1780650 334800 2737 130 1231650 58500 2450
65250 108590 7,439 651540 44634 107375 3,900 644250 23400 110000
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
243600 762127 16,265 4572762 97590 609847 36,396 3659082 218376 625000
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
14500 200282 10,821 200282 10821 302208 3,900 302208 3900 325000
51890 835282 20,288 835282 20288 645600 7,799 645600 7799 1050000
2820 281 149 8430 4470 283 149 8490 4470 400
25500 361 149 90250 37250 380 201 95000 50250 500
49050 442 149 198900 67050 468 234 210600 105300 650
4165 524 149 18340 5215 566 292 19810 10220 800
6150 687 149 34350 7450 751 370 37550 18500 1050
5800 574 149 22960 5960 1405 455 56200 18200 1600
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
104400 1789 135 1610100 121500 1122 117 1009800 105300 750
34800 119 54 71400 32400 242 58 145200 34800 250
54000 89 47 133500 70500 84 45 126000 67500 150
6500 454 68 45400 6800 396 58 39600 5800 450
7040 192 54 15360 4320 1122 117 89760 9360 200
2880 144 54 11520 4320 98 45 7840 3600 200
18424 79703 10,144 159406 20288 4,055 715 8110 1430 55000
1755 21598 1,014 21598 1014 12,842 975 12842 975 7500
8775 7664 744 38320 3720 8,787 975 43935 4875 7500
7893 3931 744 35379 6696 1,487 650 13383 5850 8500
18945 19074 744 171666 6696 18,250 975 164250 8775 6500
10451 1,014 14,194 975 10500
21056 34835 1,014 139340 4056 10,815 650 43260 2600 8500
8772 55737 1,014 111474 2028 105,640 650 211280 1300 7500
7250 434819 15,000 434819 15000 501375 24,242 501375 24242 895000
3699 33888 2,500 101664 7500 42525 909 127575 2727 50000
6020 34018 2,500 170090 12500 43050 1,429 215250 7145 60000
3612 34929 2,500 104787 7500 44100 1,801 132300 5403 67500
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
4816 38896 2,500 155584 10000 48675 2,294 194700 9176 75000
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
13100 1331 149 133100 14900 1,094 351 109400 35100 1900
2175 4598 473 4598 473 8,111 1,300.00 8111 1300 15500
5800 13412 1,623 26824 3246 14,194 715.00 28388 1430 23500
13572 585 216 30420 11232 726 210.00 37752 10920 850
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
4350 18979 3,381 37958 6762 21,061 1,235.00 42122 2470 40000
4350 14016 2,029 28032 4058 15,809 845.00 31618 1690 30000
15000 585 216 35100 12960 726 210.00 43560 12600 850
7412 610 338 20740 11492 676 130 22984 4420 1000
7250 61851 10,144 123702 20288 62,606 4,549.00 125212 9098 42500
7250 58877 10,144 117754 20288 59,720 4,549.00 119440 9098 39500
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
75000 21825000 675000 3512400 60750 31611600 546750 2164000 128,000 19476000
150 41250 11250 432 135 32400 10125 560 140 42000
150 19125 6750 125 39 5625 1755 436 140 19620
200 60000 8000 1005 313 40200 12520 3780 600 151200
200 60000 10000 641 200 32050 10000 2240 300 112000
200 58500 13000 429 134 27885 8710 980 200 63700
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
300 445000 60000 1014 284 202800 56800 918 250 183600
300 102500 15000 910 270 45500 13500 744 250 37200
150 178500 52500 416 150 145600 52500 360 200 126000
3000 210000 30000 28600 2295 286000 22950 26800 2,800 268000
2000 170000 40000 10205 1688 204100 33760 19800 2,800 396000
2000 15000 4000 8905 1688 17810 3376 14800 1,200 29600
150 390000 45000 385 150 115500 45000 990 280 297000
2000 110000 40000 1500 506 30000 10120 28000 8,800 560000
2000 110000 40000 1800 608 36000 12160 26000 8,000 520000
350 1102500 157500 2555 608 1149750 273600 2400 300 1080000
17500 660000 105000 127523 21519 765138 129114 129000 8,600 774000
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
45000 3750000 270000 637800 47250 3826800 283500 542000 39,800 3252000
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
35000 325000 35000 227172 51114 227172 51114 364800 32,600 364800
75000 1050000 75000 734856 165343 734856 165343 864000 68,000 864000
100 12000 3000 364 151 10920 4530 380 140 11400
100 125000 25000 463 192 115750 48000 440 140 110000
100 292500 45000 624 259 280800 116550 698 180 314100
150 28000 5250 710 295 24850 10325 765 200 26775
150 52500 7500 884 367 44200 18350 878 200 43900
250 64000 10000 1019 423 40760 16920 1278 300 51120
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
20000 75000 20000 58500 12150 58500 12150 56000 40000 56000
7500 110000 15000 5010 1561 10020 3122 96,000 24,000 192000
2000 7500 2000 16699 5202 16699 5202 14,800 2,400 14800
2000 37500 10000 12438 3875 62190 19375 4,800 3,500 24000
2000 76500 18000 6305 1964 56745 17676 6,800 1,500 61200
2000 58500 18000 16489 5137 148401 46233 19,800 2,400 178200
2000 11304 3521 0 0 2,800 680 0
2000 34000 8000 59782 18624 239128 74496 68,900 4,800 275600
5000 150000 15000 39552 6674 118656 20022 34000 2,800 102000
7000 300000 35000 42972 7252 214860 36260 36800 2,800 184000
7000 202500 21000 44142 7449 132426 22347 54000 3,400 162000
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
10000 300000 40000 53976 9108 215904 36432 58000 3,800 232000
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
300 190000 30000 2077 431 207700 43100 2,480 124 248000
1000 77000 14000 6357 1320 88998 18480 4200 200 58800
150 59500 10500 624 162 43680 11340 1800 150 126000
1000 15500 1000 8450 2430 8450 2430 8,800 1,400.00 8800
3000 47000 6000 17063 3544 34126 7088 18,000 1,200.00 36000
215 44200 11180 780 297 40560 15444 889 220.00 46228
150 22000 6000 737 153 29480 6120 980 140 39200
150 10625 3750 493 102 12325 2550 340 110 8500
Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Installation Supply Installation Supply Installation Supply Installation Supply Installation Supply
5000 80000 10000 22289 5015 44578 10030 24,500 3,400.00 49000
5000 60000 10000 16460 3704 32920 7408 14,800 3,000.00 29600
215 51000 12900 780 284 46800 17040 688 220.00 41280
200 34000 6800 3705 770 125970 26180 5400 400 183600
5000 85000 10000 72635 16343 145270 32686 74,000 12,400.00 148000
5000 79000 10000 69143 15557 138286 31114 66,800 12,000.00 133600
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Total (Rs) Rate (Rs.) Total (Rs) Rate (Rs.) Total (Rs)
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
Supply Installation Supply Installation Supply Min Supply Max Installation Min Installation Max
40774590 4205510
44980100
Supply Installation
19476000 288000
576 208
8850 3750
3195 1440
25280 4800
19150 6000
18265 7800
4486110 687000
734400 133280
911400 192080
Supply Installation
151400 38000
31300 9500
94500 44800
60790 6000
15000 4600
49800 10000
8928 1000
115500 30600
30000 3900
36000 3900
742500 58500
318900 18240
Supply Installation
0 0
Supply Installation
45290 2250
151610 3750
4740 2700
36250 22500
157500 40500
10045 3150
15400 4500
21600 3600
54520 14500
8750 1750
16000 2500
Supply Installation
257400 36000
66000 18000
103500 39000
30900 3000
0 0
0 0
0 1824
7256 486
7500 243
24000 1215
13383 2187
58500 2187
0 0
31024 972
0 0
434819 7250
75453 2727
152795 6020
95361 3612
Supply Installation
132064 4816
Supply Installation
9360 3120
109400 12400
0 2800
4500 1250
11200 3710
1380 390
0 0
3628 473
22580 1430
27716 10400
7600 2600
1925 325
Supply Installation
37958 2470
22580 1300
31980 12000
20740 4420
85000 3648
79000 3648
29,826,051 1,851,021
249,338
5,208,401
333,184
37,467,994
Everest Air Sy
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
1.1 AHU-1 - 9, Total Supply 40000 CFM @ 75 mm ESP Nos 9 2393929 66694
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 58989 31386
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 838 504
4.2 50 NB RMT 50 533 334
4.3 32 NB RMT 65 450 207
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 490 128
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 9831 2672
considered in the scope.
9 SITC of Butterfly type damper in GI construction. Various Sizes SQM 20 6017 1976
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 4464 760
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 880 102
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 1993 653
12.2 TYPE B Nos 20 1993 653
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 3810 236
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
17.1 50mm, 50x50 perforated tray. (16 SWG) RMT 30 158 100
17.2 100mm, 50x50 perforated tray. (16 SWG) RMT 250 145 100
17.3 150mm, 50x50 perforated tray. (16 SWG) RMT 450 355 100
17.4 200mm, 50x50 perforated tray. (16 SWG) RMT 35 287 100
17.5 300 mm, 50x50 perforated tray. (14 SWG) RMT 50 308 142
17.6 450 mm, 75x75 Ladder tray. (14 SWG) RMT 40 680 150
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 233 50
18.2 200mm, perforated tray. RMT 35 417 50
18.3 300 mm perforated tray. RMT 50 490 50
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 827 48
19.2 Panel to Roof exhaust fans RMT 600 143 48
19.3 Control cabling for sensors. RMT 1500 122 41
19.4 From panel to VRF ODU RMT 100 678 48
19.5 Starter panel to Secondary Scavenger Fan RMT 80 185 48
19.6 Starter panel to Water pump RMT 80 150 41
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 30478 9730
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 54900 4500
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 25151 4395
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 30559 4395
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 31787 4395
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 90 42
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1098 601
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 4441 1001
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 170 25
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 243 53
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 1230 1178
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 27640 15127
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 9141 5003
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 18128 3532
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 25606 6279
42.2 500 CFM @ 20 mm Static Nos 2 18806 5493
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 78645 7847
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 75306 7847
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
Supply Installation
Total (Rs)
Supply Installation
21545361 600246
471912 251088
19725 10875
Total (Rs)
Supply Installation
6750 3735
33520 20160
26650 16700
29250 13455
4826175 934320
734400 184960
929040 266560
Total (Rs)
Supply Installation
200800 67800
44400 15250
171500 44800
98310 26720
120340 39520
120340 39520
8928 1520
264000 30600
39860 13060
39860 13060
1714500 106200
731340 164784
Total (Rs)
Supply Installation
Total (Rs)
Supply Installation
312638 26680
1028542 38448
4740 3000
36250 25000
159750 45000
10045 3500
15400 7100
27200 6000
67570 14500
14595 1750
24500 2500
Total (Rs)
Supply Installation
744300 43200
85800 28800
183000 61500
67800 4800
14800 3840
12000 3280
30478 9730
13520 7848
9292 3924
46460 5890
13392 14130
154854 28251
31024 12556
109800 9000
545639 16478
75453 13185
152795 21975
95361 13185
Total (Rs)
Supply Installation
132064 17580
Total (Rs)
Supply Installation
10800 5040
109800 60100
62174 14014
8500 1250
17010 3710
18450 17670
27640 15127
9141 5003
36256 7064
31616 10556
10520 6160
3750 2075
Total (Rs)
Supply Installation
51212 12558
37612 10986
36480 12180
37638 8024
157290 15694
150612 15694
37212524 3580468
40792992
297,776
6,506,827
644,484
44,017,127 4,224,952
48,242,079
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
1.1 AHU-1 - 9, Total Supply 40000 CFM @ 75 mm ESP Nos 9 2437510 48,000
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 96000 48,000
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 750 120
4.2 50 NB RMT 50 470 120
4.3 32 NB RMT 65 290 120
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 270 150
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 29250 1,800
considered in the scope.
9 SITC of Butterfly type damper in GI construction. Various Sizes SQM 20 750 230
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 8250 750
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 690 160
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 1800 230
12.2 TYPE B Nos 20 1800 230
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 3380 750
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17 prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
17.1 50mm, 50x50 perforated tray. (16 SWG) RMT 30 210 150
17.2 100mm, 50x50 perforated tray. (16 SWG) RMT 250 280 190
17.3 150mm, 50x50 perforated tray. (16 SWG) RMT 450 350 190
17.4 200mm, 50x50 perforated tray. (16 SWG) RMT 35 420 190
17.5 300 mm, 50x50 perforated tray. (14 SWG) RMT 50 710 190
17.6 450 mm, 75x75 Ladder tray. (14 SWG) RMT 40 620 190
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 260 150
18.2 200mm, perforated tray. RMT 35 330 150
18.3 300 mm perforated tray. RMT 50 470 150
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 300 90
19.2 Panel to Roof exhaust fans RMT 600 110 30
19.3 Control cabling for sensors. RMT 1500 90 30
19.4 From panel to VRF ODU RMT 100 530 120
19.5 Starter panel to Secondary Scavenger Fan RMT 80 300 90
19.6 Starter panel to Water pump RMT 80 110 30
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 0 50,000
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 51290 2,910
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 45360 2,160
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 45920 2,160
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 47040 2,160
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 90 60
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1350 230
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 0 500
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 130 50
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 170 120
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 300 100
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 0 21,170
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 5250 750
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 16380 1,800
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 20090 1,800
42.2 500 CFM @ 20 mm Static Nos 2 14840 1,800
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 65470 3,750
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 62320 3,750
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
Supply Installation
Total (Rs)
Supply Installation
21937590 432000
768000 384000
30750 9000
Total (Rs)
Supply Installation
6750 5400
30000 4800
23500 6000
18850 7800
6183000 996150
1074400 197200
1323000 284200
Total (Rs)
Supply Installation
318000 58000
71500 14500
94500 52500
292500 18000
15000 4600
171600 15000
16500 1500
207000 48000
36000 4600
36000 4600
1521000 337500
689640 49500
Total (Rs)
Supply Installation
3939540 297000
Total (Rs)
Supply Installation
45290 2250
151610 3750
6300 4500
70000 47500
157500 85500
14700 6650
35500 9500
24800 7600
75400 43500
11550 5250
23500 7500
Total (Rs)
Supply Installation
270000 81000
66000 18000
135000 45000
53000 12000
24000 7200
8800 2400
0 50000
8000 1600
17600 800
28000 4000
50400 7200
259200 11520
96000 5120
102580 5820
534800 9000
136080 6480
229600 10800
141120 6480
Total (Rs)
Supply Installation
207680 8640
Total (Rs)
Supply Installation
10800 7200
135000 23000
0 7000
6500 2500
11900 8400
4500 1500
0 21170
5250 750
32760 3600
34320 14040
18800 4800
3500 3000
Total (Rs)
Supply Installation
40180 3600
29680 3600
39600 16200
23120 5100
130940 7500
124640 7500
42440120 3888870
46328990
349,798
7,414,351
699,997
50,204,270 4,588,867
54,793,136
SCON Proje
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
1.1 AHU-1 - 9, Total Supply 40000 CFM @ 75 mm ESP Nos 9 2512900 50,750
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 89976 43,863
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 434 140
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 18850 1,450
considered in the scope.
9 SITC of Butterfly type damper in GI construction. Various Sizes SQM 20 9295 1,160
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 9750 1,160
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 1121 140
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 6760 1,160
12.2 TYPE B Nos 20 6760 1,160
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 3250 725
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 289 58
18.2 200mm, perforated tray. RMT 35 361 73
18.3 300 mm perforated tray. RMT 50 504 87
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 1170 116
19.2 Panel to Roof exhaust fans RMT 600 218 58
19.3 Control cabling for sensors. RMT 1500 69 36
19.4 From panel to VRF ODU RMT 100 423 65
19.5 Starter panel to Secondary Scavenger Fan RMT 80 228 88
19.6 Starter panel to Water pump RMT 80 78 36
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 62457 21931
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 55,250 4,386
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 39390 1,233
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 34580 1,204
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 34710 1,204
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 98 48
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1326 131
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 3900 508
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 257 44
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 507 218
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 390 145
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 17,160 2,900.00
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 5,850 2,175.00
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 15,925 2,900.00
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 22,536 2,175.00
42.2 500 CFM @ 20 mm Static Nos 2 16,644 2,175.00
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 73,442 3,625.00
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 69,911 3,625.00
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
SCON Project
Total (Rs)
Supply Installation
Total (Rs)
Supply Installation
22616100 456750
719808 350904
19050 8700
Total (Rs)
Supply Installation
6345 3915
28400 19160
22600 15950
21515 15535
5135325 910275
884000 180200
1082900 259700
Total (Rs)
Supply Installation
280800 53000
63400 13250
151900 49000
188500 14500
185900 23200
273000 34800
19500 2320
336300 42000
135200 23200
135200 23200
1462500 326250
741000 65250
Total (Rs)
Supply Installation
3985800 243600
Total (Rs)
Supply Installation
366600 14500
1105000 51890
9180 2820
93250 25500
200250 49050
18200 4165
35750 6150
24200 5800
83810 16820
12635 2555
25200 4350
Total (Rs)
Supply Installation
1053000 104400
130800 34800
103500 54000
42300 6500
18240 7040
6240 2880
62457 21931
85886 18424
36595 1755
50050 8775
40950 7893
147231 18945
147232 21056
110500 8772
494000 7250
118170 3699
172900 6020
104130 3612
Total (Rs)
Supply Installation
139880 4816
Total (Rs)
Supply Installation
11760 5760
132600 13100
54600 7112
12850 2200
35490 15260
5850 2175
17160 2900
5850 2175
31850 5800
34476 13572
10160 4640
3525 2175
Total (Rs)
Supply Installation
45072 4350
33288 4350
39780 15000
28730 7412
146884 7250
139822 7250
44322926 3783308
48106234
303,430
7,783,064
680,996
52,409,421 4,464,304
56,873,724
Safe A
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 90572
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
3.2 32 NB RMT 45 71
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 686
4.2 50 NB RMT 50 439
4.3 32 NB RMT 65 281
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 271
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 17200
considered in the scope.
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 5616
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 686
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 13037
12.2 TYPE B Nos 20 16297
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 3957
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 291
18.2 200mm, perforated tray. RMT 35 373
18.3 300 mm perforated tray. RMT 50 536
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 1789
19.2 Panel to Roof exhaust fans RMT 600 119
19.3 Control cabling for sensors. RMT 1500 89
19.4 From panel to VRF ODU RMT 100 454
19.5 Starter panel to Secondary Scavenger Fan RMT 80 192
19.6 Starter panel to Water pump RMT 80 144
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 56433
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 55737
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 33888
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 34018
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 34929
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 91
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1331
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 2992
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 156
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 251
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 348
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 32383
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 4598
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 13412
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 18979
42.2 500 CFM @ 20 mm Static Nos 2 14016
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 61851
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 58877
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
61 3195 2745
338
338 6420015 1161030
338 1126760 229840
338 1440600 331240
68 84390 19720
68 13055 2380
68 26800 3400
47 10920 5640
68 7800 3400
81 17570 5670
47786593 4155128
51941720.9071883
282,473
8,419,997
747,923
56,489,063 4,903,051
Anukool In
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
1.1 AHU-1 - 9, Total Supply 40000 CFM @ 75 mm ESP Nos 9 2342267 41,595
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 64888 36,396
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 807 395
4.2 50 NB RMT 50 503 247
4.3 32 NB RMT 65 315 321
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 278 182
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 31860 1,329
considered in the scope.
9 SITC of Butterfly type damper in GI construction. Various Sizes SQM 20 64578 3,680
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 4582 1,119
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 704 196
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 2678 195
12.2 TYPE B Nos 20 4029 195
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 2737 130
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
17.1 50mm, 50x50 perforated tray. (16 SWG) RMT 30 283 149
17.2 100mm, 50x50 perforated tray. (16 SWG) RMT 250 380 201
17.3 150mm, 50x50 perforated tray. (16 SWG) RMT 450 468 234
17.4 200mm, 50x50 perforated tray. (16 SWG) RMT 35 566 292
17.5 300 mm, 50x50 perforated tray. (14 SWG) RMT 50 751 370
17.6 450 mm, 75x75 Ladder tray. (14 SWG) RMT 40 1405 455
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 349 195
18.2 200mm, perforated tray. RMT 35 439 195
18.3 300 mm perforated tray. RMT 50 575 195
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 1122 117
19.2 Panel to Roof exhaust fans RMT 600 242 58
19.3 Control cabling for sensors. RMT 1500 84 45
19.4 From panel to VRF ODU RMT 100 396 58
19.5 Starter panel to Secondary Scavenger Fan RMT 80 1122 117
19.6 Starter panel to Water pump RMT 80 98 45
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 0 41821
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 105,640 650
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 42525 909
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 43050 1,429
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 44100 1,801
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 78 26
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1,094 351
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 0 455
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 104 58
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 165 123
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 676 65
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 20,818 -
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 8,111 1,300.00
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 14,194 715.00
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 21,061 1,235.00
42.2 500 CFM @ 20 mm Static Nos 2 15,809 845.00
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 62,606 4,549.00
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 59,720 4,549.00
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
Anukool India
Total (Rs)
Supply Installation
Total (Rs)
Supply Installation
21080403 374355
519104 291168
27225 4875
Total (Rs)
Supply Installation
5715 1440
32280 15800
25150 12350
20475 20865
5451345 721350
955400 133280
1212260 192080
Total (Rs)
Supply Installation
296800 42000
67850 9800
97300 63700
318600 13290
1291560 73600
197680 16900
9164 2238
211200 58800
53560 3900
80580 3900
1231650 58500
644250 23400
Total (Rs)
Supply Installation
3659082 218376
Total (Rs)
Supply Installation
302208 3900
645600 7799
8490 4470
95000 50250
210600 105300
19810 10220
37550 18500
56200 18200
101210 56550
15365 6825
28750 9750
Total (Rs)
Supply Installation
1009800 105300
145200 34800
126000 67500
39600 5800
89760 9360
7840 3600
0 41821
8110 1430
12842 975
43935 4875
13383 5850
164250 8775
43260 2600
211280 1300
501375 24242
127575 2727
215250 7145
132300 5403
Total (Rs)
Supply Installation
194700 9176
Total (Rs)
Supply Installation
9360 3120
109400 35100
0 6370
5200 2900
11550 8610
10140 975
20818 0
8111 1300
28388 1430
37752 10920
14520 2600
1975 325
Total (Rs)
Supply Installation
42122 2470
31618 1690
43560 12600
22984 4420
125212 9098
119440 9098
42738026 3103436
45841462
327,936
7,482,029
558,618
50,547,991 3,662,054
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
1.1 AHU-1 - 9, Total Supply 40000 CFM @ 75 mm ESP Nos 9 2425000 75000
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 75000 25000
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 1500 200
4.2 50 NB RMT 50 1200 200
4.3 32 NB RMT 65 900 200
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 510 150
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 21000 3000
considered in the scope.
9 SITC of Butterfly type damper in GI construction. Various Sizes SQM 20 8500 2000
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 7500 2000
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 1300 150
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 5500 2000
12.2 TYPE B Nos 20 5500 2000
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 2450 350
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
17.1 50mm, 50x50 perforated tray. (16 SWG) RMT 30 400 100
17.2 100mm, 50x50 perforated tray. (16 SWG) RMT 250 500 100
17.3 150mm, 50x50 perforated tray. (16 SWG) RMT 450 650 100
17.4 200mm, 50x50 perforated tray. (16 SWG) RMT 35 800 150
17.5 300 mm, 50x50 perforated tray. (14 SWG) RMT 50 1050 150
17.6 450 mm, 75x75 Ladder tray. (14 SWG) RMT 40 1600 250
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 350 100
18.2 200mm, perforated tray. RMT 35 450 100
18.3 300 mm perforated tray. RMT 50 700 150
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 750 250
19.2 Panel to Roof exhaust fans RMT 600 250 150
19.3 Control cabling for sensors. RMT 1500 150 100
19.4 From panel to VRF ODU RMT 100 450 150
19.5 Starter panel to Secondary Scavenger Fan RMT 80 200 100
19.6 Starter panel to Water pump RMT 80 200 100
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 75000 20000
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 7500 2000
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 50000 5000
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 60000 7000
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 67500 7000
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 250 100
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1900 300
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 5500 1000
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 250 100
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 850 150
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 750 250
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 55000 20000
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 15500 1000
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 23500 3000
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 40000 5000
42.2 500 CFM @ 20 mm Static Nos 2 30000 5000
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 42500 5000
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 39500 5000
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
Supply Installation
Total (Rs)
Supply Installation
21825000 675000
600000 200000
41250 11250
Total (Rs)
Supply Installation
19125 6750
60000 8000
60000 10000
58500 13000
6955875 1030500
1258000 204000
1666000 294000
Total (Rs)
Supply Installation
445000 60000
102500 15000
178500 52500
210000 30000
170000 40000
170000 40000
15000 4000
390000 45000
110000 40000
110000 40000
1102500 157500
660000 105000
Total (Rs)
Supply Installation
3750000 270000
Total (Rs)
Supply Installation
325000 35000
1050000 75000
12000 3000
125000 25000
292500 45000
28000 5250
52500 7500
64000 10000
101500 29000
15750 3500
35000 7500
Total (Rs)
Supply Installation
675000 225000
150000 90000
225000 150000
45000 15000
16000 8000
16000 8000
75000 20000
110000 15000
7500 2000
37500 10000
76500 18000
58500 18000
34000 8000
15000 4000
895000 75000
150000 15000
300000 35000
202500 21000
Total (Rs)
Supply Installation
300000 40000
Total (Rs)
Supply Installation
30000 12000
190000 30000
77000 14000
12500 5000
59500 10500
11250 3750
55000 20000
15500 1000
47000 6000
44200 11180
22000 6000
10625 3750
Total (Rs)
Supply Installation
80000 10000
60000 10000
51000 12900
34000 6800
85000 10000
79000 10000
46410575 4557130
50967705
538,860
8,007,494
820,283
54,956,929 5,377,413
AART Integr
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
1.1 AHU-1 - 9, Total Supply 40000 CFM @ 75 mm ESP Nos 9 3512400 60750
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 72000 26000
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 1005 313
4.2 50 NB RMT 50 641 200
4.3 32 NB RMT 65 429 134
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 416 150
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 28600 2295
considered in the scope.
9 SITC of Butterfly type damper in GI construction. Various Sizes SQM 20 10205 1688
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 8905 1688
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 385 150
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 1500 506
12.2 TYPE B Nos 20 1800 608
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 2555 608
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
17.1 50mm, 50x50 perforated tray. (16 SWG) RMT 30 364 151
17.2 100mm, 50x50 perforated tray. (16 SWG) RMT 250 463 192
17.3 150mm, 50x50 perforated tray. (16 SWG) RMT 450 624 259
17.4 200mm, 50x50 perforated tray. (16 SWG) RMT 35 710 295
17.5 300 mm, 50x50 perforated tray. (14 SWG) RMT 50 884 367
17.6 450 mm, 75x75 Ladder tray. (14 SWG) RMT 40 1019 423
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 718 298
18.2 200mm, perforated tray. RMT 35 816 339
18.3 300 mm perforated tray. RMT 50 1017 422
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 286 59
19.2 Panel to Roof exhaust fans RMT 600 138 43
19.3 Control cabling for sensors. RMT 1500 127 26
19.4 From panel to VRF ODU RMT 100 397 82
19.5 Starter panel to Secondary Scavenger Fan RMT 80 0 0
19.6 Starter panel to Water pump RMT 80 0 0
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 58500 12150
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 0 0
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 39552 6674
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 42972 7252
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 44142 7449
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 702 146
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 2077 431
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 6357 1320
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 124 51
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 624 162
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 286 26
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 0 74250
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 8450 2430
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 17063 3544
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply Installation
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 22289 5015
42.2 500 CFM @ 20 mm Static Nos 2 16460 3704
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 72635 16343
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 69143 15557
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
AART Integrated
Total (Rs)
Supply Installation
Total (Rs)
Supply Installation
31611600 546750
576000 208000
32400 10125
Total (Rs)
Supply Installation
5625 1755
40200 12520
32050 10000
27885 8710
4661295 1205685
775200 220320
929040 317520
Total (Rs)
Supply Installation
202800 56800
45500 13500
145600 52500
286000 22950
204100 33760
17810 3376
115500 45000
30000 10120
36000 12160
1149750 273600
765138 129114
Total (Rs)
Supply Installation
3826800 283500
Total (Rs)
Supply Installation
227172 51114
734856 165343
10920 4530
115750 48000
280800 116550
24850 10325
44200 18350
40760 16920
208220 86420
28560 11865
50850 21100
Total (Rs)
Supply Installation
257400 53100
82800 25800
190500 39000
39700 8200
0 0
0 0
58500 12150
10020 3122
16699 5202
62190 19375
56745 17676
148401 46233
0 0
239128 74496
0 0
3442776 60750
118656 20022
214860 36260
132426 22347
Total (Rs)
Supply Installation
215904 36432
Total (Rs)
Supply Installation
84240 17520
207700 43100
88998 18480
6200 2550
43680 11340
4290 390
0 74250
8450 2430
34126 7088
40560 15444
29480 6120
12325 2550
Total (Rs)
Supply Installation
44578 10030
32920 7408
46800 17040
125970 26180
145270 32686
138286 31114
53663809 4834167
58497976
1,179,814
8,901,034
870,150
63,744,657 5,704,317
Pragmatic H
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 114000
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 3780
4.2 50 NB RMT 50 2240
4.3 32 NB RMT 65 980
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 360
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 26800
considered in the scope.
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 14800
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 990
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 28000
12.2 TYPE B Nos 20 26000
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 2400
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 528
18.2 200mm, perforated tray. RMT 35 598
18.3 300 mm perforated tray. RMT 50 724
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 850
19.2 Panel to Roof exhaust fans RMT 600 456
19.3 Control cabling for sensors. RMT 1500 288
19.4 From panel to VRF ODU RMT 100 850
19.5 Starter panel to Secondary Scavenger Fan RMT 80 0
19.6 Starter panel to Water pump RMT 80 0
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 56000
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 -
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 34000
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 36800
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 54000
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 248
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 2,480
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 4200
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 340
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 1800
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 380
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 24,800
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 8,800
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 18,000
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 24,500
42.2 500 CFM @ 20 mm Static Nos 2 14,800
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 74,000
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 66,800
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
50 153120 14500
50 20930 1750
50 36200 2500
599000 0
45 29760 5400
42176423 4743040
46919463
374,584
7,350,952
853,747
49,901,959 5,596,787
Aquachill
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 76518
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 1064
4.2 50 NB RMT 50 666
4.3 32 NB RMT 65 486
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 379
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 15091
considered in the scope.
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 7706
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 435
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 6003
12.2 TYPE B Nos 20 5607
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 3804
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 340
18.2 200mm, perforated tray. RMT 35 421
18.3 300 mm perforated tray. RMT 50 579
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 311
19.2 Panel to Roof exhaust fans RMT 600 125
19.3 Control cabling for sensors. RMT 1500 123
19.4 From panel to VRF ODU RMT 100 309
19.5 Starter panel to Secondary Scavenger Fan RMT 80 309
19.6 Starter panel to Water pump RMT 80 123
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 32583
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 119076
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 42211
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 39501
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 43389
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 125
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 2109
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 5992
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 90
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 1406
shall fire retardant UL standard approved. Size 150 NB
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 1229
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 3628
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 14403
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 20153
42.2 500 CFM @ 20 mm Static Nos 2 15027
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 64549
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 61477
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
50 8850 3750
50 4500 2250
200
200 6000945 687000
200 1027480 136000
200 1301440 196000
90 8430 2700
90 90000 22500
90 197100 40500
90 18095 3150
90 36950 4500
90 21840 3600
90 98600 26100
90 14735 3150
90 28950 4500
40 279900 36000
40 75000 24000
30 184500 45000
30 30900 3000
30 24720 2400
30 9840 2400
40 15000 4800
30 4500 1500
30 1380 450
42915421 2807160
45722581
384,771
7,477,423
505,289
50,777,615 3,312,449
Z
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 71384
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 632
4.2 50 NB RMT 50 383
4.3 32 NB RMT 65 281
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 321
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 6079
considered in the scope.
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 7765
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 944
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 2517
12.2 TYPE B Nos 20 2392
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 1650
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 188
18.2 200mm, perforated tray. RMT 35 250
18.3 300 mm perforated tray. RMT 50 376
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 445
19.2 Panel to Roof exhaust fans RMT 600 153
19.3 Control cabling for sensors. RMT 1500 118
19.4 From panel to VRF ODU RMT 100 445
19.5 Starter panel to Secondary Scavenger Fan RMT 80 153
19.6 Starter panel to Water pump RMT 80 153
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 6262
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 8,140
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 38158
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 38158
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 39137
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 96
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1,879
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 6888
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 111
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 226
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 751
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 3,131
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 6,262
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 14,245
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 20,158
42.2 500 CFM @ 20 mm Static Nos 2 14,887
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 65,697
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 62,537
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
Zamil
Rate (Rs.) Total (Rs)
298
286 4486110 982410
274 755480 186320
261 911400 255780
61 11520 7320
61 5550 3050
85 15820 5950
33803597 6180455
39984052
378,619
5,841,250
1,112,482
40,023,466 7,292,937
SAITECH H
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply of Fresh Air handling units in double skin construction as per specification with
DIDW Backward curve CENTRIFUGAL Type fan. The FAHU panels shall be Pre-coated GI
Panels of 0.6mm thick inner and outer sheet.The panels should have PUF insulation of
45 mm thick. The air handling units shall consist of fan section with fan, Motor IE3/EC,
filter sections with quick fix filter arrangement with filters. The FAHU should have a
sensible heat exchanger to pre cool the air before it is passed through the Celldeck Pad
section. No scavenger fans should be used for exhausting secondary air stream. The unit
shall have 300 mm deep cellulose pad for adiabatic cooling. Shall have 6 Pass PVC
1 eliminator with SS frame. Earthing, vibration isolator, access doors, suitable openings in
AHU for BMS, PVC ports across all filter, Celldeck and fan sections etc as per Tender
specifications, all to be included in AHU price. Serrated rubber pads below air handling
units base frame shall be provided by HVAC contractor.Quoted rate shall be inclusive of
BMS compatible AHU panel,VFD,cabling etc complete in all respect.Machine shall be
suitable for OUTDOOR application kindly consider this while bidding.ref drawing for
location. AHu shall have Fan guard at the door to prevent any accidents.
1.Filter section
The filters shall of panel / box type construction comprise of washable HDPE sandwiched
media of 10 microns prefilter. The filters frame made of GI. The velocity across filters not
more than 2.5 m/sec.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
3.Cooling Section
a. Indirect (Sensible) heat exchanger section
Air to air cross flow plate type heat exchanger made of Engineering polymer with
thermally fused Non-woven-cartridges.
The maximum efficiency of heat exchanger shall be 80%.
b. Celldeck Pad section
Celldeck pad must be of cellulose pad with 300 mm depth.
c. Tank
The water tank shall be made up of 18SWG (1.2mm) thick SS 304 plain sheet to house
both sensible and adiabatic heat exchangers. Shall be equiped with level switch
d. Pump
The unit shall have two numbers of recirculation pump of submersible type and of
approved make. Pump body, suction grill, seal housing disc and motor casing made of SS
304. The Impeller, nozzle and motor cover shall made of technopolymer reinforced with
fibreglass. The pump motor shall have Class of insulation F, IP68 Protection rating and
230V ±10%, 50 Hz single phase voltage. The pump motor shall be minimum 1/3HP, 0.3
Kw, 230 Volts, 50 Hz single phase motor. The motor shall be supplied with built-in
thermal protection with automatic reset and shall be rated for continuous duty. The unit
shall have strainer for pump made of SS 304 with 2mm hole perforation.
e. Piping
The piping shall be used of rigid UPVC material. Piping connections should be made so as
to ensure uniform distribution of water. The sump shall be fitted with float valve.
f. UV filters
Unit shall have UV filter for re-circulation line.UV filtration controls the bacterial
disinfections in the supply water line thereby restricting the growth of algae and fungus.
g. Mise eliminator
The unit shall have 6 bend mist eliminator made of PVC.
Structural steel such as Channel, Angles, Plates, I section, Beam section etc with two
2 coats of red oxide and two coats of synthetic enamale quick drying paint. The colour Ton 8 77400
shall be approved by the Architect.
SLC of Drain Piping shall be HARD PVC. The drain shall be released into the nearest
3 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
3.2 32 NB RMT 45 90
Supply, installation, testing & commissioning of G.I. Class " B ", ERW, IS 1239 Water
4 piping for make up water piping.
4.1 80 NB RMT 40 710
4.2 50 NB RMT 50 520
4.3 32 NB RMT 65 320
SITC of Powder Coated GI SPIRAL Ducting Factory Fabricated without Flanges for supply
air. Inclussive of supports GRIPPLS/ GPL and Sleeve for hanging. Shall be inclussive of all
5 accessories such as bends / Reducers and expanders etc.
Contractor to give load bearing calcultion of the Gripple and GPL wires for suitable duct
sizes
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Thermal insulation of Nitril rubber with closed cell structure, 13 mm thickness, Class "O"
7 without pre clad AL Armaflex / K-Flex make or XLPE insulation of Suppreme make. SQM 350 460
Insulation to be applied from inside the duct. Insulation shall be FM Approved
SITC of Motorised fire damper with min 90 min rating with frame. Actuator shall be
8 SQM 10 12550
considered in the scope.
10 SITC of door louver in anodised alluminium construction with powder coating. SQM 2 8640
SITC of acoustical insulation for Supply air ducting with Armaflex/ K flex open cell sound
11 insulation.Armasound/eq.super sileance duct linear with micro ban, open cell, SQM 300 930
elastomaric nitrile rubber. Thickness 12 10 mm. Insulation shall be FM Approved
SITC of Plenum Boxes as per drawing. Shall be made up of 20 G GI sheet, duly powder
12 coated in bright white colour.
12.1 TYPE A Nos 20 6450
12.2 TYPE B Nos 20 8390
13 SITC of Hit and Miss type jet diffuser - 300 mm Dia - Eye ball type Nos 450 3720
Roof type Exhaust Fans fan with galvanised steel cabinet, Direct driven centrifugal fan.
14 The fan shall be with Base support. Fan shall be suitable for 25 mm ESP. 3 Ph, Suitable
KW motor, Krugger make RDS series or Nicotra equivalent. Capacity As below:
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
HVLS Fans, 5 blades, aluminium mill finished aerofoil design. 2 hp motor, 3 phase,
variable speed. Blade to hub connection to have vibration absorbing silent block bush
connection instead of welded/riveted/ nut bolted fixtures, so as to reduce stress to hub/
blade connection. Control panel to be UL listed.
HVLS fans shall complied with the following Building Codes and Standards. Product
Control Panel to be Underwriter’s Laboratories Listed in accordance with 508A. Control
Box to be Underwriter’s Laboratories Listed in accordance with as R-5820. Interior of
panel control box must be labeled with the Underwriter’s Laboratories logo. HVLS fan to
be CE approved.
The fan shall meet the requirements of NFPA 13 (National Fire Code for Sprinklers) in
15 regards to blocking obstructions below sprinkler heads.
Fans shall have the availability to be tied in the building’s fire suppression system, if so
required.
Fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for ESFR
sprinklers.
HVLS Ceiling Fans shall complied with the following construction features:
. Number of Blades: 3-6
. Blade Material: Aluminum
. Fan to have 3 way motor to hub safety connection
. Motor to have steel motor cover.
. VFD to be included. Communication card (RS485 Modbus RTU) to be included.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, installation, testing & commissioning of prefabricated (hot dip Galvanised ) .G.I.
Ladder/Perforated trays with 50/75 mm C channels & Ruges at 200 mm cc and including
17
prefabricated accessories like bends,Tee,Right angle & tray coupling arrangements etc.
(Bends fabricated at site will not be allowed).
Supply, installation, testing & commissioning of Cable Tray Covers suitable for following
18 size trays
18.1 150mm perforated tray. RMT 290 230
18.2 200mm, perforated tray. RMT 35 280
18.3 300 mm perforated tray. RMT 50 320
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Supply, Installation, Testing and Commissioning of 1100V grade L.T. XLPE/ PVC insulated
multistrand Al./ Cu. conductor cables on provided prefabricated trays/ pipe/ in trenches
with necessary clamps, identification tag. & all other items required to complete the
19 task.
All cables above Below 6 SQM shall be Cu. COntractr to select the cable sizes based on
the actual power rating. No Claim for additional rates shall be accepted at later stage
19.1 MCC Panel to AHU panel and to AHU motor RMT 900 400
19.2 Panel to Roof exhaust fans RMT 600 150
19.3 Control cabling for sensors. RMT 1500 130
19.4 From panel to VRF ODU RMT 100 500
19.5 Starter panel to Secondary Scavenger Fan RMT 80 190
19.6 Starter panel to Water pump RMT 80 100
Supply & installation of End termination for cables as above with Brass, heavy duty,
Single / double compression glands & for outdoor Double compression, Al/ Cu lugs,
20 LS 1 19350
other consumable like insulation adhesive tape, crimping, gland hole drilling, ferrulling,
marking, etc.
27. a Water flow meter with digital display and suitable for BMS conectivity. Size 65 NB Nos 2 16770
SITC of VRF Condensing Units of following actual capacities for city Of Pune,
28 Maharashtra, India conditions with necessary interlocks & R410 C / R 410 A Refrigerent
only. All inverter compressor models shall be offered
Cassette Units with necessary 4 way grill /micro-controller, drain pump , provision for
30 fresh air Connection and cordless remote etc. The cost include the decorative HDPE
panels also.
30.1 1.0 TR capacity, 600 x 600 mm Size - Compact Cassette Nos 3 42000
30.2 1.5 TR capacity 900 x 900 mm Size Nos 5 42000
30.3 2.0 TR capacity, 900 x 900 mm Size Nos 3 43000
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Interconnecting control cabling between IDU's & ODU's. The cabling shall be well
31 Rmt 120 100
supported / tied up with the ref line.
Supply, installation, testing and commissioning of refrigerant liquid and suction gas
piping using eddy current free Copper pipes and fittings like elbows, couplers, brass
fittings, "U" loops, expansion loops etc. Supports consisting of GI box / "C" sections &
female anchor fasteners with full threaded GI rods, insulation of pipes using 19 mm thick
32 Rmt 100 1290
elastomeric closed cell Nitrile Rubber insulation material having class "O" for fire
properties, structural clamps with hard PVC pipe sleeves under the clamps to protect
insulation at supports, tagging to enable tracing connectivity to respective units as per
shop drawings to be generated by contractor and approved by consultant.
Refrigerant piping joints for VRV system as per the manufacturers std. & has to be
33 Nos. 14 3500
supplied with system. As required
34 Electrical Cabling between indoor unit and 5/15 A Socket, 4 C, 2.5 SQM RMT 50 100
Preinsulated flexible duct with end clamps as required in various sizes as below. The duct
35 RMT 70 160
shall fire retardant UL standard approved. Size 150 NB
36 5/15 A sockets for indoor and duct inline fans Nos 15 390
Nitrogen flushing, Pressure testing, Refrigerant Gas top up as per piping length,
37 LS 1 11610
Commissioning of the system (28 HP)
38 Outdoor Unit Stand in MS construction. Painted with enamale paint. Nos 1 9030
39 Duct inine fan for fresh air. Kruger make MTD silent fan or equivalent fan
39.1 600 CFM @ 15 mm Statis Nos 2 11290
SLC of Drain Piping shall be HARD PVC. Drain Piping shall be insulated 12 mm Armaflex
Class O rubber nitrile closed cell insulation. The drain shall be released into the nearest
41 toilets and shafts. Inclussive of Supports. The rate shall be inclussive of all fittings such at
bends, TEE reducer and expander, coupler etc.
Rate (Rs.)
Sl.No Description of Work Unit Qty
Supply
Inline cabinet type fan with galvanised steel cabinet, belt driven DIDW forward curved
centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable
42 for 10 mm ESP. 1 Ph, Suitable KW motor, Krugger make CCK series or Nicotra equivalent.
Capacity As below:
42.1 1500 CFM @ 20 mm Static Nos 2 21260
42.2 500 CFM @ 20 mm Static Nos 2 11290
Supply installation and testing commissioning of Short casing Axial fans, 3 Ph, 6 P Motor.
45 Fan to have safety grill on both the sides.
45.1 6000 CFM @ 15 mm Static - Exhaust Nos 2 50490
45.2 5000 CFM @ 15 mm Static - Fresh Air Nos 2 53150
TOTAL
SUB TOTAL OF HVAC WORKS
GST @ 28 % ON SUPPLY
GST @ 18 % ON SUPPLY
GST @ 18 % ON INSTALLATION
GRAND TOTAL OF HVAC WORKS
80 14250 6000
50 4050 2250
390
390 5805150 1339650
390 1020000 265200
390 1303400 382200
50 66700 14500
50 9800 1750
50 16000 2500
50 12000 6000
40 5000 2000
80 7600 3200
50 2250 1250
40774590 4205510
44980100
336,560
7,123,066
756,992
48,234,216 4,962,502
AIR DISTRIBUTION
4 9,312,453 1,783,890 11,360,000
SECTION
INSTRUMENTATION AND
9 378,342 81,599 561,780
SENSORS
L1 39,984,052
L2 40,792,992
L3 44,980,100
L4 45,722,581
L5 45,841,462
L6 46,328,990
L7 46,919,463
L8 48,106,234
L9 50,967,705
L10 51,941,721
L11 58,497,976
HTL Air Consultants SCON Project Safe Air Engineers Anukool India
INSTALLATION
348,300
206,400
37,700
2,636,650
77,400
116,100
58,050
491,750
24,640
168,360
40,160
4,205,510
44,980,100