Sie sind auf Seite 1von 43

Metrolog Data Logger

Installation and Operation Manual

Metrolog
Data Logger
Installation and Operating Manual

Technolog Limited, Ravenstor Road, Wirksworth, Derbyshire DE4 4FY


Tel: +44 (0)1629 823611 Fax: +44 (0)1629 824283
Email: technolog@technolog.com

UM109000 Issue 1
Page 1 of 43
Metrolog Data Logger
Installation and Operation Manual

Contents page

Introduction (i)

1 Equipment and Functions 1.1

2 Metrolog Data Loggers 2.1


Metrolog H 2.1
Metrolog P 2.2
Metrolog F 2.2
Metrolog NA 2.3
Metrolog 420TA 2.4
Metrolog 420MET 2.5

3 Measurement and Logging 3.1


Mode 3.1
Timebase, Channel Rate and Logging Interval 3.1
Scale Factor 3.2
Threshold Recording 3.2
Time Resolution 3.3
Flow Recording (Metrolog H, P, F, and 420MET) 3.3
Pressure Recording (Metrolog NA and 420TA) 3.4

4 Display 4.1

5 Configuration Files and Notepad 5.1


Configuration Files 5.1
Viewing Config Files on a PC 5.2
Viewing Config Files on the Psion 5.3
Selecting a Config File 5.3
Loading a Config File 5.4
Notepad 5.5
Setting the Notepad on a PC 5.5
Viewing and Setting the Notepad on the Psion 5.5

6 Installation 6.1
Metrolog H, P, F, NA and 420MET 6.1
Metrolog 420TA with PTX 530 Depth Transmitter 6.3
Flow Input Connections 6.5
Splicing Wires - Recommended Method 6.6
Comms Connections 6.7

7 Setting Up Software and Starting the Logger 7.1


Procedure 7.1
Setting Defaults on a PC 7.1
Setting Defaults on the Psion 7.2
Setting Up the Logger 7.2
Starting the Logger 7.4

UM109000 Issue 1
Page 2 of 43
Metrolog Data Logger
Installation and Operation Manual

8 Downloading Data 8.1


Data File Names 8.1
Downloading Data to a PC 8.1
Downloading Data to the Psion 8.3

9 Troubleshooting 9.1
Comms Faults 9.1
Measurement Faults 9.1
File Faults 9.2

10 Maintenance and Storage 10.1


Connectors 10.1
Pressure Ports 10.1
Storage 10.1
Battery Changing 10.1

Appendix - Standard Metrolog Config Files A.1

Metrolog Quick-Reference Guide Following


page A.1

UM109000 Issue 1
Page 3 of 43
Metrolog Data Logger
Installation and Operation Manual

Introduction
This manual applies to Metrolog data loggers types H, P, F, NA, 420TA and 420MET. It gives
guidance in selecting, configuring, installing and setting up a logger for pressure and flow
measurement using the GPS (General Purpose Software) program on a PC and a Psion Organiser,
and in downloading data.

For other information about the GPS program (and the PMAC program), refer to the software manual.

To use this manual, the following sequence is suggested:

1. Refer to Sections 1 and 2 to identify the correct type of Metrolog and other equipment for the
intended application.

2. Refer to Section 3 for an understanding of the ways in which the Metrolog takes
measurements; this will aid in using the software to set up the unit on site. If the instrument
has a display, refer to Section 4 for further details.

3. Refer to Section 5 for an understanding of the purpose and selection of Configuration files,
and of the function of the Notepad, to aid in configuring a logger and in setting up on site.

4. Install the Metrolog, referring to Section 6.

5. Set up the Software and the Metrolog, (Section 7)

6. Download the logged data when required, (Section 8).

Refer to the remaining Sections as necessary.

UM109000 Issue 1
Page 4 of 43
Metrolog Data Logger
Installation and Operation Manual

1 EQUIPMENT AND FUNCTIONS


Metrolog Systems
Metrolog data loggers are used with software and other hardware to provide a system such as that
shown in Figure 1.1. The functions of the equipment, which may be supplied to form a system, are
detailed in this Section.

Figure 1.1 EQUIPMENT AND FUNCTIONS

Metrolog Data Logger

The various versions of the Metrolog are designed to log pressure, flow, or other parameters as shown
in Table 1.1, and may employ either a single channel or two channels as indicated.

Version Channels Application


H Flow and Pressure Bi-directional flow on Kent
2000/3000 meters, and pressure
P Flow and Pressure Uni-directional flow pulse count,
and pressure
F Flow Uni-directional flow pulse count
NA Flow and Pressure Uni-directional flow pulse count and
pressure
420TA 4-20mA current loop, and 4-20mA measurement, and flow
and Pulse input pulse count
420MET
Table 1.1 METROLOG APPLICATIONS

UM109000 Issue 1
Page 5 of 43
Metrolog Data Logger
Installation and Operation Manual

The features common to all versions are as follows; for further details, and to identify a particular
model, see Section 2.

Note: Metrologs of type H, P, F, NA are identified by a label on the side of the


case which also specifies the measurement range.

The range of the 420 Metrolog 420TA is set by the Transducer range. This Transducer range must be
defined in the notepad details during setup.

Comms Connector

- for connecting a PC, Psion Organiser, or modem, for configuring and setting up the logger, and for
downloading logged data.

Input Connectors

- for connecting pressure and flow measuring devices. For direct connection to a water main for
pressure measurement, a ‘quick-fit’ hose connector is fitted. For connection to a pressure transmitter
or flow measuring device, appropriate electrical connectors are provided.

Display

- a liquid crystal display is fitted to some models to show readings without the need to connect a PC or
Psion Organiser. For more details, see Section 4.

Pressure Transmitter (for use with Metrolog 420TA and Metrolog 420 MET only)

For depth recording. (Can be factory-fitted with 10-way connector for the 420 MET. No connector is
required for the Metrolog 420 TA. Other versions available on request)

Type : PTX530 37.5 mm dia.


: PTX1830 17.5 mm dia.

Pressure Input Fittings

For connecting the unit to a water main using quick-fit connectors:

Helicoil Hydraulic Hose

- flexible hose with connectors

Reinforced Rubber Hose

- with optional 90º connector at mains end

Hydrant Cap

- with female quick-fit connector fitted

UM109000 Issue 1
Page 6 of 43
Metrolog Data Logger
Installation and Operation Manual

Fixing Hardware
For supporting data logger and cables, (see Section 6 for more details):

Clamping Screws (Metrolog H only)

- for securing logger to meter

Mounting Brackets

- stainless steel or polycarbonate

Cable Hanger Support

- stainless steel mesh support for pressure transmitter cable (Metrolog 420TA only).

Input Cables

Flow Input

- cable with MIL spec. 3-way connector for Metrolog P, NA and MET.

4-20mA Input (Metrolog 420MET only)

- cable with MIL spec. 10-way connector.

Recommended Electrical Connection Hardware


For splicing input cables to wires from other equipment (such as pulse units):

‘Scotchlok’ Connectors, ‘Scotchlok’ E-9 Tool, PVC Cap, and Silicone Sealant

Comms Cable
For connecting data logger to a PC, with 9-way or 25 way connector.

PC Software and Manual


GPS-1 or GPS-2 (General Purpose Software) Program for IBM PC, with Manual

- DOS program on 3.5in disk, for setting up data logger, downloading data locally (or remotely with
modem via PSTN), and analysing data.

Configuration Files (.CFG Files)

- on separate 3.5in disk, for configuring data logger for a specific application.

PMAC (Pressure Management and Control) Program for IBM PC

- Windows program for downloading and analysing data via a modem link.

UM109000 Issue 1
Page 7 of 43
Metrolog Data Logger
Installation and Operation Manual

Psion Organiser
For setting up a data logger, and downloading and analysing data, complete with :

Datapak - containing GPS program for setting up datalogger, downloading


data, and storage of configuration files.

Rampak - for storing retrieved data.

Comms link - for connecting the Psion Organiser to a data logger.

Modem
Line-powered modem for remote connection of data logger to a PC via a telephone line. There are two
types of modem:

Technolog LIN 003

- ‘standard’ modem, requiring external BT telephone socket.

Technolog LIN 003E

- modem in waterproof enclosure with internal BT telephone socket.

Lightning Protector

Technolog recommend the use of lightning protectors with Modems. Various enclosures can be
supplied containing lightning protectors and telephone master sockets to protect modems and data
loggers from lightning strikes.

UM109000 Issue 1
Page 8 of 43
Metrolog Data Logger
Installation and Operation Manual

2 METROLOG DATA LOGGERS

Metrolog H (Helix)

Optional
Comms connector: Photo sensor Display Quick-fit pressure input
MIL spec. 4-way connector:1/8in BSP female
serial port thread fitted with male probe

Applications The unit is designed to mount directly on a Kent Helix 2000 or 3000 water meter in place
of the mechanical index, for recording flow and pressure.

Measurement Flow measurement is bi-directional, using magnetic sensors mounted in the base of the
unit to detect meter rotation; (no flow input connector is required). Pressure is measured
by an integral pressure sensor.

Pressure Accuracy/resolution: 0.5% of range


Measurement Operating temperature range: +1 to +30° C
Ranges: 0 - 100 or 0 - 200 mH2O (absolute)
Data available at 15 minute
logging intervals: 260 days

Flow Data available at 15 minute


Measurement logging intervals: 143 days

Memory Type: Solid state, non-volatile


Size: 32K

Clock Type: Crystal controlled calendar, with leap year


adjustment
Accuracy: 100 seconds/month max. error over operating
temperature range

Recording Interval: Programmable from 1 second to 24 hours


Method: Time-based or threshold logging
Modes: Rotating store or store till full

Power Supply Type: Internal lithium cell


Life: Greater than 3 years or 1 million pressure readings

Environmental Operating temperature: -20 to +50° C


Protection classification: IP 68

UM109000 Issue 1
Page 9 of 43
Metrolog Data Logger
Installation and Operation Manual

Optional
Metrolog P (Pulse) Flow input connector: Display (optional)
MIL spec. 3-way

Comms connector: Photo sensor Quick-fit pressure input


MIL spec. 4-way connector:1/8in BSP female
serial port thread fitted with male probe

Applications Designed for connection to a flow meter pulse unit; records flow and water pressure.

Measurement Flow measurement is uni-directional; the instrument counts flow-proportional pulses from
most mechanical and electromagnetic flow meters. Pressure is measured by an integral
pressure sensor as in the Metrolog H.

Flow Input Switch closure or logic pulse, maximum rate 15Hz

Other Details As Metrolog H

Metrolog F (Flow only) Display (optional) Pre-wired flow input cable:


2-wire

Comms connector: Photo sensor


MIL spec. 4-way
serial port

Applications Single channel flow logger.

Measurement Measures flow in the same way as the Metrolog P.

Flow Input Integral open-ended cable for connecting to flow sensor. Accepts switch closure or logic
pulse, maximum rate 15Hz

Other Details As Metrolog H

UM109000 Issue 1
Page 10 of 43
Metrolog Data Logger
Installation and Operation Manual

Metrolog NA (Network Analysis)


Optional Optional
Flow input connector: Display
MIL spec. 3-way

Comms connector: Photo sensor Quick-fit pressure input


MIL spec. 4-way connector:1/8in BSP female
serial port thread fitted with male probe

Applications Flow and pressure recording to the high degree of accuracy required for Network
Analysis.

Measurement Measures flow in the same way as the Metrolog P, and pressure by ‘flash point’ or ‘mean
of a number of samples’ (see Section 3).

Pressure Accuracy: ± 0.1% of range at ambient temperature


Measurement Resolution: 0.1% of range
Operating temperature
range: +1 to +40°C

Power Supply Life: Typically 3 years at 1-minute sample rate

Other Details As Metrolog H

UM109000 Issue 1
Page 11 of 43
Metrolog Data Logger
Installation and Operation Manual

Metrolog 420TA (4-20mA input - Terminal Assembly)

Terminal Cable gland


compartment (4-20mA input)

Comms connector: Filtered vent for atmospheric Cable gland


MIL spec. 4-way pressure reference (flow input - optional)
serial port

Applications Can be used in any application where a 4-20mA current loop is available or 4-20mA
Transmitter is used. An optional flow input can be provided through an additional cable
gland.

Measurement Normally used with a depth transmitter and calibrated to record depth. The internal
battery and software are capable of operating some types of 4-20mA 2-wire transmitters
such as the PTX530 and PTX1830; (contact Technolog for more information).
Alternatively the unit can be connected to a remotely-powered 4-20mA loop to record any
other parameter. With the optional flow input, the 420TA also measures flow by pulse
count in the same way as the Metrolog P.

Current Accuracy: Better than 0.1% at ambient temperature


Measurement Resolution Better than 0.02%
Data available at 15 minute
logging intervals: Almost 6 months

Memory Type: Solid state, non-volatile


Size: 32K

Clock Type: Crystal controlled calendar, with leap year


adjustment
Accuracy: 100 seconds/month max. error over operating
temperature range

Recording Interval: Programmable from 2 seconds to 24 hours


Method: Time-based or threshold logging
Modes: Rotating store or store till full

Power Supply Type: Internal lithium cell


Life: Greater than 5 years at 3-minute sampling rate
Output: Flash powered 11V supply for transmitter

Environmental Operating temperature: -10 to +50°C


Protection classification: IP 65

UM109000 Issue 1
Page 12 of 43
Metrolog Data Logger
Installation and Operation Manual

Metrolog 420MET (4-20mA METrolog)

Optional
Flow input connector: Display (optional)
MIL spec. 3-way

Comms connector: Photo sensor


MIL spec. 4-way 4-20mA input connector:
serial port MIL spec. 10-way

Applications Two-channel data logger with a 4-20mA input for recording depth (or other variable), and
a flow input.

Measurements Like the 420TA, can be used with a pressure transmitter for depth logging, or with a
remotely-powered current loop for recording any variable. In addition, the instrument
measures flow in the same way as the Metrolog P.

Flow Input Switch closure or logic pulse, maximum rate 15Hz

Environmental Operating temperature: -20 to +50°C


Protection classification: IP 68

Other Details As Metrolog 420TA

UM109000 Issue 1
Page 13 of 43
Metrolog Data Logger
Installation and Operation Manual

3 MEASUREMENT AND LOGGING


The following terms apply to the menu options and parameters used by the GPS program to set up a
logger. Where appropriate, the corresponding menu options are given.

Mode
In Rotating Store mode, data is stored until the memory is full. If more data is recorded, the oldest day
of data is deleted and the new data is stored in its place. Rotating Store should be used when more
than two days of data are required.

In Store-till-Full mode, data is stored until the memory is full. The logger then stops logging and reverts
to standby.

PC: Newlog - Start/Stop - Mode

Psion: Start/Stop - Store Mode

Timebase, Channel Rate, and Logging Interval (Figure 3.1)


The Timebase is the ‘heartbeat’ (the clock) which regulates the logging process. At each timebase
‘beat’ the logger checks its configuration to find out whether a measurement should be taken and
responds accordingly. The Rate (the channel rate) defines the logging interval (the time between
recording two successive measurements), and must be a whole multiple of the timebase. In most
single channel applications it is usually recommended that the Timebase and channel Rate are set to
the same value. Two logging channels may have different Rates with a common Timebase.

PC: Newlog - Setup - Rate

Psion: Setup - Rate

Figure 3.1 TIMEBASE, RATE, AND LOGGING INTERVAL

UM109000 Issue 1
Page 14 of 43
Metrolog Data Logger
Installation and Operation Manual

Scale Factor
The scale factor is used in flow logging where the logger is connected to a meter or pulse unit, and
defines the flow volume per pulse. The scale factor is determined by the configuration file, (see
Section 5).

PC: Newlog - Setup - Notepad

Psion: Setup - Notepad

Threshold Recording (Figure 3.2)


Threshold recording can be used to save memory when only significant changes in a measured value
are of interest. The input is sampled at the defined Rate, and each measurement is compared with the
previously stored value. If the difference is less than the Threshold the new value is not stored; if the
difference exceeds the Threshold, the new value is stored.

PC: Newlog - Setup - Threshold

Psion: Setup - Threshold

Figure 3.2 THRESHOLD RECORDING

UM109000 Issue 1
Page 15 of 43
Metrolog Data Logger
Installation and Operation Manual

Time Resolution

The Time resolution defines the shortest time interval in which an event can be recorded, and can be
set to either 1 second or 10 seconds. It must always be set to 10 seconds for use with a Metrolog unit.

PC: Newlog - Start/Stop - Mode

Psion: Start/Stop - Time Res

Flow Recording (Metrolog H, P, F, and 420MET) - (Figure 3.3)


These units count the pulses received during each logging interval, and record the total at the logging
rate to give the mean flow for the interval, for example as shown in Figure 3.3.

Figure 3.3 FLOW RECORDING BY PULSE COUNT

Note:

The Metrolog H senses the rotation of the magnets in the Kent Helix meter, giving eight pulses per
revolution.

Pulse units, used with other models, usually give 10 pulses per revolution.

UM109000 Issue 1
Page 16 of 43
Metrolog Data Logger
Installation and Operation Manual

Pressure Recording (Metrolog NA and 420TA) - (Figure 3.4)

Pressure is read at the timebase frequency, and each value is stored temporarily. At the end of each
logging interval, the mean value for the interval is calculated and stored. The temporarily stored values
for that interval are then cleared.

Figure 3.4 PRESSURE RECORDING - NA AND 420TA

UM109000 Issue 1
Page 17 of 43
Metrolog Data Logger
Installation and Operation Manual

4 DISPLAY

Triggering (Figure 4.1)


The eight-character liquid crystal display is triggered by a photo sensor, and is normally turned off to
conserve power.

Photo sensor Display

Figure 4.1 PHOTO SENSOR AND DISPLAY

The display is activated when the ambient light level increases beyond a threshold value, for example
if an enclosure containing the unit is opened, if a manhole cover is lifted, if a torch beam is directed on
to the sensor, or if a hand is passed over the sensor.

When the display is triggered it shows a sequence of messages, and is then turned off again. To turn
the display on again, the sensor must detect another threshold increase in light level.

Messages
The messages include current, maximum and minimum values of pressure and flow, and a typical
sequence of messages is as follows:

METROLOG
VER xx (version of Metrolog firmware)
TODAY
INDEX xxx (current index reading)
PRESSURE xxx (current pressure)
FLOW xxx (current flow)
MAX PRES xxx ( )
MIN PRES xxx (Up to 15 previous days)
MAX FLOW xxx ( )
MIN FLOW xxx ( )

Some of the messages are fixed; others depend on the application of the unit. The sequence and
timing of the messages are determined by the configuration file, (see Section 5).

UM109000 Issue 1
Page 18 of 43
Metrolog Data Logger
Installation and Operation Manual

5 CONFIGURATION FILES AND NOTEPAD


Configuration Files (Table 5.1)
A configuration file is a small text file that must be loaded into a logger to configure the logger for the
required duty. Configuration files (or ‘config’ files) have the filename extension .cfg and are also
known as ‘.cfg files’; a typical filename is ‘MP10.CFG’. Each file contains the following information:

1. The versions and types of logger for which the file is intended,

2. The channels to be measured (pressure, flow, or both),

3. The pressure range (for pressure measurement), and the scale factor (for flow
measurement), as applicable.

4. The sequence of display messages (if the logger has a display).

5. Notepad information, entry fields, style and comments.

Configuration files are divided into four types, and for the purpose of configuration Metrologs are
divided into four versions. Each type of configuration file can only be used with the appropriate version
of Metrolog. The names of configuration files indicate the type of Metrolog with which they can be
used. If a full set of configuration files is supplied on disk, they may be stored in sub-directories which
also indicate the version of Metrolog to which they apply, (see Table 5.1).

Metrolog Type Version Configuration File Sub-directory


Names
H 1.vv MHxx.CFG METRO-H
P, F 2.vv MPxx.CFG METRO-P
NA 3.vv NAPxx.CFG METRO-NA
420TA, 3.vv M420xx.CFG METRO-TA
420MET
vv is the last two digits of the version number, for example 2.03.
xx is a set of characters indicating the file application; for example MP100.CFG is a
file for a pressure range of 100m. The word EDTA or EDIT in a filename indicates
that the pressure range and/or scale factor can be edited in the Notepad.

Table 5.1 LOGGERS AND CONFIGURATION FILES

Note:

A complete list of standard configuration files is given in the Appendix. Modifications to .cfg files to suit
specific applications can be obtained from Technolog.

Caution:

The configuration file selected must match the logger and associated hardware.
For copying files to a PC or Psion, refer to the software manual.

UM109000 Issue 1
Page 19 of 43
Metrolog Data Logger
Installation and Operation Manual

Before viewing the details of a file, make sure that the PC or Psion defaults have been set so that the
GPS program can access the configuration files, (see Section 7).

Before loading a file into a Metrolog, select a suitable file as detailed in this Section.

Viewing Config Files on a PC (Figure 5.1)

1. Run the GPS program, and select Newlog - Setup - Configure - Logger to give the display
shown in Figure 5.1.

2. Highlight the filename and press F2. The display will show the file application and version of
Metrolog, for example:

Metrolog ‘P’ Pressure (100m) Recording ONLY


Metrolog 2.03

If the files are stored in sub-directories, highlight the directory name and press Enter. Some
files may be stored in further sub-directories whose names indicate the file application, for
example MET-P100 = pressure recording, 100m pressure range. Highlight the directory
name and press Enter again to view the filenames.

Figure 5.1 SELECTING AND LOADING CONFIGURATION FILES

Viewing Config Files on the Psion


Press the ON/CLEAR key, then select Setup - Configure - Logger.

UM109000 Issue 1
Page 20 of 43
Metrolog Data Logger
Installation and Operation Manual

The display will show the filename and version of the logger, and the file details will scroll from right to
left repeatedly.

To view another file, press SPACE.

Selecting a Config File

Channels

Make sure that the .cfg file and the logger can measure the required channels, (pressure, flow or
both). A two-channel logger can be configured to measure only one channel if required; the full 32K of
the logger’s memory will then be assigned to that channel.

Pressure Range

Metrologs for pressure measurement have various pressure ranges, (100 or 200m, 10 or 20 Bar).
Check the label on the side of the instrument to make sure that it is the same as that specified in the
.cfg file. If you try to configure a 200m logger with a 100m .cfg file, the pressure readings will be
inaccurate because the scaling of the transducer will be incorrect.

Flow Scale Factor

The scale factor determines the flow units shown on the display, and is set by selecting the
appropriate .cfg file as detailed below to give one of three possible ranges.

Note:

The display cannot be configured for ranges other than these. If an editable .cfg file is selected in
order to apply a different scale factor to the data, the display will automatically be disabled. The
editable file for Metrolog P is MPEDIT.CFG.

Scale Factor - Metrolog P/NA/MET/TA

Designed for use with standard pulse units such as the LRP and PU10 which produce 10 pulses per
revolution, the Metrolog P displays flow values related to 1, 10 or 100 litres/pulse depending on the
size of the meter. The corresponding .cfg file configures it as follows and will automatically set the
correct scaling for the display:

Meter size Vol/rev Vol/pulse Scale factor .cfg file


(in) (litre) (litre) (cum/pulse)

6 1000 100 0.1 MP100.CFG

4 100 10 0.01 MP10.CFG

2 10 1 0.001 MP1.CFG

UM109000 Issue 1
Page 21 of 43
Metrolog Data Logger
Installation and Operation Manual

Scale Factor - Metrolog H

The Metrolog H is mounted directly on a Kent Helix meter that produces eight pulses per revolution.
Details of scale factor and .cfg files are as follows:

Meter size Vol/rev Vol/pulse Scale factor .cfg file


(in) (litre) (litre) (cum/pulse)

6 1000 125 0.125 MH1000.CFG

4 100 12.5 0.0125 MH100.CFG

2 10 1.25 0.00125 MH10.CFG

Note: Other scale factors may be entered but the display will not show the
correct scale value.

Loading a Config File


Before loading a file, make sure that the software defaults have been set and the logger connected to
the PC as detailed in Section 7.

Loading From a PC

Select Newlog - Setup - Configure - Logger. On the display shown in Figure 5.1, highlight the
required filename and press Enter. The display will show a progress bar as the file is loaded.

Loading From the Psion

Select Setup - Configure - Logger, and press SPACE to display the required file. Press EXE to load
the file.

UM109000 Issue 1
Page 22 of 43
Metrolog Data Logger
Installation and Operation Manual

Notepad
The Notepad is a data area in the logger that contains some of the logger configuration parameters
and channel scaling. Data entry fields are included for entering site specific information and
comments. These details are automatically added to the data file produced by the logger so that the
file can be identified after it has been downloaded.

Note:

To set the Notepad, the software must be configured and the logger connected to the PC as detailed
in Section 7.

Setting the Notepad on a PC


Select Newlog - Setup - Notepad. A typical display is as follows; highlighted items can be edited.

Measurement
channels

Site details

Pressure range
and scale factor,
as applicable.

Type the required information; press Tab to move to the next item. When all items are complete, press
Enter. Select Review to correct errors, Write to load data into Metrolog.

Note:

The Notepad can be viewed (but not edited) by selecting Newlog - Status - Notepad.

Viewing and Setting the Notepad on the Psion


Select Setup - Notepad. Details of the measurement channels will scroll across the display.

Press SPACE to check or enter the site name, and press EXE to move to the next item. When all
items are set, press EXE. Select Review to correct errors, Write to load data into Metrolog.

Note:

The Notepad can be viewed (but not edited) by selecting Status - Notepad.

UM109000 Issue 1
Page 23 of 43
Metrolog Data Logger
Installation and Operation Manual

6 INSTALLATION

Metrolog H, P, F, NA and 420MET


Location and Fixing (Figure 6.1)

The main considerations in choosing a location are access and frost protection.

Caution:

Although Metrologs are rated for operation at sub-zero temperatures, temperatures of 1°C and
below may result in ice formation that can destroy pressure transducers.

If possible, install the data logger in a meter chamber; Figure 6.1 shows typical arrangements. Keep
the connecting hoses as short as possible and lag them where necessary. If setting up and
downloading are to be carried out locally, make sure that the comms connector on the logger will be
easily accessible.

Metrolog H:

Remove the index from the meter (if fitted), and secure the logger to the meter with the clamping
screws.

Note:

The Metrolog H can also be mounted on top of an LRP or PU10 pulse unit.

Metrolog P, F, NA and 420MET:

Secure the logger with a wall mounting bracket.

Metrolog P, F, NA or MET Metrolog H

Meter
chamber
Insulating
disc Metrolog H Clamping screw
Metrolog
Helicoil
pressure
Index hose
Pipe
Pulse unit fitting

Meter
Kent Helix meter

Figure 6.1 METROLOG H, P AND NA - TYPICAL INSTALLATIONS

UM109000 Issue 1
Page 24 of 43
Metrolog Data Logger
Installation and Operation Manual

Pressure Connections (Figure 6.2)

Make connections to the main by means of a hydrant cap or a pipe fitting. Both of these incorporate a
‘quick-fit’ connector which will accept either a reinforced rubber hose or a helicoil hose.

Figure 6.2 PRESSURE CONNECTIONS

UM109000 Issue 1
Page 25 of 43
Metrolog Data Logger
Installation and Operation Manual

Metrolog 420TA with PTX 530 Depth Transmitter


1. Refer to Figure 6.3. Secure the logger with a mounting bracket, and fit a stainless steel cable
hanger support to the cable before making the connections. Remove the lid from the
terminal assembly and make the connections as shown.

Figure 6.3 PRESSURE TRANSMITTER INSTALLATION - METROLOG 420TA

UM109000 Issue 1
Page 26 of 43
Metrolog Data Logger
Installation and Operation Manual

2. Refer to Figure 6.4. There is an airspace between the sensing diaphragm of the depth
transmitter and the pressure port. Before installing the transmitter, remove the plastic
nosecone, fill the port with water, and refit the nosecone. This will eliminate the possibility of
slight error due to the compressibility of air trapped within the port.

Caution:

At 1°C and below, water freezing in the port will destroy the transmitter.

Figure 6.4 PRESSURE TRANSMITTER

UM109000 Issue 1
Page 27 of 43
Metrolog Data Logger
Installation and Operation Manual

Flow Input Connections


Note: Full details of connections to specific types of pulse unit can be obtained
from Technolog.

Metrolog P, NA, 420TA, 420MET - Figure 6.5

Figure 6.5 FLOW INPUT CONNECTIONS

Metrolog F

The pulse input connection is made by the integral open-ended two-wire cable. Connect the cable to
the reed switch output of the LRP or PU10 pulse unit, or the flow meter, as follows:

Red: flow channel

Black: ground

UM109000 Issue 1
Page 28 of 43
Metrolog Data Logger
Installation and Operation Manual

Splicing Wires - Recommended Method


Use the ‘Scotchlok’ connectors, ‘Scotchlok’ E-9 tool, PVC cap and silicone sealant as follows:

1. Cut and remove the outer insulation from the cables to expose 25mm of insulated wire.

2. Cut the wires evenly.

Caution:

Do not strip the insulation from the wires.

3. Holding the ‘Scotchlok’ connector with the button side down, insert the wires to be joined
fully into the ports.

4. Crimp the button using the ‘Scotchlok’ E-9 tool.

Caution:

Do not use any other tool for crimping as this could cause the wires to snap or otherwise be
damaged inside the connector, giving a faulty joint.

5. Fill a PVC cap one third full of silicone sealant.

6. Push the ‘Scotchlok’ joints into the base of the cap and fill the cap to the top with silicone
sealant.

Caution:

Make sure that both the connectors and outer cable insulation are fully submersed in the
sealant.

UM109000 Issue 1
Page 29 of 43
Metrolog Data Logger
Installation and Operation Manual

Comms Connections
A PC or Psion organiser can be connected locally by means of the Comms cable supplied and the
Comms connector on the logger. For remote connection to a PC, the arrangement shown in Figure 6.6
is required.

Note:

Technolog recommend the use of lightning protectors with modems.

Figure 6.6 REMOTE COMMS CONNECTIONS

UM109000 Issue 1
Page 30 of 43
Metrolog Data Logger
Installation and Operation Manual

7 SETTING UP SOFTWARE AND STARTING THE LOGGER


Procedure
This Section details the checks and settings needed to set up and start a logger which has been
installed on site. Before setting up, it is good practice to check that the PC or Psion’s clock is set
correctly. This is especially important if a number of loggers are to be synchronised.

The PC or Psion can be set up without the need to connect the logger, if required.

For pressure measurement, a pressure gauge will be required to check the pressure at the source.

Setting Defaults on a PC

1. Run GPS Program

Switch on the PC and run the software. (Refer to the software manual if necessary).

2. Local or Remote Comms

To use the software for local communication with a logger, no action is required.

For remote communication using a PC it will first be necessary to build up a database of


sites and telephone numbers. The software options for remote communication are:

Newlog and Database

3. Comms Ports

Select the port to which the logger will be connected:

Defaults - Comms

The Local port is usually COM 1; for local communication, set Modem to Disabled. For
remote communication, set Modem to COM 1 or COM 2 as appropriate.

4. Configuration File Directory

Check that the name (and path) of the directory in which the configuration files are stored
has been entered:

Defaults - Files

5. Baud Rate

Select Newlog - Defaults - Comms, and set the baud rate for all file transfer to 9600.

6. Save the Settings

Select Defaults - Keep to save the settings.

UM109000 Issue 1
Page 31 of 43
Metrolog Data Logger
Installation and Operation Manual

Setting Defaults on the Psion

1. Datapak and Rampak

Check that the 128K Datapak is in drive B: (the slot closest to the display).

Check that the Rampak (if used) is in drive C: (the slot furthest from the display).

2. Set Drive for Data Storage

Press the ON/CLEAR key, select Defaults - Files - Data and check that the drive is set as
follows:

Rampak fitted : drive C: (


( Press EXC to save changes
No Rampak fitted : drive A: (

3. Set Drive for Configuration Files

Select Defaults - Files - Config, and check that drive B: is selected.

4. Baud Rate

Select Defaults - Comms, and check that the baud rate is set to 9600. If necessary, use the
Up and Down arrow keys to correct the setting.

Setting Up the Logger


Note:

The following settings cannot be altered while the logger is logging:

Threshold Timebase Time Resolution


Channel Rate Clock Offset

1. Connect Logger

PC: Connect PC to Comms connector on logger with data cable.

Psion: Connect Psion to Comms connector on logger with Comms link.

2. Comms Check

Always check communications between logger and PC or Psion by confirming the logger’s state
before proceeding further:

PC: Newlog - Status - State

Psion: Status - State

If the logger is logging, stop logging:

PC: Newlog - Start/Stop

Psion: Start/Stop

UM109000 Issue 1
Page 32 of 43
Metrolog Data Logger
Installation and Operation Manual

Note :

If the GPS program on the PC is set up for modem communications, an additional menu option will be
added after selecting Newlog. For local communication, first select Local from this menu.

3. Check Notepad

PC: Newlog - Setup - Notepad

Psion: Setup - Notepad

Enter the site details. Check that the configuration details are correct, indicating that the correct .cfg
file has been loaded into the logger.

If an editable .cfg file is in use, enter the pressure range and scale factor as appropriate. If the
configuration details are incorrect, refer to Section 5 and load the correct .cfg file.

4. Set Clock

Synchronise the logger’s clock with the PC or Psion’s clock:

PC: Newlog - Setup - Clock

Psion: Setup - Clock

5. Set Channel Rate and Timebase

Note:

The Rate must be a multiple of the Timebase.

PC: Newlog - Setup - Rate

Psion: Setup - Rate - Timebase

Setup - Rate - Channel (to set Rate). Use arrow keys to change values,
press EXE to confirm.

Notes:

1. All Metrologs:
The maximum timebase is 30 min.

2. Metrolog NA:

The Metrolog NA starts logging at the next logical division of an hour. Select a Rate to give
logical divisions of 1 minute or 1 hour so that a measurement will be taken at the same time
in each hour as the start time, i.e. use:

1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 or 60 minutes or seconds.

3. Metrolog 420TA and 420MET:

If using a pressure transmitter do not set the Rate to less than 2 min, as the battery life will
be severely reduced.

UM109000 Issue 1
Page 33 of 43
Metrolog Data Logger
Installation and Operation Manual

6. Set Mode and Time Resolution

Set the Mode to Rotating store, and the Time resolution to 10 seconds:

PC: Newlog - Start/Stop - highlight items and press Enter to toggle between
selections
Psion: Start/Stop - Store Mode
Start/Stop - Time Res

7. Zero Pressure Transducer

Vent the pressure port on the Metrolog to atmosphere by disconnecting the pressure hose,
and check the pressure reading. Zero the reading if necessary:

PC: Newlog - Status - Input; press F1 to enable the reading to be changed to


zero.
Psion: Status - Input; press MODE, use the arrow keys to select the digits, and
zero the digits by pressing SHIFT and Y (=0). Press Exc to set.

8. Input Check

Reconnect the pressure hose to the source, and check the pressure and flow readings as
applicable:

PC: Newlog - Status - Input (use the arrow keys or spacebar to change
channels)
Psion: Status - Input (press SPACE to change channels)

The readings should confirm the expected values. If possible, check the actual pressure with
a pressure gauge.

Starting the Logger


1. Start Logging

PC: Newlog - Start/Stop - Clr+Start; check that the status display shows that
the logger is logging
Psion: Start/Stop - Clr+Start - to start logging

Caution:

If a logger is logging and ‘Stop logging’ is selected, any stored data will be cleared
when the logger is re-started.

2. Function Check

If the logger has been correctly configured, it will start logging. Confirm this by checking the
status:

PC: Newlog - Status - State


Psion: Status - State

3. Disconnect Metrolog

Disconnect the PC or Psion, and fit the dust caps to the data connector and any other
unused connector on the logger.

UM109000 Issue 1
Page 34 of 43
Metrolog Data Logger
Installation and Operation Manual

8 DOWNLOADING DATA

Data File Names

When data is downloaded from a logger, it is stored in the PC or the Psion as a data file (or files). File
names for use with the GPS program have the format:

DATAXXYY.NWL

- where XX is the file number (the next number available), and YY is the channel number, for example:

DATA0101 - file number 1 for channel 1

DATA0102 - file number 1 for channel 2 .

If only one channel has been recorded, YY will not appear, for example:

DATA03 - file number 3 (only one channel recorded)

Downloading Data to a PC

Caution:

Data can be downloaded while the Metrolog is logging. If logging is stopped, any stored data
will be cleared when the logger is started again.

1. Connect the PC to the Comms connector on the Metrolog with the data cable, and run the
GPS program.

2. Select Newlog - Data - Read. The software will read the Notepad, and the next screen
display will appear, containing the READ DATA menu:

The items shown on the menu will depend on the configuration of the logger. The example shows the
full range of items, which provide the following facilities:

2.1 Latest

Each time data is downloaded, the logger stores the date and time. Select this option to download the
latest data, i.e. the data stored since the last download.

UM109000 Issue 1
Page 35 of 43
Metrolog Data Logger
Installation and Operation Manual

2.2 All channels

This item will only appear if the logger has been configured to record more than one channel. (In the
example the next two options, Pressure and Flow, indicate that the logger has been configured to
record two channels).

Select this option to download the data from all channels. The software will download each channel in
turn, indicating the Measurand (the channel being downloaded) and a countdown as the data is
downloaded.

When the data has been downloaded, the name of the data file will be displayed; make a note of the
filename for later reference.

2.3 Pressure

Select one of these options to download data from the appropriate channel and the display will show
the details as for All channels. Make a note of the filename for later reference.

2.4 Flow

See Pressure

2.5 All/part

This option enables all the logged data, or the data for a selected period, to be downloaded. Highlight
the option and press Enter. Depending on the selection made previously, the display will show either:

Range of data to read all

or:

Range of data to read last


xx
The range is shown in the format: -
xx
last (specified day) - (specified day +1), days

with a maximum of last 248 - 249 days.

Each day begins at midnight, so selecting last 7 - 8 days will give at least one week of data.
To change the setting use the Shift and plus (+), and minus (-) keys to select all, or the required
range.

Press Enter; the display will again show the READ DATA menu, enabling the required channels to be
selected.

Note:

The selected setting will be stored, and will be displayed the next time All/part is selected.

3. After downloading the data and recording the names of the data files, disconnect the PC
from the logger, refit the dust cap to the Comms connector, and shut down the PC.

UM109000 Issue 1
Page 36 of 43
Metrolog Data Logger
Installation and Operation Manual

Downloading Data to the Psion

Caution:

Data can be downloaded while the Metrolog is logging. If logging is stopped, any stored data
will be cleared when the logger is started again.

1. Connect the Psion to the Comms connector on the Metrolog with the data cable, and press
ON/CLEAR.

2. Select Data - Read. The next screen display gives the same facility as the All/part option on
the PC (as detailed in Downloading Data to a PC above). Depending on the selection made
previously, the display will show either:

Read all data or Read ** - ** days


(Y/N) of data (Y/N)

To download all the data, or the pre-selected range of data, press Y.

To change the setting, press N. The display will show:

Data to read:
(present setting)

Use the arrow keys to make the required selection, (all data, or a range from 00 - 01 to a
maximum of 98 - 99 days), and press EXE.

3. If the logger has been configured to record more than one channel, the display will show:

All channels
One channel

This display gives the same options as the All channels option for the PC (as detailed in
Downloading Data to a PC above).

Selecting All channels will download the data from each channel in turn, save the data in a
single data file, and display the name of the file. Make a note of the filename for later
reference.

Selecting One channel will enable the required channel to be selected, or will enable each
channel to be downloaded in turn and the data from each channel to be saved in a separate
data file. Answer the prompts with Y or N as appropriate.

If the logger has been configured to record only one channel, the display will show:

Reading pressure (or flow, as appropriate),

and the data will be downloaded. Make a note of the filename for later reference.

4. After downloading the data and recording the names of the data files, disconnect the Psion
from the logger and refit the dust cap to the Comms connector.

UM109000 Issue 1
Page 37 of 43
Metrolog Data Logger
Installation and Operation Manual

9 TROUBLESHOOTING

Comms Faults
Symptom

PC or Psion screen shows an error message such as ‘Comms error’, ‘Retrying’ or ‘Transfer
aborted’.

Possible Cause and Remedy

Transient fault - try again to establish communication.

Cable, connection or logger fault - check that the correct Comms cable is in use. Check that
connectors are dry - if necessary dry out connectors and apply water dispersing lubricant such as
Duck Oil, (RS part No. 692-615). If necessary, substitute another logger or cable to identify the faulty
component.

Wrong Comms port selected - Check Defaults - Comms setting.

Battery exhausted - return the unit to Technolog for data recovery and battery renewal.

Measurement Faults
Symptom

Data shows incorrect units, or no units.

Possible Cause and Remedy

Wrong config file in use - select correct file (see Section 5).

Wrong scale factor entered in editable Notepad - do not stop logger; enter correct factor while logging
and download data again.

Symptom

Data shows no measurements, or measurements in wrong units, such as volts or pulses/hour.

Possible Cause and Remedy

Logger defaults set incorrectly -

PC: select Newlog - Defaults - Logger, and change Presentation from Raw
to Engineering.

Psion: select Defaults - Logger, and change Input mode to Eng. units.

Symptom

Flow measurement shows constant percentage error.

UM109000 Issue 1
Page 38 of 43
Metrolog Data Logger
Installation and Operation Manual

Possible Cause and Remedy

Scale factor too large or too small - select Newlog - Notepad and edit Notepad if possible to correct
Scale factor. If config file will not allow Notepad to be edited, send logger to Technolog to recover
data.

Symptom

Pressure measurements too high by a fixed amount.

Possible Cause and Remedy

Pressure transducer not zeroed - zero transducer and download data again. For zeroing procedure,
see Section 7 - (Function Check).

Symptom

No flow data recorded

Possible Cause and Remedy

No pulses - check pulse unit or flow meter and connections.

Pulse frequency too high (must be less than 15Hz) - re-calibrate flow meter if possible, or substitute
suitable flow meter or pulse unit.

File Faults
Symptom

PC cannot find file, or copies file to wrong directory.

Possible Cause and Remedy

Directory (PC) or drive (Psion) setting incorrect -

PC: select Newlog - Defaults - Files and set correct paths for files.

Psion: select Defaults - Files, and refer to Section 7 - (Setting Up the Psion).

UM109000 Issue 1
Page 39 of 43
Metrolog Data Logger
Installation and Operation Manual

10 MAINTENANCE AND STORAGE

Connectors

Protect electrical connectors with water dispersing lubricant such as Duck Oil, (RS part No. 692-615).

Caution:

The rubber ‘O’ ring seal may absorb lubricant and swell. Do not soak the unit with lubricant -
use a light spray and wipe off the excess.

Keep dust caps fitted to connectors at all times when the connectors are out of use.

Pressure Ports
Use two spanners when removing and refitting pressure port nipples.

Caution:

Do not insert a sharp implement into a pressure port - the port contains a delicate diaphragm
which will be damaged.

Storage
Caution:

Although Metrologs are rated for operation at sub-zero temperatures, temperatures of 1°C and
below may result in ice formation that can destroy pressure transducers.

Store data loggers at temperatures above 1°C, making sure that there is no water in the pressure port
connections.

Battery Changing
When a logger’s battery is exhausted, return the unit to Technolog for battery renewal. Battery
exhaustion is usually indicated by loss of communications, or error messages when downloading data.

UM109000 Issue 1
Page 40 of 43
Metrolog Data Logger
Installation and Operation Manual

Appendix STANDARD METROLOG CONFIG FILES

METROLOG TYPE CONFIG.FILE DESCRIPTION

Metrolog H 100m MH1.cfg Metrolog ‘H’ Pressure (100m) Recording ONLY


MH110.cfg Metrolog ‘H’ Pressure (100m) and Flow (10 l/rev) Recording
MH1100.cfg Metrolog ‘H’ Pressure (100m) and Flow (100 l/rev) Recording
MH11000.cfg Metrolog ‘H’ Pressure (100m) and Flow (1000 l/rev) Recording

Metrolog H 200m MH2.cfg Metrolog ‘H’ Pressure (200m) Recording ONLY


MH210.cfg Metrolog ‘H’ Pressure (200m) and Flow (10 l/rev) Recording
MH2100.cfg Metrolog ‘H’ Pressure (200m) and Flow (100 l/rev) Recording
MH21000.cfg Metrolog ‘H’ Pressure (200m) and Flow (1000 l/rev) Recording

Metrolog H Flow MH10.cfg Metrolog ‘H’ Flow (10 l/rev) Recording ONLY
only
MH100.cfg Metrolog ‘H’ Flow (100 l/rev) Recording ONLY
MH1000.cfg Metrolog ‘H’ Flow (1000 l/rev) Recording ONLY

Metrolog P 100m MP1.cfg Metrolog ‘P’ Pressure (100m) Recording ONLY


MP11.cfg Metrolog ‘P’ Pressure (100m) and Flow (1 l/pulse) recording
MP110.cfg Metrolog ‘P’ Pressure (100m) and Flow (10 l/Pulse) recording
MP1100.cfg Metrolog ‘P’ Pressure (100m) and Flow (100 l/Pulse) recording
MP1EDIT.cfg Metrolog ‘P’ Pressure (100m) and Flow (EDIT cum/pulse) recording

Metrolog P 200m MP2.cfg Metrolog ‘P’ Pressure (200m) Recording ONLY


MP21.cfg Metrolog ‘P’ Pressure (200m) and Flow (1 l/Pulse) Recording
MP210.cfg Metrolog ‘P’ Pressure (200m) and Flow (10 l/Pulse) Recording
MP2100.cfg Metrolog ‘P’ Pressure (200m) and Flow (100 l/Pulse) Recording
MP2EDIT.cfg Metrolog ‘P’ Pressure (200m) and Flow (EDIT cum/pulse) Recording

Metrolog P 10 Bar P10B.cfg Metrolog P Pressure (10 Bar) Recording ONLY


P10B1.cfg Metrolog P Pressure (10 Bar) and Flow (1 l/Pulse) Recording
P10B10.cfg Metrolog P Pressure (10 Bar) and Flow (10 l/Pulse) Recording
P10B100.cfg Metrolog P Pressure (10 Bar) and Flow (100 l/Pulse) Recording
P10BEDIT.cfg Metrolog P Pressure (10 Bar) and Flow (Edit cum/Pulse) Recording
PEDIT.cfg Metrolog P Flow (Edit cum/Pulse) Flow Recording Only

Metrolog P Flow MPEDIT.cfg Metrolog ‘P’ Flow (EDIT cum/pulse) Recording ONLY
only
MPX1.cfg Metrolog ‘P’ Flow (1 l/Pulse) Recording ONLY
MPX10.cfg Metrolog ‘P’ Flow (10 l/Pulse) Recording ONLY
MPX100.cfg Metrolog ‘P’ Flow (100 l/Pulse) Recording ONLY

Metrolog NA P NAP2A.cfg Metrolog NA Pressure (200.0m) Recording Only


200m
NAP21A.cfg Metrolog NA Pressure (200.0m) and Flow (1 l/pulse) Recording
NAP210A.cfg Metrolog NA Pressure (200.0m) and Flow (10 l/pulse) Recording
NAP2100A.cfg Metrolog NA Pressure (200.0m) and Flow (100 l/pulse) Recording
NAP2EDTA.cfg Metrolog NA Pressure (200.0m) and Flow (EDIT l/pulse) Recording

Metrolog NA P NAP1.cfg Metrolog NA Pressure (100.0m) Recording Only


100m
NAP11.cfg Metrolog NA Pressure (100.0m) and Flow (1 l/pulse) Recording
NAP110.cfg Metrolog NA Pressure (100.0m) and Flow (10 l/pulse) Recording
NAP1100.cfg Metrolog NA Pressure (100.0m) and Flow (100 l/pulse) Recording
NAP1EDTA.cfg Metrolog NA Pressure (100.0m) and Flow (EDIT l/pulse) Recording

Metrolog TA M420TA_1.cfg Metrolog 4-20mA TA Single Channel


M420TA_2.cfg Metrolog 4-20mA TA Two Channel
MET-420P.cfg Metrolog 4-20mA TA Depth Measurement
MET-420F.cfg Metrolog 4-20mA TA Flow Measurement
M420TABH.cfg Metrolog 4-20mA TA Single Channel - Below Datum (Borehole Use)

UM109000 Issue 1
Page 41 of 43
Metrolog Data Logger
Installation and Operation Manual

Metrolog Quick Reference Guide PC


SET DEFAULTS

1. Run GPS program

2. Select Local or Remote Comms

Local No action

Remote Newlog and Database

3. Comms Ports Defaults - Comms

Local - usually Com 1, Modem Disabled.


Remote - Modem: Com 1 or Com 2

4. Config File Directory Defaults - Files

5. Save Settings Defaults - Keep

6. Baud Rate Newlog - Defaults - Comms


Set 9600

SET UP LOGGER
1. Connect logger to PC

2. Comms Check Newlog - Status - State

Remote Comms: Local


If logging, stop logging : Newlog - Start/Stop

3. Notepad Newlog -Setup - Notepad

4. Clock Newlog - Setup - Clock

5. Channel Rate and Timebase Newlog -Setup - Rate

6. Mode and Time Resolution Newlog - Start/Stop

7. Zero Pressure Transducer Newlog - Status - Input

Vent pressure port, zero reading. F1 to zero reading

8. Input Check Newlog - Status - Input

START LOGGER

1. Start Logging Newlog - Start/Stop - Clr+Start

2. Function Check Newlog - Status - State

3. Disconnect Metrolog and Clear Site

UM109000 Issue 1
Page 42 of 43
Metrolog Data Logger
Installation and Operation Manual

Metrolog Quick Reference Guide PSION


SET DEFAULTS

1. Datapak and Rampak

Datapak - slot closest to display: drive B

Rampak -slot furthest from display: drive C

2. Set Drive for Config Files

Rampak fitted: drive C:

No Rampak fitted: drive A:


3. Baud Rate Defaults - Comms
set 9600

Assumed the Data Logger is configured correctly. If no configuration procedure should be carried out prior to No 3. (Refer to Section 5)
SET UP LOGGER

1. Connect logger to Psion

2. Comms Check Status - State


If logging, stop logging Start/Stop

3. Notepad Setup - Notepad

4. Clock Setup - Clock


5. Channel Rate and Timebase Setup - Rate - Timebase

Setup - Rate - Channel

6. Mode and Time Resolution Start/Stop - Store Mode

Start/Stop - Time Res

7. Zero Pressure Transducer Status - Input

Vent pressure port, zero reading. SHIFT and Y to zero reading

8. Input Check Status - Input


SPACE to change channels

START LOGGER

1. Start Logging Start/Stop - Clr+Start


2. Function Check Status - State

3. Disconnect Metrolog and Clear Site

UM109000 Issue 1
Page 43 of 43

Das könnte Ihnen auch gefallen