BMS WORKS for TVS

TUNNEL BUILDING INTREGRATED MANAGEMENT SYSTEM WORKS FOR ROAD TUNNEL


Qty. For Tunnel ,Control
S.No. Description Unit Building & Cross Total Qty. Rate Amount
passage

TUNNEL BUILDING INTREGRATED MANAGEMENT SYSTEM ( IBMS , FAS ,LHD & CCTV ) INR Foreign Currency INR Foreign Currency

1.00 Tunnel Building IntregratedControl System (TBICS ) Redundant Servers


19' Rack mount redundant BMS SCADA Server at Server Room
• Both Main and Redundant server should have following minimum hardware/software provision to achieve technical and functional requirement of BMS SCADA at station
level for controlling and monitoring function. No. 2

SCADA Server shall be provided with minimum following requirement:


• Processor - 3.2 GHZ Intel Xeon 64 Bit Processor (Latest series available) with heat sinks
• RAM size – DDR3/DDR4 based 4X16GB & upgradable up to 8X16 GB.
• GB dedicated graphics card.
• Hard disk- Total storage of 3TB each, with RAID-1 or suitable hard disk controller.
• Visual Display Unit- 19-inch rack integrated LED or equivalent.
• Video Card- Standard Graphics controller.
• Multimedia with accessory- Not required.
• DVD R/W- Dual Drives: 16x DVD-ROM Drive + 16 x DVD+/-RW double layer write capability.
• EMI immunity- As per IEC 801.
• Network Interface Card- Standard 10/100/1000 Base-T Ethernet Ports (6Nos).
• (Built in dual gigabit port, Ethernet GB Lan Card)
1.1 • USB ports- 3.0 USB (4 Nos)
• Server Management software- Complete with the server management software & Tool for server diagnostics and troubleshooting, including other drivers for the server.
• Accessories- Accessories Including all cables/ connectors/ Keyboard/ accessories to achieve the complete working of the system.
• Power Supply-Fully Redundant Power Supply & Fan Unit
• Operating System- Microsoft Window server 2012 R2 or latest windows server
• External Hard Disc- Not Required
• Tape Drive - Not Required
• Flash USB Drive- Not Required

Communication control, Graphical user interface (GUI), Alarm management, Historian, Energy management system, Report Generator, Word processing etc..
Operating system fully supporting the hardware, True multi-tasking providing concurrent execution of multiple real-time program, software shall fit together with the software in
the Local controller system, support multiple operator stations with adequate storage capacity to cater for 100% increase in Local controllers, monitored technical equipment’s,
HMI equipment’s etc. without upgrading hardware.
All hardware driver as required for smooth operation, Windows 2007 or latest 64bit OS preloaded operating system with Latest antivirus application including updated security
pack and minimum 3-year licence on antivirus updation. Auto recovery and auto archive software, Software for Data base management, Communication control, Graphical user
interface (GUI) Alarm management, Historian, Energy management system, Report Generator.

2.00 Tunnel Building Intregrated Control System (TBICS ) Colour Monitor


Colour monitor shall be minimum 24 inch diagonal antiglare, antistatic flat LED screen, high resolution of 1280x1024 and 16 Million colour support, on screen control support,
2.1 No. 1
Vertical & Horizonal viewing angle 160O, Tilt Swivel Support as per specifications etc. as required.
3.0 Tunnel Building IntregratedControl System (TBICS ) BMS PRINTERs

The printers shall be suitable for trend log, summary, totalizer logging, recording alarams and providing system reports. A hard copy multi-color graphics laser printer for
recording graphic displays and associated dynamic data having Print speed - Black: up to 20 ppm; colour: up to 4 ppm, First page out - 18 seconds black, 29 seconds color,
Resolution - 600 by 600 dpi, Memory - 64 MB built-in SDRAM; expandable to 192 MB with one open memory SDRAM DIMM slot, Duty cycle - 30,000 pages per month, Media,
3.01 Types Paper (plain, letterhead, bond, color, rough, preprinted, recyled), Glossy Media, Cover Paper, Color LasterJet Transparencies, labels, envelopes, and card stock, Nos. 1
Compatability - Interfaces Hi-Speed USB 2.0, IEEE 1284-B complaint parallel port, Languages - PCL 6 and Postscript level 3 emulation with automatic language switching, Font
capacibilties - 80 True Type TM internal scalable PCL 6 fonts; 80 True internal as per specification etc as required.

4.00 Tunnel Building IntregratedControl System (TBICS ) LAN/NETWORK INTERFACES


Providing, Installing, Testing & Commissioning of industrial Ethernet Switches having the following specifications to meet the functional and system requirement in a redundant
system architecture
• Ethernet 10/100/1000 MBPS Switch
4.01 • Network Protocol - IEEE 802 Set 1
• Fibre port as applicable in ref to interface requirement
Minimum 8 Port with spare consideration or as suitable to meet functional requirement With IP routing and port management function capabilities.

5.00 Tunnel Building IntregratedControl System (TBICS ) SOFTWARE


5.01 SCADA Software for HMI, Event & Alarm, PLC Logic Develolpment and Debugging etc as per specification . Set 1
6.0 Tunnel Building IntregratedControl System (TBICS ) PLC/RIO EQUIPMENT with Housing Panel

These items shall be full compensation for all works required for the supply, installation, testing & commissioning of Remote Input Output (RIO Module)/ Remote PLCs should
have (Digital Input, Digital Output, Analog Input and Analog Output Modules integrated to remote CPU interface module along with other required interface or system
module for integration of field signals; should capable of standalone monitoring and control function irrespective to master PLC interface; should fully equipped with
redundant Power Supply module, device protection and interface terminals and wiring and other devices as required to meet tender specification & functional requirement.

The contractor shall cross reference the RIO Panel and others to Housing Type as required. A by-pass switch/s shall be provided to completely by-pass the PLC in the event of a
total failure of the PLC and associates equipment to enable the normal operation of the equipment controlled by the RIO. Panels shall be fitted with a suitable pocket to contain
circuit diagrams and other relevant Definitive Design Drawings. An "as installed" set shall be having. All wiring and equipment tagging as per most acceptable international
standards and road tunnel practice.

CPU with on-board RS485port for profibus/mpi/Modbus communication. Data and program backup without external battery. CPU shall have scan time of not less than 0.1ms per
1k bit instruction and 5ms per 1k floating point instructions.

6.1 • Micro-Memory Card Power Supply Module with AC/DC converter as required. Set 1
• Al Module of 8 Channel as per Signal list with necessary spare I/O consideration. (Minimum one Module per panel)
• DI Module of 16 / 32 Channel as per Signal list with necessary spare I/O consideration. (Minimum 3 Modules per panel)
• DO Module of 8 / 16 Channel as per Signal list with necessary spare I/O consideration. (Minimum 2 Modules per panel)
• AO Module of 8 Channel as per Signal list with necessary spare I/O consideration. (Minimum 1 Modules per panel)

• BMS Workstation / Server system interface provision in PLC communication Port (Ethernet TCP/IP Rj45 connector)
• Mounting Rail and other cable containment for PLC/RIO panel different component mounting and Cable wiring.
• PLC/RIO Required firmware, protocol and data point licence as required to meet the interface and programming requirement in ref to tender specification with provision of
spare (i.e. spare of 50% of Total IO Point as future expansion requirement without any upgradation)
• Dual Ethernet Module TCP/IP 10/100 MBPS MODBUS/PROFIBUS/BACNET card as required
• Terminal block 8 slots (as required for field cable interface and termination)
• 16 channels Relay Board (all with manual overrides) PCB Mounted type, plug in relays. (As per DO module)
• Allowance for Spare I/O Points Modules and expansion shall be possible by adding more I/O modules and software pre-configuration Assorted connectors, pre-formed
connecting cables, special terminal blocks, bus cables, taps, tap links, networking accessories consisting of patch Panels, Cat 5 patch cords etc.
• Touch Screen LCD type Local control Panel Directly mounted on the PLC Housing itself, with Screen Guard protection.

7.00 Transducer and Actuators


7.01 Voltage Transducer
7.02 Current Transducer
7.03 KWH Transducer
7.04 Pressure Transmitter

8.0 NOTEBOOK PC

Colour note book PC / Laptop with built-in modem for remote dialling-in for use as a portable programming and operational (POT) tool to develop, debug, and monitor ladder
logic programs and to monitor local data tables and network, Communication or protocol testing/debug tool with high quality colour LED and minimum resolution of 1280X1024
pixels and contrast ratio 700:1 which supports 256 colours, Intel Pentium i5 or higher and be complete with min standard 4GB RAM, 4 Nos. USB Port, 1 Nos. RS 232 Serial Port,
1 TB hard disk capacity with high speed disk access, high speed DVD-R/RW, and with 82-key keyboard (101 keyboard compatible), Removable storage device ( CD / DVD - Re - Nos. 1
Write), Optical USB mouse etc as per specification.
8.1

Window’s Window 7 64bit OS or latest with standard MS Office package and updated security pack loaded in system with valid licence. Pre-Loaded Software’s with valid user
licence and updated with latest patches for PLC and SCADA GUI Programming or configuration, Logic configuration, Network Diagnosis, Communication/protocol testing and as
specified in the tender specification. Latest antivirus version with upgraded security pack with minimum 3-year licence validity during SAT testing time.

9.0 Additional Panels


TOUCH SCREEN INTREGRATED BACKUP PANEL (IBP)
9.1 For Manual activation of the Tunnel & building operation mode from the Control Room complete with all Mimic diagrams on Mosaic Tiles, LED's, ,Selector switches, cable
ducting, control wiring, fixing accessories, LV Power isolation, indicator lamps, fuses, circuit breakers, terminal rail, terminals, marker ferrules and all other accessories as may be set 1
called for under the specifications.
10.0 WIRING CONTAINMENT SYSTEMS

The class of protection against corrosion shall be as scheduled in the specifications. Class 4 shall be hot dipped galvanised. The minimum size of conduit shall be 20 mm. To
satisfy requirements for each fault loop impedance, the layout of conduit, trunking and ducting and routing of cables shall ensure that the maximum circuit lengths allowable
are not exceeded. Bending of conduit shall be done, without the use of heat, using a bending tool that complies with the British Standard appropriate to the conduit material.
Draw-in boxes shall be provided in conduit at the following maximum intervals:
a) Straight run 8 m, b) Run with one or two bends 6 m, c) Run with three bends 4 m, d) Run with four bends 2.5 m, No conduit shall be under mechanical stress. At expansion
and settlement joints suitable provision shall be made in conduit to allow for movement of the structure., Temporary plugs shall be fitted to open ends of conduit and ducting to
prevent ingress of water and solid material.

CABLE TRAY
Supply, fabrication & installation of perforated GI cable tray from 2mm thick GI sheets continuously connected including horizontal and vertical bends, reducers, tees, suspenders
and other accessories and duly suspended from the ceiling with GI suspensions.
10.01 300 mm wide x 75 mm deep L.S(RMT) 1500
10.02 150 mm wide x 50 mm deep L.S(RMT) 1000
10.03 100 mm wide x 50 mm deep L.S(RMT) 8000
CONTROL CABLE WIRING
600/1000V grade armoured Fire Survival cables tested to BS-6387 for circuit integrity under fire, ZH Copper (Cu) conductor STP cable screened control cables on existing
trays/walls/columns/indoor/trenches including the cost of supports with suitable clamps, hooks, bolts etc and including the cost of proper dressing of cable.

10.04 2Cx1.5sq.mm L.S(RMT) 2000


10.05 4Cx1.5sq.mm L.S(RMT) 1500
10.06 12Cx1.5sq.mm L.S(RMT) 1000

The control cable for critical/emergency/fire equipment shall be fire resistant type in accordance with the Specification. Control panel, switchboards and distribution boards
wiring shall be clearly identified in accordance with the Definitive Design Drawings using cable core markers. Cable core markers shall read left to right or top to bottom.
Wiring shall be enclosed in metal ducts or neatly loomed with nylon ties or spiral binding as required. Wiring ducts shall be filled to a maximum space factor to 50%. Where
wiring is required to connect to devices mounted on doors it shall be arranged such that opening and closing of the door is not impeded whilst minimising flexing of the wiring
loom. The loom shall be effectively fixed at both ends of the door opening with insulated saddles or clamps. Wire colours shall comply with the following requirements: Phases
Red, Yellow, Blue, Neutral Black AC Control Grey, DC Positive Orange, DC Negative Lilac, Earth Green with Yellow trace.

Terminals shall be clearly numbered, and shall be rail mounted, adequately sized to suite wiring size and provided with 20% spare rail space. The bridging of terminals shall be
provided by the use of terminal bridging links as supplied by the terminal manufacturer. Control wiring shall be terminated using pre-insulated pin or spade type crimb lugs.
Condcutors terminating to study type terminals shall be fitted with spade type crimb lugs. A separate earth bar shall be provided for the termination of all earth wires. Only one
wire shall be connected into each termination point. Minimum conductor size shall be 1.5 mm2.
10.07 LAN Cable Cat 6e or higher (LSZH) L.S(RMT) 10000
EARTHING
Copper Strips/ LSZH wire for interconnecting the equipments, panels, etc. of the following sizes in built up trenches/surface/wall/ground & alongwith cable trays etc complete
10.08 with holes and fixing, jointing/terminating accessories as per specifications. L.S(RMT) 100

1 of 11
BMS WORKS for TVS

TUNNEL BUILDING INTREGRATED MANAGEMENT SYSTEM WORKS FOR ROAD TUNNEL


Qty. For Tunnel ,Control
S.No. Description Unit Building & Cross Total Qty. Rate Amount
passage

TOTAL OF TUNNEL BUILDING INTREGRATED MANAGEMENT SYSTEM


11 FIRE ALARM AND DETECTION SYSTEM
SITC (Suply , Installation , Testing , Commisioning ) Fire Alarm Control Panel (FACP)
SITC of 32-bit Microprocessor based Intelligent Addressable, Peer-to-Peer networkable, 10-loop FACP (Fire Alarm Control Panel. FACP shall accommodate up to 2 nos. of
12V/50AH batteries in its own housing and shall have a battery charging capacity of (up to) 2 nos. of 12V/100 AH housed externally. FACP shall have 854 character display and at
11.1 least 5 custom-programmable buttons for user-specific programmable functions. Each Detection Loop of FACP shall accommodate up to 250 detectors and devices in any Nos. 1
combination. FACP shall accommodate up to 2500 detectors and devices at 100% capacity in any combination. FACP shall have a dedicated flash storage of upto 2GB built-in to
store site-related back-up of Auto-CAD As-Built Drawings, Configuration Software Back-Up, Reports, Logs etc.

Bacnet/Communication Module for 3rd Party Integration


SITC of Active Repeater Panel
11.2 SITC of Active Repeater Panel with 80-Character (2x40) display with supervised power supply from FACP. Repeater Panel shall monitor and control (Scroll, Acknowledge, Reset &
Mute) all the events of the FACP to which it is connected and it shall have Port Vectoring / Event Filtering capability of showing only ALARMS, TROUBLES or SUPERVISORY or Nos. 1
customized combinations of user selected events.
SITC of Color Graphic User Interface Work Station

SITC of PC based Color Graphic User Interface Station (Client) to provide Annunciation, Status display, Monitoring & Control of each and every element connected to Fire Alarm
11.2 System and Networks. Graphic User Interface (Client) shall be connected to the server PC via TCP/IP or, if necessary, Wireless connectivity. Client station shall provide full Nos. 2
functionality of the server in terms of monitoring and control. However it shall have a provision of customized configuration where filtering of events shall be possible. It shall
have provision for the configuration multiple password-protected operators with varying customized authority levels.

SITC of Multi Sensor (Photoelectric Optical Smoke + Heat) detector with base

SITC of Intelligent Addressable Multi-Sensor (Optical Smoke + Heat) detector with base. The optical sensor element shall have multiple selectable sensitivity levels from 0.2%
Obs/ft to 3.7% Obs/ft. The ROR detection element shall have selectable rate of rise setting of 8°C per minute & 11°C per minute (or close to this value not deviating more than
11.3 1°C). Fixed temp detection element shall have two selectable settings of 57°C and 68°C (or closer to this value not deviating by 1°C). Multis-sensor detector shall have a
configuration mode that gives separate alarms for smoke detection and heat detection and shall indicate the cause of alarm (smoke or heat). Also the multi-sensor shall have Nos. 55
combined configuration mode of smoke and heat detection that gives only one evaluated alarm from a multi-sensor detector in case of a fire event. The detector shall have
operating temperature range from -9°C to 50°C and humidity tolerance range up to 95% RH, Non-Condensing.

SITC of CO2 detector with base


SITC of Intelligent Addressable Optical CO detector with base. The optical sensor element shall have multiple selectable sensitivity levels from 0.2% Obs/ft to 3.7% Obs/ft. The
11.4 Next Generation CO Sensing Technology with Advanced electrochemical carbon monoxide sensing technology , Uses existing wiring , Automatic device mapping, Sensor Nos. 100
Markings Provide Easy Testing Identification , Up To 250 Total Signature Adresses Per Loop , Non-volatile memory , Electronic addressing , Automatic day/night sensitivity
adjustment , Bicolor (green/red) status LED , Standard, relay, fault isolator, and audible mounting bases .
SITC of Indoor Application Manual Call Points

11.7 SITC of Intelligent Addressable Double Action Indoor Application Manual Pull Stations / Manual Call Points suitable for wall/column mounting. MCP shall have red coloured
housing with molded, raised-letter operating instructions of contrast colour. The MCP shall latch mechanically upon operation and shall remain so until manually reset with its key Nos. 128
by an authorized operator. The MCP shall have operating temperature range from 0°C to 50°C and humidity tolerance range up to 93% RH, Non-Condensing.

SITC of Addressable Notification Appliances - Hooter with Strobe

SITC of Addressable Notification Devices (Hooter with Strobe). Hooter with Strobe unit shall sit directly on addressable NAC (Notification Appliance Circuit) of FACP, fully
supervised and powered from FACP. Hooter and Strobe elements of the combined unit shall have independent activation & deactivation criteria. Hooter shall stop at alarm
"Acknowledge" and the Strobe shall stop at panel "Reset". The Hooter and Strobe element of Hooter cum Strobe combined unit shall be selected and triggered independently
11.8 from FACP for performance check and maintenanace. Hooter with Strobe unit shall have provision to be tested by a hand-held field diagnostic tool in "Silent Mode" and "Full Nos. 128
Operation Sound Mode". The Strobe shall have multiple selectable candela settings configured and selected from the FACP. The hooter cum Strobe unit shall deliver ouput up to
94 db at 3m from its installed location. The sounder/strobe unit shall display the voltage received by them at the control panel. The activation & deactivation requirement of
Notification devices shall not be deviated. Suppliers not having single notification device meeting these requirements shall quote for Hooter cum Strobe with supervised control
module separately, powered by FACP NAC. No external 3rd party power supply shall be permitted.

SITC of Monitor Module


11.9 SITC of Intelligent Addressable, Supervised Monitor Module monitoring Potential-free, Normally Open Dry Contact input. The Monitor Module shall have operating temperature
Nos. 128
range from 0°C to 70°C and a humidity tolerance of up to 93% RH, Non-Condensing.
SITC of Control Modules
11.10 SITC of Intelligent Addressable Potential-free, Form-C, SPDT contact based control module to trigger 3rd party utilities like AHU shut-off, Pressurization fan activation, Special
notification activation etc. The contact shall be rated for 2A@24Vdc (Resistive) & 1A@24Vdc (Inductive). The control module shall have operating temperature range from 0°C to Nos. 128
49°C and a humidity tolerance of up to 93% RH, Non-Condensing.
SITC of Short Circuit Isolator
11.11 SITC of Intelligent Addressable, Supervised Short-Circuit Isolator. The Isolator Monitor Module shall have operating temperature range from 0°C to 49°C and a humidity tolerance
of up to 90% RH, Non-Condensing. Nos. 128
SITC of Addressable Fire Detection and Control MINIPLEX Transponders

> Transponder operation is available as standard or with local mode operation


> Communications with the host fire alarm control panel use the Remote Unit Interface (RUI/RUI+) format
> Initiating functions include:
• Addressable device support including TrueAlarm analog sensor compatibility
• Conventional initiating device circuit (IDC) support
> Notification functions include:
• Addressable strobe and horn notification using enhanced power delivery IDNAC SLCs
• Emergency voice/alarm communications
11.12 • Conventional DC notification appliance circuits (NACs)
> Local mode operation provides: Nos. 80
• Default local initiating and notification operation in the event of a communications loss with the host control panel
• Enabling of an optional Local Mode Controller with a local alarm sounder, LED status indicators, and key switch enabled control switches
• Support for IDNet addressable devices, addressable and conventional notification appliances, and default output tones from local amplifiers
> Optional modules include:
• Digital or Analog audio riser modules for connection to system audio signals
• Digital or analog input audio amplifiers with integral on-board NACs
• Power supplies with or without battery chargers
• City Connect modules and RS-232 ports for printers or maintenance terminals
• Alarm relays, auxiliary relays, additional IDC modules, and NAC expansion modules

Cables
11.13
SITC of 2-Core, Copper Conductor, Multi-Strand, PVC insulated, Armoured, UTP (Unshielded Twisted Pair), FRLS Cable. Mtr. 18000

2 of 11
BMS WORKS for TVS

TUNNEL BUILDING INTREGRATED MANAGEMENT SYSTEM WORKS FOR ROAD TUNNEL


Qty. For Tunnel ,Control
S.No. Description Unit Building & Cross Total Qty. Rate Amount
passage
TOTAL OF FIRE ALARM AND DETECTION SYSTEM
12 LINEAR HEAT DETECTION SYSTEM ( TUNNEL)
Supply, Installation, Testing and Commissioning of LHD Fire detection system shall provide fast and spatially well-resolved fire detection along optical fibres with ranges up
to 10km per channel.
• Shall have Selectable alarm and pre-alarm criteria. Shall have Small sampling interval – down to 0.25 m.
• Shall Have Signal processing have based on OFDR-Technology. (Optical Frequency Domain Reflectometry).
• shall have 1000 free programmable Zones. Shall have 1, 2 with channels with 1, 2, 4, 6, or 10 km sensor cable per channel and 2 channels with 1, 2, 4 or 6 km sensor cable
per channel.
• Shall be Suitable for wind speeds of up to 10 m/s Shall have 48 (optional up to 106) Programmable outputs (potential-free)
• Shall have 4 (optional up to 40) Programmable inputs
• Shall have Communication interfaces LON, TCP/IP, Modbus,
• RS232, USB. Shall have Operating temperature -10 to +60 °C
12.1 • Shall suitable for Mains voltage (AC Controller) AC 100 … 240 V. Set 1
• Shall Include UPS/Battery backup for 1 Hour Normal Operation and 30 Mins
• Alarm condition. shall be suitable for Humidity (non-condensing) ≤95 % rel.
• Shalll have Protection class (IEC 60529) IP51
• Shall be Laser product class 1M according DIN EN 60825-1
• Shall be UL and VdS approved

LHD Software
12.2 - for Windows XP, Vista or 7 Set 1
Color Graphic User Interface Work Station for LHD

SITC of PC based Color Graphic User Interface Station (Client) to provide Annunciation, Status display, Monitoring & Control of each and every element connected to Fire Alarm
12.3 System and Networks. Graphic User Interface (Client) shall be connected to the server PC via TCP/IP or, if necessary, Wireless connectivity. Client station shall provide full Nos. 2
functionality of the server in terms of monitoring and control. However it shall have a provision of customized configuration where filtering of events shall be possible. It shall
have provision for the configuration multiple password-protected operators with varying customized authority levels.

Supply, Installation, Testing & Commissioning of Splice Box for Metal Free Sensor Cable (4-Channel). shall Provide four entries for sensor cables and one entry for up to four
12.4 pigtail cables. Shall be made of halogen free Polycarbonate. Protection grade of the box shall be IP65. Shall have operating temperature range from -40°C to 80°C. Compliant to Nos
RoHS, Box: UL94-V2
Supply, Installation, Testing & Commissioning of Termination Box for Metal Free Fibre Optic Linear Heat Detection Sensor Cable for Installation at the end of the sensor cable
for low reflective termination of the end of the optical fibre.
12.5 Shall have Peak of backscattered end reflection of < 0.1dB Protection grade of the box shall be IP65. Shall have operating temperature range from -40°C to 80°C. Compliant to Nos
RoHS, Box: UL94-V2

Supply, Installation, Testing & Commissioning of Metal free black color Fibre Optic Linear Heat Detection sensing cable having Graded index of 62,5/125μm.Having Outer
12.6 diameter of 2.0 mm, Loose tube filled with Hydrophobic gel as fibre protection, longitudinal watertight. Nos

TOTAL OF LINEAR HEAT DETECTION SYSTEM


13 CCTV SYSTEM
DOME CAMERA- Supply of 5 Megapixel CMOS Vandal-proof Network Dome Camera, Shutter speed, Image sensor 1/3" Progressive Scan CMOS, Min. illumination 0.01Lux @ (F1.2,
AGC ON), 0 Lux with IR 0.014 Lux @ (F1.4, AGC ON), 0 Lux with IR. Shutter speed 1/3 s to 1/100,000s, Lens 2.8-12 mm. Angle view: 104°. Day Night IR cut fitter with auto switch.
3D DNR, 120 dB WDR, Video Compression H.265/H.264/MJPEG. Video Bit Rate: 32Kbps-8Mbps.Max Resolution 2944*1656. Image Setting Rotate mode, Saturation, ocus,
Brightness, Contrast adjustment by client software or web browser. ROI support. Network storage: Local storage: Built-in Micro SD/SDHC/SDXC card slot up to 128 GB.NAS.
Support two way communication, Triple stream with digital I/O. (Support NFS, SMB/CIFS). Protocol TCP/IP, ICMP, HTTP, FTP, DHCP, DNS, DDNS, RTP, RTSP, RTCP, PPPoE, UPnP,
13.1 SMTP, IGMP.ONVIF (certified by ONVIF site), PSIA, CGI, ISAPI, Communication interface: 1RJ45 10M/100M Ethernet interface. IR range: 30 Mtr., Ingress Protection Level IP-67 No. 12
with IK10 (with Certificate). Power supply: 12 V DC, PoE (802.3af). Support tripe wire, intrusion detection, Unattended Baggage & Face detection. Certification UL, EN (61000,
55022, 60950), RoHS, WEEE and CAN ICES-3(B) and need to attached with technical bid.

PTZ CAMERA - Supply of 5 Megapixel CMOS Vandal-proof Network PTZ Camera, Shutter speed, Image sensor 1/3" Progressive Scan CMOS, Min. illumination 0.01Lux @ (F1.2,
AGC ON), 0 Lux with IR 0.014 Lux @ (F1.4, AGC ON), 0 Lux with IR. Shutter speed 1/3 s to 1/100,000 s 50m IR, Lens 2.8-12 mm. Angle view: 104°. Day Night IR cut fitter with auto
switch.3D
13.2 DNR, 120 dB WDR, Video Compression H.265/H.264/MJPEG. Video Bit Rate: 32Kbps- 8Mbps.Max Resolution 2944*1656. Image Setting Rotate mode, Saturation, focus, No. 536
Brightness, Contrast adjustment by client software or web browser. ROI support. Network storage: Local storage: Built-in Micro SD/SDHC/SDXC card slot up to 128 GB. NAS.

SERVER - Support two way communication, Triple stream with digital I/O. (Support NFS, SMB/CIFS) Protocol TCP/IP, ICMP, HTTP, FTP, DHCP, DNS, DDNS, RTP, RTSP, RTCP, PPPoE,
UPnP, SMTP, IGMP. ONVIF (certified by ONVIF site), PSIA, CGI, ISAPI, Communication interface: 1RJ45 10M/100M Ethernet interface.IR range: 30 Mtr., Ingress Protection Level IP-
67 with IK10 (with Certificate). Power supply: 12 V DC, PoE (802.3af). Support tripe wire, intrusion detection, Unattended Baggage & Face detection. Certification UL, EN (61000,
55022, 60950), RoHS, WEEE and CAN ICES-3(B).Supply of 64 channel Network Video Recorder Linux based & shall support up to 96 TB HDD with ANR technology, HDD hot swap,
output HDMI1, HDMI2, shall support 1 e-SATA interfaces, with Hot swappable facility with 1E-SATA for Video back up, support RAID 0,1,5,10, shall be 19" rack mountable. No. 01
10M/100M/1000M network interfaces (2 LAN Ports), support N+1 redundancy third party ONVIF cameras supportable. with analytics, Support tripe wire, intrusion detection,
camera tampering, abounded baggage, H. Unattended Baggage & Face detection. Video Recorder shall be UL 60950-1 certified, CE Certified, FCC Certified.

13.3 Supply of 6 TB surveillance HDD to be assembled in NVR. No. 01


Supply of 8 Port Unmanaged POE Switch 8x10/100/1000 Mbps PoE ports, each port support 802.3af/802.3 at self adaption, 1x10/100 Mbps uplink port,123watts PoE, 250 mtr.
13.4 transmission, 4 kV surge protection, plug and play installation. No. 1
13.5 Supply of 55" LED professional display monitor 24 x 7 operations. No. 2
Supply and laying of CAT6 4 pair LAN cable with solid annealed bare electrolytic grade copper conductor and overall FR PVC jacketing shielded twisted pair (STP) in existing
13.6 channel / conduit, etc. as required. Make: D-link / Digisol. Mtr. 1
13.7 Supply of 3C x 1.5 sq.mm, 1.1 kV grade, PVC power copper cable. Mtr. 1
13.8 Supply Desktop PC (Core I.5. 16GB RAM, 2 TB HDD, DVD RW, loaded with original windows, antivirus with Live view software for parallel monitoring. No. 2
13.9 LIVE view Software for parallel monitoring 10 users. No. 2
TOTAL OF CCTV SYSTEM

3 of 11
BMS WORKS for TVS

TUNNEL BUILDING INTREGRATED MANAGEMENT SYSTEM WORKS FOR ROAD TUNNEL


Qty. For Tunnel ,Control
S.No. Description Unit Building & Cross Total Qty. Rate Amount
passage

14 PUBLIC ADDRESS SYSTEM


Supply installation, Testing & Commissioning of RMS 480w Power amplifier,battery voltage 24Vdc (max. 10% deviation) Frequency response 60Hz to 15kHz (+1/-3dB) Inputs XLR &
14.1 Phone Jack, SIN >85dB, as per detailed technical specification etc as required.BOSCH or equivalent. Nos 2
14.3 Supply installation, Testing & Commissoing of speaker 6W Ceiling Speaker complete with all accessories.LBD 0606/10BOSCH or equivalent. Nos 4
Supply installation, Testing & Commissoing of wall mounted speaker 12W wooden cabinet, factory fitted Speaker complete with all accessories.BOSCH or equivalent
14.4 Nos 534
Supply installation, Testing & Commissoing of Controller Voltage VAS 230VAC, ±15%, 50/60 Hz, power consumption 600 VA, Voltage 24 VDC, +15% / -15% Output power RMS 240
W/360W, Frequency response 60 Hz to 18 kHz (+1/-3 dB at -10 dB ref rated output), Connector XLR, 6.3 mm jack, Sensitivity 1 mV (mic), 1 V (line), 255 messages, format WAV-file,
14.5 16-bit PCM, mono, Memory capacity 16 MB Flash ROM, as per detailed technical specification as required.BOSCH or equivalent. Nos 2

Supply installation, Testing & Commissoing of Keypad station Voltage 18 to 24 VDC or VAC external power supply, Current consumption <30 mA (plus <15 mA per keypad) Input
14.6 sound level (max) 110 dB, SPL Frequency response 100 Hz to 16 kHz, Speech filter -3dB at 315 Hz, high-pass, 6 dB/oct, Output impedance 200 ohm, expandable upto 8 units, as Nos 2
per detailed technical specification as required BOSCH or equivalent.
Supply installation, Testing & Commissoing of Rated power 12w, Volume Control Attenuation step 5x3db+off, Frequency response 50Hz to 20kHz (-1 dB) as per detailed technical
14.7 specification as required BOSCH LBC or equivalent. Nos 2

Supply installation, Testing & Commissoing of musical instrument named with Plena easy line SD tuner bgm source suitable for MP3 stored on SD card and USB memory stick
14.8 with FM tunner, FM tunner with RDS, presets and digital control,seprate output for digital source and FM tunner, Power 115-230 VAC, 50/60 Hz, FM Range 87.5 to 108 MHz, Nos 2
Maximum storage capacity 32 GB, track 2000, Frequency response 50 Hz to 20kHz, as per detailed technical specification as required.
Supply installation, Testing & Commissoing of MS Equipment Rack to place the Amplifiers, Player, and motioned all the above devises, having regulated power supply strip for all
14.9 the devices, door lock and key, openable from front and rear, and required devises as per detailed technical specification as required. Nos 2
Supply installation, Testing & Commissoing of Protocol Integration Connectors with suitable shielded copper conductor cables as per detailed technical specification etc as per
14.11 required. Nos 4

Cable/Wire
Supply & Laying of 2x1.5 sqmm unsheathed twin parallel PVC insulated FRLS Copper conductor, 1.1KV Grade along with all materials and wiring with soldered
14.11 terminals on either ends in existing PVC conduits. Mtr. 18000

TOTAL OF PUBLIC ADDRESSABLE SYSTEM

15 DIGITAL EPABX SYSTEM (TELECOM & RADIO COMMUNICATION SERVER)


15.1 EPABX
Supply Installation, Testing and Commissioning of Server Based EPABX Fully Computerized IP System, SIP Compliant. Multi slot 10: U Rack Mountable 2U Rack Expandable upto
200 Ports Presently Configuration as Below
• CO Line 16 Nos.
• PRI (30 Channel) 1 Nos.
• Digital Extension Circuits 10 Nos. Nos 2
• Analog Extension Circuits 150 Nos.
• 64 SIP VOIP Trunk 1 Nos.
• Integrated Voicemail System 1 Nos.

Supply Installation, Testing and Commissioning of 4 Level IVR software with 6 different languages and 4 time schedule with Supply Installation, Testing and Commissioning of PC .
15.2 Nos 2

15.3 Supply Installation, Testing and Commissioning of Digital Phone (32Key).Ip Telephones , Control centre desks Nos 60
15.4 Supply Installation, Testing and Commissioning of Digital Phone (12Key).IP Emergency Telephone System @ 200 mtrs Nos 84
15.5 Supply Installation, Testing and Commissioning of Cordless Phone with base dilling minimum 80-100 meters range. For technical staff in tunnel Nos 10
15.6 Supply Installation, Testing and Commissioning of Analog Speaker Phone with backlight and 4 memorable Key. Nos 4
TOTAL OF DIGITAL EPABX SYSTEM (TELECOM & RADIO COMMUNICATION SERVER)

TRAFFIC MANAGEMENT AND SIGNAGES


16 VMS at Portal near entrance detection system Nos. 2
16.01 Pictorial Tunnel Advisory Display Board in side tunnel @ 1000 mtrs & @ 500 mtrs Nos. 64
16.02 VMS at in side tunnel Nos.
16.03 Variable Speed Limit Sign Nos. 256
16.04 Entrance Variable sign with Red cross and Green Arrow Nos.
16.05 Traffic Lights Three Colored - Red, Green, Amber Nos. 128
16.06 Amber Flashing Warning Light with both side lights for Emergency Telephone System Nos.
16.07 SITC of Luminous Traffic Sign for marking of Emergency Telephone System Nos.
16.08 SITC of Traffic Sign "Fire Fighting Niche" or SOS Or Emergency Comm. Nos.
16.09 SITC of Luminous Traffic Sign for marking of escape exits to cross passage entrance Nos.
16.10 SITC of Luminous Traffic Sign for marking of escape direction between escape exits Nos.
16.11 SITC of Luminous Traffic Sign for marking direction & distance to exit (other Tunnel) Nos.
16.13 SITC of Outside entrance road gantry for VMS -bridge type Nos.
16.14 Height Detection System Nos.
16.15 SITC of Rigid Height Barrier Nos.
16.16 SITC of Traffic Sign "Overtaking Prohibition" TYPE-A Nos.
16.17 SITC of Traffic Sign "Switch Vehicle Lights On !" TYPE-B Nos.
16.18 SITC of Traffic Sign "Switch Vehicle Lights Off !" TYPE-C Nos.
16.19 SITC of Traffic Sign "Limits Cancelled !" TYPE-D Nos.
16.20 SITC of Information Plate with tunnel length and name Nos.
16.21 SITC of Information traffic sign - with transmitted broadcasting station frequency and name Nos.
16.22 Pole Lot
TCMS Client workstation - SITC of PC based Color Graphic User Interface Station (Client) to provide Annunciation, Status display, Monitoring & Control of each and every element
connected to Fire Alarm System and Networks. Graphic User Interface (Client) shall be connected to the server PC via TCP/IP or, if necessary, Wireless connectivity. Client station
shall provide full functionality of the server in terms of monitoring and control. However it shall have a provision of customized configuration where filtering of events shall be
16.23 possible. It shall have provision for the configuration multiple password-protected operators with varying customized authority levels. Nos. 2

TOTAL OF TRAFFIC MANAGEMENT AND SIGNAGES

17 VENTILLATION SENSOR
17.1 CO, NO (NOx) & Temp monitor for tunnels, including connection cables, no control unit Nos. 32
17.2 Air velocity / direction monitor for tunnels, 2 analogue outputs, no control unit Nos. 32
17.3 Meteorological Detector Nos. 32
Tunnel Craft 3 USB-RS 485 comms. Box-Common for TunnelCraft 3 Air flow monitors and Air quality monitors
17.4 Nos. 32

17.5 Lux sensor Nos. 32


TOTAL OF VENTILLATION SENSOR

18 BOOM-BARRIER
Supplying, installation, testing and commissioning of boom-barrier for outdoor application, with 3.25 upto 6mt. straight Boom, extruded, made of aluminium alloy, opening and
closing time 1.5 upto 6s, 50 Hz, 230V AC, 100% duty cycle, MTBF: 2 million operations, IP 44, UL listed and complete with loop detector, contol pillar and all accessories as per the
18.1 specification. Boom barrier shall function in integeration with proximity card based access control system as per the specification. Nos. 2

Supplying, installation, testing and commissioning of access control for boom barrier complete in all respect as per the specification. The access control system shall consist of
18.3 TCP/IP based single door network controller cum reader with 13.56 RF data transmission,RS-232 port, 32 bit 100 bit RISC processor, installed in aluminium front plate of control Nos. 2
pillar as per the specifications.
Cable and conduit
Supplying and laying of 4 pair Category 6 UTP cable in existing surface/recess steel/PVC conduit or underground GI conduit.The cable shall consist of 23 AWG solid bare copper
18.4 conductor, polyolefin insulation and with end termination as per the specification and required hardware with end connectors to devices. The cable should have flexible jacket Mtr. 400
and ripcord for easy stripability .
18.5 Supplying and drawing of 6 core single mode optical fiber in existing underground HDPE pipe. The work including all accessories for end termination to devices. Mtr. 400
TOTAL OF BOOM-BARRIER

19 VIDEO WALL (FOR CONTROL BUILDING CONFERENCE ROOM)


Display Solution
19.1 Supply & receiving of 60" LED TV Each 2
Supply & receiving of Wall mount kit for above mentioned
19.2 Display. Each 2
Audio Solution
19.3 Supply & receiving of CEILING SPEAKER Each 2
19.4 Supply & receiving of WALL SPEAKER Each 2
19.5 Supply & receiving of AMPLIFIER Each 2
SWITCHING
19.6 Supply & receiving of VGA Switcher. Each 2
19.7 Supply & receiving of HDMI Switcher. Each 2
Supply & receiving of HDMI, COMPONENT & COMPUTER
19.8 GRAFICS VIDEO TO HDMI PRO Each 2
Supply & receiving of Cable CUBBY having 1 VGA, 1 HDMI, 2 PowerPoint, 1 LAN, 1
19.9 EP Ports. Mtr. 500
TOTAL OF VIDEO WALL (FOR CONTROL BUILDING CONFERENCE ROOM)

VHF LEAKY FEEDER CABLE


A 75 ohm leaky feeder or radiating coaxial cable approved by MSHA (Mine Safety and Health Administration) with a Low Smoke Zero Halogen (LSZH) jacket with frequency
20 support to 450 MHz. Typically this cable is used in 150 MHz VHF radio wireless systems in tunnels. Mtr. 18000
TOTAL OF VHF LEAKY FEEDER CABLE

TOTAL OF TBICS

4 of 11
Maintenance
C
Footway
Cross
Each Side Each Side Passages
Sl.No Area Emergency
Kms Mtrs @ 200 Fixed Box
mtrs Manual Call
Camera
Button

1 TUNNEL 1 8 8000 40 160 40

1 TUNNEL 2 8 8000 40 160 40

5 North portal control room 500

6 South portal control room 500

Total 17000 80 320 80


Cross Passage
Ip Telephones - Digital
Addressable VENTILLATION Phone (12Key) , Control
Door Fire Detection Manual SENSOR @ centre desks at every
Magnetic 500 mtrs cross passage sub -
Position and Control Glass
Holders station
Sensor MINIPLEX Break Unit
Transponders

40 40 40 160 16

40 40 40 160 16

30

30

80 80 80 320 60
IP IP
Variable Message Variable Speed Pictorial
Manual Glass Break Unit Emergency Emergency
Signs (VMS) Limit Signs Advisory
Telephone System @ Telephone Telephone
1 No. on each (VSLS) every Signs 1 @
125 mtrs System @ System @
tunnel portal 250m 1000 mtrs
Entry & Exit 200 mtrs

64 2 40 1 128 32

64 2 40 1 128 32

128 4 80 2 256 64
Pictorial PTZ at ANPR at
Traffic lights three CCTV Video Public Address
Advisory Portal Portal Traffic data
colored @ 500mtrs Incident Detection System @ 30
Signs 1 @ Entry & Entry & Loops
distance @ 60Mtrs mtrs
500 mtrs Exit Exit

144 64 268 267 2 4 4

144 64 268 267 2 4 4

288 128 536 534 12 8 8


Driver Height Detection Boom Air Flow & Redundant
CO/NO/So Wind
awareness at Barrier at Portal Barriers at each quality NAS for Video
x/Visibility Direction
Portal Entry Entry lane entry/Exit monitors 1 Years

4 1 4 16 16 16

4 1 4 16 16 16

8 2 8 32 32 32 2
Fire Detection Access Control
Public Address CCTV System PLC with
System in Control System Control
FDA LHD System Control Control Room@ distributed
Room@ 500 Room@ 500
Room@ 500 Sqmtr 500 Sqmtr redudancy
Sqmtr Sqmtr

1 167 167 10 20 2

1 167 167 10 20 2

2 2 334 334 20 40 4
RIO Video Wall Server WS Remarks

12

12

1 2 7

1 2 7

24 2 4 14