Sie sind auf Seite 1von 1

TABLE 100.

14
Insulation Resistance Conversion Factors (20° C)
Table 100.14.1
Test Temperatures to 20° C
Temperature Multiplier
Apparatus Containing
Apparatus Containing Solid Insulation
°C °F
Immersed Oil Insulation Other Than Rotating
Machinery
-10 14 0.125 0.25
-5 23 0.180 0.32
0 32 0.25 0.40
5 41 0.36 0.50
10 50 0.50 0.63
15 59 0.75 0.81
20 68 1.00 1.00
25 77 1.40 1.25
30 86 1.98 1.58
35 95 2.80 2.00
40 104 3.95 2.50
45 113 5.60 3.15
50 122 7.85 3.98
55 131 11.20 5.00
60 140 15.85 6.30
65 149 22.40 7.90
70 158 31.75 10.00
75 167 44.70 12.60
80 176 63.50 15.80
85 185 89.789 20.00
90 194 127.00 25.20
95 203 180.00 31.60
100 212 254.00 40.00
105 221 359.15 50.40
110 230 509.00 63.20

Derived from Stitch in Time…The Complete Guide to Electrical Insulation Testing, Megger.
Formula: Example: Resistance test on oil-immersion insulation at 104° F
Rc = Ra x K Ra = 2 megohms @ 104° F
Where: Rc is resistance corrected to 20° C K = 3.95
Ra is measured resistance at test Rc = Ra x K
temperature Rc = 2.0 x 3.95
K is applicable multiplier Rc = 7.90 megohms @ 20° C

Page 222