Beruflich Dokumente
Kultur Dokumente
3B 73/06
INSTRUCTION MANUAL
®
®
H Series
E
N
G
Contents L
I
GENERAL SAFETY INFORMATION ............................... 2 S
RECEIVING, STORING, MOVING, UNPACKING H
1.0 DESCRIPTION ........................................................... 3
2.0 INSTALLATION ......................................................... 4
2.1 Location .............................................................. 4
2.2 Position in the compressed air system ............... 4
2.3 Mounting ............................................................. 4
2.4 Piping .................................................................. 4
2.5 Electrical ............................................................. 4
2.6 Air-Cooled Models .............................................. 5 E
2.7 Compressor tiedown nuts - S
7 1/2 and 10 horsepower units only .................... 5 P
A
3.0 OPERATION ............................................................... 6 REFRIGERATED
3.1 Start-up and Shut down Procedures ................... 6
Ñ
3.2 Operational Sequence ........................................ 8 O
3.3 Fault Conditions .................................................. 10 L
3.4 Lights and Gauges .............................................. 10 TYPE
3.5 Operational Check Points ................................... 10
1. PRESSURIZED DEVICES:
2. ELECTRICAL:
A. RECEIVING
This shipment has been thoroughly checked, packed and inspected before leaving our plant.
It was received in good condition by the carrier and was so acknowledged.
Upon receipt:
B. STORING/SHUT DOWN
Dryer should not be stored outside (either crated or uncrated) or exposed to the weather. Damage
to electrical and control components may result.
C. MOVING
Dryer is shipped on wooden pads to accommodate a fork lift truck. Move the dryer with a fork lift or rollers so as
to support it by the bottom of the frame or lift using lifting rings on frame.
Never lift dryer by attaching hooks or slings to the air inlet and outlet connections or to any part
within the dryer frame except lifting holes. Severe structural damage could result.
D. UNPACKING
Packaging material should be left in place until unit is in position.
Care should be taken during unpacking so that sharp objects do not come in contact with refrig-
eration lines, condenser tubing, etc., as a refrigeration leak could result.
2
1.0 DESCRIPTION B. Operation
Compressed air, saturated with water vapor, enters
A. Function the dryer and is precooled by the outgoinq refriger-
Refrigerated type compressed air dryers reduce the ated air in an air-to-air heat exchanger. Precooling
moisture content in compressed air by lowering the removes some of the heat load from the incoming
air temperature causing water vapor to condense air allowing the use of a more efficient refrigeration
into a liquid. The liquid is then separated from the air condensing section. The precooled air then enters
stream and discharged to drain. As long as the an air-to-refrigerant heat exchanger (refrigeration
temperature of the compressed air, as it travels evaporator) where it is cooled to a preset level by
through a plant’s air system, does not fall below the giving up heat to the refrigeration system. As the air
temperature to which it was chilled in the dryer cools, water vapor condenses into liquid droplets
(referred to as dewpoint temperature), no more which are separated out of the air stream by a
water vapor will condense into troublesome liquid. In separator. Liquid condensate is discharged to drain
addition, the air is filtered of all solid particles three by three automatic condensate drains.
microns and larger. Clean, dry compressed air leaving The cold air then exits after it has passed through
the other side of the air-to-air heat exchanger E
the dryer minimizes maintenance and repair of N
pneumatic distribution, instrument and control, and where it is warmed by the incoming hot air. This
reheating increases the air's effective volume G
actuation devices, reduces product contamination,
and increases productivity. (enabling it to do more work) and prevents pipe L
sweating downstream. I
S
FLOW SCHEMATIC H
6 5
5
13 4
F 14
E F D
3 COOLING
E WATER (OUT)
B C 7
2
A
H 15 16 COOLING
WATER (IN)
F 12
E
14 11 10
G 8
9 1
CRANKCASE HEATER
3
2.0 Installation B. Holes are provided in the dryer base to permanently
2.1 Location mount it to a level solid floor. Ensure the dryer is level
by grouting, if necessary. The structural steel base is of
A. A moderately heated, well ventilated area is the best an open design to facilitate cleaning and washing
location for the installation of the dryer. under the unit.
2.2 Position in the compressed air system C. Water-Cooled Models - Water Supply and Drain Lines
Connect cooling water inlet and outlet. Unit is
This type of dryer is normally located downstream of the supplied with water strainer and water regulating
compressor receiver tank and before the main plant air valve. See Technical Data Section for cooling water
distribution line(s). A three valve bypass should always be requirements.
installed to permit the continued use of the plant com- NOTE: It is preferable to install inlet and outlet water
pressed air system during any dryer maintenance or pressure and temperature gauges in water system.
servicing operations. No prefilter upstream of the dryer is
required unless an excessive amount of scale and/or oil is 2.5 Electrical
present in the compressed air system.
If a disconnect switch is utilized, only time
2.3 Mounting delay, dual-element fuses (Fusetron, or equal) should be
used.
A. At the permanent dryer location, remove the dryer
from its shipping pads. The dryer is designed to run continuously
and must not be wired to cycle on and off with the air
compressor. Dryer compressor can be placed in Standby
Mode during shutdown periods.
4
Air-Cooled Models with
Integral Condenser
(Optional)
Air Inlet
Cooling Water
Air Outlet Cooling Water
Inlet
Outlet
Control Panel
Condensate
Electrical
Drain
Enclosure
Connection E
N
SIDE VIEW G
L
FRONT VIEW I
A. Electrical entry is through electrical connection entry 2. After condenser is in place, run refrigeration lines S
hole in electrical enclosure. If optional disconnect between dryer and condenser; cut off brazed ends of H
supplied use entry hole in disconnect enclosure. refrigeration lines and braze new lines to cut off ends
B. Connect power to proper terminals. using appropriate couplings.
C. Recommended branch circuit and unit fuse protection Interconnecting refrigerant lines must
can be found in the Technical Data Section. be adequately sized and designed to ensure proper oil
return, including traps, check valves, and separators
D. Be sure that voltage to unit is as marked on unit where necessary.
nameplate and on condensing unit baseplate.
3. Using access ports on hot gas and liquid lines, evacu-
E. Air-Cooled models - remote condensers - wire ate lines with vacuum pump to remove air and mois-
condenser to terminals in dryer electrical enclosure ture. Add refrigerant only if necessary.
identified on electrical schematic.
2.7 Compressor shipping spacers - 7 1/2 and 10
F. Remote Alarm Connection horsepower units only
Connection for external alarm is made on the terminal
strip found in the main electrical enclosure. See The following procedure must be followed
electrical drawings supplied with the unit for connec- to prevent compressor damage.
tions. If provisions for multiple alarms are provided
(optional) see schematic. A. Remove the upper mounting nuts and shipping
spacers from the four (4) mounting studs.
NOTE: Two (2) amps is the maximum current draw
through the alarm contacts. B. Place one (1) rubber spacer on each stud, and replace
mounting nut, leaving 1/16" space between the
G. Optional Remote Standby/Run - See Electrical Wiring mounting nut and upper spacer.
Schematic on page 9.
MOUNTING STUD
isolation valves in the off position and are shipped fully MOUNTING BASE
5. Check that automatic condensate drain valve isolation Turn Stand-by/Auto Selector Switch to STAND-BY position.
valves are open. Allow dryer to operate in this mode during shutdown
period. (Master switch remains in ON position).
6. Air-Cooled models - Check that any isolation valves D. Maintenance Shut-Down Procedure
between dryer and condenser are open.
This procedure is used to shut unit down for extended
B. Start-Up Procedure - (Dryer energized; master switch maintenance periods.
OFF)
1. Turn Stand-by/Auto Selector Switch to STAND-BY
DRYER MUST BE ENERGIZED (POWER ON position. Allow unit to cycle several times.
LIGHT ILLUMINATED) TWENTY-FOUR (24) HOURS BEFORE 2. Push the Master switch to the OFF position.
START-UP OF THE REFRIGERATION COMPRESSOR.
NOTE: Except for maintenance reasons, leave dryer
1. After dryer has been energized at least twenty-four energized. This allows the crankcase heater to func-
(24) hours pull Master switch to ON position. Dryer tion.
display will indicate either STANDBY or SYSTEM EN-
ABLED on operator interface. De-energize dryer at disconnect if
working on electrical or rotating components.
6
E. Start-Up Procedure - (Master switch on; dryer in Stand- 1. Turn Stand-by/Auto selector switch to AUTO.
by mode.)
2. Allow at least 15 minutes of dryer operation before
POWER TO THE DRYER MUST BE ENER- flowing compressed air through dryer.
GIZED (POWER ON LIGHT ILLUMINATED) TWENTY-FOUR
(24) HOURS BEFORE START-UP OF THE REFRIGERATION 3. Review Operational Check Points, section 3.5.
COMPRESSOR
Master Switch
Operator
O I Interface
E
N
G
F5 F6 F7 F8
L
1 2 F1 F2 F3 F4
I
Power on
Stand-by/Auto Selector OPERATOR INTERFACE SHIFT
ESC ENTER
Light (White) S
Switch H
(momentary switch - turn
to desired operating mode 1 2
and release - verify status STANDBY AUTO
General Alarm
on Operator Interface • Modo de • Modo
Espera Automático (fault) Light
Display • Attente Standby
Mode
• Auto Mode
(Red)
Control Panel
Display Functions
F1 - Return to status display
F2 - System pressures display
F3 - System temperatures display
F4 - Electric drain - push-to-test (for use with models supplied with electric drains)
F5 - (shift + F1) - Sensor calibration; low pressure cutout setting (password required)
F6 - (shift + F2) - English or metric unit selection
F7 - (shift + F3) - Refrigerant low pressure cutout override
F8 - (shift + F4) - Electric drain - time between discharge setting; for use with models
F5 F6 F7 F8 supplied with electric drains)
F1 F2 F3 F4 1. Use Up and Down arrows to put cursor over DRAIN DELAY ad press ENTER.
OPERATOR INTERFACE SHIFT
2. Use Up and Down arrows to set time between discharges and press ENTER.
ESC ENTER
Up and Down Arrows - Use to scroll through multiple messages
Operator Interface To reset head and oil pressure faults press F1. To clear use arrow keys to place
cursor on alarm message and press ENTER.
Function
To clear all other faults from display select message with the arrow keys and press
Buttons ENTER.
Note: Do not use ESC key; if inadvertently pressed, press again to clear. 7
Operator Interface Display
Condition Display Message
Dryer energized; Master Switch Off DRYER ENERGIZED
Dryer energized; Master Switch On STANDBY or SYSTEM ENABLED
Status Stand-by Selected Dryer will pump down if suction pressure is high
(indicated by "DRYER PUMPING DOWN") followed by
"STAND-BY"
Auto Selected PREPARING TO RUN followed by
COMPRESSOR LOADING and 33%, 50%, 66%, 75%
83%, or 100%
Refrigerant (low-side) Suction SUCTION PRESSURE
Pressures Refrigerant (high-side) Head HEAD PRESSURE
Compressed air at inlet to dryer INLET AIR PRESSURE
E Optional - Differential pressure across dryer AIR PRESSURE DROP
N Temperatures Optional - Compressed air at inlet to dryer INLET AIR TEMP
G Optional - Lowest air temperature LOWEST AIR TEMP
L
Compressor Solid State Motor Protector Open SSMP-1MTR
I
Compressor Solid State Motor SSMP-2MTR
S Protector Open (2nd Compressor)*
H Motor Starter Protector Open MTR STARTER - 1MTR
Motor Starter Protector Open (2nd Compressor)* MTR STARTER - 2MTR
Low oil pressure OIL PRESSURE -1 MTR
Low oil pressure (2nd Compressor)* OIL PRESSURE - 2MTR
Low (low or suction) side refrigerant pressure LOW REFRIG PRESS
Faults High (high or head) side refrigerant pressure HIGH REFRIG PRESS
High evaporator air temperature HI EVAP AIR TEMP
Optional - Low water pressure LOW WATER PRESS
(water-cooled models)
Optional - High differential pressure CHECK SEPARATOR
Optional - Low evaporator air temperature LOW EVAP AIR TEMP
Optional - High condensate level (air-to-air drain) DRAIN 1 HIGH LEVEL
Optional - High condensate level (air-to- DRAIN 2 HIGH LEVEL
refrigerant drain
Optional - High condensate level (separator drain) DRAIN 3 HIGH LEVEL
Optional - High inlet compressed air temperature INLET AIR TEMP
* 50 HP and larger
3.2 Operating Sequence b. As low side system pressure drops to unloader set
point(s), PLC output(s) energize solenoids(s) 3SOL
1. With master switch OFF (pushed in), turn disconnect and 4SOL (35 HP and larger) which unload com-
switch "DISC" to on. Control transformer "IT", and pressor cylinder(s). As pressure rises above the
crankcase heater "HTR", are energized. Power on light unloader set point(s), compressor will load in
(white) illuminates. "DRYER ENERGIZED" is indicated on reverse sequence. Percentage following "Com-
display. Disconnect switch "DISC" must be left on pressor Loading" indicates percentage of cylinders
except for maintenance reasons. Crankcase heater loaded.
"HTR" must be energized twenty-four (24) hours prior
to start up. c. Compressor runs automatically unless a SSMP,
motor starter, low oil pressure, high head pressure,
2. Pull master switch on. Display indicates STANDBY or or low suction pressure fault occurs.
SYSTEM ENABLED.
4. To put in STANDBY turn momentary Stand-by/Auto
3. To "START" turn momentary Stand-by/Auto selector selector switch to STANDBY and release.
switch to AUTO and release.
a. Display indicates "DRYER PUMPING DOWN".
a. If STANDBY is displayed and no fault condition b. Compressor motor "MTR" continues the pump
exists, motor starter "M" coil, liquid valve solenoid down cycle until low side system pressure reaches
"1SOL", and hot gas by-pass valve solenoid "2SOL", the low pressure cutout point. At cutout point,
are energized. Display indicates "PREPARING TO the PLC de-energizes motor starter "M" coil.
RUN" followed by "DRYER RUNNING" or "COMP Display indicates STANDBY.
LOADING". If "SYSTEM ENABLED" is displayed dryer
will pumpdown prior to valves energizing. c. If low side system pressure rises to low pressure
set point, compressor starts and pumpdown
repeats automatically.
8
E
N
G
L
I
S
H
10
4.0 Maintenance b. Starting from outside (cartridges closest to vessel
4.1 Separator/Filter Sleeve Replacement wall) screw separator/filter cartridge(s) (1) into inlet
manifold connection(s). A cone in the manifold will
A. When to replace Filter Sleeves guide the cartridge bolt into the female threads. It
At rated flow conditions, when removing liquids, is only necessary to finger tighten the cartridge to
pressure drop will normally be 1 psi (0.07 bar) or less ensure the seal.
across the separator or 5 psi (0.35 bar) or less across DO NOT WRENCH TIGHTEN
the entire dryer. An increase in pressure drop will
occur only as the filter sleeve becomes loaded with c. Reinstall grooved pipe coupling or hand hole cover
solid particles. It is recommended that, for maximum after inspecting gasket to ensure its integrity.
filtration efficiency, the filter sleeves be replaced when
pressure drop across the separator exceeds 10 psi (0.7 d. Reinstall insulation cap.
bar) or total pressure drop across the dryer exceeds 15 GROOVED PIPE COUPLING
psi (1.05 bar). Grooved
Pipe Cap Gasket
B. Procedure for changing separator/filter sleeves E
NOTE: Refer to Technical Data Section for correct Coupling
N
replacement sleeve set. Half G
L
1. Bypass the unit to permit servicing. Grooved Pipe I
Depressurize the dryer assembly before on Housing
S
servicing. H
2. Remove screws and lift off insulation cap from top of
separator vessel.
3. Models with grooved pipe coupling - loosen bolts and HAND HOLE
remove coupling, gasket, and pipe cap. Bolts
Models with hand hole - loosen nut and remove yoke,
gasket, and seal plate.
9. Slide new filter sleeve (5) over separator core (6) and 3
replace cap (4) and nut (3). 4
2 6
11
4.2 Air-Cooled Refrigerant Condensers - Special 4.3 Water-Cooled Refrigerant Condenser - Special
Instructions Instructions (Cleanable shell and tube type)
A. The coil of the condensing section must be kept clean A. Water tubes should normally be mechanically cleaned
to maintain refrigeration capacity. Monthly, or as periodically to assure optimum condenser efficiency.
required, blow out condenser coil with compressed air. How often should they need cleaning depends on so
If heavily contaminated, coils can be cleaned with mild many variables that it is impossible to recommend a
detergent and water. In exceptionally dirty locations a schedule. Some will never need cleaning, others
furnace type filter can be installed in front of the perhaps need cleaning once a year. In rare cases,
condenser intake to prevent rapid fouling of coil. If a cleaning is required several times a year.
filter is used it must be changed regularly to prevent a
restriction of the cooling air flow. Frequency of cleaning will depend on individual water
conditions, so a suitable cleaning schedule should be
B. Operational Deficiencies worked out based on experience. An inspection of the
water tubes is recommended after the first six (6)
E months of operation to aid in establishing a cleaning
1. Condenser Cooling System - High head pressure can
schedule.
N be caused by insufficient cooling air flow across the
G condenser, too high an ambient air temperature or a Proper operation of cooling towers will increase the
L dirty condenser. Check to determine if condenser interval between cleaning considerably. The tower
I fan(s) are running (see fan control note below) and overflow (bleed-off) rate should be checked fre-
S that no obstructions are too near the face of the quently. Most cooling tower manufacturers recom-
H condenser. Ambient air temperature should be mend an overflow of about ten percent (10%) of the
checked at local heat sources or recirculating air might water circulated. If a tower is operated with insuffi-
raise the actual air temperature above the average cient overflow, the resulting mineral concentration in
room temperature. The condenser should be checked the water can cause rapid and heavy fouling inside the
and cleaned, if dirty. condenser tubes. This will necessitate excessively
frequent cleaning and may lead to severe corrosion.
2. Fan Control - In order to assure satisfactory operation See CLEANING INSTRUCTIONS (Section 4.3.C) for de-
of the air-cooled unit at low ambient temperatures, a tailed cleaning instructions, methods and procedures.
fan control switch has been provided to automatically
B. Operational Deficiencies
stop and start fan(s). This switch is actuated by the
unit head pressure and operates fan(s) individually to 1. High head pressures- particularly high (head) pressure
maintain a minimum head pressure. indicates (but does not always mean) a fouled con-
denser. It is advisable to double check the refrigeration
system to make sure that fouling is actually causing
the trouble.
12
h. Fully opened compressor discharge service valve: c. Algae or slime can usually be controlled by means
Check to see that it is closed two (2) complete of an intermittent or batch treatment to shock the
turns. See 3.0 Operation, Section 3.1.A.2.C "Open- organisms. Chemicals used for this treatment are
ing Refrigeration Valves" for more information. chlorine, bromine, pentachlorphenate, copper-
sulphate, or potassium permangenate. Some of
2. Low or high water temperatures at the condenser these, however, may promote corrosion if used in
outlet-The condenser is regulated by a pressure excessive quantities or if not properly controlled.
actuated water regulating valve supplied by the
factory. In normal operation, the temperature differ- d. Conductivity Galvanic Corrosion
ence between the water temperature leaving the
condenser and the refrigerant condensing tempera- Water treatment should be under-
ture [saturation temperature, from refrigerant table, taken only by those who are qualified and compe-
corresponding to discharge (head) pressure] will be tent to prescribe what is required for each indi-
between 5°F/9°C and 12°F/22°C. This normal tempera- vidual problem. Beware of secret compounds and
ture difference occurs regardless of the water tem- guarantee’s that claim (to render) obviously
perature entering the condenser. E
improbable results.
N
If a low water temperature (more than 12°F/22°C G
below the refrigerant saturated condensing tempera- NOTE: In consideration of the above, it should be
apparent to the user that the manufacturer cannot L
ture) is experienced, cleaning is indicated. Good heat
exchange is not being accomplished because of water accept responsibility for inefficient operation or I
tube fouling. corrosion of the condenser when caused by S
foreign materials or failure to use adequate water H
If a high water temperature at the outlet is experi- treatment. Again, necessary water treatment
enced, something other than a fouled condenser may should be initiated at, or before, the time of
be causing improper system operation and/or high installation since deterioration, when once started,
discharge (head) pressures. Restricted water flow, or a is extremely difficult to stop.
low water supply pressure, is indicated. A restriction
can occur with foreign matter in the condenser, but it C. Water-cooled Refrigerant Condenser Cleaning
is also likely to be somewhere in the water system.
1. The following procedures and precautions should be
3. Water Treatment observed when cleaning is undertaken. The warranty
on the condenser is void if it is damaged by improper
The long range performance of the refrigerant methods or tools.
condenser will be adversely affected by poor water
conditions. Therefore, it is recommended that an The condenser heads (end plates) are removable on all
analysis of the condenser water be made and treat- models. For reference, the “water head” is the end
ment, if required, commenced prior to operating the plate to which all condenser water piping is connected
refrigeration system. and the “return head” is the end plate on the oppo-
site end of the condenser.
Chemical additives, including those to stop algae and
related growths, should be obtained only from a 2. Chemical Cleaning - the condenser manufacturer
reputable, established supplier, and used specifically does not recommend any particular chemical prepara-
according to directions. Excessive or incorrect treat- tion. The same treatment is not applicable to all
ment of the water can cause more harm than none at installations. See MAINTENANCE WATER COOLED
all; the pump, piping and cooling tower may be REFRIGERANT CONDENSER (Section 4.3.B.3) for general
damaged as well as the condenser. information on water treatment.
a. Scale control is usually undertaken with phosphate (b) Follow directions exactly- particularly regarding
compounds. Scale is most often encountered amounts to use, and flushing or neutralizing
when the ph of the water is high or on the alkaline procedure after cleaning.
side.
3. Mechanical Cleaning
b. Corrosion is generally the result of low ph, or on
the acidic side. Among the chemicals used for a. Before disassembly of the condenser for mechani-
corrosion control are glassy phosphates, cal cleaning, the following must be performed:
chromates, and nitrates. Chromates are poisonous
and must be handled carefully. (1) Stop operation of the refrigeration system. The
refrigerant does not need to be pumped out of
If the ph of the water is maintained between six the condenser.
and eight, there will be the minimum tendency
toward scale on the high (above 8.0 ph) side and (2) Stop operation of the water circulating pump
corrosion on the low (below 6.0) side. and the cooling tower, if applicable.
13
(3) Close the condenser water shut-off valves When using a cleaning tool, keep the inside of the
adjacent to the unit. tube wet, and move the tool slowly from one end
to the other while rotating it at a moderate speed.
(4) Drain the water from the condenser. Many A hand drill brace is recommended. If an electric
models have a drain plug in the return head. drill is used, a low speed attachment on a 1/4" size
drill is preferred. Larger units are powerful enough
b. Disassembly to damage a tube if for any reason the cleaning
tool should stick. After one or two passes in each
Remove the bolts or nuts, as applicable, heads and tube, it should be flushed and inspected. Often
gaskets from both ends of the condenser. Note this is enough, although some deposits may
gasket markings, if any. Some gaskets are marked require more cleaning. In any case, stop when a
with ridges, notches or letters. If space is limited, few places begin to show a copper color in each
the tubes can be cleaned with only one end open, tube.
although it is difficult to flush out the clogged end
d. Reassembly
E passages.
N After cleaning, wipe all foreign matter from the
If a head gasket does not lift off from the tube
G tube sheets and studs. Install each gasket exactly
sheet and the head, do not try to pry it off. A
L as it was removed. Note the gasket markings, if
surface may be cut, which would cause a leak. To
any.
I free a sticking gasket, replace the head and tap it
S on the outer face with a mallet or a block of wood. Install each head exactly as it was removed.
H After a few taps, the gasket should spring free. Tighten all bolts or nuts, as applicable, evenly and
firmly.
c. Cleaning Procedures
If the gaskets seal surface or ridge is damaged, and
Gaskets need only be rinsed in running water as a replacement is not immediately available, water
rust, scale or dirt will not generally stick firmly to leaks can be stopped by removing the gasket,
the gasket material. A rag or a soft bristle brush is drying it, and applying a thin film of a non-harden-
all that should be required to remove any foreign ing gasket sealer, such as Peratex #2, around the
matter. seal surface or ridge. This film should be quite thin
(no thicker than the height of the seal ridge itself,
The inside of the heads, the outer tube sheet if applicable) and about 3/ 16 inch wide. Then
surfaces and the studs should be cleaned with reassemble.
clear water only and a rag or a soft bristle brush. A
worn paint brush is excellent. These surfaces have If a new gasket is put on later, be sure to remove
been coated with a special plastic base material, on any grit or particles that stick to the sealer film on
some models which will give years of protection the tube sheet. It is not necessary to remove all
against corrosion, unless damaged. Never use a traces of the sealer before installing a new gasket,
wire brush, or a strong caustic on these surfaces. as long as no particles that could cut into the new
gasket remain on the surface.
Condenser tubes should be flushed clear with air,
water or a piece of rag on a stick or wire. In many
cases this is all that is required. If the inside sur-
faces are smooth, even though discolored, further
cleaning is not necessary. It is useless to try to get
a bright copper surface on the inside of the tubes.
They will discolor almost immediately in service,
and the condenser has been designed with an
adequate reserve for moderate fouling on these
surfaces.
14
Cooling Water Requirements
15
4.4 Condensate Drains - Pneumatically Operated B. Disassemble and service at least once a year. NOTE:
Before starting the servicing procedure, make sure you
A. Monthly- Flush out accumulated sludge and dirt by have a repair parts kit on hand.
opening manual drain valves.
24 1. Close valve ahead of drain.
20
2. Depressurize drain by opening manual drain valve.
29
27
3. Disconnect drain lines.
DETAIL B
10 19 j. Reassemble key washer (7), piston assembly, lock
washer (11), and nut (19) to valve stem assembly.
13
Make sure “V” shape of piston seal is in the same
38 position as shown on Detail B and that the key on
14 the key washer is in the hole (37) directly opposite
drain connection on valve body.
DETAIL C
16
m. Place seal ring retainer (24) into bottom shell 4.5 Condensate drains - Electrically Operated
assembly (26) making sure that end of float arm
assembly with counterweight (20) is positioned in A. Monthly - Flush out accumulated sludge and dirt by
open area of seal ring retainer. For 506 series opening manual drain valve.
models, make sure rod on top of float assembly
fits into hole in seal ring retainer as shown in Detail
B. Periodically clean internal strainer in bottom of
C.
reservoir.
n. Before reassembling shell, make sure float mecha-
nism moves freely up and down.
o. Position new case seal ring (29) ABOVE the small lip
on the seal ring retainer.
17
TROUBLE SHOOTING GUIDE
SYMPTOM / FAULT POSSIBLE CAUSES CORRECTIVE ACTION
Compressor stopped because 1. Faulty high pressure transducer (PT200) Check pressure reading, calibrate/
of high head pressure replace. (Consult factory for calibration)
"HIGH REFRIG PRESS" 2. Refrigerant overcharge Reclaim excess refrigerant.
3. Air in refrigeration system Check for leaks and recharge unit.
Properly dispose of old refrigerant.
4. Air load on unit during start-up Take air load off unit during start-up.
5. Water-cooled units - Insufficient water flow
through condenser
(1) Water regulating valve not adjusted Adjust water regulating valve.
(2) Dirty water strainer Clean water strainer.
(3) Water lines too small Increase water main size to condenser.
(4) Discharge shutoff valve not fully open Open valve.
(5) Condenser water pump off Check and start.
E (6) Plugged or scaled condenser tubes Clean tubes.
N (7) Low water pressure differential Check. Should be a 40 psi differential.
G (8) Inlet water temperature too high Use cooler water.
6. Air-cooled units
L
a) Condenser dirty Clean condenser.
I b) Fans not operating Check for power. Check fan switch pressure
S set point. Fan motor faulty repair or replace.
H Compressor stopped because 1. Low refrigerant charge Check for leaks and repair; add refrigerant.
low suction pressure 2. Suction pressure setting incorrect Adjust hot gas by-pass valve.
"LOW REFRIG PRESS" 3. Incorrect low pressure switch setting Check technical data for proper setting.
4. Hot gas valve sticking Check and repair.
5. Faulty low-pressure transducer. (PT100) Check pressure reading, Calibrate/
replace. (Consult factory for calibration)
6. Defective CPU or component module Check/replace.
7. Refrigerant compressor not unloading Check unloader mechanism/replace.
properly (20 HP and up)
Compressor stopped because 1. Low oil charge Add oil.
2. Clogged oil suction strainer Clean.
of low oil pressure
3. Worn oil pump Replace pump assembly.
"LOW OIL PRESSURE" 4. Worn compressor bearings Replace compressor.
5. See: Cold Compressor
6. Suction line filter restricted Check for pressure drop across filter/
replace elements.
7. Air load supplied to unit during start-up. Take air load off dryer to start.
8. 7-1/2 - 15 HP units - compressor could See: SSMP 1, 2, and 3
have tripped on internal overload.
1. Low voltage Check power supply.
Compressor stopped because
2. Line imbalance Check power supply.
solid state motor protector 3. Excessive return gas temperature. Check liquid injection valve and refrigerant charge.
open 4. Defective SSMP module Check/replace.
"SSMP" 5. Defecitve motor sensor Refer to Section 3.3 of Manual. Check sensors at
room temp. Should be between 500-10,000 ohms.
Compressor stopped because 1. Low voltage Check power supply.
motor starter protector open 2. Line imbalance Check power supply.
"MTR STARTER" 3. Compressor motor drawing excess current Check motor winding resistance.
High air temperature leaving 1. Unit overload Check inlet flow, pressure and temperature
the evaporator and verify if within design conditions.
2. Insufficient cooling Check refrigeration system temperatures.
"HIGH EVAP AIR TEMP"
3. Faulty temperature switch Measure air temperature.
4. No air flow through dryer Check inlet flow
1. Power off Check main switch, fuses and wiring.
Compressor will not start
2. Master off/on switch Pull master off/on switch out.
3. Loose electrical connections or faulty wiring Check wiring and tighten connections.
4. Hot gas or liquid line solenoid valve closed Check for burned out holding coil.
5. Unit in STANDBY mode Turn switch to auto.
6. Compressor motor burned out Replace, if defective.
Compressor cycles 1. Leaking liquid line solenoid Remove obstruction or replace valve.
intermittently in standby mode 2. Leaking hot gas valve Replace valve.
3. Leaking valves in compressor Replace valve plate assembly.
Low refrigerant head pressure 1. Water-cooled units - Excessive water flow Adjust water regulating valve or, on 3" and
through condenser 4" water valve clean power head.
2. Air-cooled units-Fan switch not cycling properly. Check/replace fan switch.
3. Leaky compressor suction valve Examine valve discs & seats; replace if necessary.
4. Worn piston rings Replace if worn.
18
TROUBLE SHOOTING GUIDE
SYMPTOM / FAULT POSSIBLE CAUSES CORRECTIVE ACTION
System Noise 1. Unit foundation improperly isolated. Isolate foundation.
2. Improper support or isolation of piping. Use correct piping techniques, and
support piping with suitable hangers.
3. Slugging due to refrigerant feed back. Check expansion valve setting; check
sensor bulb for looseness and correct location.
4. Piping vibration. Support pipes as required, check piping
connections.
5. Hissing (insufficient refrigerant flow through Reclaim refrigerant, replace strainer, and recharge
expansion valve or clogged liquid line strainer). with the proper amount of refrigerant.
6. Hot gas by-pass valve chattering. The chattering noise is normal and
does not affect the operation of the unit.
Compressor will not unload 1. Unloader solenoid stuck. Repair.
2. Unloader solenoid coil defective. Replace.
3. Hot gas by-pass valve set too high or sticking. Reset or repair. E
4. Faulty low pressure transducer. Check pressure reading. Calibrate/replace. N
(Consult factory for calibration). G
Compressor will not load 1. Unloader solenoid stuck open. Reset or repair. L
2. Faulty low pressure transducer. Check pressure reading. Calibrate/replace. I
(Consult factory for calibration). S
Rapid Unloader Cycling 1. Excessive fluctuation in suction pressure. Check hot gas valve set point. H
2. System load fluctuating. Stabilize load.
3. Hot gas valve set too high. Return valve to factory set point.
Cold Compressor 1. Low suction pressure. Reset hot gas valve to factory set point.
(Cylinders and Crankcase 2. Defective or improperly set expansion valve. Reset to 3-6°F/1.7-3.3°C superheat.
Sweating 3. Defective or improperly set liquid injection Reset to 65°F/18.3°C return gas temperature
valve. at no load.
4. Suction line filter restricted. Check for pressure drop across filter/replace elements.
Compressor Flooding 1. See: Cold compressor
Low Crankcase Oil Level 1. Oil return screen clogged Clean.
2. Freon leak Repair leak.
3. See: Cold compressor
High Crankcase Tempera- 1. Desuperheating valve is out of adjustment Check operation and adjust.
ture (should be 100°F/38°C 2. Liquid line filter clogged Check/replace.
to 130°F/55°C) 3. Discharge temperature of 275°F/135°C Check unit application.
4. Compressor internal valves worn or Replace.
damaged
5. Defective liquid injection valve. Replace.
6. Compressor not unloading properly. (20 HP Unloader mechanism. Check/replace.
and up)
7. Refrigeration system leak Leak check/repair and recharge system.
High inlet air temperature to 1. Unit overload Check inlet air temperature, must be below
unit "HI INLET AIR TEMP" 120°F/49°C.
(optional) 2. Defective Temperature sensor. (TT1) Check/Replace.
Low air temperature in 1. Low suction pressure Reset hot gas valve to factory setting.
evaporator "LOW EVAP AIR 2. Incorrect superheat setting on TXV Rest to 3-6°F/1.7-3.3°C superheat.
TEMP" (optional) 3. Defective temperature sensor. (TT2) Check/Replace.
High condensate level in 1. Incorrect setting on drain valve. Increase drain open time or decrease time
drains "DRAIN # HI LEVEL" between opening.
(optional) 2. Drain valve not operating properly. Repair or replace.
3. Float switch defective Check/Replace.
Low water pressure enter- 1. See "HIGH REFRIG PRESS"
ing condenser (water- water-cooled units
cooled units) "LOW WATER
PRESS" (optional)
High pressure drop across 1. Dirty separator element cartridges Replace separator cartridges. See section
dryer air side 4.0 in Manual.
"CHECK SEPARATOR" 2. Unit overload Check inlet flow, pressure, and temperature and
(optional) verify if within design conditions.
3. Inlet and/or outlet pressure transducers Replace and/or calibrate. For calibration
(PT1 and PT2) defective/out of calibration. consult factory.
4. Defective CPU or component module. Check/Replace.
19
WARRANTY
The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and
maintained in accordance with procedures and recommendations outlined in manufacturer’s instruction
manuals, to be free from defects in material or workmanship for a period of one (1) year from the date of
shipment to the buyer by the manufacturer or manufacturer’s authorized distributor, or eighteen months
from the date of shipment from the factory, whichever occurs first, provided such defect is discovered and
brought to the manufacturer’s attention within the aforesaid warranty period. The manufacturer will repair or
replace any product or part determined to be defective by the manufacturer within the warranty period,
provided such defect occurred in normal service and not as a result of misuse, abuse, neglect or accident.
The warranty covers parts and labor for the warranty period. Repair or replacement shall be made at the
factory or the installation site, at the sole option of the manufacturer. Any service performed on the product
by anyone other than the manufacturer must first be authorized by the manufacturer. Normal maintenance
items requiring routine replacement are not warranted. Unauthorized service voids the warranty and any
E resulting charge or subsequent claim will not be paid. Products repaired or replaced under warranty shall be
N warranted for the unexpired portion of the warranty applying to the original product. The foregoing is the
G exclusive remedy of any buyer of the manufacturer’s product. The maximum damages liability of the manufac-
L turer is the original purchase price of the product or part.
I
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, OR
S STATUTORY, AND IS EXPRESSED IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED
H WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR
DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN,
MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY
LATENT DEFECTS INHERENT THEREIN. THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE
LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR
DAMAGES INCURRED BY THE BUYER, WHETHER ARISING FROM BREACH OF WARRANTY, NEGLIGENCE OR STRICT
LIABILITY IN TORT.
The manufacturer does not warrant any product, part, material, component, or accessory
manufactured by others and sold or supplied in connection with the sale of manufacturer’s products.
01/01/93
20
7610.719.3B 73/06
MANUAL DE INSTRUCCIONES
®
Serie H
Contenido
2. EQUIPO ELECTRICO
3. AIRE RESPIRABLE
• El aire tratado por este equipo no es adecuado para respiración sin filtración especial posterior.
• Refiérase al estándar OSHA 190.134 para determinar los requerimientos del aire con calidad respirable.
A. RECEPCION
Este embarque ha sido ampliamente verificado, empacado e inspeccionado antes de abandonar nuestra planta.
Fué recibido en buenas condiciones por el transportista y así fué manifestado.
E Al recibir el equipo:
S
1. Verifique cualquier daño o pérdida visible.
P
Si el embarque muestra evidencia de pérdida o daño al momento de recibirlo, insista que se anote en el recibo
A de entrega del agente transportista.
Ñ 2. Verifique cualquier daño o pérdida oculta.
O Cuando el embarque se ha entregado aparentemente en buenas condiciones, pero se detecta algún daño
L después de desempacar la mercancía, notifique al transportista inmediatamente e insista en que su agente
inspeccione el embarque. El tiempo máximo para requerir tal inspección es de quince días después de
recibir la mercancía. Reportar los daños al transportista es responsabilidad del consignatario.
B. ALMACENAJE/APAGADO
El secador no debe ser almacenado en el exterior (con o sin huacal) y no debe ser expuesto
a malas condiciones ambientales, ya que se puede ocasionar algún daño a los componentes
eléctricos o de control.
C. TRANSPORTE
El secador se embarca en una tarima que se ajusta a las tenazas de un montacargas. Transporte el secador con un
montacargas o sobre rodillos de tal forma que siempre se soporte de la base metálica o cárguelo utilizando las orejas
provistas para ello.
No utilice cadenas o correas para levantar el equipo de la tubería de entrada o de salida o de alguna otra
parte del marco metálico del secador. Utilice los orificios provistos para ello. No observar ésta advertencia puede
ocasionar daños estructurales severos.
D. DESEMPACADO
El material de empaque debe dejarse en su lugar hasta que el equipo esté en su posición de operación.
Se debe de tener cuidado al desempacar el equipo para que ningún objeto afilado entre en contacto con
las líneas de refrigerante, tubos del condensador, etc., ya que se puede ocasionar alguna fuga.
2 SP
1.0 Descripción del Equipo B. Operación
El aire comprimido, saturado con vapor de agua, entra
A. Función al secador donde es preenfriado por el aire frío que
Los secadores de aire comprimido tipo refrigerativo sale del intercambiador térmico aire/refrigerante. El
reducen el contenido de humedad en el aire preenfriamiento remueve algo de la carga térmica del
comprimido bajando la temperatura del aire y así aire de entrada, permitiendo usar un condensador de
logrando que se condense el vapor de agua. refrigeración más eficiente. El aire preenfriado entra
Posteriormente el líquido se separa de la corriente de al intercambiador de calor aire/refrigerante
aire y se descarga a través de una trampa. Mientras no (evaporador de refrigeración) donde se enfría a una
baje la temperatura del aire comprimido que viaja por temperatura preajustada, entregando parte de su
todo el sistema neumático a una temperatura menor a energía térmica al sistema de refrigeración. Mientras el
la que fué enfriado en el secador (referida como punto aire se enfría, el vapor de agua se condensa y forma
de rocío), no existirá ninguna formación de gotas que pueden ser facilmente eliminadas de la
condensados. Adicionalmente, el aire se filtra para corriente de aire por el separador. Los condensados
eliminar todas las partículas de tres micrones y líquidos se descargan del sistema por tres trampas
mayores. El aire comprimido limpio y seco que sale del automáticas de condensados.
secador minimiza el mantenimiento y reparación del Después de que el aire frío pasa a través del otro lado
equipo de distribución, control e instrumentación del intercambiador de calor aire-aire, donde se calienta
neumática, dispositivos actuadores, reduce la por el aire de entrada, sale del secador listo para ser
contaminación del producto e incrementa la usado en el sistema. Este recalentamiento aumenta el
productividad de la planta. volumen efectivo del aire (permitiéndole realizar un
mayor trabajo) y previene que se formen condensados
en la parte externa de la tubería neumática de la
planta.
DIAGRAMA DE FLUJO
6 5
5
13 4 E
F 14 S
P
E F D A
3 AGUA DE
Ñ
E ENFRIAMIENTO (SALIDA)
B C 7 O
2
A L
H 15 16 AGUA DE
ENFRIAMIENTO (ENTRADA)
F 12
E
14 11 10
G 8
9 1
CALENTADOR DEL CARTER
Entrada de
Aire
Entrada de Agua
Salida de Agua
Salida de de Enfriamiento
de Enfriamiento
Aire
Panel de
Control
Conexión de los
Gabinete
Drenes de
Eléctrico
Condensados
VISTA LATERAL
VISTA FRONTAL
A. La conexión eléctrica deberá hacerse a través de la 2. Una vez que el condensador se encuentre en su lugar,
perforación provista en la caja de control principal. Si el instale la tubería entre el condensador y el secador; corte
equipo cuenta con protección opcional, utilice la las puntas de las tuberías de refrigeración selladas y solde
perforación de la caja de protección. la tubería utilizando las conexiones adecuadas.
Luz de Unidad
Selector de Modo F5 F6 F7 F8
Energizada
Espera/Auto (Interruptor 1 2 F1 F2 F3 F4
(blanca)
momentáneo-Gírelo a la OPERATOR INTERFACE SHIFT
ESC ENTER
E
S
P
A
Ñ
O
L
Panel de Control
Display Funciones
F1 - Regreso al display de estado
F2 - Display de presiones del sistema
F3 - Display de temperaturas del sistema
F4 - Drenes eléctricos - presione-para-prueba (para usarse con modelos
que cuenten con drenes eléctricos)
F5 - (shift + F1) - Calibración de sensores; ajuste del interruptor de
baja presión (Se requiere contraseña)
F6 - (shift + F2) - Selección de unidades métricas o sistema Inglés
F7 - (shift + F3) - Supresión del interruptor por baja presión de refrigerante
F5 F6 F7 F8
F1 F2 F3 F4 F8 - (shift + F4) - Drenes Eléctricos - Ajuste del tiempo entre descargas para usarse en
modelos que cuenten con drenes eléctricos)
OPERATOR INTERFACE SHIFT
ESC ENTER 1. Utilice las flechas Arriba y Abajo para colocar el cursor sobre el mensaje
retrazo del dren "DRAIN DELAY" y presione aceptar "ENTER".
2. Utilice las flechas Arriba y Abajo para ajustar el tiempo entre descargas y presione
Interfase del Operador
aceptar "ENTER".
Flechas Arriba y Abajo - Se usan para ver los distintos mensajes
Botones de
Para restablecer las alarmas de presión de alta y de aceite presione F1. Para borrar
Función
utilice las flechas para colocar el cursor en el mensaje de alarma y presione aceptar
"ENTER".
Para borrar todas las otras alarmas, utilice las flechas para seleccionar el mensaje
de alarma y presione aceptar "ENTER".
7 SP
Nota: No utilice el botón ESC; Si se presiona inadvertidamente, presiónelo otra vez.
Display de Interfase del Operador
Condición Mensaje del Display
Secador energizado; Interruptor Principal Apagado (OFF) DRYER ENERGIZED (Secador Energizado)
Secador energizado; Interruptor Principal Encendido (ON) STAND BY o SYSTEM ENABLED (espera o sistema
habilitado)
Estado Seleccionado Modo de Espera (Stand-by) El secador automáticamente comenzará el ciclo de
paro si la presión de succión está alta (indica "DRYER
PUMPING DOWN") seguido de "STAND-BY" (Espera)
Seleccionado Modo Automático (Auto) PREPARING TO RUN (Preparando para operación)
seguido de COMPRESSOR LOADING (Carga del compresor) y 33%, 50%, 66%, 75% 83%, o 100%
Succión de Refrigerante (lado de baja) SUCTION PRESSURE (Presión de succión)
Presiones Refrigerante Lado de Alta (Cabeza) HEAD PRESSURE (Presión lado de alta)
Aire comprimido a la entrada del secador INLET AIR PRESSURE (Presión de aire de entrada)
Opcional - Presión diferencial en el secador AIR PRESSURE DROP (Caída de presión del aire)
Temperaturas Opcional - Aire comprimido a la entrada del secador INLET AIR TEMP (Temperatura de entrada del aire)
Opcional - Temperatura menor del aire LOWEST AIR TEMP (Temperatura menor del aire)
Protector de estado sólido del compresor abierto SSMP-1MTR
Protector de estado sólido del compresor abierto SSMP-2MTR
(segundo compresor)*
Protector del arrancador del motor Abierto MTR STARTER - 1MTR
Protector del arrancador del motor Abierto (2° compres.)* MTR STARTER - 2MTR
Baja presión de aceite OIL PRESSURE -1 MTR
Baja presión de aceite (segundo compresor)* OIL PRESSURE - 2MTR
Baja presión de refrigerante (lado de baja o succión) LOW REFRIG PRESS
Fallas Alta presión de refrigerante (lado de alta o cabeza) HIGH REFRIG PRESS
Alta temperatura del aire en el evaporador HI EVAP AIR TEMP
Opcional - Baja presión de agua (modelos enfriados por LOW WATER PRESS
E agua)
S Opcional - Alta presión diferencial CHECK SEPARATOR (Verifique el separador)
P Opcional - Baja temperatura del aire en el evaporador LOW EVAP AIR TEMP
A Opcional - Alto nivel de condensados en el dren aire-aire DRAIN 1 HIGH LEVEL
Ñ Opcional - Alto nivel de condensados en el dren aire- DRAIN 2 HIGH LEVEL
O refrigerante
Opc. - Alto nivel de condensados en dren del separador DRAIN 3 HIGH LEVEL
L
Opcional - Alta temperatura del aire de entrada INLET AIR TEMP
* 50 HP y mayores
3.2 Secuencia de Operación de que se energicen las válvulas.
b. Al bajar la presión del lado de baja presión hasta
1. Con el interruptor principal presionado, en la posición de alcanzar el punto de ajuste de(l) (los) descargador(es),
apagado (off), posicione el interruptor «DISC» en la la(s) salida(s) del PLC energizará(n) la(s) solenoide(s)
posición de encendido (ON). Se energizan el 3SOL (y 4SOL en los modelos 35HP y mayores) que
transformador de control «IT» y el calentador del carter descargarán los cilindros del compresor. Cuando
«HTR». Se enciende la luz blanca de unidad energizada. El aumenta la presión por encima del punto de ajuste, el
display indica “DRYER ENERGIZED” (Secador energizado). El compresor comenzará a comprimir en secuencia
interruptor principal «DISC» deberá permanecer inversa. El porcentaje después de carga del
encendido (ON) excepto por razones de mantenimiento. compresor "COMPRESSOR LOADING" indica el
El calentador del carter «HTR» deberá estar energizado porcentaje de cilindros comprimiendo.
por lo menos veinticuatro (24) horas antes de arrancar el c. El compresor operará automáticamente a menos que
compresor. ocurra una condición de falla en el arrancador del
2. Jale el interruptor principal a la posición de encendido. El motor SSMP, baja presión de aceite, alta presión de
display mostrará en espera "STAND BY" o sistema refrigerante, o baja presión de succión.
habilitado "SYSTEM ENABLED". 4. Para poner el secador en espera "STAND BY" gire
3. Para arrancar gire momentáneamente el selector Paro/ momentáneamente el selector Espera/Auto a la posición
Auto a la posición AUTO y suéltelo. paro y suéltelo.
a. Si se muestra en espara "STAND BY" y no existe a. El display indica secador en paro "PUMP DOWN".
condición de falla, deberán estar energizadas la b. El motor del compresor “MTR” continuará el ciclo de
bobina del arrancador del motor “M”, la bobina de la paro hasta que la presión de refrigerante del lado de
válvula de la línea de líquido “1SOL”, y la bobina de la baja alcance el punto de ajuste del interruptor por
válvula de derivación de gas caliente “2SOL”. El display baja presión. Al momento del paro, el PLC
indicará preparado para operar "PREPARING TO RUN" desenergiza la bobina del arrancador “M”. El display
seguido de secador en operación. "DRYER RUNNING" indicará en espera "STAND BY”.
o cargo del compresor "COMPRESSOR LOADING". Si se c. Si aumenta la presión del lado de baja presión hasta el
muestra sistema habilitado "SYSTEM ENABLED" el punto de ajuste del interruptor, el compresor arranca
secador entrará en ciclo de paro (Pump Down) antes automáticamente y el ciclo de paro se repite
8 SP automáticamente.
E
S
P
A
Ñ
O
L
A. El radiador del condensador debe ser limpiado A. Los tubos del agua deben ser limpiados periódicamente
periódicamente para mantener la capacidad de para asegurar la eficiencia óptima del condensador. Qué
refrigeración. Limpie el condensador con aire comprimido tan frecuente se requiere limpiarlos depende de muchas
mensualmente o tantas veces como se requiera. Si el variables, que no se recomienda establecer un programa.
condensador está extremadamente contaminado, se Algunos nunca necesitarán limpiarse, otros quizá una vez
puede limpiar con detergente neutro y agua. En al año. En casos muy raros se requiere de varias limpiezas
instalaciones excepcionalmente contaminadas, se puede al año.
instalar un filtro ambiental en la entrada del condensador
para prevenir que se obstruya rápidamente. Si se utiliza La frecuencia de las limpiezas dependerá de las
un filtro de este tipo, deberá cambiarse regularmente condiciones individuales del agua, por lo que se puede
para prevenir que exista restricción en el flujo de aire de establecer un programa de limpieza basado en la
enfriamiento. experiencia. Se recomienda una inspección de los tubos
después de los primeros seis (6) meses de operación para
B. Deficiencias en la Operación ayudar a establecer el programa.
1. Sistema de Enfriamiento del Condensador - Presiones Una operación adecuada de las torres de enfriamiento
muy altas en la cabeza pueden ser causadas por incrementará considerablemente el intervalo entre
insuficiente flujo de aire de enfriamiento en el limpiezas. El sobreflujo de la torre de enfriamiento
condensador, temperatura ambiente muy alta o un (bleed-off) deberá verificarse frecuentemente. La mayoría
condensador sucio. Verifique que los ventiladores del de los fabricantes de torres recomiendan un sobreflujo
condensador estén operando (refiérase a la nota sobre de cerca de diez por ciento (10%) del agua circulante. Si
control de ventiladores más adelante) y que no existan se opera la torre con sobreflujo insuficiente, la
obstrucciones muy cerca del condensador. Se debe concentración de minerales en el agua resultante puede
verificar que no existan fuentes de calor o corrientes de ocasionar una rápida obstrucción dentro de los tubos. Se
aire caliente que incrementen la temperatura ambiente requerirá una limpieza excesivamente frecuente y podrá
por encima de la temperatura media del cuarto. Se ocasionar una corrosión severa. Observe las
deberá revisar y limpiar el condensador si se encuentra INSTRUCCIONES DE LIMPIEZA (Sección 4.2.C) que indican
E sucio. especificamente los métodos y procedimientos de
S limpieza.
P 2. Control de ventiladores - Para asegurar la operación
satisfactoria de las unidades enfriadas por aire cuando B. Deficiencias en la Operación
A
existen bajas temperaturas ambiente, el equipo cuenta 1. Presiones muy altas en la cabeza - particularmente
Ñ indican (pero no siempre significan) un condensador
con interruptores automáticos en los ventiladores. El
O interruptor opera con la presión de cabeza (lado de alta obstruído. Es aconsejable verificar ampliamente el
L presión) de la unidad, y controla individualmente los sistema de refrigeración para asegurarse que la
ventiladores para mantener una presión mínima en el obstrucción es la causa real del problema.
12 SP
fábrica. lado de bajo pH (menos de 6.0).
h. Válvula de servicio de descarga completamente c. La formación de algas o limo puede ser controlado
abierta: verifique que después de estar por medio de tratamientos intermitentes o rutinarios
completamente abierta se cierre dos (2) vueltas para matar a los organismos. Los productos químicos
completas. Refiérase a Operación "Abrir las válvulas de utilizados en este tratamiento son el cloro, bromo,
refrigeración" para mayor información. penta-clorfenato, sulfato de cobre o permanganato
de potasio. Algunos de ellos pueden causar corrosión,
2. Temperatura del agua en la descarga muy alta o muy baja si se utilizan en cantidades excesivas o si no son
- El condensador es controlado por un regulador de flujo adecuadamente controlados.
de agua operado a presión instalado en la fábrica. d . Corrosión por conductividad galvánica
Operando normalmente, la diferencia en la temperatura
El tratamiento de agua deberá ser realizado
del agua en la descarga del condensador y la temperatura
exclusivamente por técnicos calificados y
de condensación del refrigerante [temperatura de
competentes para diagnosticar lo indicado para cada
saturación, de la tabla del refrigerante, correspondiente a
problema en particular. Tenga cuidado de
la presión (head) de descarga] es entre 9°C y 22°C (5°F y
componentes secretos y garantías que reclaman (y
12°F). Deberá existir ésta diferencia de temperatura
cumplen) oviamente resultados improbables.
independientemente de la temperatura del agua que
entra al condensador. NOTA: Considerando lo anterior, deberá estar claro
para el consumidor que el fabricante no puede
Si se detecta una baja temperatura (más de 22°C [12°F]
aceptar responsabilidades por una operación
por debajo de la temperatura de saturación del
ineficiente o por corrosión del condensador cuando
refrigerante) es necesario realizar una limpieza. No se
sean causados por materiales extraños o por no
está logrando un buen intercambio de calor debido a
utilizar el tratamiento adecuado para el agua de
posibles obstrucciones en los tubos de agua.
enfriamiento. Una vez más, el tratamiento necesario
Si se detecta una temperatura muy alta en el agua de del agua deberá iniciarse al momento de la instalación
descarga, la falla puede ser algo más que una obstrucción del equipo o antes, ya que el deterioro, una vez
en el condensador y puede ser la causa de una operación comenzado, es extremadamente dificil detenerlo.
incorrecta del sistema y/o altas presiones en la descarga
C. Limpieza del condensador enfriado por agua
(head pressure). Esta falla indica un flujo de agua
restringido o baja presión de agua. Una restricción puede 1. Se deberán observar los siguientes procedimientos y
ser ocasionada por algún material extraño en el precauciones siempre que se realice una limpieza. La E
condensador, pero también puede ser en alguna otra garantía del condensador se invalida si se daña por utilizar S
parte del sistema de agua. métodos o herramientas incorrectas. P
3. Tratamiento de agua A
Las tapas del condensador (cabezas) son removibles en
El rendimiento a largo plazo del secador se verá afectado todos los modelos. Como referencia «la tapa de agua» es
Ñ
adversamente por malas condiciones del agua. Se la placa donde se conecta la tubería de agua al O
recomienda, por lo tanto, que se realice un análisis y condensador y la «tapa de retorno» es la placa del lado L
tratamiento, si se requiere, del agua de enfriamiento del opuesto del condensador.
condensador antes de operar el sistema de refrigeración.
2. Limpieza química - El fabricante del condensador no
Los aditivos químicos, incluyendo aquellos para detener la
recomienda ninguna preparación química en particular.
formación de algas, deben obtenerse solamente de
El mismo tratamiento no es aplicable a todas las
proveedores establecidos, de buena reputación y deben
instalaciones. Refiérase a la sección 4.3.B.3
ser usados de acuerdo a sus propias indicaciones. Un
MANTENIMIENTO DEL CONDENSADOR DE REFRIGERANTE
tratamiento excesivo o incorrecto al agua, puede causar
ENFRIADO POR AGUA para obtener información general
más daño que el no realizarlo; la bomba, tuberías y torre
sobre tratamiento de agua.
de enfriamiento pueden resultar dañados tanto como el
condensador. En cualquier caso:
(a) Utilice únicamente preparaciones que provengan de
Como información general, los tres mayores problemas
una fuente confiable y establecida.
que el tratamiento de agua debe tener en cuenta son: 1)
(b) Siga las instrucciones exactamente, particularmente
formación de escamas en las superficies del condensador,
en lo referente a las cantidades a utilizar, y los
2) corrosión y 3) formación de algas o limo.
procedimientos de evacuación y neutralización
a. El control de escamas se realiza con componentes de después de realizar la limpieza.
fosfato. La formación de escamas es más frecuente
cuando el pH (acidez) del agua es alto o en el lado 3. Limpieza mecánica
alcalino. a. Antes de desarmar el condensador para realizar una
b. La corrosión es generalmente el resultado de un pH limpieza mecánica, se debe realizar lo siguiente:
bajo, o del lado ácido. Entre los productos químicos
(1) Detenga la operación del sistema de refrigeración.
utilizados para el control de corrosión se encuentran
El refrigerante no necesita ser evacuado del
los fosfatos, cromatos y nitratos pulverizados. Los
condensador.
cromatos son altamente venenosos y deben
(2) Detenga la operación de la bomba de recirculación
manejarse con precaución.
de agua y la torre de enfriamiento si es necesario.
Si se mantiene un pH en el agua entre 6 y 8, habrá
(3) Cierre las válvulas de paso de agua adyacentes a la
una tendencia mínima para la formación de escamas
unidad.
del lado de alto pH (arriba de 8.0) y de corrosión en el
(4) Drene el agua del condensador. Muchos modelos
13 SP
tienen una válvula de dren en la tapa de retorno. marcar el tubo de cobre.
b. Desarmado Cuando utilice alguna herramienta de limpieza,
mantenga húmeda la parte interior del tubo, y mueva
Remueva las tuercas o tornillos, tapas y sellos de lentamente la herramienta de un lado al otro del
ambos lados del condensador. Anote las marcas de tubo, mientras gira a una velocidad moderada. Se
los sellos, si existen. Algunos sellos están marcados recomienda utilizar un berbiquí manual. Si se utiliza
con patas, muescas o letras. Si el espacio es limitado, un taladro eléctrico, es preferible usar un taladro de
los tubos pueden ser limpiados con solamente una 1/4" con accesorio de baja velocidad. Los taladros
tapa abierta, aunque es difícil de limpiar los tubos del más grandes son lo suficientemente potentes para
lado cerrado. dañar el tubo, si por alguna razón se atora la
herramienta. Después de una o dos pasadas en cada
Si los sellos de la tapa no se separan del grupo de tubo, deberán ser enjuagados e inspeccionados.
tubos o de la cabeza, no trate de forzarlos. Se puede Frecuentemente este procedimiento es suficiente,
romper alguna superficie y ocasionará fugas. Para aunque algunos depósitos podrán requerir otra
despegar los sellos, coloque la tapa y golpee la pasada. En cualquier caso, detenga la limpieza de
superficie con un mazo o con un bloque de madera. cada tubo cuando en algunos lugares aparezca el
Después de varios golpes los sellos deberán color cobre.
despegarse.
d. Ensamble
c. Procedimientos de limpieza
Después de realizar la limpieza, elimine todos los
Los sellos requieren únicamente enjuagarse con materiales extraños de los tubos y los cabezales.
agua, ya que el óxido, escamas o suciedad
generalmente no están pegados firmemente al Instale los sellos exactamente como fueron
material del sello. Todo lo que se requiere para removidos. Verifique las marcas de los sellos, si
remover cualquier material extraño es un trapo o un existen.
cepillo de cerdas suaves.
Instale las tapas exactamente como fueron
La parte interior de las tapas, las superficies exteriores removidas. Apriete firmemente los tornillos o
del grupo de tubos deben ser limpiados con agua y tuercas.
un trapo o un cepillo de cerdas suaves. Una brocha
usada es excelente. Esas superficies han sido Si la superficie del sello está dañada, y no se dispone
E cubiertas, en algunos modelos, con un material de un sello de reemplazo, las fugas de agua se
S plástico especial que, a menos que sea dañado, pueden detener removiendo el sello, secándolo, y
P proporciona años de protección contra la corrosión. aplicando una delgada capa de algún sellador de
A Nunca utilice sobre esas superficies ningún cepillo de empaques que no se haga duro, como Permatex #2,
Ñ alambre, o componente cáustico. sobre la superficie del sello. Esta película debera ser
O delgada (no más gruesa que la altura del sello mismo)
Los tubos del condensador deben limpiarse con aire, y de 3/16" de ancho. Reensamble la unidad.
L agua, o un trapo amarrado a una barra o alambre. En
muchos casos, esto es todo lo que se requiere. Si las Cuando posteriormente se instale el nuevo sello,
superficies interiores están lisas, a pesar de estar asegúrese de remover todas las partículas que se le
manchadas, no es necesario una limpieza mayor. Es hayan adherido a la película del sellador en los tubos.
inútil tratar de obtener una superficie brillante color No es necesario remover todos los restos del sellador
cobre en la parte interna de los tubos. Perderán su antes de instalar el nuevo empaque mientras no
brillo inmediatamente después de entrar en servicio, existan partículas que puedan obstruir el sello.
y el condensador ha sido diseñado con una reserva
adecuada para trabajar correctamente aún bajo esas
situaciones.
14 SP
Requerimientos de Agua de Enfriamiento
15 SP
drenes manuales.
4.4 Trampa de Condensados - Operadas B. Desármelas y repárelas por lo menos una vez al año.
Antes de iniciar el procedimiento de servicio, asegúrese
Neumáticamente
de tener a la mano las refacciones.
A. Mensualmente - Elimine los sedimentos sólidos
1. Cierre la válvula que está antes de la trampa.
acumulados en las24trampas abriendo las válvulas de los
20
2. Despresurice la trampa abriendo la válvula de dren
manual.
29
3. Desconecte las líneas de drenado.
27
DETALLE C
16 SP
vaselina. 4.5 Drenes de Condensados - Operados
l. Ensamble el cilindro (13) al cuerpo de la válvula Electricamente
utilizando seis tornillos. Asegúrese que el orificio de
alivio (38) en el cilindro no esté obstruido. Suba y baje
A. Mensualmente - Elimine la suciedad y partículas
el ensamble de la válvula para asegurarse que
acumuladas abriendo la válvula manual del dren.
funcione libremente.
m. Coloque el retén del sello (24) dentro del ensamble B. Periodicamente limpie el cedazo interno en la parte
inferior de la trampa (26) asegurándose de colocar el inferior del deposito.
contrapeso (20) del brazo del flotador en el área libre
del retén del sello. En los modelos 506, asegúrese
que la barra superior del flotador asiente en el orificio
del retén del sello como se muestra en el Detalle C.
E
S
P
A
Ñ
O
L
17 SP
GUIA EN CASO DE FALLAS
SINTOMA CAUSAS PROBABLES ACCION CORRECTIVA
El compresor se para por 1. Transductor de alta presión defectuoso (PT200) Verifique la lectura de presión, calibre/reemplace.
alta presión de refrigerante (Consulte a planta para su calibración)
"HIGH REFRIG PRESS" 2. Sobrecarga de refrigerante Remueva el exceso de refrigerante.
3. Aire en el sistema de refrigeración Verifique que no existan fugas y recargue la
unidad. Deseche adecuadamente el refrigerante
usado.
4. Flujo de aire en la unidad al momento del arranque Elimine el flujo de aire durante el arranque
5. Unidades enfriados por agua - insuficiente flujo de
agua a través del condensador.
(1) Válvula de flujo de agua descalibrada Ajuste la válvula de flujo de agua.
(2) Cedazo de agua obstruído Limpie el cedazo.
(3) Líneas de agua muy pequeñas Incremente el diámetro de la tubería de agua.
(4) Válvula de descarga de agua parcialmente cerrada Abra la válvula completamente.
(5) Bomba de agua de enfriamiento apagada Verifique y arranque.
(6) Tubos del condensador obstruídos Limpie los tubos del condensador.
(7) Baja presión diferencial en el agua Verifique-deberá tener un diferencial de 40 psi.
(8) Alta temperatura de entrada del agua Utilice agua fría
5. Unidades enfriadas por aire
a) Condensador obstruído o sucio Limpie el condensador.
b) No funcionan los ventiladores Verifique que exista energía eléctrica. Verifique
el punto de ajuste del interruptor de presión del
ventilador. Motor del ventilador defectuoso
repare o reemplace.
El compresor no arranca 1. Baja carga de refrigerante Verifique que no existan fugas y agregue
debido a baja presión refrigerante.
de refrigerante 2. Ajuste incorrecto de la presión de succión Ajuste la válvula de gas caliente.
"LOW REFRIG PRESS" 3. Ajuste incorrecto del interruptor de baja presión Verifique la información técnica para el ajuste
adecuado
4. Válvula de gas caliente pegada Verifique y repare.
5. Transductor de baja presión fallando. (PT100) Verifique la lectura de presión, calibre/reemplace.
(Consulte a fábrica para su calibración)
6. CPU o componente del modulo defectuoso Verifique/reemplace.
7. El compresor de refrigeración no descarga Verifique el mecanismo del descargador/reemplace.
E adecuadamente (20 HP y mayores)
S
El compresor no arranca 1. Bajo nivel de aceite Agregue aceite.
P debido a baja presión de 2. Cedazo de la succión de aceite obstruído Limpie.
A aceite 3. Bomba de aceite desgastada Reemplace el ensamble de la bomba de aceite.
"OIL PRESSURE" 4. Baleros del compresor desgastados Reemplace el compresor.
Ñ 5. Vea: Compresor frío
O 6. Filtro de la línea de succión obstruido Verifique la presión diferencial en el filtro/
L reemplace los elementos.
7. Carga de aire en la unidad durante el arranque. Quite la carga de aire del secador al arranque.
8. Unidades de 7-1/2 - 15 hp – el compresor pudo Refiérase a SSMP 1, 2 y 3
haberse autoprotegido internamente.
18 SP
GUIA EN CASO DE FALLAS
SINTOMA CAUSAS PROBABLES ACCION CORRECTIVA
Baja presión en la descarga 1. Unidades enfriadas por agua - Flujo de agua excesivo Ajuste el regulador de flujo de agua o en las válvulas
a través del condensador de agua de 3" y 4" limpie la cabeza de potencia.
2. Unidades enfriadas por aire - el interruptor del Verifique/reemplace el interruptor del ventilador.
ventilador no está funcionando adecuadamente
3. Válvulas del compresor no sellan Examine los discos de las válvulas y los asientos de
4. Desgaste en los anillos del compresor válvulas. Reemplácelas si es necesario.
Reemplácelos si es necesario.
Ruidos en el sistema 1. Cimientos de la unidad incorrectamente aislados Aisle los cimientos.
2. Soporte o aislamiento incorrecto de la tubería Utilice técnicas adecuadas para conectar la
tubería y utilice soportes adecuados.
3. Tiempo de respuesta muy lento debido a Verifique el ajuste de las válvulas de expansión;
retroalimentación de refrigerante verifique que el bulbo no esté flojo y en su
posición correcta.
4. Vibración en la tubería Soporte la tubería donde se requiera y verifique
las conexiones.
5. Ruido en las válvulas (Flujo insuficiente a través de las Agregue refrigerante, reemplace el cedazo y
válvulas de expansión o cedazo del refrigerante obstruído) recargue la cantidad correcta de refrigerante.
6. Ruido en la válvula de derivación de gas caliente El ruido es normal y no afecta a la operación de
la unidad.
El compresor no descarga 1. Válvula solenoide del descargador bloqueada Repare.
correctamente 2. Bobina de la válvula solenoide del descargador defectuosa Reemplace.
3. Válvula de derivación de gas caliente ajustada a Ajuste o repare.
presión muy alta o bloqueada
4. Transductor de baja presión defectuoso. Verifique la lectura de presión, calibre/reemplace.
(Consulte a fábrica para su calibración)
El compresor no carga 1. Válvula solenoide del descargador bloqueada Repare.
2. Transductor de baja presión defectuoso. Verifique la lectura de presión, calibre/reemplace.
(Consulte a fábrica para su calibración)
Ciclo de descarga muy 1. Fluctuación excesiva de la presión de succión Verifique el ajuste de la válvula de gas caliente.
rápido 2. Fluctuación de la carga del sistema Estabilice la carga.
3. Válvula de gas caliente calibrada muy alto Regrese la válvula al ajuste de fábrica.
Compresor operando muy 1. Baja presión de succión Restablezca al ajuste de fábrica de la válvula de
frío (cilindros y el carter gas caliente E
húmedos) 2. Válvula de expansion mal ajustada o defectuosa Ajuste supercalor a 3-6°F/1.7-3.3°C o reemplace. S
3. Válvula de inyección liquida mal ajustada o defectuosa Ajuste la temperatura del gas retorno a
65°F/18.3°C sin carga. P
4. Filtro de línea de succión obstruido Verifique la caída de presión a través del filtro/ A
reemplace los elementos. Ñ
Refrigerante líquido en el 1. Vea: Compresor frío O
lado de baja del sistema L
Bajo nivel de aceite en el 1. Cedazo de retorno de aceite obstruído Limpie.
compresor 2. Fuga de refrigerante Repare la fuga.
3. Vea: Compresor frío
Alta temperatura en el 1. Válvula de inyección líquida descalibrada Verifique la operación y ajuste.
carter (normal 100°F/38°C a 2. Filtro de línea de líquido obstruído Verifique/reemplace.
105°F/41°C en el cuerpo del 3. Temperatura de descarga por encima de 275°F/135°C Verifique la operación de la unidad.
carter) 4. Válvulas internas del comprsor desgastadas o dañadas. Reemplace.
5. Válvula de inyección líquida defectuosa Reemplace.
6. El compresor no está descargando adecuadamente (20 Mecanismo del descargador. Verifique/
hp y mayores) reemplace.
7. Fuga en el sistema de refrigeración Verifique las fugas/repare y recargue el sistema.
Alta temperatura de entrada del 1. Unidad sobrecargada Verifique la temperatura del aire de entrada,
aire a la unidad “HI INLET deberá se menor de 120°F/49°C.
TEMP” (opcional) 2. Sensor de temperatura defectuoso. (TT1) Verifique/Reemplace.
Baja temperatura del aire 1. Baja presión de succión Restablezca el ajuste de fábrica de la válvula de
en el evaporador “LOW gas caliente.
EVAP AIR TEMP” (opcional) 2. Ajuste incorrecto del supercalor en la TXV Restablezca el supercalor a 3-6°F/1.7-3.3°C.
3. Sensor de temperatura defectuoso. (TT2) Verifique/Reemplace.
Alto nivel de condensador 1. Ajuste incorrecto en la válvula del dren. Incremente el tiempo de apertura del dren o
en los drenes “HI LEVEL disminuya el tiempo entre aperturas.
DRAIN #” (opcional) 2. Válvula del dren no opera adecuadamente. Repare o reemplace.
3. Interruptor del flotador defectuoso Verifique/Reemplace.
Baja presión de agua entrando 1. Refiérase a: Alta Presión del Refrigerante "HIGH
al condensador (unidades REFRIG PRESS" Unidades enfriadas por agua
enfriadas por agua) “LOW
WATER PRESS” (opcional)
Alta presión diferencial a 1. Elementos del cartucho del separador sucios Reemplace los cartuchos del separador. Refiérase
través del lado del aire del a la sección 4.0 del manual de instrucciones.
secador "CHECK SEPARA- 2. Sobrecarga de la unidad Verifique que el flujo, presión y temperatura de entrada
TOR” (opcional) se encuentren dentro de los parámetros de diseño.
3. Transductores de presión de entrada y/o salida (PT1 y Reemplace y/o calibre. Para su calibración,
PT2) defectuosos o fuera de calibración. consulte a fábrica.
4. CPU o componente del módulo defectuoso Verifique/reemplace
19 SP
GARANTIA
El fabricante garantiza que su producto, cuando éste fué instalado adecuadamente, operado, aplicado y mantenido
de acuerdo a los procedimientos y recomendaciones indicadas en el manual de instrucciones del fabricante, está libre
de defectos en los materiales o en la mano de obra por un período de un (1) año a partir de la fecha de embarque del
fabricante o del distribuidor autorizado al comprador, o dieciocho meses a partir de la fecha de embarque de la
fábrica, lo que ocurra primero, siempre y cuando se descubra y se avise al fabricante de dicho defecto dentro del
período de garantía mencionado anteriormente. El fabricante reparará o reemplazará cualquier producto o parte que
se determine defectuoso dentro del período de garantía, siempre y cuando tal defecto ocurra por operación normal
del equipo y no como resutado de mal uso, abuso, negligencia o accidente.
La garantía cubre partes y mano de obra durante su vigencia. La reparación o el reemplazo podrá ser realizado en la
fábrica o en el sitio de instalación, a juicio del fabricante. Cualquier servicio realizado en el equipo por personas ajenas
al fabricante, debe ser primero autorizado por el fabricante. Las partes que sufran de desgaste debido a la operación
normal del equipo que requieran reemplazarse rutinariamente no están cubiertas por la garantía. Cualquier servicio
que no sea autorizado primero por el fabricante anula la garantía, y cualquier costo resultante o cualquier reclamación
subsecuente no será pagada. Los productos reparados o reemplazados bajo garantía, serán garantizados únicamente
por el período restante de la garantía del producto original. Lo anterior es la única responsabilidad ante cualquier
comprador del producto del fabricante. La responsabilidad máxima del fabricante por daños es el precio original de
compra del producto o parte.
LA ANTERIOR GARANTIA ES EXCLUSIVA Y LIMITA TODAS LAS OTRAS GARANTIAS, SEAN ESCRITAS, ORALES O ESTATUTORIAS Y
LIMITA EXPRESAMENTE LA GARANTIA EXPLICITA DE COMERCIALIDAD Y LA GARANTIA IMPLICITA DE AJUSTARSE A UN
PROPOSITO EN PARTICULAR. EL FABRICANTE NO ES RESPONSABLE POR PERDIDAS O DAÑOS POR RAZONES DE
RESPONSABILIDAD ESTRICTA O NEGLIGENCIA EN NINGUNA FORMA, SEA DE DISEÑO, FABRICACION, MANUFACTURA O
INSPECCION DEL EQUIPO O SU FALLA AL DETECTAR, REPORTAR, REPARAR O MODIFICAR DEFECTOS LATENTES INHERENTES.
EL FABRICANTE, SU REPRESENTANTE O DISTRIBUIDOR NO SERA RESPONSABLE POR PERDIDAS DEBIDAS AL USO DEL
PRODUCTO, O NINGUN COSTO INCIDENTAL O CONSECUENTE, GASTOS O DAÑOS OCASIONADOS POR EL COMPRADOR, SEAN
DERIVADAS POR UNA INFRACCION A LA GARANTIA, NEGLIGENCIA O LA ESTRICTA RESPONSABILIDAD DE LA GARANTIA.
E El fabricante no garantiza ningún producto, parte, material, componente o accesorio
S manufacturado por otros y vendido o proveeido en conexión con la venta del producto del fabricante.
P 01/01/93
A
Ñ
O ES NECESARIO OBTENER AUTORIZACION DEL DEPARTAMENTO DE SERVICIO
ANTES DE QUE EL MATERIAL SE REGRESE A LA FABRICA O QUE SE REALICE
L
CUALQUIER REPARACION EN EL EQUIPO.
20 SP