50Hz, degree
of protection IP54 for LT & HT compartments and IP23D for Transformer compartment, Cable termination facility, internal illumination,
earthing, interconnection of Transformer with HT & LT equipments and comprising of the following.
G.I Sheet steel encloser manufactured from 2.0 mm suitably with angles/channel, stiffeners and
doors/covers as required. Base shall be welded design, shall be shot blasted and galvanized &
1.1 painted with black paint. Roof shall be manufactured from Galvanized sheet & painted with blue 1 No.
paint. Enclosure sides and doors shall be manufactured from Galvnized sheet & shall be powder
coated, paint shade : RAL 7032. Enclosure shall be designed suitably for outdoor application.
2 HT SECTION
RMU (SF6 gas insulated ): Sheet steel enclosed, free standing, indoor mounted, 11 kV, 21kA ,
630A SF6 insulated, 3way (1xLBS +1xVCB) non extensible RMU, consisting of 1 no. 630A
2.1 Breaker( Manual charging & closing ) with integral earth switch & 1 nos . of Load break Switch
with integral earth switch. Protection CTs, PTs and metering arrangements and meters ,Self- 1 No.
powered fixed type series trip O/C & E/F protection relay, mechanical ON/OFF indicator, shunt
trip coil, live cable indicator, pad locking facility, SF6 gas manometer.
3.2 1000 KVA, 11kV / 433 V , Dry type Transformer with OCTL 1 No.
4 LT PANEL
ACB : 2000 A, 4P, 433V, 50kA EDO Type, Microprocessor based release with O/L , S/C , E/F
4.1 Protection. 1 No.
4.18 Cable termination arrangement for outgoing cable from bottom of ACB. Cable termination kit,
lugs, glands and accessories shall not form part of our scope of supply.