Design, engineering, manufacturing, testing and supply of Outdoor type 11KV Unitised sub-station ( CSS) suitable for 11kV,

50Hz, degree
of protection IP54 for LT & HT compartments and IP23D for Transformer compartment, Cable termination facility, internal illumination,
earthing, interconnection of Transformer with HT & LT equipments and comprising of the following.

No. DESCTRIPTION Qty


Unit Remarks
1 STRUCTURE

G.I Sheet steel encloser manufactured from 2.0 mm suitably with angles/channel, stiffeners and
doors/covers as required. Base shall be welded design, shall be shot blasted and galvanized &
1.1 painted with black paint. Roof shall be manufactured from Galvanized sheet & painted with blue 1 No.
paint. Enclosure sides and doors shall be manufactured from Galvnized sheet & shall be powder
coated, paint shade : RAL 7032. Enclosure shall be designed suitably for outdoor application.

2 HT SECTION

RMU (SF6 gas insulated ): Sheet steel enclosed, free standing, indoor mounted, 11 kV, 21kA ,
630A SF6 insulated, 3way (1xLBS +1xVCB) non extensible RMU, consisting of 1 no. 630A
2.1 Breaker( Manual charging & closing ) with integral earth switch & 1 nos . of Load break Switch
with integral earth switch. Protection CTs, PTs and metering arrangements and meters ,Self- 1 No.
powered fixed type series trip O/C & E/F protection relay, mechanical ON/OFF indicator, shunt
trip coil, live cable indicator, pad locking facility, SF6 gas manometer.

2.2 Power Pack having I/P-230V AC,O/P-110V DC ,100VA 1 No.


2.3 Cable connection from outgoing of HT section to primary of Transformer by 1C x 95sq.mm.
Aluminium XLPE cable per phase
2.4 Termination kit 12 No.
Cable termination arrangement for bottom entry of cables for HT incoming cable size 3no. 3c x
2.5 300sq mm. Cable termination kits, lugs, glands and accessories shall not form part of our
scope of supply.
3 TRANSFORMER

3.2 1000 KVA, 11kV / 433 V , Dry type Transformer with OCTL 1 No.
4 LT PANEL

ACB : 2000 A, 4P, 433V, 50kA EDO Type, Microprocessor based release with O/L , S/C , E/F
4.1 Protection. 1 No.

4.9 Multifunction meter of class 1 accuracy for ACB 1 No.

4.1 R,Y,B, On, Off, Trip indicating Lamp No. AS REQUIRED

4.12 Aluminium bus bar from Transformer to LT 2000 A AS REQUIRED


4.13 Aluminium Busbar from ACB to MCCBs, with sleeve & MCCB outgoings AS REQUIRED
4.14 Copper flexible

4.15 EARTH Busbar Al (50 X 6 )mm


4.16 Misc item - Fans, Lugs, Terminals, Heaters, CFL, Sleeve,insulator,Cooper Flexible 1 Set
4.17 Hardware ,locks,handle,gasket, tie rods and other boughtout itmes 1 Set

4.18 Cable termination arrangement for outgoing cable from bottom of ACB. Cable termination kit,
lugs, glands and accessories shall not form part of our scope of supply.