Beruflich Dokumente
Kultur Dokumente
Cabling system
ConneXium hub and transceiver
3 Connectors
Medium
–
–
Length of optical fibre 50/125 μm –
62.2/125 μm –
Optical fibre 50/125 μm fibre –
attenuation analysis 62.2/125 μm fibre –
cUL 60950, UL 508 and CSA 22.2 No. 142, UL 1604 and CSA 22.2 No. 213 class 1 division 2,
7 Conforming to standards
e, GL, C-Tick
FM 3810, FM 3611 class 1 division 2
Alarm relay Power supply fault, Ethernet network fault or communication port fault (volt-free contact
8 1 A max. at 24 V c)
10
1 x 100BASE-TX port
2
RJ45
Shielded twisted pair, category CAT 5E
100 m
1 x 100BASE-FX port
SC
Multimode optical fibre
3
3000 m (1)
3000 m (1)
8 dB
11 dB
– 4
–
0…+ 60°C
10… 95% non condensing
IP 20
6
47 x 135 x 111 mm
On symmetrical DIN rail, 35 mm wide
0.230 kg
cUL 60950, UL 508 and CSA 22.2 No. 142, UL 1604 and CSA 22.2 No. 213 Class 1 Division 2, e, GL, C-Tick
7
P1 and P2 power supplies, Ethernet link/port status
Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A max. at 24 V c)
8
499 NTR 101 00
48384/6
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 2000 m).
10
2
Interfaces Copper cable ports Number and type 5 x 10BASE-T/100BASE-TX ports 8 x 10BASE-T/100BASE-TX ports
Shielded connectors M12 (type D) RJ45
Medium Shielded twisted pair, category CAT 5E
62.2/125 μm fibre –
Ethernet services Storage and re-routing of received data, –
auto MDI/MDX, automatic negotiation of
10/100 Mbps and duplex mode (on all ports)
5
Topology Number of switches Cascaded Unlimited
Redundant in a ring –
Conforming to standards cUL 508 and CSA 22.2 No. 142 cUL 60950, UL 508 and CSA 22.2 No. 142,
8 UL 1604 and CSA 22.2 No. 213 class 1
division 2, e, GL, C-Tick
LED indicators Power supply, link status, data rate P1 and P2 power supplies, Ethernet link/port
status
10
2
8 x 10BASE-T/100BASE-TX ports 3 x 10BASE-T/100BASE-TX ports 4 x 10BASE-T/100BASE-TX ports 5 x 10BASE-T/100BASE-TX ports
RJ45 RJ45
Shielded twisted pair, category Shielded twisted pair, category CAT 5E
CAT 5E
100 m 100 m 3
– – 1 x 100BASE-FX port –
– – Duplex SC –
– – Multimode optical fibre –
– – 5000 m (1) –
– – 4000 m (1) –
– – 8 dB – 4
– – 11 dB
Storage and re-routing of received Storage and re-routing of received data, auto MDI/MDX, automatic
data, auto MDI/MDX, automatic negotiation of 10/100 Mbps and duplex mode (on all ports)
negotiation of 10/100 Mbps and
duplex mode (on all ports),
automatic change of polarity
5
Unlimited Unlimited
– –
– –
UL 508 and CSA 22.2 No.142 UL 508 and CSA 22.2 No. 142
IEC/EN 61131-2,
IEC 60825-1 class 1, CISPR 11A
IEC/EN 61131-2, IEC 60825-1 class 1, CISPR 11A
8
Power supply, copper port activity, Power supply, copper port activity, 10 or 100 Mbps data rate
10 or 100 Mbps data rate
– Fibre port activity and status –
– –
9
TCS ESU 083FN0 TCS ESU 033FN0 TCS ESU 043F1N0 TCS ESU 053FN0
48384/7 48384/8
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 2000 m).
10
Type of device Unmanaged switches, 5 ports, copper twisted pair and fibre optic
2
Interfaces Copper cable ports Number and type 4 x 10BASE-T/ 3 x 10BASE-T/ 4 x 10BASE-T/ 3 x 10BASE-T/
100BASE-TX ports 100BASE-TX ports 100BASE-TX ports 100BASE-TX ports
Shielded connectors RJ45
Medium Shielded twisted pair, category CAT 5E
Total length of pair 100 m
Conforming to standards cUL 60950, cUL 508 and CSA 22.2 No. 142, UL 1604 and CSA 22.2 No. 213 class 1 division 2,
e, GL, C-Tick
8 LED indicators P1 and P2 power supplies, Ethernet link status, transmission activity
Alarm relay Activity, power supply fault, Ethernet network fault or communication port fault (volt-free contact
1 A max. at 24 V c)
Reference 499 NMS 251 01 499 NMS 251 02 499 NSS 251 01 499 NSS 251 02
9 Page 48384/8
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical
value: 2000 m).
(2) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical
value: 15,000 m).
10
2
3 x 10/100BASE-TX ports 2 x 10/100BASE-TX ports 3 x 10/100BASE-TX ports 2 x 10/100BASE-TX ports
RJ45
Shielded twisted pair, category CAT 5E
100 m
1 x 100BASE-FX port 2 x 100BASE-FX ports 1 x 100BASE-FX port 2 x 100BASE-FX ports
3
Duplex SC
Multimode optical fibre Single mode optical fibre
5000 m (1) –
4000 m (1) –
– 32,500 m (2)
8 dB – 4
11 dB –
– 16 dB
FDR, SMTP V3, SNTP client, multicast filtering for optimization of the Global Data protocol, configuration via Web access,
VLAN, IGMP Snooping, RSTP (Rapid Scanning Tree Protocol), priority port, data stream control, secure port
Unlimited
Up to 50 5
Redundant power supplies, redundant single ring, ring coupling
47 x 131 x 111 mm
On symmetrical DIN rail, 35 mm wide
7
0.400 kg
IEC 61131-2, UL 508, UL 1604 class 1 division 2, CSA 22.2 No. 142 (cUL), CSA 22.2 No. 213 class 1 division 2 (cUL), e, GL, C-Tick
Power supply status, alarm relay status, active redundancy, redundancy management, copper port status and copper port activity
8
Power supply fault, Ethernet network fault, communication port fault, redundancy fault (volt-free contact 1 A max. at 24 V c)
TCS ESM 043F1CU0 TCS ESM 043F2CU0 TCS ESM 043F1CS0 TCS ESM 043F2CS0
48384/9
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 2000 m).
9
(2) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 15,000 m).
10
2 Interfaces Copper cable ports Number and type 4 x 10/100BASE-TX ports 8 x 10/100BASE-TX ports
3 Connectors
Medium
–
–
Length of optical fibre 50/125 μm –
62.2/125 μm –
9/125 μm fibre –
Attenuation analysis 50/125 μm fibre –
62.2/125 μm fibre –
4 9/125 μm fibre –
Ethernet services FDR, SMTP V3, SNTP client, multicast filtering for optimization of the Global Data protocol,
configuration via Web access, VLAN, IGMP Snooping, RSTP (Rapid Scanning Tree Protocol),
priority port, data stream control, secure port
Power supply Voltage 9.6...60 V c/18…30 V a safety extra low voltage (SELV)
Consumption 5.3 W
Removable terminal block 6 terminals
Conforming to standards IEC/EN 61131-2, UL 508, UL 1604 class 1 division 2, CSA 22.2 No. 214 (cUL),
CSA 22.2 No. 213 class 1 division 2 (cUL), e, GL, C-Tick
LED indicators Power supply status, alarm relay status, Power supply status, alarm relay status,
8 active redundancy, redundancy management,
copper port status and copper port activity
active redundancy, redundancy management,
fibre port status and fibre port activity
Alarm relay Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A
max. at 24 V c)
10
Unlimited
Up to 50
5
Redundant power supplies, redundant single ring, ring coupling
0…+ 60°C 6
10… 90% non condensing
IP 20
75 x 131 x 111 mm
On symmetrical DIN rail, 35 mm wide
7
0.410 kg
IEC/EN 61131-2, UL 508, UL 1604 class 1 division 2, CSA 22.2 No. 214 (cUL), CSA 22.2 No. 213 class 1 division 2 (cUL), e, GL, C-Tick
Power supply status, alarm relay status, active redundancy, redundancy management, fibre port status and fibre port activity
8
Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A max. at 24 V c)
TCS ESM 083F1CU0 TCS ESM 083F2CU0 TCS ESM 083F1CS0 TCS ESM 083F2CS0
48384/10
9
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 2000 m).
(2) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 15,000 m).
10
4 Ethernet services
9/125 μm fibre –
FDR, SNTP client, multicast filtering for optimization of the Global Data protocol, configuration
via Web access, IGMP Snooping, RSTP (Rapid Scanning Tree Protocol), priority port
5 Redundancy P1 and P2 redundant power supplies, redundant single ring, ring coupling
Conforming to standards IEC/EN 61131-2, UL 508, UL 1604 class 1 division 2, CSA 22.2 No. 214 (cUL),
CSA 22.2 No. 213 class 1 division 2 (cUL), e, GL, C-Tick
LED indicators Power supply status, alarm relay status, active redundancy, redundancy management,
copper port status and copper port activity
8 Alarm relay Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A
max. at 24 V c)
10
Unlimited
Up to 50
0…+ 60°C
95% max. non condensing 6
IP 20
74 x 131 x 111 mm
On symmetrical DIN rail, 35 mm wide
0.400 kg
7
IEC/EN 61131-2, UL 508, UL 1604 class 1 division 2, CSA 22.2 No. 214 (cUL), CSA 22.2 No. 213 class 1 division 2 (cUL), e, GL, C-Tick
Power supply status, alarm relay status, active redundancy, redundancy management, fibre port status and fibre port activity
Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A max. at 24 V c) 8
TCS ESB 083F2CU0 TCS ESB 093F2CU0
48384/10
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 2000 m).
(2) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 15,000 m). 9
10
Type of device Managed switches, 8 extended ports, copper twisted pair and fibre optic
2 Interfaces Copper cable ports Number and type 8 x 10/100BASE-TX ports 6 x 10/100BASE-TX ports 6 x 10/100BASE-T ports
Shielded connectors RJ45
Medium Shielded twisted pair, category CAT 5E
Total length of pair 100 m
Fibre optic ports Number and type – 2 x 100BASE-FX ports
Connectors – Duplex SC
3 Medium – Multimode optical fibre Single mode optical fibre
Length of optical fibre 50/125 μm – 5000 m (1) –
62.2/125 μm – 4000 m (1) –
9/125 μm fibre – – 32,500 m (2)
Attenuation analysis 50/125 μm fibre – 8 dB –
62.2/125 μm fibre – 11 dB –
4 Ethernet services
9/125 μm fibre – – 16 dB
FDR, SMTP V3, SNTP client, multicast filtering for optimization of the Global Data protocol,
configuration via Web access,VLAN, IGMP Snooping, RSTP (Rapid Scanning Tree Protocol),
priority port, data stream control, secure port
Conforming to standards IEC/EN 61131-2, IEC 61850-3, UL 508, UL 1604 class 1 division 2, CSA 22.2 No. 214 (cUL),
CSA 22.2 No. 213 class 1 division 2 (cUL), e, GL, C-Tick, LR, BV
8
LED indicators Power supply status, alarm relay status, active redundancy, redundancy management, copper
port status and copper port activity
Alarm relay Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A
9 max. at 24 V c, 2-way)
Reference TCS ESM 083F23F1 TCS ESM 063F2CU1 TCS ESM 063F2CS1
Page 48384/10
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical
value: 2000 m).
10 (2) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical
value: 15,000 m).
Unlimited
Up to 50
0…+ 60°C
6
10… 90% non condensing 95% max. non condensing 10… 90% non condensing
IP 20
cUL 60950, UL 508 and CSA 22.2 No. 142, UL 1604 and CSA 22.2 No. 213 IEC/EN 61131-2, cUL 60950, UL 508 and
class 1 division 2 UL 508, UL 1604 class 1 division 2, CSA 22.2 No. 142, UL 1604 and
CSA 22.2 No. 214 (cUL), CSA 22.2 No. 213 class 1 division 2
CSA 22.2 No. 213 class 1 division 2
(cUL), e, GL, C-Tick
8
Power supply status, alarm relay Power supply status, alarm relay status, active redundancy, redundancy management, fibre port status and fibre port
status, active redundancy, activity
redundancy management, copper
port status and copper port activity
Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A max. at 24 V c)
9
TCS ESM 163F23F0 TCS ESM 163F2CU0 TCS ESM 163F2CS0 TCS ESM 243F2CU0
48384/11
(1) Length dependent on the attenuation analysis and attenuation of the optical fibre (typical value: 2000 m).
10
Type of device Managed switch, 8 ports and 2 Gigabit ports, copper twisted pair and fibre optic
Power supply Voltage 9.6...60 V c/18…30 V a safety extra low voltage (SELV)
Consumption 8.9 W + 1 W per SFP fibre optic module
6 Removable terminal block 6 terminals
Degree of protection IP 20
Conforming to standards cUL 60950, UL 508 and CSA 22.2 No. 142, UL 1604 and CSA 22.2 No. 213 class 1 division 2,
e, GL
8 LED indicators Power supply status, alarm relay status, active redundancy, redundancy management,
fibre port status and fibre port activity
Alarm relay Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A
max. at 24 V c)
10
Unlimited
Up to 50 5
Redundant power supplies, redundant single ring, ring coupling
IP 20
cUL 60950, UL 508 and CSA 22.2 No. 142, UL 1604 and CSA 22.2 No. 213 class 1 division 2, e, GL
Power supply status, alarm relay status, active redundancy, redundancy management, fibre port status and fibre port activity
8
Power supply fault, Ethernet network fault or communication port fault (volt-free contact 1 A max. at 24 V c)
10