HVAC CALCULATION

QATAR ARMED FORCES JOINT


WARFARE SIMULATION CENTRE BUILDING

Page 1
_______________________________________________________________________________

QATAR JOINT WARFARE TRAINING CENTER AT AL DUHAILIYATH,QATAR

HVAC CALCULATIONS

TABLE OF CONTENTS

CL. NO. TITLE PAGE NO.

INDEX SHEET Page 2

COMPUTER CALCULATIONS
* DESIGN CRITERIA Page 3 – 5
* SCHEDULE OF VRF Page 6 – 7
* SCHEDULE OF AHU & FAHU Page 8
* SCHEDULE OF AIR COOLED CONDENSING UNITS Page 9
* HVAC HAP SPACE INPUT Page 10 - 75
* HVAC HAP OUTPUT FOR VRF SUSTEM Page 76- 267
* HVAC HAP OUTPUT FOR AHU & FAHU SYSTEM Page 268-298
* U VALUES ........................................................................................................Page 299-304
* PUMP ROOM ……………………………………………………………………….. Page 305-326
* GUARD ROOM ……………………………………………………………………... Page 327-335
* SUBSTATION……………………………………………………………………….. Page 336-343
* HEATER BATTERY…………………………………………………………..…….. Page 344

_________________________________________________________________________________
Q.E.A. Page 2
HVAC CALCULATION QATAR ARMED FORCES JOINT WARFARE SIMULATION CENTER BUILDING
___________________________________________________________________________________________________________________________________________________________

1. DESIGN CRITERIA

The broad design parameters of air conditioning system shall be as follows:

Latitude : 25° North

Outside design conditions

a. Summer : 46°C. DB, 30°C. WB


(115°F. DB, 86°F. WB)
b. Winter : 10°C. DB, 90% RH
(50°F. DB, 90% RH)
Inside design conditions

i. All Offices : 24±3°C DB, 30 to 70% RH


ii. Auditorium and Lobbies : 24±3°C DB, 30 to 70% RH
iii. Cafeteria : 24±3°C DB, 30 to 70% RH
iv. Pantries : 26±1°C DB, 50 to 70% RH
v. Server Room / Data Room : 20±1°C DB, 50±55% RH

Notes:

1. Humidity control is required for Server Room / Data Room.

Page 3
HVAC CALCULATION QATAR ARMED FORCES JOINT WARFARE SIMULATION CENTER BUILDING
___________________________________________________________________________________________________________________________________________________________

Occupancy and Lighting Load


Occupancy Lighting Load
(persons) (watts/m²)
Ground Floor

G01 Air Lock : 2 20


G02 Entrance & Foyer : 5 20
G03 QAF System : 1 20
G04 Telecom Room : 1 20
G06 Security : - 20
G07 Pantry : 1 20
G08 Data Center : - 20
G09 Female WC : - 20
G10 Male WC : - 20
G11 Response Cells Hall Divisible Two RCS : 12 20
G12 Response Cells Opfor Hall (Warning Lab) : 37 20
Divisible to Four RCS
G13 Side Meeting Room / Office (Briefing / : 6 20
Debriefing Room) Divisible to Two Rooms
G14 Chief of Excen : 1 20
G15 Sitcen Battle Management Room : 23 20
G16 Printing / Shredding : 1 20
G18 Response Cells Divisible to Two RCS : 12 20
G19 Driver Room : 1 20
G20 Battle Management Auditorium for 252 : 252 20
People
G21 Mechanical Room : 1 20
G22 Headquarter Cells Divisible to Two Cells : 12 20
G23 Side Meeting Room / Office Divisible to 6 20
Two Rooms
G24 Printing / Shredding : 1 20
G25 JOC : 23 20
G26 Chief of JOC : 1 20
G27 Side Meeting Room / Office (Briefing / : 7 20
Debriefing Room) Divisible to Two Rooms

Page 4
HVAC CALCULATION QATAR ARMED FORCES JOINT WARFARE SIMULATION CENTER BUILDING
___________________________________________________________________________________________________________________________________________________________

G28 Headquarter Cells (Wargaming Lab) : 37 20


Divisible to Four Cells
G29 Headquarter Cells Divisible to Two Cells : 12 20
G30 Male WC : - 20
G32 VIP Room : 5 20
Corridor : 2 20
Electrical & UPS Room : 1 20
Storage : - 20
Stair-1 : - 20
Stair-2 : - 20

First Floor

F01 CCTV Room : 1 20


F02 Commanders Room : 1 20
F03 Front Office : 1 20
F04 WC : - 20
F05 Commanders Meeting Room : 10 20
F06 Production : 36 20
F07 Chief Production : 1 20
F08 Workshop : 4 20
F09 Chief SME : 1 20
F10 SME Division : 15 20
F11 Analyst Branch : 9 20

Page 5
HVAC CALCULATION QATAR ARMED FORCES JOINT WARFARE SIMULATION CENTER BUILDING
___________________________________________________________________________________________________________________________________________________________

SCHEDULE OF VRF UNITS - GROUND FLOOR


SELECTED UNIT
AIR SELECTED UNIT
EQUIPMENT ROOM REF. TOTAL ELECTRICAL
S.N. AREA SERVED QTY TOTAL SENSIBLE QTY TYPE
REF. NO. NO COOLING LOAD LOAD (kW)
(L/S) LOAD (kW)
(kW)

1 VRF-GF-01&02 G02 ENTRANCE & FOYER 405 3.3 2.55 2 DUCTED VRF UNIT 0.15

2 VRF-GF-03 G06 SECURITY 62 . 1 WALL MOUNTED


3 VRF-GF-04 --- RIGHT SIDE CORRIDOR/G16 451 3.3 2.9 1 DUCTED VRF UNIT 0.15

4 VRF-GF-05&06 G11 RESPONSE CELLS HALL DIVISIBLE TO TWO RCS / 1 BY 2 315 3.5 3.1 2 DUCTED VRF UNIT 0.15
VRF-GF-
5 G12 RESPONSE CELLS HALL DIVISIBLE TO TWO RCS / 1 BY 4 347 3.8 3.2 4 DUCTED VRF UNIT 0.15
07,08,09,10
SIDE MEETING ROOM / OFFICE DIVISIBLE TO TWO
6 VRF-GF-11&12 G13 178 2 1.8 2 DUCTED VRF UNIT 0.1
ROOMS (BRIEFING / DEBRIEFING ROOM)

7 VRF-GF-13 G14 CHIEF OF EXCEN 150 1.4 1.4 1 DUCTED VRF UNIT 0.1
8 VRF-GF-14 G15 SITCEN BATTLE MANAGEMENT ROOM 1200 9 7.5 1 DUCTED VRF UNIT 0.25
SIDE MEETING ROOM / OFFICE DIVISIBLE TO TWO
9 VRF-GF-16&17 G17 164 1.5 1.2 2 DUCTED VRF UNIT 0.1
ROOMS
10 VRF-GF-18&19 G18 RESPONSE CELLS DIVISIBLE TO TWO RCS 277 3 2.6 2 DUCTED VRF UNIT 0.15
11 VRF-GF-20 G19 DRIVER ROOM 119 1.2 1.2 1 WALL MOUNTED 0.1
12 VRF-GF-21 G18 ELECTRICAL AND UPS ROOM 426 2.7 2.7 1 DUCTED VRF UNIT 0.15
13 VRF-GF-22&23 G22 HEADQUARTER CELLS DIVISIBLE TO TWO CELLS 277 3 2.6 2 DUCTED VRF UNIT 0.15
SIDE MEETING ROOM / OFFICE DIVISIBLE TO TWO
14 VRF-GF-25&26 G23 164 1.5 1.2 2 DUCTED VRF UNIT 0.1
ROOMS
15 VRF-GF-27 G25 JOC 1200 9 7.5 1 DUCTED VRF UNIT 0.25
16 VRF-GF-28 G26 CHIEF OF JOC 150 1.4 1.4 1 DUCTED VRF UNIT 0.1
SIDE MEETING ROOM / OFFICE DIVISIBLE TO TWO
17 VRF-GF-29&30 G27 178 2 1.8 2 DUCTED VRF UNIT 0.1
ROOMS (BRIEFING / DEBRIEFING ROOM)
VRF-GF-
18 G28 HEAD QUARTER CELLS DIVISIBLE BY 4 337 3.8 3.3 4 DUCTED VRF UNIT 0.15
31,32,33,34
19 VRF-GF-35&36 G29 HEAD QUARTER CELLS DIVISIBLE TO TWO CELLS 304 3.4 2.9 2 DUCTED VRF UNIT 0.15
20 VRF-GF-37 --- LEFT SIDE CORRIDOR/G24 451 3.3 2.9 1 DUCTED VRF UNIT 0.15
21 VRF-GF-38 G32 VIP ROOM 496 4.2 4.2 1 DUCTED VRF UNIT 0.15
22 VRF-GF-39 G01 AIRLOCK 429 5.6 4.7 1 WALL MOUNTED 0.15
23 VRF-GF-40 G07 PANTRY 113 1.6 1.3 1 WALL MOUNTED 0.1
24 VRF-GF-41 G21 MECH ROOM 119 1.2 1.2 1 WALL MOUNTED 0.1

Page 6
HVAC CALCULATION QATAR ARMED FORCES JOINT WARFARE SIMULATION CENTER BUILDING
___________________________________________________________________________________________________________________________________________________________

SCHEDULE OF VRF UNITS - FIRST FLOOR

SELECTED UNIT
AIR SELECTED UNIT
EQUIPMENT ROOM REF. TOTAL ELECTRICAL
S.N. AREA SERVED QTY TOTAL COOLING QTY TYPE
REF. NO. NO SENSIBLELOAD LOAD (kW)
(L/S) LOAD (kW)
(kW)

1 VRF-FF-01 F03 FRONT OFFICE 158 1.2 1.2 1 DUCTED VRF UNIT 0.1
2 VRF-FF-02 --- RIGHT SIDE CORRIDOR 624 4.6 4.6 1 DUCTED VRF UNIT 0.2

VRF-FF-
3 F06 PRODUCTION DIVISION 490 4 3.4 4 DUCTED VRF UNIT 0.15
03,04,05,06

4 VRF-FF-07 F07 CHIEF PRODUCTION 262 2.7 2.7 1 DUCTED VRF UNIT 0.1
5 VRF-FF-08 F10 SME DIVISION 759 6.7 5.1 1 DUCTED VRF UNIT 0.2
6 VRF-FF-09 F09 CHIEF SME 209 2.2 1.9 1 DUCTED VRF UNIT 0.1
7 VRF-FF-10 F08 WORKSHOP 190 2.1 1.9 1 DUCTED VRF UNIT 0.1
8 VRF-FF-11 F11 ANALYST BRANCH 457 3.5 2.9 1 DUCTED VRF UNIT 0.15
9 VRF-FF-12 F12 MOSQUE 460 4.7 3.7 1 DUCTED VRF UNIT 0.15
10 VRF-FF-13 F19 LADIES OFFICE 322 2.8 2.6 1 DUCTED VRF UNIT 0.15

11 VRF-FF-14 F20&F21 REGISTRY & CLASSIFIED DOCUMENT ROOM 321 3 3 1 DUCTED VRF UNIT 0.15

12 VRF-FF-15 F22 C4IS DIVISION 585 5.6 4.7 1 DUCTED VRF UNIT 0.2
13 VRF-FF-16 F23 MEDIA SIM / STUDIO ROOM 562 5.1 4.3 1 DUCTED VRF UNIT 0.2
14 VRF-FF-17 F24 CBT SYSTEM 771 8.8 7.1 1 DUCTED VRF UNIT 0.3
15 VRF-FF-18 F26 CHIEF OF PLANNING 201 1.7 1.7 1 DUCTED VRF UNIT 0.1
16 VRF-FF-19 F27 CHIEF OF C4IS 290 2.8 2.8 1 DUCTED VRF UNIT 0.15
17 VRF-FF-20 F28 CHIEF OF SUPPORT 238 2 2 1 DUCTED VRF UNIT 0.1
18 VRF-FF-21 F29 SUPPORT DIVISION 439 4.7 4.1 1 DUCTED VRF UNIT 0.15
19 VRF-FF-22 F30 PLANNING DIVISION 625 6.7 6.1 1 DUCTED VRF UNIT 0.2
20 VRF-FF-23 F31 DOSS STAFF 400 3.9 3.5 1 DUCTED VRF UNIT 0.15
21 VRF-FF-24 F32 DIRECTOR OF STAFF 355 3.9 3.9 1 DUCTED VRF UNIT 0.15
22 VRF-FF-25 --- LEFT SIDE CORRIDOR 344 2.6 2.6 1 DUCTED VRF UNIT 0.15
23 VRF-FF-26 F13/F14/F15 CENTER CORRIDOR 670 5.7 5.7 1 DUCTED VRF UNIT 0.2
24 VRF-FF-27 F01 CCTV ROOM 235 2.2 2.2 1 DUCTED VRF UNIT 0.1
25 VRF-FF-28 --- TRANSLATOR 109 1.2 1.1 1 DUCTED VRF UNIT 0.1

Page 7
HVAC CALCULATION QATAR ARMED FORCES JOINT WARFARE SIMULATION CENTER BUILDING
___________________________________________________________________________________________________________________________________________________________

SCHEDULE FOR AHU 

AIR ON COIL  AIR OFF COIL  TOTAL  SENSIBLE 


SUPPLY FRESH  AHU  AHU  EXT. ST. PR.  ELECTRICAL 
S.N.  UNIT REF. NO.  QTY  COOLING  COOLING CAP. 
AIR (L/S)  AIR (L/S)  (Pa)  LOAD (KW) 
CAP. (KW)  (KW) 
DBᵒC  WBᵒC  DBᵒC  WBᵒC 

1  AHU‐01 (AUDITORIUM)  1  4043  720  25.8  19.5  13.3  12.7  93.1  61.1  250  8 

AHU‐02 (CANTEEN & 
2  1  1890  168  23.8  18.1  9.8  9.4  51.5  31.9  250  4 
CAFETERIA 

AHU‐03 (COMMNADER 
3  1  1251  92  23.2  17.1  13.6  13.1  18.9  14.4  250  3 
& MEETING) 

SCHEDULE FOR FAHU 

AIR ON COIL  AIR OFF COIL  TOTAL  SENSIBLE 


SUPPLY FRESH  AHU  AHU  EXT. ST. PR.  ELECTRICAL 
S.N.  UNIT REF. NO.  QTY  COOLING  COOLING CAP. 
AIR (L/S)  AIR (L/S)  (Pa)  LOAD (KW) 
CAP. (KW)  (KW) 
DBᵒC  WBᵒC  DBᵒC  WBᵒC 

1  FAHU‐01 (LEFT SIDE)  1  1252  1252  46  30  12.8  12.1  93.7  50.1  500  3.5 

2  FAHU‐02 (RIGHT SIDE)  1  996  996  46  30  12.8  12.1  74.6  39.8  500  3 

NOTES: 
1. FAN MOTOR TO OPERATE ON 415V,3Ph,50 Hz A.C. SUPPLY
2. CONTRACTOR SHALL BE RESPONSIBLE TO CHECK THE ACTUAL STATIC PRESSURE IN CONJUCTION WITH THE PROPOSED EQUIPMENT AND RELATED SYSTEM
AND SUBMIT THE SAME FOR ENGINEER'S APPROVAL. 
3. ALL THE FRESH AIR HANDLING UNIT / AHU'S SHALL BE HORIZONTAL TYPE WITH HORIZONTAL DISCHARGE.
4. CONTRACTOR SHALL BE RESPONSIBLE TO CHECK THE ACTUAL MOTOR RATING IN CONJUNCTION WITH THE PROPOSED EQUPMENT OFFERED.
5. CONTRACTOR SHALL BE RESPONSIBLE TO CALCULATE AND COORDINATE WITH THE ELECTRICAL SECTION THE ACTUAL POWER CONSUMPTION IN
CONJUNCTION WITH THE EQUIPMENT SELECTED. 

Page 8
HVAC CALCULATION QATAR ARMED FORCES JOINT WARFARE SIMULATION CENTER BUILDING
___________________________________________________________________________________________________________________________________________________________

SCHEDULE OF AIR COOLED CONDENSING UNITS 
COOLING CAPACITY AIR ON CONDENSER  ELECTRICAL LOAD 
ACCU REF.  TYPE  QTY  REFRIGERANT 
KW   (ᵒC)  (KW) 

AIR COOLED 
ACCU‐01  1  R134A/R407C  93  46  30 
CONDENSER UNIT 

AIR COOLED 
ACCU‐02  1  R134A/R407C  63.2  46  25 
CONDENSER UNIT 

AIR COOLED 
ACCU‐03  1  R134A/R407C  18.9  46  7 
CONDENSER UNIT 

AIR COOLED 
ACCU‐04  1  R134A/R407C  96.6  46  40 
CONDENSER UNIT 

AIR COOLED 
ACCU‐05  1  R134A/R407C  86.4  46  35 
CONDENSER UNIT 

NOTE: 
1. THE EXTERNAL PRESSURE / RESISTANCE INDICATED IS APPROXIMATE, HOWEVER, CONTRACTOR CHECK PRESSURE HEAD IN CONJUNCTON WITH THE
EQUIPMENT AND RELATED SYSTEM. 
2. CONDENSER SECTION SHALL BE SUITABLE TO OPERATE UPTO 50ᵒC AMBIENT TEMPERATURE.
3. POWER SUPPLY 380‐415V,3Ph,50Hz.

Page 9
_______________________________________________________________________________

HVAC HAP SPACE INPUTS

_________________________________________________________________________________
Q.E.A.
Page 10
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 01 CCTV ROOM

1. General Details:
Floor Area ........................................................... 24.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 25.10 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 300.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 18.0 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 24.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 10.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 11
Hourly Analysis Program vv5.01 Page 1 of 71 1
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 02 COMMANDER ROOM

1. General Details:
Floor Area ........................................................... 60.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 .............................................. 50.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 3.0 People
Wattage ............................................................ 12.40 W/m² Activity Level ......................................... Heavy Work
Ballast Multiplier ................................................. 1.25 Sensible ........................................................... 153.9 W/person
Schedule ................................................. LIGHTING Latent ............................................................... 271.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 43.3 1 0 0
ENE 17.0 0 0 0
WSW 9.2 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type ........................................................... W1

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

3.3. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 60.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: Uncondit. Space Max Temp .............................. 43.0 °C
Partition Type ..................................... Wall Partition Ambient at Space Max Temp ............................ 46.0 °C
Area .................................................................... 13.3 m² Uncondit. Space Min Temp ............................... 30.0 °C
U-Value ............................................................ 1.370 W/(m²ꞏK) Ambient at Space Min Temp ............................. 35.3 °C

Page 12
Hourly Analysis Program vv5.01 Page 2 of 71 2
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

7.2. 2nd Partition Details: (No partition data).

Page 13
Hourly Analysis Program vv5.01 Page 3 of 71 3
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 03 FRONT OFFICE

1. General Details:
Floor Area ........................................................... 13.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 26.60 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 13.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 3.7 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 14
Hourly Analysis Program vv5.01 Page 4 of 71 4
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 05 COMMANDER MEETING

1. General Details:
Floor Area ........................................................... 50.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 .............................................. 42.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 10.0 People
Wattage ............................................................ 10.65 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 600.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 31.5 3 0 0
WSW 20.5 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 50.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 6.3 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C
Page 15
Hourly Analysis Program vv5.01 Page 5 of 71 5
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

Page 16
Hourly Analysis Program vv5.01 Page 6 of 71 6
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 06 PRODUCTION DIVISI

1. General Details:
Floor Area ......................................................... 170.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 36.0 People
Wattage ............................................................ 18.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 89.5 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 170.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 17
Hourly Analysis Program vv5.01 Page 7 of 71 7
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 07 CHIEF PRODUCTION

1. General Details:
Floor Area ........................................................... 21.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 12.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 22.4 3 0 0
ENE 9.6 1 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 18
Hourly Analysis Program vv5.01 Page 8 of 71 8
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 08 WORK SHOP

1. General Details:
Floor Area ........................................................... 17.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 4.0 People
Wattage ............................................................ 30.30 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 19
Hourly Analysis Program vv5.01 Page 9 of 71 9
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 09 CHIEF SME

1. General Details:
Floor Area ........................................................... 18.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 4.0 People
Wattage ............................................................ 30.10 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 20
Hourly Analysis Program vv5.01 Page 10 of 71 10
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 10 SME DIVISION

1. General Details:
Floor Area ........................................................... 72.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 15.0 People
Wattage ............................................................ 21.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1000.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 72.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 21
Hourly Analysis Program vv5.01 Page 11 of 71 11
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 11 ANALYST BRANCH

1. General Details:
Floor Area ........................................................... 46.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 9.0 People
Wattage ............................................................ 12.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 46.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 22
Hourly Analysis Program vv5.01 Page 12 of 71 12
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 12 MOSQUE

1. General Details:
Floor Area ........................................................... 57.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 15.0 People
Wattage ............................................................ 12.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 57.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 23
Hourly Analysis Program vv5.01 Page 13 of 71 13
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 19 LADIES OFFICE

1. General Details:
Floor Area ........................................................... 31.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 4.0 People
Wattage ............................................................ 27.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 300.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 10.4 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 24
Hourly Analysis Program vv5.01 Page 17 of 71 17
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 20 REGISRY

1. General Details:
Floor Area ........................................................... 20.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage ............................................................ 30.20 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 300.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 20.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 25
Hourly Analysis Program vv5.01 Page 18 of 71 18
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 21 CLASSIFIED DOCS

1. General Details:
Floor Area ........................................................... 12.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 34.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 6.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 26
Hourly Analysis Program vv5.01 Page 19 of 71 19
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 22 C4IS

1. General Details:
Floor Area ........................................................... 56.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 13.0 People
Wattage ............................................................ 20.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1000.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 56.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 27
Hourly Analysis Program vv5.01 Page 20 of 71 20
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 23 MEDIA/STUDIO

1. General Details:
Floor Area ........................................................... 56.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 3.0 People
Wattage ............................................................ 20.50 W/m² Activity Level ......................................... Heavy Work
Ballast Multiplier ................................................. 1.25 Sensible ........................................................... 153.9 W/person
Schedule ................................................. LIGHTING Latent ............................................................... 271.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1000.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 56.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 28
Hourly Analysis Program vv5.01 Page 21 of 71 21
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 24 CBT SYSTEM

1. General Details:
Floor Area ........................................................... 63.2 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 25.0 People
Wattage ............................................................ 18.25 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1000.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 38.1 3 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 63.2 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 29
Hourly Analysis Program vv5.01 Page 22 of 71 22
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 26 CHIEF PLANNING

1. General Details:
Floor Area ........................................................... 17.7 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 21.70 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 19.2 1 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.7 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 30
Hourly Analysis Program vv5.01 Page 23 of 71 23
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 27 CHIEF OF C4IS

1. General Details:
Floor Area ........................................................... 19.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 22.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 26.0 1 0 0
ENE 19.2 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 19.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 31
Hourly Analysis Program vv5.01 Page 24 of 71 24
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 28 CHIEF OF SUPPORT

1. General Details:
Floor Area ........................................................... 20.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 31.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 10.7 1 0 0

3.1. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 20.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 32
Hourly Analysis Program vv5.01 Page 25 of 71 25
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 29 SUPPORT DIVISION

1. General Details:
Floor Area ........................................................... 47.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 9.0 People
Wattage ............................................................ 24.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 25.2 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 47.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 33
Hourly Analysis Program vv5.01 Page 26 of 71 26
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 30 PLANNING DIVISION

1. General Details:
Floor Area ........................................................... 53.5 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 10.0 People
Wattage ............................................................ 24.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 24.0 1 0 0

3.1. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall
1st Window Type ....................................................... W 1.8

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 53.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 34
Hourly Analysis Program vv5.01 Page 27 of 71 27
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 31 DOS STAFF

1. General Details:
Floor Area ........................................................... 34.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 6.0 People
Wattage ............................................................ 26.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 26.0 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 34.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 7.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 35
Hourly Analysis Program vv5.01 Page 28 of 71 28
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 32 DIRECTOR OF STAFF

1. General Details:
Floor Area ........................................................... 28.6 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 30.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 14.8 2 0 0
SSE 19.6 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 28.6 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 14.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C
Page 36
Hourly Analysis Program vv5.01 Page 29 of 71 29
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

Page 37
Hourly Analysis Program vv5.01 Page 30 of 71 30
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 33 KITCHEN

1. General Details:
Floor Area ........................................................... 30.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 .............................................. 25.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage ............................................................ 27.20 W/m² Activity Level ......................................... Heavy Work
Ballast Multiplier ................................................. 1.25 Sensible ........................................................... 153.9 W/person
Schedule ................................................. LIGHTING Latent ............................................................... 271.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .............................................................. 300 W
Schedule .......................................................... None Schedule ..................................................... PEOPLE
Latent .................................................................. 600 W
Schedule ..................................................... PEOPLE
2.3. Electrical Equipment:
Wattage .......................................................... 1000.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 16.0 1 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 30.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 38
Hourly Analysis Program vv5.01 Page 31 of 71 31
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F 34 CAFATERIA

1. General Details:
Floor Area ......................................................... 110.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ............................................ 143.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 44.0 People
Wattage ............................................................ 21.30 W/m² Activity Level ......................................... Heavy Work
Ballast Multiplier ................................................. 1.25 Sensible ........................................................... 153.9 W/person
Schedule ................................................. LIGHTING Latent ............................................................... 271.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule ..................................................... PEOPLE
Latent ...................................................................... 0 W
Schedule ..................................................... PEOPLE
2.3. Electrical Equipment:
Wattage ............................................................ 300.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 17.0 0 0 0
ENE 8.2 0 0 0
SSE 40.0 1 0 0

3.1. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

3.3. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type ........................................................... W1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 110.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: Uncondit. Space Max Temp .............................. 43.0 °C
Partition Type ..................................... Wall Partition Ambient at Space Max Temp ............................ 46.0 °C
Area .................................................................... 33.0 m² Uncondit. Space Min Temp ............................... 30.0 °C
U-Value ............................................................ 1.370 W/(m²ꞏK) Ambient at Space Min Temp ............................. 35.3 °C

Page 39
Hourly Analysis Program vv5.01 Page 32 of 71 32
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

7.2. 2nd Partition Details: (No partition data).

Page 40
Hourly Analysis Program vv5.01 Page 33 of 71 33
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F CORRIDOR CENTER

1. General Details:
Floor Area ........................................................... 98.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage .............................................................. 9.70 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 600.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 98.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 64.5 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 41
Hourly Analysis Program vv5.01 Page 34 of 71 34
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F CORRIDOR LEFT

1. General Details:
Floor Area ........................................................... 56.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage ............................................................ 12.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 56.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 42
Hourly Analysis Program vv5.01 Page 35 of 71 35
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F CORRIDOR RIGHT

1. General Details:
Floor Area ........................................................... 73.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage ............................................................ 13.10 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 100.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 51.0 4 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 73.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 43
Hourly Analysis Program vv5.01 Page 36 of 71 36
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

1 F TRANSLATOR

1. General Details:
Floor Area ........................................................... 10.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage ............................................................ 30.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 300.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 44
Hourly Analysis Program vv5.01 Page 37 of 71 37
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

AUDITORIUM

1. General Details:
Floor Area ......................................................... 240.5 m²
Avg. Ceiling Height ............................................... 3.8 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ............................................ 702.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ....................................................... 262.0 People
Wattage ............................................................ 20.88 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 46.3 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 240.5 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ............... Floor Above Unconditioned Space
Floor Area ......................................................... 240.5 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Unconditioned Space Max Temp. ...................... 46.0 °C
Ambient at Space Max Temp. ............................ 46.0 °C
Unconditioned Space Min Temp. ....................... 30.0 °C
Ambient at Space Min Temp. ............................. 35.3 °C

7. Partitions:
(No partition data).

Page 45
Hourly Analysis Program vv5.01 Page 38 of 71 38
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

FAHU AUDITORIUM

1. General Details:
Floor Area ............................................................. 1.0 m²
Avg. Ceiling Height ............................................... 1.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 .......................................... 2596.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 0.0 Person
Wattage .............................................................. 0.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule .......................................................... None Latent ................................................................. 60.1 W/person
Schedule .......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ................................................................ 0.0 Watts
Schedule .......................................................... None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 46
Hourly Analysis Program vv5.01 Page 39 of 71 39
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

FAHU LEFT SIDE

1. General Details:
Floor Area ............................................................. 1.0 m²
Avg. Ceiling Height ............................................... 1.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 .......................................... 1348.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 0.0 Person
Wattage .............................................................. 0.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule .......................................................... None Latent ................................................................. 60.1 W/person
Schedule .......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ................................................................ 0.0 Watts
Schedule .......................................................... None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 47
Hourly Analysis Program vv5.01 Page 40 of 71 40
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

FAHU RIGHT SIDE

1. General Details:
Floor Area ............................................................. 1.0 m²
Avg. Ceiling Height ............................................... 1.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 .......................................... 1156.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 0.0 Person
Wattage .............................................................. 0.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule .......................................................... None Latent ................................................................. 60.1 W/person
Schedule .......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ................................................................ 0.0 Watts
Schedule .......................................................... None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Page 48
Hourly Analysis Program vv5.01 Page 41 of 71 41
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 01 AIRLOCK

1. General Details:
Floor Area ........................................................... 31.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 3.0 People
Wattage .............................................................. 5.00 W/m² Activity Level ......................................... Heavy Work
Ballast Multiplier ................................................. 1.25 Sensible ........................................................... 153.9 W/person
Schedule ................................................. LIGHTING Latent ............................................................... 271.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 100.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 29.0 1 0 2

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type .................................. AIRLOCK FRONT
Door Type ....................................................................... D1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 31.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 49
Hourly Analysis Program vv5.01 Page 42 of 71 42
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 02 ENTERANCE & FOYER

1. General Details:
Floor Area ......................................................... 155.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 5.0 People
Wattage .............................................................. 5.00 W/m² Activity Level ......................................... Heavy Work
Ballast Multiplier ................................................. 1.25 Sensible ........................................................... 153.9 W/person
Schedule ................................................. LIGHTING Latent ............................................................... 271.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ......................................................... 155.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 49.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 50
Hourly Analysis Program vv5.01 Page 43 of 71 43
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 06 SECURITY

1. General Details:
Floor Area ............................................................. 7.2 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 28.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 200.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 6.4 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 7.2 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 51
Hourly Analysis Program vv5.01 Page 47 of 71 47
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 07 PANTRY

1. General Details:
Floor Area ............................................................. 9.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 22.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .............................................................. 300 W
Schedule .......................................................... None Schedule ...................................... MISC. ELECTRIC
Latent .................................................................. 300 W
Schedule ...................................... MISC. ELECTRIC
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 9.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 52
Hourly Analysis Program vv5.01 Page 48 of 71 48
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 11 RESPONCE CELL

1. General Details:
Floor Area ........................................................... 62.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 12.0 People
Wattage ............................................................ 20.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 31.3 3 0 0
WSW 20.5 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 62.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 22.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 53
Hourly Analysis Program vv5.01 Page 49 of 71 49
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 12 HEADQUATER CELL

1. General Details:
Floor Area ......................................................... 185.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 37.0 People
Wattage ............................................................ 20.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 22.4 1 0 0
WSW 85.0 2 0 0
ENE 6.4 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.3. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ......................................................... 185.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 54
Hourly Analysis Program vv5.01 Page 50 of 71 50
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 13 SIDE MEETING ROOM

1. General Details:
Floor Area ........................................................... 30.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 8.0 People
Wattage ............................................................ 27.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 27.5 2 0 0
ENE 6.4 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 30.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 55
Hourly Analysis Program vv5.01 Page 51 of 71 51
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 14 CHIEF OF EXCEN

1. General Details:
Floor Area ............................................................. 9.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 22.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 8.6 1 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 9.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 13.2 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 56
Hourly Analysis Program vv5.01 Page 52 of 71 52
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 15 SITCEN

1. General Details:
Floor Area ......................................................... 122.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 23.0 People
Wattage ............................................................ 20.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ......................................................... 122.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 11.2 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 57
Hourly Analysis Program vv5.01 Page 53 of 71 53
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 16 PRINTING

1. General Details:
Floor Area ............................................................. 9.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 22.00 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 100.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 9.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 58
Hourly Analysis Program vv5.01 Page 54 of 71 54
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 17 SIDE MEETING ROOM

1. General Details:
Floor Area ........................................................... 30.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 6.0 People
Wattage ............................................................ 27.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 30.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 8.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 59
Hourly Analysis Program vv5.01 Page 55 of 71 55
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 18 ELECTRICAL AND UPS

1. General Details:
Floor Area ........................................................... 44.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 22.00 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 800.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 20.3 0 0 1

3.1. Construction Types for Exposure NNE


Wall Type ........................................ Medium Weight Wall
Door Type ....................................................................... D3

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 44.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 60
Hourly Analysis Program vv5.01 Page 56 of 71 56
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 18 HEADQUARTER CELL

1. General Details:
Floor Area ........................................................... 58.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 12.0 People
Wattage ............................................................ 21.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 58.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 24.8 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 61
Hourly Analysis Program vv5.01 Page 57 of 71 57
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 19 DRIVER ROOM

1. General Details:
Floor Area ............................................................. 8.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 50.00 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 300.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 8.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 6.4 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 62
Hourly Analysis Program vv5.01 Page 58 of 71 58
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 21 MECH ROOM

1. General Details:
Floor Area ............................................................. 8.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 50.00 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 300.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 8.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 6.4 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 63
Hourly Analysis Program vv5.01 Page 59 of 71 59
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 22 HEADQUARTER CELL

1. General Details:
Floor Area ........................................................... 58.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 12.0 People
Wattage ............................................................ 21.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 58.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 24.8 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 64
Hourly Analysis Program vv5.01 Page 60 of 71 60
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 23 SIDE MEETING ROOM

1. General Details:
Floor Area ........................................................... 30.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 6.0 People
Wattage ............................................................ 27.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 30.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area ...................................................................... 8.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 65
Hourly Analysis Program vv5.01 Page 61 of 71 61
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 24 PRINTING

1. General Details:
Floor Area ............................................................. 9.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 22.00 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 100.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 9.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 66
Hourly Analysis Program vv5.01 Page 62 of 71 62
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 25 JOC

1. General Details:
Floor Area ......................................................... 122.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 23.0 People
Wattage ............................................................ 20.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ......................................................... 122.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 11.2 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 67
Hourly Analysis Program vv5.01 Page 63 of 71 63
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 26 CHIEF OF JOC

1. General Details:
Floor Area ............................................................. 9.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 22.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 250.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 8.6 1 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 9.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 13.2 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 68
Hourly Analysis Program vv5.01 Page 64 of 71 64
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 27 SIDE MEETING ROOM

1. General Details:
Floor Area ........................................................... 30.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 8.0 People
Wattage ............................................................ 27.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 27.5 2 0 0
ENE 6.4 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 30.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 69
Hourly Analysis Program vv5.01 Page 65 of 71 65
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 28 HEADQUATER CELL

1. General Details:
Floor Area ......................................................... 185.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 37.0 People
Wattage ............................................................ 20.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 22.4 1 0 0
ENE 85.0 2 0 0
WSW 6.4 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.3. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ......................................................... 185.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 70
Hourly Analysis Program vv5.01 Page 66 of 71 66
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 29 HEADQUATER

1. General Details:
Floor Area ........................................................... 62.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ......................................................... 12.0 People
Wattage ............................................................ 20.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 31.3 3 0 0
ENE 20.5 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

3.2. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall
1st Window Type .......................................................... W 2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 62.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 22.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 71
Hourly Analysis Program vv5.01 Page 67 of 71 67
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G 32 VIP

1. General Details:
Floor Area ........................................................... 52.0 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 5.0 People
Wattage ............................................................ 10.00 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 26.2 1 0 0
WSW 16.0 0 0 0
ENE 7.7 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type ........................................ Medium Weight Wall
1st Window Type ........................................................... W1

3.2. Construction Types for Exposure WSW


Wall Type ........................................ Medium Weight Wall

3.3. Construction Types for Exposure ENE


Wall Type ........................................ Medium Weight Wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 52.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 38.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C
Page 72
Hourly Analysis Program vv5.01 Page 68 of 71 68
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

Page 73
Hourly Analysis Program vv5.01 Page 69 of 71 69
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G CORRIDOR LEFT

1. General Details:
Floor Area ........................................................... 60.8 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 6.0 People
Wattage ............................................................ 12.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 600.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 6.4 0 0 1

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
Door Type ....................................................................... D2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 60.8 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 74
Hourly Analysis Program vv5.01 Page 70 of 71 70
Space Input Data
QATAR JOINT WARFARE 07-05-2018
qea 08:30AM

G CORRIDOR RIGHT

1. General Details:
Floor Area ........................................................... 60.8 m²
Avg. Ceiling Height ............................................... 3.2 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 6.0 People
Wattage ............................................................ 12.50 W/m² Activity Level ......................................... Office Work
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 71.8 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 60.1 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 600.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 6.4 0 0 1

3.1. Construction Types for Exposure NNW


Wall Type ........................................ Medium Weight Wall
Door Type ....................................................................... D2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 60.8 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 75
Hourly Analysis Program vv5.01 Page 71 of 71 71
_______________________________________________________________________________

HVAC HAP OUTPUT FOR VRF SYSTEM

_________________________________________________________________________________
Q.E.A.
Page 76
Zone Sizing Summary for G 01 AIRLOCK
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Air System Information


Air System Name ............................ G 01 AIRLOCK Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 22.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 5.6 4.7 22.7 / 17.1 13.6 / 13.1 - Jul 1400 19.48

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 429 0.108 0.086 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.7 Jul 1300 0.6 22.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 01 AIRLOCK 1 4.7 Jul 1300 429 0.6 22.0 19.48

Page 77
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 01 AIRLOCK
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 01 AIRLOCK 1 22.0 3.0 428.7 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 428.7 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 78
Air System Design Load Summary for G 01 AIRLOCK
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 1157 - 16 m² - -
Wall Transmission 0 m² 5 - 0 m² 2 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 741 - 16 m² 336 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 13 m² 1573 - 13 m² 265 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 138 W 137 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 3 462 813 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 418 81 0% 0 0
>> Total Zone Loads - 4593 895 - 603 0
Zone Conditioning - 4520 895 - 76 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 86 - - -86 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4606 895 - -9 0
Terminal Unit Cooling - 4606 892 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4606 892 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 79
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 01 AIRLOCK
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 1157 - 16 m² - -
Wall Transmission 0 m² 5 - 0 m² 2 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 741 - 16 m² 336 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 13 m² 1573 - 13 m² 265 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 138 W 137 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 3 462 813 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 418 81 0% 0 0
>> Total Zone Loads - 4593 895 - 603 0

Page 80
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G CORRIDOR RIGHT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:12PM

Air System Information


Air System Name .................. G CORRIDOR RIGHT Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 69.8 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 3.3 2.9 21.7 / 18.1 16.4 / 16.0 - Jul 1200 6.47

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 451 0.114 0.090 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.7 Jul 2100 0.0 69.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 16 PRINTING 1 0.5 Jul 2300 76 0.0 9.0 8.41
G CORRIDOR RIGHT 1 2.3 Jul 2100 376 0.0 60.8 6.18

Page 81
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G CORRIDOR RIGHT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:12PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 16 PRINTING 1 9.0 1.0 75.7 0.00 0.00 0.0 0.0 0.0
G CORRIDOR RIGHT 1 60.8 6.0 375.8 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 451.5 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 82
Air System Design Load Summary for G CORRIDOR RIGHT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:12PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 51 - 4 m² 24 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 18 - 2 m² 8 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1198 W 1197 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 700 W 700 - 0 0 -
People 7 498 396 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 247 40 0% 0 0
>> Total Zone Loads - 2712 435 - 32 0
Zone Conditioning - 2719 435 - 30 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 90 - - -90 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2809 435 - -61 0
Terminal Unit Cooling - 2809 431 - -61 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2809 431 - -61 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 83
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G CORRIDOR RIGHT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:12PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 51 - 4 m² 24 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 18 - 2 m² 8 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1198 W 1197 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 700 W 700 - 0 0 -
People 7 498 396 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 247 40 0% 0 0
>> Total Zone Loads - 2712 435 - 32 0

Page 84
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

Air System Information


Air System Name .................... G CORRIDOR LEFT Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 69.8 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 3.3 2.9 21.7 / 18.1 16.4 / 16.0 - Jul 1200 6.47

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 451 0.114 0.090 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.7 Jul 2100 0.0 69.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G CORRIDOR LEFT 1 2.3 Jul 2100 376 0.0 60.8 6.18
G 24 PRINTING 1 0.5 Jul 2300 76 0.0 9.0 8.41

Page 85
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G CORRIDOR LEFT 1 60.8 6.0 375.8 0.00 0.00 0.0 0.0 0.0
G 24 PRINTING 1 9.0 1.0 75.7 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 451.5 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 86
Air System Design Load Summary for G CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 51 - 4 m² 24 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 18 - 2 m² 8 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1198 W 1197 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 700 W 700 - 0 0 -
People 7 498 396 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 247 40 0% 0 0
>> Total Zone Loads - 2712 435 - 32 0
Zone Conditioning - 2719 435 - 30 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 90 - - -90 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2809 435 - -61 0
Terminal Unit Cooling - 2809 431 - -61 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2809 431 - -61 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 87
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 51 - 4 m² 24 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 18 - 2 m² 8 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1198 W 1197 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 700 W 700 - 0 0 -
People 7 498 396 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 247 40 0% 0 0
>> Total Zone Loads - 2712 435 - 32 0

Page 88
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 32 VIP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

Air System Information


Air System Name ....................................... G 32 VIP Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 52.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 4.2 4.2 21.8 / 15.7 14.7 / 13.0 - Jul 1500 9.54

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 496 0.125 0.099 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.2 Jul 1500 0.4 52.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 32 VIP 1 4.2 Jul 1500 496 0.4 52.0 9.54

Page 89
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 32 VIP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 32 VIP 1 52.0 5.0 496.0 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 496.0 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 90
Air System Design Load Summary for G 32 VIP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 408 - 6 m² - -
Wall Transmission 44 m² 593 - 44 m² 251 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 273 - 6 m² 118 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 52 m² 0 - 52 m² 0 -
Partitions 38 m² 1023 - 38 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 650 W 650 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 381 30 0% 0 0
>> Total Zone Loads - 4186 331 - 370 0
Zone Conditioning - 4150 331 - 87 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 99 - - -99 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4249 331 - -13 0
Terminal Unit Cooling - 4249 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4249 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 91
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 32 VIP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 408 - 6 m² - -
Wall Transmission 44 m² 593 - 44 m² 251 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 273 - 6 m² 118 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 52 m² 0 - 52 m² 0 -
Partitions 38 m² 1023 - 38 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 650 W 650 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 381 30 0% 0 0
>> Total Zone Loads - 4186 331 - 370 0

Page 92
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 29 HEADQUATER
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

Air System Information


Air System Name ................... G 29 HEADQUATER Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 62.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 6.0 6.0 21.7 / 17.3 16.6 / 15.5 - Jul 1600 15.68

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 972 0.245 0.194 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.9 Jul 1400 0.4 62.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 29 HEADQUATER 1 5.9 Jul 1400 972 0.4 62.0 15.68

Page 93
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 29 HEADQUATER
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 29 HEADQUATER 1 62.0 12.0 972.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 972.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 94
Air System Design Load Summary for G 29 HEADQUATER
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 808 - 8 m² - -
Wall Transmission 43 m² 608 - 43 m² 247 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 407 - 8 m² 176 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 62 m² 0 - 62 m² 0 -
Partitions 22 m² 592 - 22 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1550 W 1550 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 533 72 0% 0 0
>> Total Zone Loads - 5859 793 - 423 0
Zone Conditioning - 5668 793 - 164 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 194 - - -194 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5862 793 - -31 0
Terminal Unit Cooling - 5862 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 5862 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 95
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 29 HEADQUATER
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:11PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 808 - 8 m² - -
Wall Transmission 43 m² 608 - 43 m² 247 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 407 - 8 m² 176 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 62 m² 0 - 62 m² 0 -
Partitions 22 m² 592 - 22 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1550 W 1550 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 533 72 0% 0 0
>> Total Zone Loads - 5859 793 - 423 0

Page 96
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 28 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Air System Information


Air System Name ......... G 28 HEADQUATER CELL Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .............................................................. 185.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 15.3 12.9 21.8 / 17.0 14.0 / 13.6 - Jul 1700 7.43

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 1374 0.347 0.275 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 12.4 Jul 1600 0.7 185.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 28 HEADQUATER CELL 1 12.4 Jul 1600 1374 0.7 185.0 7.43

Page 97
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 28 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 28 HEADQUATER CELL 1 185.0 37.0 1374.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 1374.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 98
Air System Design Load Summary for G 28 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 643 - 5 m² - -
Wall Transmission 109 m² 1610 - 109 m² 618 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 185 m² 0 - 185 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4625 W 4625 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 37 2657 2224 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1128 222 0% 0 0
>> Total Zone Loads - 12407 2446 - 724 0
Zone Conditioning - 12244 2446 - 245 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 275 - - -275 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12519 2446 - -30 0
Terminal Unit Cooling - 12519 2422 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 12519 2422 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 99
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 28 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 643 - 5 m² - -
Wall Transmission 109 m² 1610 - 109 m² 618 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 185 m² 0 - 185 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4625 W 4625 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 37 2657 2224 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1128 222 0% 0 0
>> Total Zone Loads - 12407 2446 - 724 0

Page 100
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 27 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Air System Information


Air System Name ....... G 27 SIDE MEETING ROOM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 30.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 4.0 3.5 22.0 / 16.9 13.9 / 13.4 - Jul 1600 11.87

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 356 0.090 0.071 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.4 Jul 1600 0.2 30.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 27 SIDE MEETING ROOM 1 3.4 Jul 1600 356 0.2 30.0 11.87

Page 101
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 27 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 27 SIDE MEETING ROOM 1 30.0 8.0 356.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 356.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 102
Air System Design Load Summary for G 27 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 400 - 3 m² - -
Wall Transmission 31 m² 395 - 31 m² 173 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 163 - 3 m² 71 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1031 W 1031 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 8 574 481 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 306 48 0% 0 0
>> Total Zone Loads - 3370 529 - 244 0
Zone Conditioning - 3342 529 - 62 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 71 - - -71 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3414 529 - -10 0
Terminal Unit Cooling - 3414 525 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 3414 525 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 103
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 27 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 400 - 3 m² - -
Wall Transmission 31 m² 395 - 31 m² 173 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 163 - 3 m² 71 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1031 W 1031 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 8 574 481 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 306 48 0% 0 0
>> Total Zone Loads - 3370 529 - 244 0

Page 104
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 26 CHIEF OF JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Air System Information


Air System Name .................... G 26 CHIEF OF JOC Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .................................................................. 9.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.4 1.4 22.1 / 13.1 14.1 / 9.7 - Jul 1600 16.68

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 150 0.038 0.030 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.4 Jul 1600 0.1 9.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 26 CHIEF OF JOC 1 1.4 Jul 1600 150 0.1 9.0 16.68

Page 105
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 26 CHIEF OF JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 26 CHIEF OF JOC 1 9.0 1.0 150.1 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 150.1 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 106
Air System Design Load Summary for G 26 CHIEF OF JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 200 - 2 m² - -
Wall Transmission 7 m² 85 - 7 m² 39 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 0 - 9 m² 0 -
Partitions 13 m² 355 - 13 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 129 6 0% 0 0
>> Total Zone Loads - 1420 66 - 75 0
Zone Conditioning - 1378 66 - 25 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 30 - - -30 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1408 66 - -5 0
Terminal Unit Cooling - 1408 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1408 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 107
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 26 CHIEF OF JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 200 - 2 m² - -
Wall Transmission 7 m² 85 - 7 m² 39 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 0 - 9 m² 0 -
Partitions 13 m² 355 - 13 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 129 6 0% 0 0
>> Total Zone Loads - 1420 66 - 75 0

Page 108
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 25 JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Air System Information


Air System Name ..................................... G 25 JOC Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .............................................................. 122.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 9.0 7.5 21.9 / 18.5 16.7 / 16.4 - Jul 2000 9.84

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 1200 0.303 0.240 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 7.2 Jul 1500 0.0 122.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 25 JOC 1 7.2 Jul 1500 1200 0.0 122.0 9.84

Page 109
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 25 JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 25 JOC 1 122.0 23.0 1200.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 1200.3 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 110
Air System Design Load Summary for G 25 JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 122 m² 0 - 122 m² 0 -
Partitions 11 m² 302 - 11 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3126 W 3126 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 23 1651 1382 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 658 138 0% 0 0
>> Total Zone Loads - 7237 1521 - 0 0
Zone Conditioning - 7104 1521 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 240 - - -240 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7344 1521 - -240 0
Terminal Unit Cooling - 7344 1478 - -240 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 7344 1478 - -240 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 111
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 25 JOC
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 122 m² 0 - 122 m² 0 -
Partitions 11 m² 302 - 11 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3126 W 3126 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 23 1651 1382 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 658 138 0% 0 0
>> Total Zone Loads - 7237 1521 - 0 0

Page 112
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 23 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Air System Information


Air System Name ....... G 23 SIDE MEETING ROOM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 30.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.9 2.5 21.7 / 17.7 15.5 / 15.1 - Jul 1300 10.94

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 328 0.083 0.066 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.4 Jul 1500 0.0 30.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 23 SIDE MEETING ROOM 1 2.4 Jul 1500 328 0.0 30.0 10.94

Page 113
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 23 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 23 SIDE MEETING ROOM 1 30.0 6.0 328.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 328.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 114
Air System Design Load Summary for G 23 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 8 m² 215 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1013 W 1012 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 216 36 0% 0 0
>> Total Zone Loads - 2374 397 - 0 0
Zone Conditioning - 2390 397 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 66 - - -66 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2455 397 - -66 0
Terminal Unit Cooling - 2455 394 - -66 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2455 394 - -66 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 115
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 23 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:10PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 8 m² 215 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1013 W 1012 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 216 36 0% 0 0
>> Total Zone Loads - 2374 397 - 0 0

Page 116
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 22 HEADQUARTER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Air System Information


Air System Name ...... G 22 HEADQUARTER CELL Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 58.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 5.9 5.1 21.8 / 17.0 14.2 / 13.8 - Jul 1700 9.55

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 554 0.140 0.111 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.0 Jul 1500 0.0 58.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 22 HEADQUARTER CELL 1 5.0 Jul 1500 554 0.0 58.0 9.55

Page 117
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 22 HEADQUARTER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 22 HEADQUARTER CELL 1 58.0 12.0 553.6 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 553.6 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 118
Air System Design Load Summary for G 22 HEADQUARTER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 58 m² 0 - 58 m² 0 -
Partitions 25 m² 668 - 25 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1523 W 1522 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 455 72 0% 0 0
>> Total Zone Loads - 5007 793 - 0 0
Zone Conditioning - 4934 793 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 111 - - -111 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5045 793 - -111 0
Terminal Unit Cooling - 5045 786 - -111 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 5045 786 - -111 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 119
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 22 HEADQUARTER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 58 m² 0 - 58 m² 0 -
Partitions 25 m² 668 - 25 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1523 W 1522 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 455 72 0% 0 0
>> Total Zone Loads - 5007 793 - 0 0

Page 120
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 21 MECH ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Air System Information


Air System Name ...................... G 21 MECH ROOM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .................................................................. 8.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.2 1.2 22.1 / 11.6 13.9 / 8.0 - Jul 1500 14.82

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 119 0.030 0.024 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.1 Jul 1500 0.0 8.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 21 MECH ROOM 1 1.1 Jul 1500 119 0.0 8.0 14.82

Page 121
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 21 MECH ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 21 MECH ROOM 1 8.0 1.0 118.6 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 118.6 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 122
Air System Design Load Summary for G 21 MECH ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 8 m² 0 - 8 m² 0 -
Partitions 6 m² 172 - 6 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 500 W 500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 104 4 0% 0 0
>> Total Zone Loads - 1144 39 - 0 0
Zone Conditioning - 1136 39 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 24 - - -24 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1160 39 - -24 0
Terminal Unit Cooling - 1160 0 - -24 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1160 0 - -24 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 123
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 21 MECH ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 8 m² 0 - 8 m² 0 -
Partitions 6 m² 172 - 6 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 500 W 500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 104 4 0% 0 0
>> Total Zone Loads - 1144 39 - 0 0

Page 124
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 19 DRIVER ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Air System Information


Air System Name ................... G 19 DRIVER ROOM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .................................................................. 8.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.2 1.2 22.1 / 11.6 13.9 / 8.0 - Jul 1500 14.82

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 119 0.030 0.024 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.1 Jul 1500 0.0 8.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 19 DRIVER ROOM 1 1.1 Jul 1500 119 0.0 8.0 14.82

Page 125
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 19 DRIVER ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 19 DRIVER ROOM 1 8.0 1.0 118.6 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 118.6 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 126
Air System Design Load Summary for G 19 DRIVER ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 8 m² 0 - 8 m² 0 -
Partitions 6 m² 172 - 6 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 500 W 500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 104 4 0% 0 0
>> Total Zone Loads - 1144 39 - 0 0
Zone Conditioning - 1136 39 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 24 - - -24 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1160 39 - -24 0
Terminal Unit Cooling - 1160 0 - -24 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1160 0 - -24 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 127
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 19 DRIVER ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 8 m² 0 - 8 m² 0 -
Partitions 6 m² 172 - 6 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 500 W 500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 104 4 0% 0 0
>> Total Zone Loads - 1144 39 - 0 0

Page 128
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 18 ELECTRICAL AND UPS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Air System Information


Air System Name ..... G 18 ELECTRICAL AND UPS Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 44.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.7 2.7 21.9 / 8.2 16.7 / 5.6 - Jul 1900 9.69

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 426 0.108 0.085 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.6 Jul 1900 0.1 44.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 18 ELECTRICAL AND UPS 1 2.6 Jul 1900 426 0.1 44.0 9.69

Page 129
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 18 ELECTRICAL AND UPS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 18 ELECTRICAL AND UPS 1 44.0 1.0 426.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 426.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 130
Air System Design Load Summary for G 18 ELECTRICAL AND UPS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 213 - 16 m² 89 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 38 - 5 m² 17 -
Floor Transmission 44 m² 0 - 44 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1210 W 1210 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 800 W 800 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 233 4 0% 0 0
>> Total Zone Loads - 2562 39 - 106 0
Zone Conditioning - 2588 39 - 73 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 85 - - -85 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2673 39 - -13 0
Terminal Unit Cooling - 2673 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2673 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 131
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 18 ELECTRICAL AND UPS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:09PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 213 - 16 m² 89 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 38 - 5 m² 17 -
Floor Transmission 44 m² 0 - 44 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1210 W 1210 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 800 W 800 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 233 4 0% 0 0
>> Total Zone Loads - 2562 39 - 106 0

Page 132
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 17 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Air System Information


Air System Name ....... G 17 SIDE MEETING ROOM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 30.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.9 2.5 21.7 / 17.7 15.5 / 15.1 - Jul 1300 10.94

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 328 0.083 0.066 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.4 Jul 1500 0.0 30.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 17 SIDE MEETING ROOM 1 2.4 Jul 1500 328 0.0 30.0 10.94

Page 133
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 17 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 17 SIDE MEETING ROOM 1 30.0 6.0 328.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 328.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 134
Air System Design Load Summary for G 17 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 8 m² 215 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1013 W 1012 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 216 36 0% 0 0
>> Total Zone Loads - 2374 397 - 0 0
Zone Conditioning - 2390 397 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 66 - - -66 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2455 397 - -66 0
Terminal Unit Cooling - 2455 394 - -66 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2455 394 - -66 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 135
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 17 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 8 m² 215 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1013 W 1012 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 216 36 0% 0 0
>> Total Zone Loads - 2374 397 - 0 0

Page 136
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 15 SITCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Air System Information


Air System Name ................................ G 15 SITCEN Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .............................................................. 122.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 9.0 7.5 21.9 / 18.5 16.7 / 16.4 - Jul 2000 9.84

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 1200 0.303 0.240 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 7.2 Jul 1500 0.0 122.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 15 SITCEN 1 7.2 Jul 1500 1200 0.0 122.0 9.84

Page 137
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 15 SITCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 15 SITCEN 1 122.0 23.0 1200.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 1200.3 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 138
Air System Design Load Summary for G 15 SITCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 122 m² 0 - 122 m² 0 -
Partitions 11 m² 302 - 11 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3126 W 3126 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 23 1651 1382 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 658 138 0% 0 0
>> Total Zone Loads - 7237 1521 - 0 0
Zone Conditioning - 7104 1521 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 240 - - -240 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7344 1521 - -240 0
Terminal Unit Cooling - 7344 1478 - -240 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 7344 1478 - -240 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 139
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 15 SITCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 122 m² 0 - 122 m² 0 -
Partitions 11 m² 302 - 11 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3126 W 3126 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 23 1651 1382 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 658 138 0% 0 0
>> Total Zone Loads - 7237 1521 - 0 0

Page 140
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 14 CHIEF OF EXCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Air System Information


Air System Name ............... G 14 CHIEF OF EXCEN Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .................................................................. 9.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.4 1.4 22.1 / 13.1 14.1 / 9.7 - Jul 1600 16.68

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 150 0.038 0.030 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.4 Jul 1600 0.1 9.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 14 CHIEF OF EXCEN 1 1.4 Jul 1600 150 0.1 9.0 16.68

Page 141
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 14 CHIEF OF EXCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 14 CHIEF OF EXCEN 1 9.0 1.0 150.1 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 150.1 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 142
Air System Design Load Summary for G 14 CHIEF OF EXCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 200 - 2 m² - -
Wall Transmission 7 m² 85 - 7 m² 39 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 0 - 9 m² 0 -
Partitions 13 m² 355 - 13 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 129 6 0% 0 0
>> Total Zone Loads - 1420 66 - 75 0
Zone Conditioning - 1378 66 - 25 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 30 - - -30 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1408 66 - -5 0
Terminal Unit Cooling - 1408 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1408 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 143
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 14 CHIEF OF EXCEN
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 200 - 2 m² - -
Wall Transmission 7 m² 85 - 7 m² 39 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 0 - 9 m² 0 -
Partitions 13 m² 355 - 13 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 129 6 0% 0 0
>> Total Zone Loads - 1420 66 - 75 0

Page 144
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 13 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Air System Information


Air System Name ....... G 13 SIDE MEETING ROOM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 30.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 4.0 3.5 22.0 / 16.9 13.9 / 13.4 - Jul 1600 11.87

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 356 0.090 0.071 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.4 Jul 1600 0.2 30.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 13 SIDE MEETING ROOM 1 3.4 Jul 1600 356 0.2 30.0 11.87

Page 145
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 13 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 13 SIDE MEETING ROOM 1 30.0 8.0 356.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 356.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 146
Air System Design Load Summary for G 13 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 400 - 3 m² - -
Wall Transmission 31 m² 395 - 31 m² 173 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 163 - 3 m² 71 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1031 W 1031 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 8 574 481 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 306 48 0% 0 0
>> Total Zone Loads - 3370 529 - 244 0
Zone Conditioning - 3342 529 - 62 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 71 - - -71 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3414 529 - -10 0
Terminal Unit Cooling - 3414 525 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 3414 525 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 147
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 13 SIDE MEETING ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 400 - 3 m² - -
Wall Transmission 31 m² 395 - 31 m² 173 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 163 - 3 m² 71 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1031 W 1031 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 8 574 481 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 306 48 0% 0 0
>> Total Zone Loads - 3370 529 - 244 0

Page 148
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 12 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Air System Information


Air System Name ......... G 12 HEADQUATER CELL Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .............................................................. 185.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 15.3 12.9 21.8 / 17.0 14.1 / 13.6 - Jul 1600 7.50

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 1387 0.350 0.277 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 12.5 Jul 1600 0.7 185.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 12 HEADQUATER CELL 1 12.5 Jul 1600 1387 0.7 185.0 7.50

Page 149
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 12 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 12 HEADQUATER CELL 1 185.0 37.0 1386.8 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 1386.8 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 150
Air System Design Load Summary for G 12 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 865 - 5 m² - -
Wall Transmission 109 m² 1403 - 109 m² 618 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 185 m² 0 - 185 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4625 W 4625 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 37 2657 2224 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1129 222 0% 0 0
>> Total Zone Loads - 12422 2446 - 724 0
Zone Conditioning - 12261 2446 - 247 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 277 - - -277 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12538 2446 - -30 0
Terminal Unit Cooling - 12538 2440 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 12538 2440 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 151
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 12 HEADQUATER CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:08PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 865 - 5 m² - -
Wall Transmission 109 m² 1403 - 109 m² 618 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 185 m² 0 - 185 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4625 W 4625 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 37 2657 2224 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1129 222 0% 0 0
>> Total Zone Loads - 12422 2446 - 724 0

Page 152
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 11 RESPONCE CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Air System Information


Air System Name .............. G 11 RESPONCE CELL Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 62.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 6.9 6.1 21.8 / 16.7 13.8 / 13.3 - Jul 1500 10.15

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 629 0.159 0.126 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 6.1 Jul 1600 0.4 62.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 11 RESPONCE CELL 1 6.1 Jul 1600 629 0.4 62.0 10.15

Page 153
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 11 RESPONCE CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 11 RESPONCE CELL 1 62.0 12.0 629.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 629.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 154
Air System Design Load Summary for G 11 RESPONCE CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1029 - 8 m² - -
Wall Transmission 43 m² 561 - 43 m² 247 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 407 - 8 m² 176 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 62 m² 0 - 62 m² 0 -
Partitions 22 m² 592 - 22 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1550 W 1550 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 550 72 0% 0 0
>> Total Zone Loads - 6051 793 - 423 0
Zone Conditioning - 6013 793 - 109 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 126 - - -126 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6139 793 - -17 0
Terminal Unit Cooling - 6139 788 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 6139 788 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 155
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 11 RESPONCE CELL
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1029 - 8 m² - -
Wall Transmission 43 m² 561 - 43 m² 247 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 407 - 8 m² 176 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 62 m² 0 - 62 m² 0 -
Partitions 22 m² 592 - 22 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1550 W 1550 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 550 72 0% 0 0
>> Total Zone Loads - 6051 793 - 423 0

Page 156
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 07 PANTRY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Air System Information


Air System Name .............................. G 07 PANTRY Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .................................................................. 9.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.6 1.3 23.1 / 17.8 13.9 / 13.5 - Jul 2300 12.61

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 113 0.029 0.023 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.2 Jul 2300 0.0 9.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 07 PANTRY 1 1.2 Jul 2300 113 0.0 9.0 12.61

Page 157
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 07 PANTRY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 07 PANTRY 1 9.0 1.0 113.5 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 113.5 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 158
Air System Design Load Summary for G 07 PANTRY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 0 - 9 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 300 300 - 0 0
Safety Factor 10% / 10% 112 36 0% 0 0
>> Total Zone Loads - 1231 396 - 0 0
Zone Conditioning - 1231 396 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 23 - - -23 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1254 396 - -23 0
Terminal Unit Cooling - 1254 393 - -23 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1254 393 - -23 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 159
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 07 PANTRY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 0 - 9 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 300 300 - 0 0
Safety Factor 10% / 10% 112 36 0% 0 0
>> Total Zone Loads - 1231 396 - 0 0

Page 160
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 06 SECURITY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Air System Information


Air System Name ........................... G 06 SECURITY Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .................................................................. 7.2 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 0.8 0.7 22.8 / 16.7 13.5 / 12.9 - Jul 1800 8.59

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 62 0.016 0.012 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 0.7 Jul 2100 0.0 7.2

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 06 SECURITY 1 0.7 Jul 2100 62 0.0 7.2 8.59

Page 161
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 06 SECURITY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 06 SECURITY 1 7.2 1.0 61.9 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 61.9 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 162
Air System Design Load Summary for G 06 SECURITY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 6 m² 79 - 6 m² 36 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 0 - 7 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 252 W 252 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 60 6 0% 0 0
>> Total Zone Loads - 663 66 - 36 0
Zone Conditioning - 660 66 - 11 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 12 - - -12 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 672 66 - -1 0
Terminal Unit Cooling - 672 66 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 672 66 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 163
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 06 SECURITY
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 6 m² 79 - 6 m² 36 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 0 - 7 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 252 W 252 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 60 6 0% 0 0
>> Total Zone Loads - 663 66 - 36 0

Page 164
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for G 02 Enterance & Foyer
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Air System Information


Air System Name ............. G 02 Enterance & Foyer Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .............................................................. 136.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 6.6 5.1 21.7 / 18.5 16.5 / 16.2 - Jul 1700 5.95

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 810 0.204 0.162 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.9 Jul 1500 0.0 136.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
G 02 ENTERANCE & FOYER 1 4.9 Jul 1500 810 0.0 136.0 5.95

Page 165
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for G 02 Enterance & Foyer
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
G 02 ENTERANCE & FOYER 1 136.0 5.0 809.8 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 809.8 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 166
Air System Design Load Summary for G 02 Enterance & Foyer
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 72 m² 0 - 72 m² 0 -
Partitions 49 m² 1319 - 49 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 850 W 850 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 5 769 1356 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 444 136 0% 0 0
>> Total Zone Loads - 4882 1491 - 0 0
Zone Conditioning - 4664 1491 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 162 - - -162 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4826 1491 - -162 0
Terminal Unit Cooling - 4826 1480 - -162 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4826 1480 - -162 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 167
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for G 02 Enterance & Foyer
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:07PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 72 m² 0 - 72 m² 0 -
Partitions 49 m² 1319 - 49 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 850 W 850 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 5 769 1356 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 444 136 0% 0 0
>> Total Zone Loads - 4882 1491 - 0 0

Page 168
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 01 CCTV ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:16PM

Air System Information


Air System Name .................... 1 F 01 CCTV ROOM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 24.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.2 2.2 21.7 / 10.8 13.9 / 7.3 - Jul 1900 9.81

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 235 0.059 0.047 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.1 Jul 1800 0.2 24.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 01 CCTV ROOM 1 2.1 Jul 1800 235 0.2 24.0 9.81

Page 169
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 01 CCTV ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:16PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 01 CCTV ROOM 1 24.0 1.0 235.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 235.3 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 170
Air System Design Load Summary for 1 F 01 CCTV ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:16PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 18 m² 233 - 18 m² 102 -
Roof Transmission 24 m² 280 - 24 m² 105 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 269 - 10 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 753 W 753 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 191 6 0% 0 0
>> Total Zone Loads - 2098 66 - 207 0
Zone Conditioning - 2076 66 - 41 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 47 - - -47 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2123 66 - -6 0
Terminal Unit Cooling - 2123 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2123 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 171
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 01 CCTV ROOM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:16PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 18 m² 233 - 18 m² 102 -
Roof Transmission 24 m² 280 - 24 m² 105 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 269 - 10 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 753 W 753 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 191 6 0% 0 0
>> Total Zone Loads - 2098 66 - 207 0

Page 172
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F TRANSLATOR
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:25PM

Air System Information


Air System Name ....................... 1 F TRANSLATOR Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 10.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.2 1.1 21.7 / 16.4 13.3 / 12.8 - Jul 0200 10.92

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 109 0.028 0.022 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.1 Jul 2200 0.0 10.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F TRANSLATOR 1 1.1 Jul 2200 109 0.0 10.0 10.92

Page 173
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F TRANSLATOR
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:25PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F TRANSLATOR 1 10.0 2.0 109.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 109.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 174
Air System Design Load Summary for 1 F TRANSLATOR
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:25PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 117 - 10 m² 44 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 375 W 375 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 94 12 0% 0 0
>> Total Zone Loads - 1029 132 - 44 0
Zone Conditioning - 1022 132 - 19 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 22 - - -22 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1044 132 - -3 0
Terminal Unit Cooling - 1044 131 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1044 131 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 175
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F TRANSLATOR
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:25PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 117 - 10 m² 44 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 375 W 375 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 94 12 0% 0 0
>> Total Zone Loads - 1029 132 - 44 0

Page 176
Hourly Analysis Program v5.01 Page 4 of 4
Ventilation Sizing Summary for 1 F CORRIDOR RIGHT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F CORRIDOR RIGHT 1 73.0 2.0 624.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 624.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 177
Air System Design Load Summary for 1 F CORRIDOR RIGHT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 800 - 7 m² - -
Wall Transmission 44 m² 541 - 44 m² 252 -
Roof Transmission 73 m² 850 - 73 m² 319 -
Window Transmission 7 m² 325 - 7 m² 141 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1195 W 1195 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 396 12 0% 0 0
>> Total Zone Loads - 4352 132 - 712 0
Zone Conditioning - 4248 132 - 112 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 125 - - -125 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4373 132 - -13 0
Terminal Unit Cooling - 4373 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4373 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 178
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F CORRIDOR RIGHT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 800 - 7 m² - -
Wall Transmission 44 m² 541 - 44 m² 252 -
Roof Transmission 73 m² 850 - 73 m² 319 -
Window Transmission 7 m² 325 - 7 m² 141 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1195 W 1195 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 396 12 0% 0 0
>> Total Zone Loads - 4352 132 - 712 0

Page 179
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Air System Information


Air System Name .................. 1 F CORRIDOR LEFT Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 56.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.6 2.6 21.8 / 12.2 15.5 / 9.6 - Jul 0200 6.15

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 344 0.087 0.069 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.5 Jul 2200 0.2 56.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F CORRIDOR LEFT 1 2.5 Jul 2200 344 0.2 56.0 6.15

Page 180
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F CORRIDOR LEFT 1 56.0 2.0 344.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 344.3 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 181
Air System Design Load Summary for 1 F CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 56 m² 652 - 56 m² 245 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 840 W 840 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 214 12 0% 0 0
>> Total Zone Loads - 2350 132 - 245 0
Zone Conditioning - 2347 132 - 63 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 69 - - -69 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2416 132 - -6 0
Terminal Unit Cooling - 2416 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2416 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 182
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F CORRIDOR LEFT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 56 m² 652 - 56 m² 245 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 840 W 840 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 214 12 0% 0 0
>> Total Zone Loads - 2350 132 - 245 0

Page 183
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F CORRIDOR CENTER ,F13
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Air System Information


Air System Name .... 1 F CORRIDOR CENTER ,F13 Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 78.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 5.7 5.7 21.8 / 11.1 14.7 / 7.9 - Jul 1500 8.60

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 670 0.169 0.134 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.7 Jul 1600 0.3 78.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F CORRIDOR CENTER 1 4.5 Jul 1600 533 0.3 72.0 7.41
1 F 13 ELEC ROOM 1 1.2 Jul 1600 137 0.0 6.0 22.82

Page 184
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F CORRIDOR CENTER ,F13
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F CORRIDOR CENTER 1 72.0 2.0 533.5 0.00 0.00 0.0 0.0 0.0
1 F 13 ELEC ROOM 1 6.0 1.0 136.9 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 670.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 185
Air System Design Load Summary for 1 F CORRIDOR CENTER ,F13
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 78 m² 909 - 78 m² 341 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 68 m² 1831 - 68 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1265 W 1265 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 900 W 900 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 512 18 0% 0 0
>> Total Zone Loads - 5632 198 - 341 0
Zone Conditioning - 5582 198 - 118 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 134 - - -134 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5716 198 - -16 0
Terminal Unit Cooling - 5716 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 5716 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 186
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F CORRIDOR CENTER ,F13
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 78 m² 909 - 78 m² 341 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 68 m² 1831 - 68 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1265 W 1265 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 900 W 900 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 512 18 0% 0 0
>> Total Zone Loads - 5632 198 - 341 0

Page 187
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 32 DIRECTOR OF STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Air System Information


Air System Name ..... 1 F 32 DIRECTOR OF STAFF Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 28.6 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 3.9 3.9 22.1 / 9.6 13.1 / 5.3 - Jul 1500 12.42

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 355 0.090 0.071 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.9 Jul 1500 0.4 28.6

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 32 DIRECTOR OF STAFF 1 3.9 Jul 1500 355 0.4 28.6 12.42

Page 188
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 32 DIRECTOR OF STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 32 DIRECTOR OF STAFF 1 28.6 1.0 355.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 355.3 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 189
Air System Design Load Summary for 1 F 32 DIRECTOR OF STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 686 - 7 m² - -
Wall Transmission 28 m² 389 - 28 m² 157 -
Roof Transmission 29 m² 333 - 29 m² 125 -
Window Transmission 7 m² 325 - 7 m² 141 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 377 - 14 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1073 W 1072 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 351 6 0% 0 0
>> Total Zone Loads - 3856 66 - 423 0
Zone Conditioning - 3783 66 - 61 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 71 - - -71 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3854 66 - -10 0
Terminal Unit Cooling - 3854 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 3854 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 190
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 32 DIRECTOR OF STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 686 - 7 m² - -
Wall Transmission 28 m² 389 - 28 m² 157 -
Roof Transmission 29 m² 333 - 29 m² 125 -
Window Transmission 7 m² 325 - 7 m² 141 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 377 - 14 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1073 W 1072 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 351 6 0% 0 0
>> Total Zone Loads - 3856 66 - 423 0

Page 191
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 31 DOS STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Air System Information


Air System Name ...................... 1 F 31 DOS STAFF Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 34.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 3.9 3.5 21.8 / 17.1 14.6 / 14.1 - Jul 1900 11.77

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 400 0.101 0.080 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.4 Jul 1900 0.3 34.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 31 DOS STAFF 1 3.4 Jul 1900 400 0.3 34.0 11.77

Page 192
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 31 DOS STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 31 DOS STAFF 1 34.0 6.0 400.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 400.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 193
Air System Design Load Summary for 1 F 31 DOS STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 26 m² 406 - 26 m² 148 -
Roof Transmission 34 m² 396 - 34 m² 149 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 7 m² 188 - 7 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1105 W 1105 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 303 36 0% 0 0
>> Total Zone Loads - 3329 397 - 296 0
Zone Conditioning - 3334 397 - 69 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 80 - - -80 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3414 397 - -11 0
Terminal Unit Cooling - 3414 395 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 3414 395 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 194
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 31 DOS STAFF
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:23PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 26 m² 406 - 26 m² 148 -
Roof Transmission 34 m² 396 - 34 m² 149 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 7 m² 188 - 7 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1105 W 1105 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 303 36 0% 0 0
>> Total Zone Loads - 3329 397 - 296 0

Page 195
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 30 PLANNING DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Air System Information


Air System Name ....... 1 F 30 PLANNING DIVISION Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 53.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 6.7 6.1 22.0 / 16.7 13.9 / 13.4 - Jul 0800 11.68

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 625 0.158 0.125 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 6.0 Jul 0800 0.5 53.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 30 PLANNING DIVISION 1 6.0 Jul 0800 625 0.5 53.5 11.68

Page 196
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 30 PLANNING DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 30 PLANNING DIVISION 1 53.5 10.0 624.9 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 624.9 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 197
Air System Design Load Summary for 1 F 30 PLANNING DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1045 - 8 m² - -
Wall Transmission 16 m² 251 - 16 m² 91 -
Roof Transmission 54 m² 623 - 54 m² 234 -
Window Transmission 8 m² 384 - 8 m² 166 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1605 W 1605 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 513 60 0% 0 0
>> Total Zone Loads - 5638 661 - 492 0
Zone Conditioning - 5585 661 - 109 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 125 - - -125 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5710 661 - -16 0
Terminal Unit Cooling - 5710 654 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 5710 654 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 198
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 30 PLANNING DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1045 - 8 m² - -
Wall Transmission 16 m² 251 - 16 m² 91 -
Roof Transmission 54 m² 623 - 54 m² 234 -
Window Transmission 8 m² 384 - 8 m² 166 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1605 W 1605 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 513 60 0% 0 0
>> Total Zone Loads - 5638 661 - 492 0

Page 199
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 29 SUPPORT DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Air System Information


Air System Name ........ 1 F 29 SUPPORT DIVISION Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 47.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 4.7 4.1 21.8 / 16.8 14.0 / 13.6 - Jul 2000 9.33

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 439 0.111 0.088 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.0 Jul 2100 0.3 47.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 29 SUPPORT DIVISION 1 4.0 Jul 2100 439 0.3 47.0 9.33

Page 200
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 29 SUPPORT DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 29 SUPPORT DIVISION 1 47.0 9.0 438.7 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 438.7 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 201
Air System Design Load Summary for 1 F 29 SUPPORT DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 393 - 25 m² 143 -
Roof Transmission 47 m² 548 - 47 m² 206 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1410 W 1410 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 9 646 541 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 350 54 0% 0 0
>> Total Zone Loads - 3847 595 - 349 0
Zone Conditioning - 3752 595 - 78 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 88 - - -88 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3840 595 - -10 0
Terminal Unit Cooling - 3840 591 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 3840 591 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 202
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 29 SUPPORT DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 393 - 25 m² 143 -
Roof Transmission 47 m² 548 - 47 m² 206 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1410 W 1410 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 9 646 541 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 350 54 0% 0 0
>> Total Zone Loads - 3847 595 - 349 0

Page 203
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 28 CHIEF OF SUPPORT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Air System Information


Air System Name ....... 1 F 28 CHIEF OF SUPPORT Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 20.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.0 2.0 21.8 / 8.8 14.7 / 5.4 - Jul 0900 11.92

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 238 0.060 0.048 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.0 Jul 0800 0.2 20.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 28 CHIEF OF SUPPORT 1 2.0 Jul 0800 238 0.2 20.0 11.92

Page 204
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 28 CHIEF OF SUPPORT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 28 CHIEF OF SUPPORT 1 20.0 1.0 238.5 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 238.5 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 205
Air System Design Load Summary for 1 F 28 CHIEF OF SUPPORT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 222 - 2 m² - -
Wall Transmission 9 m² 141 - 9 m² 51 -
Roof Transmission 20 m² 233 - 20 m² 87 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 775 W 775 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 177 6 0% 0 0
>> Total Zone Loads - 1951 66 - 174 0
Zone Conditioning - 1973 66 - 41 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 48 - - -48 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2021 66 - -6 0
Terminal Unit Cooling - 2021 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2021 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 206
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 28 CHIEF OF SUPPORT
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 222 - 2 m² - -
Wall Transmission 9 m² 141 - 9 m² 51 -
Roof Transmission 20 m² 233 - 20 m² 87 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 775 W 775 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 177 6 0% 0 0
>> Total Zone Loads - 1951 66 - 174 0

Page 207
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 27 CHIEF OF C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Air System Information


Air System Name ................. 1 F 27 CHIEF OF C4IS Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 19.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.8 2.8 22.0 / 10.2 14.0 / 6.5 - Jul 1600 14.89

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 290 0.073 0.058 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.8 Jul 1600 0.4 19.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 27 CHIEF OF C4IS 1 2.8 Jul 1600 290 0.4 19.5 14.89

Page 208
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 27 CHIEF OF C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 27 CHIEF OF C4IS 1 19.5 1.0 290.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 290.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 209
Air System Design Load Summary for 1 F 27 CHIEF OF C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 643 - 5 m² - -
Wall Transmission 40 m² 545 - 40 m² 228 -
Roof Transmission 20 m² 227 - 20 m² 85 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 548 W 548 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 253 6 0% 0 0
>> Total Zone Loads - 2782 66 - 419 0
Zone Conditioning - 2740 66 - 50 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 58 - - -58 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2798 66 - -8 0
Terminal Unit Cooling - 2798 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2798 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 210
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 27 CHIEF OF C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:22PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 643 - 5 m² - -
Wall Transmission 40 m² 545 - 40 m² 228 -
Roof Transmission 20 m² 227 - 20 m² 85 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 548 W 548 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 253 6 0% 0 0
>> Total Zone Loads - 2782 66 - 419 0

Page 211
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 26 CHIEF PLANNING
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

Air System Information


Air System Name ............ 1 F 26 CHIEF PLANNING Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 17.7 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.7 1.7 21.8 / 11.5 14.6 / 8.3 - Jul 1600 11.36

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 201 0.051 0.040 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.7 Jul 1600 0.2 17.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 26 CHIEF PLANNING 1 1.7 Jul 1600 201 0.2 17.7 11.36

Page 212
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 26 CHIEF PLANNING
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 26 CHIEF PLANNING 1 17.7 1.0 201.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 201.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 213
Air System Design Load Summary for 1 F 26 CHIEF PLANNING
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 200 - 2 m² - -
Wall Transmission 18 m² 214 - 18 m² 100 -
Roof Transmission 18 m² 206 - 18 m² 77 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 150 6 0% 0 0
>> Total Zone Loads - 1654 66 - 212 0
Zone Conditioning - 1657 66 - 35 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 40 - - -40 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1697 66 - -5 0
Terminal Unit Cooling - 1697 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1697 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 214
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 26 CHIEF PLANNING
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 200 - 2 m² - -
Wall Transmission 18 m² 214 - 18 m² 100 -
Roof Transmission 18 m² 206 - 18 m² 77 -
Window Transmission 2 m² 81 - 2 m² 35 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 150 6 0% 0 0
>> Total Zone Loads - 1654 66 - 212 0

Page 215
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 24 CBT SYSTEM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

Air System Information


Air System Name ................... 1 F 24 CBT SYSTEM Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 63.2 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 8.8 7.1 21.8 / 17.2 14.1 / 13.7 - Jul 1600 12.20

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 771 0.194 0.154 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 7.0 Jul 1600 0.6 63.2

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 24 CBT SYSTEM 1 7.0 Jul 1600 771 0.6 63.2 12.20

Page 216
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 24 CBT SYSTEM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 24 CBT SYSTEM 1 63.2 25.0 770.9 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 770.9 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 217
Air System Design Load Summary for 1 F 24 CBT SYSTEM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 600 - 5 m² - -
Wall Transmission 33 m² 404 - 33 m² 188 -
Roof Transmission 63 m² 736 - 63 m² 276 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1442 W 1442 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 25 1795 1503 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 622 150 0% 0 0
>> Total Zone Loads - 6844 1653 - 570 0
Zone Conditioning - 6769 1653 - 134 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 154 - - -154 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6923 1653 - -21 0
Terminal Unit Cooling - 6923 1645 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 6923 1645 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 218
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 24 CBT SYSTEM
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 600 - 5 m² - -
Wall Transmission 33 m² 404 - 33 m² 188 -
Roof Transmission 63 m² 736 - 63 m² 276 -
Window Transmission 5 m² 244 - 5 m² 106 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1442 W 1442 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 25 1795 1503 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 622 150 0% 0 0
>> Total Zone Loads - 6844 1653 - 570 0

Page 219
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 23 MEDIA/STUDIO
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

Air System Information


Air System Name ................ 1 F 23 MEDIA/STUDIO Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 56.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 5.1 4.3 21.7 / 17.7 15.4 / 15.0 - Jul 0000 9.95

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 562 0.142 0.112 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Jul 2200 0.2 56.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 23 MEDIA/STUDIO 1 4.1 Jul 2200 562 0.2 56.5 9.95

Page 220
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 23 MEDIA/STUDIO
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 23 MEDIA/STUDIO 1 56.5 3.0 562.1 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 562.1 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 221
Air System Design Load Summary for 1 F 23 MEDIA/STUDIO
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 57 m² 658 - 57 m² 247 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1448 W 1448 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 3 462 813 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 357 81 0% 0 0
>> Total Zone Loads - 3924 895 - 247 0
Zone Conditioning - 3963 895 - 97 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 112 - - -112 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4075 895 - -15 0
Terminal Unit Cooling - 4075 887 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4075 887 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 222
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 23 MEDIA/STUDIO
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:21PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 57 m² 658 - 57 m² 247 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1448 W 1448 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 3 462 813 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 357 81 0% 0 0
>> Total Zone Loads - 3924 895 - 247 0

Page 223
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 22 C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:20PM

Air System Information


Air System Name .................................. 1 F 22 C4IS Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 56.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 5.6 4.7 21.7 / 17.5 15.0 / 14.6 - Jul 0100 10.36

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 585 0.148 0.117 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.6 Jul 2200 0.2 56.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 22 C4IS 1 4.6 Jul 2200 585 0.2 56.5 10.36

Page 224
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 22 C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:20PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 22 C4IS 1 56.5 13.0 585.1 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 585.1 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 225
Air System Design Load Summary for 1 F 22 C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:20PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 57 m² 658 - 57 m² 247 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1448 W 1448 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 13 933 781 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 404 78 0% 0 0
>> Total Zone Loads - 4443 859 - 247 0
Zone Conditioning - 4376 859 - 101 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 117 - - -117 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4493 859 - -16 0
Terminal Unit Cooling - 4493 842 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4493 842 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 226
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 22 C4IS
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:20PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 57 m² 658 - 57 m² 247 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1448 W 1448 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 13 933 781 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 404 78 0% 0 0
>> Total Zone Loads - 4443 859 - 247 0

Page 227
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 20 & 21 REGISTRY /CLASSI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

Air System Information


Air System Name 1 F 20 & 21 REGISTRY /CLASSI Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 32.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 3.0 3.0 21.7 / 15.1 14.0 / 12.1 - Jul 2200 9.89

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 321 0.081 0.064 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.9 Jul 2000 0.1 32.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 20 REGISRY 1 1.7 Jul 2200 183 0.1 20.5 8.92
1 F 21 CLASSIFIED DOCS 1 1.3 Jul 1700 139 0.1 12.0 11.55

Page 228
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 20 & 21 REGISTRY /CLASSI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 20 REGISRY 1 20.5 2.0 182.8 0.00 0.00 0.0 0.0 0.0
1 F 21 CLASSIFIED DOCS 1 12.0 1.0 138.6 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 321.4 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 229
Air System Design Load Summary for 1 F 20 & 21 REGISTRY /CLASSI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 33 m² 379 - 33 m² 142 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 6 m² 162 - 6 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 550 W 550 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 259 18 0% 0 0
>> Total Zone Loads - 2848 198 - 142 0
Zone Conditioning - 2862 198 - 55 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 64 - - -64 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2926 198 - -9 0
Terminal Unit Cooling - 2926 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2926 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 230
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 20 & 21 REGISTRY /CLASSI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 33 m² 379 - 33 m² 142 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 6 m² 162 - 6 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 550 W 550 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 259 18 0% 0 0
>> Total Zone Loads - 2848 198 - 142 0

Page 231
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 19 LADIES OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

Air System Information


Air System Name ............... 1 F 19 LADIES OFFICE Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 31.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.8 2.6 21.7 / 17.2 15.0 / 14.6 - Jul 1500 10.40

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 322 0.081 0.064 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.5 Jul 1800 0.1 31.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 19 LADIES OFFICE 1 2.5 Jul 1800 322 0.1 31.0 10.40

Page 232
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 19 LADIES OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 19 LADIES OFFICE 1 31.0 4.0 322.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 322.3 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 233
Air System Design Load Summary for 1 F 19 LADIES OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 31 m² 361 - 31 m² 136 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 280 - 10 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1046 W 1046 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 227 24 0% 0 0
>> Total Zone Loads - 2502 264 - 136 0
Zone Conditioning - 2527 264 - 55 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 64 - - -64 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2591 264 - -9 0
Terminal Unit Cooling - 2591 252 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2591 252 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 234
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 19 LADIES OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 31 m² 361 - 31 m² 136 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 280 - 10 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1046 W 1046 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 227 24 0% 0 0
>> Total Zone Loads - 2502 264 - 136 0

Page 235
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 12 MOSQUE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

Air System Information


Air System Name .......................... 1 F 12 MOSQUE Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 57.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 4.7 3.7 21.7 / 17.7 15.0 / 14.6 - Jul 1900 8.00

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 460 0.116 0.092 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.6 Jul 2200 0.3 57.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 12 MOSQUE 1 3.6 Jul 2200 460 0.3 57.5 8.00

Page 236
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 12 MOSQUE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 12 MOSQUE 1 57.5 15.0 459.9 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 459.9 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 237
Air System Design Load Summary for 1 F 12 MOSQUE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 58 m² 670 - 58 m² 252 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 898 W 898 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 15 1077 902 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 315 90 0% 0 0
>> Total Zone Loads - 3460 992 - 252 0
Zone Conditioning - 3498 992 - 82 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 92 - - -92 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3590 992 - -10 0
Terminal Unit Cooling - 3590 989 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 3590 989 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 238
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 12 MOSQUE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:19PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 58 m² 670 - 58 m² 252 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 898 W 898 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 15 1077 902 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 315 90 0% 0 0
>> Total Zone Loads - 3460 992 - 252 0

Page 239
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 11 ANALYST BRANCH
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

Air System Information


Air System Name ......... 1 F 11 ANALYST BRANCH Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 46.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 3.5 2.9 21.9 / 18.5 16.7 / 16.4 - Jul 2200 9.94

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 457 0.115 0.091 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.8 Jul 2200 0.2 46.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 11 ANALYST BRANCH 1 2.8 Jul 2200 457 0.2 46.0 9.94

Page 240
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 11 ANALYST BRANCH
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 11 ANALYST BRANCH 1 46.0 9.0 457.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 457.3 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 241
Air System Design Load Summary for 1 F 11 ANALYST BRANCH
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 46 m² 536 - 46 m² 201 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 719 W 719 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 9 646 541 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 240 54 0% 0 0
>> Total Zone Loads - 2641 595 - 201 0
Zone Conditioning - 2580 595 - 79 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 91 - - -91 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2672 595 - -12 0
Terminal Unit Cooling - 2672 590 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2672 590 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 242
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 11 ANALYST BRANCH
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 46 m² 536 - 46 m² 201 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 719 W 719 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 9 646 541 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 240 54 0% 0 0
>> Total Zone Loads - 2641 595 - 201 0

Page 243
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 10 SME DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

Air System Information


Air System Name .................. 1 F 10 SME DIVISION Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 72.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 6.7 5.7 21.7 / 17.6 15.4 / 15.0 - Jul 2100 10.47

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 759 0.191 0.152 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.5 Jul 2200 0.3 72.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 10 SME DIVISION 1 5.5 Jul 2200 759 0.3 72.5 10.47

Page 244
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 10 SME DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 10 SME DIVISION 1 72.5 15.0 758.8 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 758.8 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 245
Air System Design Load Summary for 1 F 10 SME DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 73 m² 845 - 73 m² 317 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1903 W 1903 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 15 1077 902 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 482 90 0% 0 0
>> Total Zone Loads - 5307 992 - 317 0
Zone Conditioning - 5129 992 - 131 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 152 - - -152 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5280 992 - -21 0
Terminal Unit Cooling - 5280 983 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 5280 983 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 246
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 10 SME DIVISION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 73 m² 845 - 73 m² 317 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1903 W 1903 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 15 1077 902 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 482 90 0% 0 0
>> Total Zone Loads - 5307 992 - 317 0

Page 247
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 09 CHIEF SME
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

Air System Information


Air System Name ....................... 1 F 09 CHIEF SME Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 18.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.2 1.9 21.9 / 17.0 14.3 / 13.8 - Jul 2200 11.59

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 209 0.053 0.042 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.9 Jul 2200 0.1 18.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 09 CHIEF SME 1 1.9 Jul 2200 209 0.1 18.0 11.59

Page 248
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 09 CHIEF SME
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 09 CHIEF SME 1 18.0 4.0 208.6 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 208.6 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 249
Air System Design Load Summary for 1 F 09 CHIEF SME
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 18 m² 210 - 18 m² 79 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 677 W 677 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 167 24 0% 0 0
>> Total Zone Loads - 1842 264 - 79 0
Zone Conditioning - 1833 264 - 35 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 42 - - -42 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1875 264 - -6 0
Terminal Unit Cooling - 1875 262 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1875 262 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 250
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 09 CHIEF SME
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:18PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 18 m² 210 - 18 m² 79 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 677 W 677 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 167 24 0% 0 0
>> Total Zone Loads - 1842 264 - 79 0

Page 251
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 08 WORK SHOP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Air System Information


Air System Name .................... 1 F 08 WORK SHOP Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 17.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.1 1.9 22.0 / 16.8 13.9 / 13.4 - Jul 2200 11.19

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 190 0.048 0.038 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.8 Jul 2200 0.1 17.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 08 WORK SHOP 1 1.8 Jul 2200 190 0.1 17.0 11.19

Page 252
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 08 WORK SHOP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 08 WORK SHOP 1 17.0 4.0 190.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 190.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 253
Air System Design Load Summary for 1 F 08 WORK SHOP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 17 m² 198 - 17 m² 74 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 644 W 644 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 163 24 0% 0 0
>> Total Zone Loads - 1792 264 - 74 0
Zone Conditioning - 1786 264 - 32 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 38 - - -38 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1824 264 - -6 0
Terminal Unit Cooling - 1824 262 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1824 262 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 254
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 08 WORK SHOP
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 17 m² 198 - 17 m² 74 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 644 W 644 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 163 24 0% 0 0
>> Total Zone Loads - 1792 264 - 74 0

Page 255
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 07 CHIEF PRODUCTION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Air System Information


Air System Name ...... 1 F 07 CHIEF PRODUCTION Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 21.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 2.7 2.7 22.0 / 10.6 13.6 / 6.7 - Jul 1600 12.49

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 262 0.066 0.052 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.7 Jul 1600 0.4 21.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 07 CHIEF PRODUCTION 1 2.7 Jul 1600 262 0.4 21.0 12.49

Page 256
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 07 CHIEF PRODUCTION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 07 CHIEF PRODUCTION 1 21.0 1.0 262.2 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 262.2 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 257
Air System Design Load Summary for 1 F 07 CHIEF PRODUCTION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 822 - 7 m² - -
Wall Transmission 25 m² 336 - 25 m² 144 -
Roof Transmission 21 m² 245 - 21 m² 92 -
Window Transmission 7 m² 325 - 7 m² 141 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 315 W 315 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 236 6 0% 0 0
>> Total Zone Loads - 2601 66 - 377 0
Zone Conditioning - 2531 66 - 46 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 52 - - -52 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2583 66 - -7 0
Terminal Unit Cooling - 2583 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 2583 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 258
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 07 CHIEF PRODUCTION
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 822 - 7 m² - -
Wall Transmission 25 m² 336 - 25 m² 144 -
Roof Transmission 21 m² 245 - 21 m² 92 -
Window Transmission 7 m² 325 - 7 m² 141 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 315 W 315 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 236 6 0% 0 0
>> Total Zone Loads - 2601 66 - 377 0

Page 259
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 06 PRODUCTION DIVISI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Air System Information


Air System Name ....... 1 F 06 PRODUCTION DIVISI Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area .............................................................. 170.0 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 15.8 13.5 21.7 / 18.0 16.0 / 15.7 - Jul 2100 11.51

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 1957 0.493 0.391 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 13.0 Jul 2200 1.3 170.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 06 PRODUCTION DIVISI 1 13.0 Jul 2200 1957 1.3 170.0 11.51

Page 260
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 06 PRODUCTION DIVISI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 06 PRODUCTION DIVISI 1 170.0 36.0 1956.6 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 1956.6 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 261
Air System Design Load Summary for 1 F 06 PRODUCTION DIVISI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 90 m² 1151 - 90 m² 508 -
Roof Transmission 170 m² 1981 - 170 m² 744 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3825 W 3825 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 36 2585 2164 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1104 216 0% 0 0
>> Total Zone Loads - 12145 2380 - 1252 0
Zone Conditioning - 12231 2380 - 339 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 391 - - -391 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12623 2380 - -52 0
Terminal Unit Cooling - 12623 2321 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 12623 2321 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 262
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 06 PRODUCTION DIVISI
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 90 m² 1151 - 90 m² 508 -
Roof Transmission 170 m² 1981 - 170 m² 744 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3825 W 3825 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 36 2585 2164 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1104 216 0% 0 0
>> Total Zone Loads - 12145 2380 - 1252 0

Page 263
Hourly Analysis Program v5.01 Page 4 of 4
Zone Sizing Summary for 1 F 03 FRONT OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Air System Information


Air System Name ................ 1 F 03 FRONT OFFICE Number of zones .......................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 13.5 m²
Air System Type ................................................ VRF Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.2 1.2 21.7 / 12.7 15.5 / 10.0 - Jul 2000 11.70

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -17.8 / -17.8 0.00 158 0.040 0.032 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.1 Jul 1800 0.1 13.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 03 FRONT OFFICE 1 1.1 Jul 1800 158 0.1 13.5 11.70

Page 264
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for 1 F 03 FRONT OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 03 FRONT OFFICE 1 13.5 1.0 157.9 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 157.9 0.0

Hourly Analysis Program v5.01 Page 2 of 4

Page 265
Air System Design Load Summary for 1 F 03 FRONT OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 14 m² 157 - 14 m² 59 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 4 m² 100 - 4 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 449 W 449 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 103 6 0% 0 0
>> Total Zone Loads - 1130 66 - 59 0
Zone Conditioning - 1127 66 - 27 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 32 - - -32 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1159 66 - -5 0
Terminal Unit Cooling - 1159 0 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1159 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 266
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for 1 F 03 FRONT OFFICE
Project Name: QATAR JOINT WARFARE 09-20-2018
Prepared by: qea 12:17PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 14 m² 157 - 14 m² 59 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 4 m² 100 - 4 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 449 W 449 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 103 6 0% 0 0
>> Total Zone Loads - 1130 66 - 59 0

Page 267
Hourly Analysis Program v5.01 Page 4 of 4
_______________________________________________________________________________

HVAC HAP OUTPUT FOR AHU & FAHU SYSTEM

_________________________________________________________________________________
Q.E.A.
Page 268
Air System Sizing Summary for 1 F KITCHEN & CAFETARIA
Project Name: QATAR JOINT WARFARE 09-25-2018
Prepared by: qea 02:39PM

Air System Information


Air System Name ...... 1 F KITCHEN & CAFETARIA Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .............................................................. 140.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ..................................................... 63.3 kW Load occurs at .................................................. Jul 1500
Sensible coil load ............................................... 37.4 kW OA DB / WB ................................................... 46.0 / 30.0 °C
Coil L/s at Jul 1500 ............................................ 1833 L/s Entering DB / WB ........................................... 26.5 / 19.9 °C
Max block L/s at Jul 1700 .................................. 1833 L/s Leaving DB / WB ............................................... 9.6 / 9.2 °C
Sum of peak zone L/s ....................................... 1889 L/s Coil ADP .................................................................... 7.8 °C
Sensible heat ratio ............................................ 0.590 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 2.2 Resulting RH ............................................................... 50 %
W/m² ................................................................. 452.2 Design supply temp. ................................................ 12.5 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ............................... 0.1 K

Central Heating Coil Sizing Data

Max coil load ........................................................ 9.1 kW Load occurs at .................................................. Jul 0500
Coil L/s at Jul 0500 ............................................ 1833 L/s W/m² ........................................................................ 65.1
Max coil L/s ....................................................... 1833 L/s Ent. DB / Lvg DB .............................................. 9.4 / 13.6 °C
Water flow @ 11.1 K drop .................................. N/A

Supply Fan Sizing Data

Actual max L/s at Jul 1700 ................................ 1833 L/s Fan motor BHP ........................................................ 0.43 BHP
Standard L/s ...................................................... 1831 L/s Fan motor kW .......................................................... 0.34 kW
Actual max L/(sꞏm²) .......................................... 13.09 L/(sꞏm²) Fan static .................................................................. 100 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 370 L/s L/s/person ................................................................ 8.04 L/s/person
L/(sꞏm²) ............................................................... 2.64 L/(sꞏm²)

Hourly Analysis Program v5.01 Page 1 of 5


Zone Sizing Summary for 1 F KITCHEN & CAFETARIA
Project Name: QATAR JOINT WARFARE 09-25-2018
Prepared by: qea 02:39PM

Air System Information


Air System Name ...... 1 F KITCHEN & CAFETARIA Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .............................................................. 140.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 1833 1833 13.09 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 18.8 Jul 1700 1.2 140.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 33 KITCHEN 1 3.7 Jul 2000 364 0.2 30.0 12.13
1 F 34 CAFATERIA 1 15.1 Jul 1700 1470 0.9 110.0 13.36

Hourly Analysis Program v5.01 Page 2 of 5


Ventilation Sizing Summary for 1 F KITCHEN & CAFETARIA
Project Name: QATAR JOINT WARFARE 09-25-2018
Prepared by: qea 02:39PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................ 370 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 33 KITCHEN 1 30.0 2.0 364.0 0.00 0.00 70.0 0.0 70.0
1 F 34 CAFATERIA 1 110.0 44.0 1469.8 0.00 0.00 300.0 0.0 300.0
Totals (incl. Space Multipliers) 1833.8 370.0

Hourly Analysis Program v5.01 Page 3 of 5


Air System Design Load Summary for 1 F KITCHEN & CAFETARIA
Project Name: QATAR JOINT WARFARE 09-25-2018
Prepared by: qea 02:39PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 529 - 7 m² - -
Wall Transmission 74 m² 978 - 74 m² 420 -
Roof Transmission 140 m² 1631 - 140 m² 612 -
Window Transmission 7 m² 355 - 7 m² 154 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 888 - 33 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3949 W 3949 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1300 W 1300 - 0 0 -
People 46 7079 12471 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 300 600 - 0 0
Safety Factor 10% / 10% 1701 1307 0% 0 0
>> Total Zone Loads - 18710 14378 - 1186 0
Zone Conditioning - 18580 14378 - -810 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1833 L/s 0 - 1833 L/s 0 -
Ventilation Load 370 L/s 10874 11561 370 L/s 1154 0
Supply Fan Load 1833 L/s 339 - 1833 L/s -339 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 374 - 2% 24 -
>> Total System Loads - 30167 25939 - 29 0
Central Cooling Coil - 37372 25939 - 0 0
Central Heating Coil - -7762 - - 0 -
>> Total Conditioning - 29610 25939 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v5.01 Page 4 of 5


Zone Design Load Summary for 1 F KITCHEN & CAFETARIA
Project Name: QATAR JOINT WARFARE 09-25-2018
Prepared by: qea 02:39PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 529 - 7 m² - -
Wall Transmission 74 m² 978 - 74 m² 420 -
Roof Transmission 140 m² 1631 - 140 m² 612 -
Window Transmission 7 m² 355 - 7 m² 154 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 888 - 33 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3949 W 3949 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1300 W 1300 - 0 0 -
People 46 7079 12471 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 300 600 - 0 0
Safety Factor 10% / 10% 1701 1307 0% 0 0
>> Total Zone Loads - 18710 14378 - 1186 0

Hourly Analysis Program v5.01 Page 5 of 5


Air System Sizing Summary for 1 F KITCHEN & CAFETARIA
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 08:53AM

Air System Information


Air System Name ...... 1 F KITCHEN & CAFETARIA Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .............................................................. 140.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ..................................................... 51.5 kW Load occurs at .................................................. Jul 1500
Sensible coil load ............................................... 31.9 kW OA DB / WB ................................................... 46.0 / 30.0 °C
Coil L/s at Jul 1500 ............................................ 1890 L/s Entering DB / WB ........................................... 23.8 / 18.1 °C
Max block L/s .................................................... 1890 L/s Leaving DB / WB ............................................... 9.8 / 9.4 °C
Sum of peak zone L/s ....................................... 1890 L/s Coil ADP .................................................................... 8.3 °C
Sensible heat ratio ............................................ 0.619 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 2.7 Resulting RH ............................................................... 50 %
W/m² ................................................................. 367.9 Design supply temp. ................................................ 12.5 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ............................... 0.1 K

Central Heating Coil Sizing Data

Max coil load ........................................................ 8.8 kW Load occurs at .................................................. Jul 0500
Coil L/s at Jul 0500 ............................................ 1890 L/s W/m² ........................................................................ 62.6
Max coil L/s ....................................................... 1890 L/s Ent. DB / Lvg DB .............................................. 9.7 / 13.6 °C
Water flow @ 11.1 K drop .................................. N/A

Supply Fan Sizing Data

Actual max L/s ................................................... 1890 L/s Fan motor BHP ........................................................ 0.44 BHP
Standard L/s ...................................................... 1888 L/s Fan motor kW .......................................................... 0.35 kW
Actual max L/(sꞏm²) .......................................... 13.50 L/(sꞏm²) Fan static .................................................................. 100 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 168 L/s L/s/person ................................................................ 3.65 L/s/person
L/(sꞏm²) ............................................................... 1.20 L/(sꞏm²)

Page 269
Hourly Analysis Program v5.01 Page 1 of 5
Air System Sizing Summary for 1 F02 COMMANDER/ MEETING
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:08AM

Air System Information


Air System Name . 1 F02 COMMANDER/ MEETING Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .............................................................. 110.5 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ..................................................... 18.9 kW Load occurs at .................................................. Jul 1500
Sensible coil load ............................................... 14.4 kW OA DB / WB ................................................... 46.0 / 30.0 °C
Coil L/s at Jul 1500 ............................................ 1251 L/s Entering DB / WB ........................................... 23.2 / 17.7 °C
Max block L/s .................................................... 1251 L/s Leaving DB / WB ........................................... 13.6 / 13.1 °C
Sum of peak zone L/s ....................................... 1251 L/s Coil ADP .................................................................. 12.6 °C
Sensible heat ratio ............................................ 0.763 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 5.9 Resulting RH ............................................................... 50 %
W/m² ................................................................. 170.7 Design supply temp. ................................................ 14.0 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ............................... 0.0 K

Central Heating Coil Sizing Data

Max coil load ........................................................ 2.8 kW Load occurs at .................................................. Jul 0700
Coil L/s at Jul 0700 ............................................ 1251 L/s W/m² ........................................................................ 25.5
Max coil L/s ....................................................... 1251 L/s Ent. DB / Lvg DB ............................................ 13.8 / 15.6 °C
Water flow @ 11.1 K drop .................................. N/A

Supply Fan Sizing Data

Actual max L/s ................................................... 1251 L/s Fan motor BHP ........................................................ 0.29 BHP
Standard L/s ...................................................... 1250 L/s Fan motor kW .......................................................... 0.23 kW
Actual max L/(sꞏm²) .......................................... 11.32 L/(sꞏm²) Fan static .................................................................. 100 Pa

Outdoor Ventilation Air Data


Design airflow L/s .................................................. 92 L/s L/s/person ................................................................ 7.08 L/s/person
L/(sꞏm²) ............................................................... 0.83 L/(sꞏm²)

Page 274
Hourly Analysis Program v5.01 Page 1 of 5
Zone Sizing Summary for 1 F02 COMMANDER/ MEETING
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:08AM

Air System Information


Air System Name . 1 F02 COMMANDER/ MEETING Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .............................................................. 110.5 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 1214 1214 10.98 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 10.2 Jul 1600 1.4 110.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
1 F 02 COMMANDER ROOM 1 5.0 Jul 1600 591 0.7 60.5 9.77
1 F 05 COMMANDER MEETING 1 5.3 Jul 1600 623 0.6 50.0 12.46

Page 275
Hourly Analysis Program v5.01 Page 2 of 5
Ventilation Sizing Summary for 1 F02 COMMANDER/ MEETING
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:08AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................. 92 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
1 F 02 COMMANDER ROOM 1 60.5 3.0 591.0 0.00 0.00 50.0 0.0 50.0
1 F 05 COMMANDER MEETING 1 50.0 10.0 622.8 0.00 0.00 42.0 0.0 42.0
Totals (incl. Space Multipliers) 1213.8 92.0

Hourly Analysis Program v5.01 Page 3 of 5

Page 276
Air System Design Load Summary for 1 F02 COMMANDER/ MEETING
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:08AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1437 - 14 m² - -
Wall Transmission 107 m² 1436 - 107 m² 610 -
Roof Transmission 111 m² 1287 - 111 m² 483 -
Window Transmission 14 m² 680 - 14 m² 295 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 20 m² 528 - 20 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1603 W 1603 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1100 W 1100 - 0 0 -
People 13 1180 1414 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 925 141 0% 0 0
>> Total Zone Loads - 10176 1556 - 1389 0
Zone Conditioning - 10189 1556 - -240 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1251 L/s 0 - 1251 L/s 0 -
Ventilation Load 92 L/s 2735 2908 92 L/s 465 0
Supply Fan Load 1251 L/s 232 - 1251 L/s -232 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 204 - 2% 28 -
>> Total System Loads - 13359 4464 - 21 0
Central Cooling Coil - 14401 4464 - 0 0
Central Heating Coil - -1042 - - 0 -
>> Total Conditioning - 13359 4464 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 277
Hourly Analysis Program v5.01 Page 4 of 5
Zone Design Load Summary for 1 F02 COMMANDER/ MEETING
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:08AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1437 - 14 m² - -
Wall Transmission 107 m² 1436 - 107 m² 610 -
Roof Transmission 111 m² 1287 - 111 m² 483 -
Window Transmission 14 m² 680 - 14 m² 295 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 20 m² 528 - 20 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1603 W 1603 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1100 W 1100 - 0 0 -
People 13 1180 1414 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 925 141 0% 0 0
>> Total Zone Loads - 10176 1556 - 1389 0

Page 278
Hourly Analysis Program v5.01 Page 5 of 5
Air System Sizing Summary for AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:09AM

Air System Information


Air System Name ............................... AUDITORIUM Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .............................................................. 240.5 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ..................................................... 93.1 kW Load occurs at .................................................. Jul 1400
Sensible coil load ............................................... 61.1 kW OA DB / WB ................................................... 45.7 / 29.9 °C
Coil L/s at Jul 1400 ............................................ 4043 L/s Entering DB / WB ........................................... 25.8 / 19.5 °C
Max block L/s .................................................... 4043 L/s Leaving DB / WB ........................................... 13.3 / 12.7 °C
Sum of peak zone L/s ....................................... 4043 L/s Coil ADP .................................................................. 11.9 °C
Sensible heat ratio ............................................ 0.657 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 2.6 Resulting RH ............................................................... 50 %
W/m² ................................................................. 386.9 Design supply temp. ................................................ 12.5 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ............................... 0.0 K

Supply Fan Sizing Data

Actual max L/s ................................................... 4043 L/s Fan motor BHP ........................................................ 0.94 BHP
Standard L/s ...................................................... 4038 L/s Fan motor kW .......................................................... 0.75 kW
Actual max L/(sꞏm²) .......................................... 16.81 L/(sꞏm²) Fan static .................................................................. 100 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 702 L/s L/s/person ................................................................ 2.68 L/s/person
L/(sꞏm²) ............................................................... 2.92 L/(sꞏm²)

Page 279
Hourly Analysis Program v5.01 Page 1 of 5
Zone Sizing Summary for AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:09AM

Air System Information


Air System Name ............................... AUDITORIUM Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .............................................................. 240.5 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 3921 3921 16.30 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 40.2 Jul 1600 1.3 240.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
AUDITORIUM 1 40.2 Jul 1600 3921 1.3 240.5 16.30

Page 280
Hourly Analysis Program v5.01 Page 2 of 5
Ventilation Sizing Summary for AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:09AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................ 702 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
AUDITORIUM 1 240.5 262.0 3921.3 0.00 0.00 702.0 0.0 702.0
Totals (incl. Space Multipliers) 3921.3 702.0

Hourly Analysis Program v5.01 Page 3 of 5

Page 281
Air System Design Load Summary for AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:09AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 46 m² 566 - 46 m² 263 -
Roof Transmission 241 m² 2802 - 241 m² 1052 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 241 m² 7657 - 241 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 6277 W 6277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 262 17659 9222 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3646 922 0% 0 0
>> Total Zone Loads - 40106 10145 - 1315 0
Zone Conditioning - 39054 10145 - -2047 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4043 L/s 0 - 4043 L/s 0 -
Ventilation Load 702 L/s 20498 21581 702 L/s 2850 0
Supply Fan Load 4043 L/s 749 - 4043 L/s -749 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 802 - 2% 26 -
>> Total System Loads - 61103 31725 - 80 0
Central Cooling Coil - 61103 31717 - 0 0
>> Total Conditioning - 61103 31717 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 282
Hourly Analysis Program v5.01 Page 4 of 5
Zone Design Load Summary for AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:09AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 46 m² 566 - 46 m² 263 -
Roof Transmission 241 m² 2802 - 241 m² 1052 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 241 m² 7657 - 241 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 6277 W 6277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 262 17659 9222 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3646 922 0% 0 0
>> Total Zone Loads - 40106 10145 - 1315 0

Page 283
Hourly Analysis Program v5.01 Page 5 of 5
Air System Sizing Summary for FAHU AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:12AM

Air System Information


Air System Name .................... FAHU AUDITORIUM Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .................................................................. 1.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing ..................... Coincident space loads

Central Cooling Coil Sizing Data

Total coil load ................................................... 194.3 kW Load occurs at .................................................. Jul 1500
Sensible coil load ............................................. 103.8 kW OA DB / WB ................................................... 46.0 / 30.0 °C
Coil L/s at Jul 1500 ............................................ 2596 L/s Entering DB / WB ........................................... 46.0 / 30.0 °C
Max block L/s at Des Htg .................................. 2596 L/s Leaving DB / WB ........................................... 12.8 / 12.1 °C
Sum of peak zone L/s ....................................... 2676 L/s Coil ADP .................................................................... 9.1 °C
Sensible heat ratio ............................................ 0.534 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 0.0 Resulting RH ............................................................... 50 %
W/m² ........................................................... 194343.9 Design supply temp. ................................................ 13.0 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ............................... 0.0 K

Central Heating Coil Sizing Data

Max coil load ...................................................... 27.8 kW Load occurs at .................................................. Jul 0500
Coil L/s at Jul 0500 ............................................ 2596 L/s W/m² .................................................................. 27753.7
Max coil L/s ....................................................... 2596 L/s Ent. DB / Lvg DB ............................................ 11.7 / 20.6 °C
Water flow @ 11.1 K drop .................................. N/A

Supply Fan Sizing Data

Actual max L/s at Des Htg ................................. 2596 L/s Fan motor BHP ........................................................ 1.52 BHP
Standard L/s ...................................................... 2593 L/s Fan motor kW .......................................................... 1.20 kW
Actual max L/(sꞏm²) ...................................... 2596.00 L/(sꞏm²) Fan static .................................................................. 250 Pa

Outdoor Ventilation Air Data


Design airflow L/s .............................................. 2596 L/s L/s/person ................................................................ 0.00 L/s/person
L/(sꞏm²) ......................................................... 2596.00 L/(sꞏm²)

Page 284
Hourly Analysis Program v5.01 Page 1 of 5
Zone Sizing Summary for FAHU AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:12AM

Air System Information


Air System Name .................... FAHU AUDITORIUM Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .................................................................. 1.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing ..................... Coincident space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 2596 2596 2596.00 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 0.0 Des Htg 0.0 1.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
FAHU AUDITORIUM 1 0.0 Des Htg 2596 0.0 1.0 2596.00

Page 285
Hourly Analysis Program v5.01 Page 2 of 5
Ventilation Sizing Summary for FAHU AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:12AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .............................................................. 2596 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
FAHU AUDITORIUM 1 1.0 0.0 2596.0 0.00 0.00 2596.0 0.0 2596.0
Totals (incl. Space Multipliers) 2596.0 2596.0

Hourly Analysis Program v5.01 Page 3 of 5

Page 286
Air System Design Load Summary for FAHU AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:12AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 0% 0 0
>> Total Zone Loads - 0 0 - 0 0
Zone Conditioning - 0 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2596 L/s 0 - 2596 L/s 0 -
Ventilation Load 2596 L/s 78256 90512 2596 L/s 1206 0
Supply Fan Load 2596 L/s 1202 - 2596 L/s -1202 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 0 - 2% 0 -
>> Total System Loads - 79458 90512 - 4 0
Central Cooling Coil - 103832 90512 - 0 0
Central Heating Coil - -24374 - - 0 -
>> Total Conditioning - 79458 90512 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 287
Hourly Analysis Program v5.01 Page 4 of 5
Zone Design Load Summary for FAHU AUDITORIUM
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:12AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 0% 0 0
>> Total Zone Loads - 0 0 - 0 0

Page 288
Hourly Analysis Program v5.01 Page 5 of 5
Air System Sizing Summary for FAHU LEFT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:22AM

Air System Information


Air System Name ........................ FAHU LEFT SIDE Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .................................................................. 1.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing ..................... Coincident space loads

Central Cooling Coil Sizing Data

Total coil load ..................................................... 93.7 kW Load occurs at .................................................. Jul 1500
Sensible coil load ............................................... 50.1 kW OA DB / WB ................................................... 46.0 / 30.0 °C
Coil L/s at Jul 1500 ............................................ 1252 L/s Entering DB / WB ........................................... 46.0 / 30.0 °C
Max block L/s at Des Htg .................................. 1252 L/s Leaving DB / WB ........................................... 12.8 / 12.1 °C
Sum of peak zone L/s ....................................... 1291 L/s Coil ADP .................................................................... 9.1 °C
Sensible heat ratio ............................................ 0.534 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 0.0 Resulting RH ............................................................... 50 %
W/m² ............................................................. 93728.2 Design supply temp. ................................................ 13.0 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ............................... 0.0 K

Central Heating Coil Sizing Data

Max coil load ...................................................... 13.4 kW Load occurs at .................................................. Jul 0500
Coil L/s at Jul 0500 ............................................ 1252 L/s W/m² .................................................................. 13385.1
Max coil L/s ....................................................... 1252 L/s Ent. DB / Lvg DB ............................................ 11.7 / 20.6 °C
Water flow @ 11.1 K drop .................................. N/A

Supply Fan Sizing Data

Actual max L/s at Des Htg ................................. 1252 L/s Fan motor BHP ........................................................ 0.73 BHP
Standard L/s ...................................................... 1251 L/s Fan motor kW .......................................................... 0.58 kW
Actual max L/(sꞏm²) ...................................... 1252.00 L/(sꞏm²) Fan static .................................................................. 250 Pa

Outdoor Ventilation Air Data


Design airflow L/s .............................................. 1252 L/s L/s/person ................................................................ 0.00 L/s/person
L/(sꞏm²) ......................................................... 1252.00 L/(sꞏm²)

Page 289
Hourly Analysis Program v5.01 Page 1 of 5
Zone Sizing Summary for FAHU LEFT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:22AM

Air System Information


Air System Name ........................ FAHU LEFT SIDE Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .................................................................. 1.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing ..................... Coincident space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 1252 1252 1252.00 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 0.0 Des Htg 0.0 1.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
FAHU LEFT SIDE 1 0.0 Des Htg 1252 0.0 1.0 1252.00

Page 290
Hourly Analysis Program v5.01 Page 2 of 5
Ventilation Sizing Summary for FAHU LEFT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:22AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .............................................................. 1252 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
FAHU LEFT SIDE 1 1.0 0.0 1252.0 0.00 0.00 1252.0 0.0 1252.0
Totals (incl. Space Multipliers) 1252.0 1252.0

Hourly Analysis Program v5.01 Page 3 of 5

Page 291
Air System Design Load Summary for FAHU LEFT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:22AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 0% 0 0
>> Total Zone Loads - 0 0 - 0 0
Zone Conditioning - 0 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1252 L/s 0 - 1252 L/s 0 -
Ventilation Load 1252 L/s 37741 43652 1252 L/s 584 0
Supply Fan Load 1252 L/s 580 - 1252 L/s -580 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 0 - 2% 0 -
>> Total System Loads - 38321 43652 - 4 0
Central Cooling Coil - 50076 43652 - 0 0
Central Heating Coil - -11755 - - 0 -
>> Total Conditioning - 38321 43652 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 292
Hourly Analysis Program v5.01 Page 4 of 5
Zone Design Load Summary for FAHU LEFT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:22AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 0% 0 0
>> Total Zone Loads - 0 0 - 0 0

Page 293
Hourly Analysis Program v5.01 Page 5 of 5
Air System Sizing Summary for FAHU RIGHT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:23AM

Air System Information


Air System Name ...................... FAHU RIGHT SIDE Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .................................................................. 1.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing ..................... Coincident space loads

Central Cooling Coil Sizing Data

Total coil load ..................................................... 74.6 kW Load occurs at .................................................. Jul 1500
Sensible coil load ............................................... 39.8 kW OA DB / WB ................................................... 46.0 / 30.0 °C
Coil L/s at Jul 1500 .............................................. 996 L/s Entering DB / WB ........................................... 46.0 / 30.0 °C
Max block L/s at Des Htg .................................... 996 L/s Leaving DB / WB ........................................... 12.8 / 12.1 °C
Sum of peak zone L/s ....................................... 1027 L/s Coil ADP .................................................................... 9.1 °C
Sensible heat ratio ............................................ 0.534 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 0.0 Resulting RH ............................................................... 50 %
W/m² ............................................................. 74563.4 Design supply temp. ................................................ 13.0 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ............................... 0.0 K

Central Heating Coil Sizing Data

Max coil load ...................................................... 10.6 kW Load occurs at .................................................. Jul 0500
Coil L/s at Jul 0500 .............................................. 996 L/s W/m² .................................................................. 10648.2
Max coil L/s ......................................................... 996 L/s Ent. DB / Lvg DB ............................................ 11.7 / 20.6 °C
Water flow @ 11.1 K drop .................................. N/A

Supply Fan Sizing Data

Actual max L/s at Des Htg ................................... 996 L/s Fan motor BHP ........................................................ 0.58 BHP
Standard L/s ........................................................ 995 L/s Fan motor kW .......................................................... 0.46 kW
Actual max L/(sꞏm²) ........................................ 996.00 L/(sꞏm²) Fan static .................................................................. 250 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................ 996 L/s L/s/person ................................................................ 0.00 L/s/person
L/(sꞏm²) ........................................................... 996.00 L/(sꞏm²)

Page 294
Hourly Analysis Program v5.01 Page 1 of 5
Zone Sizing Summary for FAHU RIGHT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:23AM

Air System Information


Air System Name ...................... FAHU RIGHT SIDE Number of zones .......................................................... 1
Equipment Class ................................... PKG ROOF Floor Area .................................................................. 1.0 m²
Air System Type ........................................... SZCAV Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing ..................... Coincident space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 996 996 996.00 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 0.0 Des Htg 0.0 1.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
FAHU RIGHT SIDE 1 0.0 Des Htg 996 0.0 1.0 996.00

Page 295
Hourly Analysis Program v5.01 Page 2 of 5
Ventilation Sizing Summary for FAHU RIGHT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:23AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................ 996 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
FAHU RIGHT SIDE 1 1.0 0.0 996.0 0.00 0.00 996.0 0.0 996.0
Totals (incl. Space Multipliers) 996.0 996.0

Hourly Analysis Program v5.01 Page 3 of 5

Page 296
Air System Design Load Summary for FAHU RIGHT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:23AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 0% 0 0
>> Total Zone Loads - 0 0 - 0 0
Zone Conditioning - 0 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 996 L/s 0 - 996 L/s 0 -
Ventilation Load 996 L/s 30024 34726 996 L/s 479 0
Supply Fan Load 996 L/s 461 - 996 L/s -461 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 0 - 2% 0 -
>> Total System Loads - 30485 34726 - 17 0
Central Cooling Coil - 39837 34726 - 0 0
Central Heating Coil - -9352 - - 0 -
>> Total Conditioning - 30485 34726 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 297
Hourly Analysis Program v5.01 Page 4 of 5
Zone Design Load Summary for FAHU RIGHT SIDE
Project Name: QATAR JOINT WARFARE 09-22-2018
Prepared by: qea 09:23AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 0% 0 0
>> Total Zone Loads - 0 0 - 0 0

Page 298
Hourly Analysis Program v5.01 Page 5 of 5
_______________________________________________________________________________

U VALUES

_________________________________________________________________________________
Q.E.A.
Page 299
Section 12: Thermal Insulation of Building

All Air conditioned new buildings and addition to existing building shall be
provided with insulation as mentioned in the section 12.2 and 12.3.
12.1 Definitions :
U Value (Overall Heat Transfer Coefficient): Heat transmission in unit time
through unit area of material of construction and the boundary of air films,
induced by unit temperature difference between the environments on each side.
Units of U are W/m2 ºC ( Btu/h.ft2 ºF ).
Shading Coefficient (SC) : The ratio of solar heat gain at normal incidence
through glazing to that occurring through 1/8 in thick clear double strength glass.
Window Wall Ratio (WWR) : The window wall ratio is the ratio of vertical
fenestration area to gross exterior wall area. The fenestration area is the rough
opening ie it includes the frame, sash and other nonglazed window components.
The gross exterior wall area is measured vertically from top of the floor to bottom
of the roof.
Visible Transmittance (VT) : It is the fraction of visible light transmitted through
the glazing material .

12.2 Wall And Roof Assembly Maximum U Value:

Thermal insulation material used in the building external wall/roof must not
exceed the following U Value.

Roof : 0.437 W/m2 ºC (0.077 Btu/h ft2 ºF)


External Wall : 0.568 W/m2 ºC (0.100 Btu/h ft2 ºF)

U value mentioned are maximum permitted values, designer to reduce the


overall heat transfer coefficient values by properly selecting materilals, in such a
way that materials should be available in the State of Qatar. Building materials
resistence value shall be determined as per ASHRAE Fundmametals Handbook
or approved lab test result data published by the manufacturer.

12.3 Window Requirements:

The total glass area in the building shall be reasonable to minimize the heat
transmission and solar gain through the glazing. For different Window Wall ratio,
overall U Value and Shading Coefficient of the glass assembly does not exceed
the following values.

Window Wall Ratio Maximum U value- Maximum Shading


( WWR ) W/m2 ºC ( Btu/ft2h F ) Coefficient ( SC )
5 - 40 % 3.30 ( 0.58 ) 0.40.

Above 40 % 2.10 ( 0.36 ) 0.35.

Page 300
For the showroom building, double galzing shall be used with maximum U value
2.10 ( 0.36 ) W/m2 ºC ( Btu/ft2h F ), maximum SC 0.6 and with minimum Visible
Transmittance 0.3.

U value shall be calculated in summer as per ASHRAE specifications. U


Value and Shading Coefficient shall be certified by the manufacturer or other
responsible party.

12.4 Compliance:

Consultant should submit U value calculation for the walls, roof and Windows for
KAHRAMAA approval. Sample building envelope compliance forms are provided
in the Appendix 04.

Buildings failing to comply with minimum insulation requirements will not be


considered for supply of electricity.

The material used for the thermal insulation shall be approved by Qatar General
Electricity & Water Corporation “KAHRAMAA” before being installed, and as per
the approval on the building permit application form.

Page 301
Page 302
Page 303
Page 304
________________________________________________________________________________

PUMP ROOM

________________________________________________________________________________
Q.E.A.
Page 305
Space Input Data
IMAR INSTANBUL PUMP ROOM 09-23-2018
qea 04:50PM

FIRE PUMP ROOM

1. General Details:
Floor Area ........................................................... 47.8 m²
Avg. Ceiling Height ............................................... 3.4 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage ............................................................ 900.0 Watts Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.00 Sensible ............................................................. 67.4 W/person
Schedule ............................................. LIGHTING(1) Latent ................................................................. 35.2 W/person
Schedule ................................................ PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1000.0 Watts
Schedule ................................. MISC. ELECTRIC(1)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 17.4 0 0 0
SSE 30.6 0 0 1

3.1. Construction Types for Exposure WSW


Wall Type .................................... Medium Weight Wall(1)

3.2. Construction Types for Exposure SSE


Wall Type .................................... Medium Weight Wall(1)
Door Type .................................................................... PD1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 47.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................... Medium Weight Roof(1)

5. Infiltration:
Design Cooling ................................................... 1.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 47.8 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 306
Hourly Analysis Program vv5.01 Page 1 of 2
Space Input Data
IMAR INSTANBUL PUMP ROOM 09-23-2018
qea 04:50PM

WATER PUMP ROOM

1. General Details:
Floor Area ........................................................... 15.0 m²
Avg. Ceiling Height ............................................... 3.4 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 900.0 Watts Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.00 Sensible ............................................................. 67.4 W/person
Schedule ............................................. LIGHTING(1) Latent ................................................................. 35.2 W/person
Schedule ................................................ PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 500.0 Watts
Schedule ................................. MISC. ELECTRIC(1)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 17.0 1 0 0
SSE 10.2 0 0 1

3.1. Construction Types for Exposure ENE


Wall Type .................................... Medium Weight Wall(1)
1st Window Type ........................................................ PW1

3.2. Construction Types for Exposure SSE


Wall Type .................................... Medium Weight Wall(1)
Door Type .................................................................... PD1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.0 0 0

4.1. Construction Types for Exposure H


Roof Type ................................... Medium Weight Roof(1)

5. Infiltration:
Design Cooling ................................................... 1.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 15.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 307
Hourly Analysis Program vv5.01 Page 2 of 2
________________________________________________________________________________

OUTPUT DATA FOR PUMP ROOM

________________________________________________________________________________
Q.E.A.
Page 308
Air System Sizing Summary for FIRE PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

Air System Information


Air System Name ...................... FIRE PUMP ROOM Number of zones ........................................................... 1
Equipment Class ..................................... SPLT AHU Floor Area ................................................................ 47.8 m²
Air System Type .......................................... CAV/RH Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 4.9 kW Load occurs at .................................................. Jul 1700
Sensible coil load ................................................. 3.7 kW OA DB / WB ................................................... 44.9 / 29.8 °C
Coil L/s at Jul 1700 .............................................. 186 L/s Entering DB / WB ........................................... 31.9 / 21.8 °C
Max block L/s at Jul 1700 .................................... 186 L/s Leaving DB / WB ............................................ 15.6 / 14.7 °C
Sum of peak zone L/s ......................................... 186 L/s Coil ADP .................................................................. 13.8 °C
Sensible heat ratio ............................................ 0.753 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 9.8 Resulting RH ............................................................... 42 %
W/m² ................................................................. 101.6 Design supply temp. ................................................ 13.0 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0.0 K

Supply Fan Sizing Data

Actual max L/s at Jul 1700 .................................. 186 L/s Fan motor BHP ........................................................ 0.04 BHP
Standard L/s ........................................................ 186 L/s Fan motor kW .......................................................... 0.03 kW
Actual max L/(sꞏm²) ............................................ 3.89 L/(sꞏm²) Fan static .................................................................... 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s .................................................... 0 L/s L/s/person ................................................................ 0.00 L/s/person
L/(sꞏm²) ............................................................... 0.00 L/(sꞏm²)

Page 309
Hourly Analysis Program v5.01 Page 1 of 10
Zone Sizing Summary for FIRE PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

Air System Information


Air System Name ...................... FIRE PUMP ROOM Number of zones ........................................................... 1
Equipment Class ..................................... SPLT AHU Floor Area ................................................................ 47.8 m²
Air System Type .......................................... CAV/RH Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 186 186 3.89 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Jul 1700 0.5 47.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
FIRE PUMP ROOM 1 3.8 Jul 1700 186 0.5 47.8 3.89

Page 310
Hourly Analysis Program v5.01 Page 2 of 10
Ventilation Sizing Summary for FIRE PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
FIRE PUMP ROOM 1 47.8 2.0 186.0 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 186.0 0.0

Page 311
Hourly Analysis Program v5.01 Page 3 of 10
Air System Design Load Summary for FIRE PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 9.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 44 m² 332 - 44 m² 272 -
Roof Transmission 48 m² 353 - 48 m² 230 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 22 - 4 m² 17 -
Floor Transmission 48 m² 0 - 48 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 872 1064 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 181 57 0% 0 0
>> Total Zone Loads - 3795 1191 - 520 0
Zone Conditioning - 3596 1191 - 32 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 186 L/s 0 - 186 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 186 L/s 33 - 186 L/s -33 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3629 1191 - -2 0
Central Cooling Coil - 3629 1191 - 0 0
>> Total Conditioning - 3629 1191 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 312
Hourly Analysis Program v5.01 Page 4 of 10
Zone Design Load Summary for FIRE PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 9.2 °C
OCCUPIED T-STAT 30.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 44 m² 332 - 44 m² 272 -
Roof Transmission 48 m² 353 - 48 m² 230 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 22 - 4 m² 17 -
Floor Transmission 48 m² 0 - 48 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 872 1064 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 181 57 0% 0 0
>> Total Zone Loads - 3795 1191 - 520 0

Page 313
Hourly Analysis Program v5.01 Page 5 of 10
Air System Sizing Summary for WATER PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

Air System Information


Air System Name ................. WATER PUMP ROOM Number of zones ........................................................... 1
Equipment Class ..................................... SPLT AHU Floor Area ................................................................ 15.0 m²
Air System Type .......................................... CAV/RH Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 2.8 kW Load occurs at .................................................. Jul 1400
Sensible coil load ................................................. 2.4 kW OA DB / WB ................................................... 45.7 / 29.9 °C
Coil L/s at Jul 1400 .............................................. 118 L/s Entering DB / WB ........................................... 31.9 / 21.0 °C
Max block L/s at Jul 1500 .................................... 118 L/s Leaving DB / WB ............................................ 15.4 / 14.4 °C
Sum of peak zone L/s ......................................... 118 L/s Coil ADP .................................................................. 13.5 °C
Sensible heat ratio ............................................ 0.842 Bypass Factor ........................................................ 0.100
m²/kW ................................................................... 5.3 Resulting RH ............................................................... 38 %
W/m² ................................................................. 187.2 Design supply temp. ................................................ 13.0 °C
Water flow @ 5.6 K rise ..................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0.0 K

Supply Fan Sizing Data

Actual max L/s at Jul 1500 .................................. 118 L/s Fan motor BHP ........................................................ 0.03 BHP
Standard L/s ........................................................ 118 L/s Fan motor kW .......................................................... 0.02 kW
Actual max L/(sꞏm²) ............................................ 7.90 L/(sꞏm²) Fan static .................................................................... 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s .................................................... 0 L/s L/s/person ................................................................ 0.00 L/s/person
L/(sꞏm²) ............................................................... 0.00 L/(sꞏm²)

Page 314
Hourly Analysis Program v5.01 Page 6 of 10
Zone Sizing Summary for WATER PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

Air System Information


Air System Name ................. WATER PUMP ROOM Number of zones ........................................................... 1
Equipment Class ..................................... SPLT AHU Floor Area ................................................................ 15.0 m²
Air System Type .......................................... CAV/RH Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing ...................... Peak zone sensible load
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 118 118 7.90 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.4 Jul 1500 0.3 15.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
WATER PUMP ROOM 1 2.4 Jul 1500 118 0.3 15.0 7.90

Page 315
Hourly Analysis Program v5.01 Page 7 of 10
Ventilation Sizing Summary for WATER PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
WATER PUMP ROOM 1 15.0 1.0 118.5 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 118.5 0.0

Page 316
Hourly Analysis Program v5.01 Page 8 of 10
Air System Design Load Summary for WATER PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 9.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 184 - 2 m² - -
Wall Transmission 21 m² 204 - 21 m² 131 -
Roof Transmission 15 m² 111 - 15 m² 72 -
Window Transmission 2 m² 53 - 2 m² 42 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 22 - 4 m² 17 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 274 382 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 116 21 0% 0 0
>> Total Zone Loads - 2431 438 - 262 0
Zone Conditioning - 2334 438 - 19 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 118 L/s 0 - 118 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 118 L/s 21 - 118 L/s -21 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2355 438 - -2 0
Central Cooling Coil - 2355 438 - 0 0
>> Total Conditioning - 2355 438 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 317
Hourly Analysis Program v5.01 Page 9 of 10
Zone Design Load Summary for WATER PUMP ROOM
Project Name: IMAR INSTANBUL PUMP ROOM 09-23-2018
Prepared by: qea 04:57PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 9.2 °C
OCCUPIED T-STAT 30.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 184 - 2 m² - -
Wall Transmission 21 m² 204 - 21 m² 131 -
Roof Transmission 15 m² 111 - 15 m² 72 -
Window Transmission 2 m² 53 - 2 m² 42 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 22 - 4 m² 17 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 274 382 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 116 21 0% 0 0
>> Total Zone Loads - 2431 438 - 262 0

Page 318
Hourly Analysis Program v5.01 Page 10 of 10
________________________________________________________________________________

QATAR JOINT WARFARE TRAINING CENTER


PUMP ROOM
HVAC CALCULATIONS

*****************************************************

________________________________________________________________________________
Q.E.A.
Page 319
________________________________________________________________________________

DESIGN CRITERIA

AIR CONDITIONING

1.0 BASIS OF DESIGN


AS PER CLAUSE NO. 1.6, 1.6.1, 1.6.2, 1.6.3, 1.6.4, 1.6.5 OF SPECIFICATION

a. Outside Design Conditions:

* Summer : 46°C. DB, 30°C. WB


* Winter : 10°C DB, 90% RH
* Predominantly high humidity and saline

b. Indoor Design Conditions

Room Temperature (DB) / %RH Noise Level


Summer Winter (NC)

Pump Room 32±2°C. DB, 50% RH Not controlled 50

ASSUMPTION FOR DESIGN

a. Fresh Air Requirement


Basis of Fresh air = 1 air change

b. Safety margin = 5% Sensible and 5% Latent included in


computer calculation

c. U Value - As per Kahra-maa Circular No. 73 and QCS values

* Roofs = 0.437 watts/m² °K


* Walls = 0.568 watts/m² °K
* Glass = 2.1 watts/m² °K with max. SC 0.6
As per technical specification:
* Insulated doors = 0.36 watts/m² °K

d. Building Dimension for Calculation

* For A.C. calculation


* For Ventilation Inside clear dimensions

e. Software used

Software used for heat load A.C. calculations is CARRIER - Hourly Analysis Program
5.01

________________________________________________________________________________
Q.E.A.
Page 320
________________________________________________________________________________

2.0 INTERNAL LOAD FOR CALCULATIONS

Tentative
Sl. Occupancy Equipment Lighting Load (watts)
Room
No. (persons) Load (watts) including Ballast Factor

1. Pump Room 2 1,000 900

Notes:

1. Occupancy and equipment load are assumed figures.


2. Lighting loads are as per electrical calculations.

________________________________________________________________________________
Q.E.A.
Page 321
________________________________________________________________________________

3.0 PRESSURISATION AND VENTILATION

3.1 Pump room

Sl. Volume Air Quantity


Room Air change
No. (m3) (l/s.)

1. Pump Room 162 1 45

Infiltration 45

Note:

1. For normal operation of A.C. system, fresh air is assumed through infiltration.

3.2 Ventilation of Pump room

3.3 Air ventilation calculation based on engine heat load

Since engines are not to be used for continuous duty and only for stationary emergency
standby fire pump services, in the event of fire, fire fighting deluge system is designed for
20 minutes as per Kahra-maa specifications.

Engine data’s heat dissipation (according to technical specification attached)

a. Engine radiated heat = 11.8 kW


b. Lighting load = 0.9 kW
---------
Total = 12.7 kW

By using air ventilation formula: Q = kW


1.2 x ΔT
Where:
a. Temperature rise °k.
 Maximum allowable temperature
(air to engine inlet) temperature = 54.4 + 273 = 327.4°k
 Ambient temperature = 46 + 273 = 319°k
b. Q = m³/s
c. H = heat load (kW)

By substitution:

Q = 12.7 .
1.2 (327.4 – 319)
= 1.259 m³/s or 1259 l/s
 Fresh air intake connection will be sized for 1259 l/s.
 Exhaust air fan at full load shall be in capacity of 1259 l/s for removal of heat dissipation
in the Pump room.

________________________________________________________________________________
Q.E.A.
Page 322
________________________________________________________________________________

Note

1. Split units, fresh air motorized damper and exhaust fans shall be interlocked, so that at
a time only one item shall operate.
2. Fresh air intake is provided with motorized damper and all other accessories as per
specification.

________________________________________________________________________________
Q.E.A.
Page 323
________________________________________________________________________________

4.0 SELECTION OF EQUIPMENT

4.1 Split Unit – (Pump room)

Computer Calculations

* Total Cooling Load = 2.8 kW


* Sensible Coil Load = 2.4 kW
* Supply Fan (Actual max. air flow) = 118 l/s.

* Kahra-maa regulation requirement = 20% reserve

 Total cooling capacity = 2.8 x 1.2 = 3.36 kW


 Total sensible capacity = 2.4 x 1.2 = 2.88 kW
 Total air quantity = 118 x 1.2 = 142 l/s.
* Infiltration (I ACH) = 45 l/s.

________________________________________________________________________________
Q.E.A.
Page 324
5.0 SCHEDULE OF EQUIPMENT

5.1 SCHEDULE OF SPLIT A.C. UNIT FOR PUMPROOM

COOLING SENSIBLE
UNIT REF. AREA SERVED DESCRIPTION OF A.C. UNIT ELECTRICAL SUPPLY CAPACITY CAPACITY QTY.
kW kW

IU-01/OU-1 & Pump room Air cooled Split ceiling / wall mounted 220 - 240 V / 1 Ph / 50 Hz 3.36 2.88 2
IU-02/OU-2 unit with remote outdoor unit (1 working +
1 standby)

Notes:
1. The above mentioned cooling / heating capacities are based on 46°C.DB, 30°C. WB ambient condition.
2. Fan motor and compressor of the outdoor and package unit shall be suitable to operate upto 50°C. ambient temperature without tripping.

___________________________________________________________________________________________________________________________
Q.E.A.

Page 325
5.3 SCHEDULE OF FRESH AIR FANS

UNIT REF. AREA SERVED EXHAUST AIR FLOW (l/s) TYPE EXT. STATIC PRESSURE (Pa) QTY.

EF 01 Pump room 1259 Wall-mounted Free Discharge 1

EF 02 Pump room 45 Wall-mounted Free Discharge 1

Notes:
1. Guard room fan Electrical Supply: 240 V, 1 Ph., 50 Hz. AC supply.
2. Pump room fan Electrical Supply: 415 V, 3 Ph., 50 Hz., and motor and complete fan assembly shall be suitable upto 400°C. temperature.

___________________________________________________________________________________________________________________________
Q.E.A.

Page 326
________________________________________________________________________________

GUARD ROOM

________________________________________________________________________________
Q.E.A.
Page 327
________________________________________________________________________________

INPUT DATA GUARD ROOM

________________________________________________________________________________
Q.E.A.
Page 328
Space Input Data
QATAR JOINT WARFARE 09-24-2018
qea 09:01AM

guard room

1. General Details:
Floor Area ............................................................. 8.0 m²
Avg. Ceiling Height ............................................... 2.4 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 2.0 People
Wattage ............................................................ 12.00 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 100.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 8.7 0 0 1
S 8.7 1 0 0
E 7.0 1 0 0
W 7.0 1 0 0

3.1. Construction Types for Exposure N


Wall Type ........................................ Medium Weight Wall
Door Type ..................................................................... D11

3.2. Construction Types for Exposure S


Wall Type ........................................ Medium Weight Wall
1st Window Type ........................................................... W4

3.3. Construction Types for Exposure E


Wall Type ........................................ Medium Weight Wall
1st Window Type ........................................................... W5

3.4. Construction Types for Exposure W


Wall Type ........................................ Medium Weight Wall
1st Window Type ........................................................... W5

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

Page 329
Hourly Analysis Program vv5.01 Page 1 of 2
Space Input Data
QATAR JOINT WARFARE 09-24-2018
qea 09:01AM

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ............................................................. 8.0 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
(No partition data).

Page 330
Hourly Analysis Program vv5.01 Page 2 of 2
________________________________________________________________________________

OUTPUT DATA FOR GUARD ROOM

________________________________________________________________________________
Q.E.A.
Page 331
Zone Sizing Summary for guard room
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:02AM

Air System Information


Air System Name .................................. guard room Number of zones ........................................................... 1
Equipment Class ............................................ TERM Floor Area .................................................................. 8.0 m²
Air System Type ........................................ SPLT-FC Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 1.8 1.8 22.8 / 13.5 13.9 / 9.8 - Jul 1600 21.22

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.3 19.0 / 20.3 - 170 0.000 0.000 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.8 Jul 1600 0.3 8.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
guard room 1 1.8 Jul 1600 170 0.3 8.0 21.22

Page 332
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for guard room
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:02AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
guard room 1 8.0 2.0 169.7 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 169.7 0.0

Page 333
Hourly Analysis Program v5.01 Page 2 of 4
Air System Design Load Summary for guard room
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:02AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 656 - 5 m² - -
Wall Transmission 24 m² 302 - 24 m² 122 -
Roof Transmission 8 m² 90 - 8 m² 31 -
Window Transmission 5 m² 245 - 5 m² 100 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 17 - 2 m² 7 -
Floor Transmission 8 m² 0 - 8 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 166 7 0% 0 0
>> Total Zone Loads - 1831 77 - 261 0
Zone Conditioning - 1786 77 - 262 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1786 77 - 262 0
Terminal Unit Cooling - 1786 0 - 0 0
Terminal Unit Heating - 0 - - 262 -
>> Total Conditioning - 1786 0 - 262 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 334
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for guard room
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:02AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 656 - 5 m² - -
Wall Transmission 24 m² 302 - 24 m² 122 -
Roof Transmission 8 m² 90 - 8 m² 31 -
Window Transmission 5 m² 245 - 5 m² 100 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 17 - 2 m² 7 -
Floor Transmission 8 m² 0 - 8 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 166 7 0% 0 0
>> Total Zone Loads - 1831 77 - 261 0

Page 335
Hourly Analysis Program v5.01 Page 4 of 4
________________________________________________________________________________

SUBSTATION

________________________________________________________________________________
Q.E.A.
Page 336
________________________________________________________________________________

INPUT DATA FOR SUBSTATION

________________________________________________________________________________
Q.E.A.
Page 337
Space Input Data
QATAR JOINT WARFARE 09-24-2018
qea 09:20AM

substation lv switchroom

1. General Details:
Floor Area ........................................................... 37.8 m²
Avg. Ceiling Height ............................................... 3.7 m
Building Weight ................................................ 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ...................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s
OA Requirement 2 .............................................. 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ......................... Recessed (Unvented) Occupancy ........................................................... 1.0 Person
Wattage ............................................................ 12.00 W/m² Activity Level .................................... Seated at Rest
Ballast Multiplier ................................................. 1.25 Sensible ............................................................. 67.4 W/person
Schedule ................................................. LIGHTING Latent ................................................................. 35.2 W/person
Schedule ..................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .............................................................. 0.00 W/m² Sensible .................................................................. 0 W
Schedule .......................................................... None Schedule .......................................................... None
Latent ...................................................................... 0 W
Schedule .......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 1500.0 Watts
Schedule ...................................... MISC. ELECTRIC

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 22.2 0 0 1

3.1. Construction Types for Exposure NW


Wall Type ........................................ Medium Weight Wall
Door Type ................................................................... sd1a

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 37.8 0 0

4.1. Construction Types for Exposure H


Roof Type ....................................... Medium Weight Roof

5. Infiltration:
Design Cooling ................................................... 0.00 L/s
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ....................................... Slab Floor On Grade
Floor Area ........................................................... 37.8 m²
Total Floor U-Value .......................................... 1.440 W/(m²ꞏK)
Exposed Perimeter ............................................... 0.0 m
Edge Insulation R-Value .................................... 0.00 (m²ꞏK)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Wall Partition (No partition data).
Area .................................................................... 69.0 m²
U-Value ............................................................ 1.370 W/(m²ꞏK)
Uncondit. Space Max Temp ............................... 43.0 °C
Ambient at Space Max Temp ............................. 46.0 °C
Uncondit. Space Min Temp ................................ 30.0 °C
Ambient at Space Min Temp .............................. 35.3 °C

Page 338
Hourly Analysis Program vv5.01 Page 1 of 1
________________________________________________________________________________

OUTPUT DATA FOR SUBSTATION

________________________________________________________________________________
Q.E.A.
Page 339
Zone Sizing Summary for substation lv switchroom
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:20AM

Air System Information


Air System Name .......... substation lv switchroom Number of zones ........................................................... 1
Equipment Class ............................................ TERM Floor Area ................................................................ 37.8 m²
Air System Type ........................................ SPLT-FC Location ...................................................... Doha, Qatar

Sizing Calculation Information

Calculation Months .................................... Jul to Jul Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(sꞏm²)
Zone 1 4.9 4.9 22.9 / 7.9 14.1 / 3.4 - Jul 1600 12.30

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.3 19.0 / 19.5 - 465 0.000 0.000 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.0 Jul 1600 0.3 37.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
substation lv switchroom 1 5.0 Jul 1600 465 0.3 37.8 12.30

Page 340
Hourly Analysis Program v5.01 Page 1 of 4
Ventilation Sizing Summary for substation lv switchroom
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:20AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Zone Name / Space Name Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Mult. (m²) Occupants (L/s) (L/s/person) (L/(sꞏm²)) (L/s) (% of supply) (L/s)
Zone 1
substation lv switchroom 1 37.8 1.0 465.0 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 465.0 0.0

Page 341
Hourly Analysis Program v5.01 Page 2 of 4
Air System Design Load Summary for substation lv switchroom
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:20AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 18 m² 220 - 18 m² 93 -
Roof Transmission 38 m² 424 - 38 m² 149 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 32 - 4 m² 13 -
Floor Transmission 38 m² 0 - 38 m² 0 -
Partitions 69 m² 1763 - 69 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 567 W 567 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 457 4 0% 0 0
>> Total Zone Loads - 5030 39 - 255 0
Zone Conditioning - 4891 39 - 257 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4891 39 - 257 0
Terminal Unit Cooling - 4891 0 - 0 0
Terminal Unit Heating - 0 - - 257 -
>> Total Conditioning - 4891 0 - 257 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Page 342
Hourly Analysis Program v5.01 Page 3 of 4
Zone Design Load Summary for substation lv switchroom
Project Name: QATAR JOINT WARFARE 09-24-2018
Prepared by: qea 09:20AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 30.0 °C HEATING OA DB / WB 10.0 °C / 6.0 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 18 m² 220 - 18 m² 93 -
Roof Transmission 38 m² 424 - 38 m² 149 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 32 - 4 m² 13 -
Floor Transmission 38 m² 0 - 38 m² 0 -
Partitions 69 m² 1763 - 69 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 567 W 567 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 457 4 0% 0 0
>> Total Zone Loads - 5030 39 - 255 0

Page 343
Hourly Analysis Program v5.01 Page 4 of 4
1.0 HEATER CALCUALTION TO MAINTAIN REALTIVE HUMIDITY IN WINTER CONDITION

Outdoor temp. In winter (To) = 100C

50±5% Relative Humidity has to maintained in the room heating is required to maintain relative
humidity. Header is provided to raise the air temperature by 2.50C

Heater KW FAHU 01 = Air flow rate x H x1.2


= 1252 x 2.5x1.2
= 3753
= 3.7 Kw
= 4 Kw

Heater KW FAHU 02 = Air flow rate x H x1.2


= 996 x 2.5x1.2
= 2988
= 2.9 Kw
= 3 Kw

Page 344

Das könnte Ihnen auch gefallen