VISIONr
Technical Manual
VISIONr TECHNICAL MANUAL Issue 3
Contents
1 INTRODUCTION. ...............................................................................................................7
1.1 Protection Functions..............................................................................................7
1.2 Real Time Metering Data. ......................................................................................7
2 TECHNICAL SPECIFICATION.............................................................................................8
2.1 Power Supply.........................................................................................................8
2.2 Measurement. ........................................................................................................8
2.3 Protection Functions..............................................................................................8
2.4 Relay Contacts Ratings..........................................................................................8
3 ENVIRONMENTAL TESTS...................................................................................................9
4 FUNCTIONAL BLOCK DIAGRAM. .....................................................................................11
5 FRONT PANEL..................................................................................................................12
5.1 LCD and Keypad...................................................................................................12
5.1.1 Status LEDs ............................................................................................12
5.1.2 RS232 connection. .................................................................................12
5.1.3 Protection Enabled (Pushbutton and Indicator). ...................................12
5.1.4 Live Line Enabled (Pushbutton and Indicator). .....................................12
5.1.5 Earth Fault Enabled (Pushbutton and Indicator). ..................................12
5.1.6 Reclose Enabled (Pushbutton and Indicator). .......................................13
5.1.7 Remote Enabled (Pushbutton and Indicator). .......................................13
5.1.8 AUX 1 (Pushbutton and Indicator). .......................................................13
5.1.9 AUX 2 (Pushbutton and Indicator). .......................................................13
5.1.10 AUX 3 (Pushbutton and Indicator). .....................................................13
5.1.11 TRIP (Pushbutton and Indicator). .......................................................13
5.1.12 CLOSE (Pushbutton and Indicator)......................................................13
6 PROTECTION SETTING SUMARY.....................................................................................14
7 GRAPHICAL DISPLAY......................................................................................................17
7.1 Menu Screens. .....................................................................................................17
7.2 DISPLAY SCROLL .................................................................................................17
7.3 Data Menu. ..........................................................................................................18
7.3.1 Measured Values. ...................................................................................18
7.3.1.1 Digital Values...............................................................................19
7.3.1.2 Analogue Values. ..........................................................................19
7.3.1.3 Disturb Values. .............................................................................19
7.3.2 Stats. ......................................................................................................20
7.3.3 Fault Data...............................................................................................20
7.3.3.1 Active Faults. ................................................................................20
7.3.3.2 Last Fault......................................................................................20
7.3.3.2.1 Last Trip. ............................................................................21
7.3.3.2.2 Last Alarm. .........................................................................21
7.3.3.3 Fault History. ................................................................................21
7.3.3.3.1 Trip History.........................................................................21
7.3.3.3.2 Alarm History. ....................................................................21
7.3.3.3.3 SER Summary. ....................................................................22
7.4 Breaker Control....................................................................................................22
7.5 Settings Menu......................................................................................................23
7.5.1 Control Settings. ....................................................................................23
7.5.1.1 Breaker Settings. ..........................................................................23
Page 3 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Page 4 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Page 5 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Page 6 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
1 INTRODUCTION.
The VISIONr is a sophisticated microprocessor based autoreclose protection relay designed specifically for the
FKI made Horizon circuit breaker and GVR pole mounted recloser.
The relay measures currents and voltages in the main circuit. This enables the relay to provide flexible
autoreclose protection and also a comprehensive range of metered data.
All of the setting parameters can be programmed using the integral keypad and LCD.
A RS232 connection on the front of the relay permits setting data to be retrieved from the relay or downloaded
from a PC. This connection also permits disturbance records to be retrieved for viewing.
A RS485 connection on the rear of the relay permits full control of the relay via a number of communication
protocols.
The relay provides optically isolated inputs for control of the relay. The status of these inputs is available via the
integral LCD.
The relay also provides a number of relay contact outputs. These can be configured to provide indication of the
relay status.
During operational conditions the LCD also gives access to accurate load, statistical and fault data.
Phase Currents
Earth Fault Current
Phase Volts
Phase Power kW
Phase Power Factor
Phase Apparent Power
Phase Real Power
Kilowatt Hours
Total Power
No. of Operations
Page 7 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
2 TECHNICAL SPECIFICATION.
Frequency 45 - 65 Hz
Maximum Power Consumption 10VA
2.2 MEASUREMENT.
T im e -O v e r c u r r e n t E le m e n ts
± 2 0 m S a n d ± 5 % (to E N 6 0 2 5 5 -3 ) o f
F a u lt T im e A c c u r a c y c u r v e t im e f o r c u r r e n ts b e t w e e n 2 & 2 0
m u lt ip le s o f p ic k u p
P ic k u p A c c u r a c y ± 10m A and ± 3 % o f s e t t in g
M in im u m R e s p o n s e T im e 50m S
Page 8 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
3 ENVIRONMENTAL TESTS.
Page 9 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Page 10 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The VISIONr relay is equipped with 4 x CT inputs for Phase Current and Earth fault measurement. The Earth CT
can be residually connected from the 3 x Phase CT’s as an alternative to the above diagram.
Three (3) Phase to Neutral VT inputs are used to monitor the voltage of a 3 phase system. Normal VT’s can be
connected or Capacitive VTs can be used as shown above. A residual neutral voltage is calculated which is
used to determine the direction of earth fault current for required applications. Alternatively when this residual
voltage is not required a fourth VT input is available for check synchronisation.
As standard the VISIONr has twelve (12) optically isolated (9 programmable) digital inputs with a separate
control voltage source to allow for either dc or ac inputs without consideration needed to be given to the auxiliary
supply voltage. Eight (8) changeover contact output relays are provided on the relay, Outputs 1 and 2 are set as
Trip and Close allowing the other 6 to be freely programmed.
Page 11 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
5 FRONT PANEL.
The LCD and keypad have been designed to display and access all the information an operator may require.
The LCD is a fully graphic display and is navigated by 4 software driven function keys. On each screen
appropriate options are displayed adjacent to the 4 keys. This allows the user to easily navigate through the
screens.
Two tri-colour LEDS immediately beneath the display provide information about the breaker and relay status.
A RS232 connection on the front panel permits downloading of settings and retrieval of historic data.
This button enables the protection functions of the relay. The associated LED illuminates to show that Protection
is enabled. If protection is not enabled then the relay will not respond to fault level currents.
This button switches all protection features to a single instantaneous trip for both the phase and earth fault
protection, as denoted by the Live Line protection settings. The associated LED illuminates to show that Live
Line protection is enabled.
This button enables the Earth Fault protection functions. The associated LED illuminates to show that Earth
Fault protection is enabled.
Page 12 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
This button enables autoreclosing. The associated LED illuminates to show that Reclose is enabled. If Reclose
is not enabled then the relay will respond to any fault condition with a single trip in accordance with its “Single
Shot” settings.
This button enables remote control of the relay and circuit breaker. The button must be continuously pressed for
3 seconds in order to enable or disable remote control. The associated indicator illuminates to show that Remote
control is enabled. If Remote control is enabled then the relay and breaker will respond to the hardwired digital
inputs and to control commands received via the rear communications port.
This button provides for a future auxiliary function. The associated indicator illuminates to show that this
auxiliary function is selected.
This button provides for a future auxiliary function. The associated indicator illuminates to show that this
auxiliary function is selected.
This button provides for a future auxiliary function. The associated indicator illuminates to show that this
auxiliary function is selected.
This button sends an open pulse to the circuit breaker. The associated indicator illuminates to show that the
breaker is in the open position.
This button sends a closing pulse to the circuit breaker. The associated indicator illuminates to show that the
breaker is in the closed position.
Page 13 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Active in
# Selectable O ption
Remote
Change Name
Indicators 1-4
Warn 1
Warn 2
Inhibit
Alarm
Block
Serial
Panel
! Not Selectable E xtended I/O Version
Auto
Test
Trip
" Not Changeable V ISIO N PM R
ANSI Available
Protective Function Available Action V ariable Range Step
No. Reset
Characteristic DEFT, NIN V, VINV , E INV
Tim e M ultiplier 0.1 - 10 0.01
50/51 O vercurrent 1 " # # # # # # " ! ! ! #
SHOT 1 PROTECTION SET
Page 14 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Active in
# Selectable Option
Remote
Change Name
Indicators 1-4
Warn 1
Warn 2
Inhibit
Alarm
Serial
Block
Panel
! Not Selectable Extended I/O Version
Auto
Test
Trip
" Not Changeable VISION PMR
ANSI Available
Protective Function Available Action Variable Range Step
No. Reset
Characteristic DEFT, NINV, VINV, EINV
50/51 Cold Load Pick-Up
CLPU PROTECTION SET
Page 15 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Dead Times 1, 2 and 3 are the breaker open time between a trip and the subsequent reclose.
The Reclaim Time is the time period between a fault current that has cleared and the relay reverting back to
Protection Set 1, hence allowing a full sequence to occur again before lockout.
The Sequence reset time is the time period that maintains the last protection set characteristics if the breaker is
manually closed after a lockout, before then reverting back to Protection Set 1 characteristics.
Manual Close and Open delays are the time periods between a panel close or open being requested by the
operator and the VISIONr issuing the command to the breaker. This is to allow the operator to gain safe
distance before the breaker is operated.
The Breaker Type and Dead Time Offsets are configured during factory build and are to ensure correct
operation and permissible operation time between the breaker and VISIONr.
Page 16 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
7 GRAPHICAL DISPLAY.
The VISIONr’s graphical display provides access to all dynamic and historical data, protection parameter set
points and control set-up.
On power up the VISIONr screen appears for a few seconds. The screen shows the software version and the
unit serial number, which should be noted in all correspondence with FKI Switchgear regarding the relay.
After the introduction screen disappears then the initial screen appears, shown right.
The main portion of the screen shows the three phase currents. Various message banners can appear under
different conditions to alert the operator to the present situation. These can be time to trip messages, countdown
to reset or clear inhibit messages and so on. The name of the fault condition causing the trip will also appear
along with the timer.
The four menu driven software keys each navigate to four main areas of the menu structure. These are
DISPLAY SCROLL, DATA MENU, BREAKER CONTROL and the SETTINGS MENU.
The DISPLAY SCROLL button scrolls through various measured values. This feature is described fully in section
7.2.
The DATA MENU button provides access to numerous ‘layered’ screens that display a multitude of historical and
dynamic data the VISIONr is presently metering or has recorded. This feature is described fully in section 7.3.
The BREAKER CONTROL button permits operation of the breaker via the LCD and software keys and shows
the permitted and inhibited sources of breaker control. This feature is described fully in section 7.4.
The SETTINGS MENU button provides access to numerous ‘layered’ screens that display the full range of
settings available within the VISIONr. This feature is described fully in section 7.5.
The DISPLAY SCROLL button scrolls in a loop displaying various measured values and drive status data. Any
one of these pages can be selected as the ‘default’ page, so that if the unit is left whilst in a sub menu the
screen can return to a pre-selected page after a set time-out period.
Page 17 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Those in grey are only applicable to VISIONr when supplied with directional earth fault.
DIGITAL
VALUES This screen continues to show all the data that is given by the initial screen but there are sub
screens accessible to the user by pressing any of the four buttons.
ANALOGUE
VALUES
DISTURB
VALUES
EXIT
Page 18 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
A filled box represents an active or energised input, a clear box represents a de-energised input.
DIGITAL
VALUES UP SELECT 7.3.1.3 Disturb Values.
ANALOGUE Disturbance Trace
VALUES View Trace If Disturbance Recording is enabled, this screen is accessible
Trace Time Empty and allows the viewing and configuring of the disturbance
Trace Input I1
DISTURB Enable Ov erwrite No traces.
VALUES Clear Traces
Tr igger On Tr ip
Tr igger Position
EXIT 0 / 100% This facility is explained in further detail in section 13.
DOWN EXIT
Page 19 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
7.3.2 Stats.
UP RESET
The list of data can be scrolled through using the top-left button (UP) and the
Stats bottom-left button (DOWN).
Hours this Close
0H
Total Hours Close The bottom-right button takes you back to the DATA MENU. The RESET button
0H
kW Hrs Total
(top-right) resets the value highlighted to zero. The list of statistical data is as
0.0
kW Hours 1 0.0 follows:
kW Hours 2 0.0
DOWN EXIT
MEASURED
VALUES
This screen lists the options for the viewing of previous alarms and faults that have occurred
as well as faults and alarms that are currently active. There are three further screens that are
accessible:
STATS
If a fault occurs which results in a TRIP, the unit automatically displays the
FAULT active faults page.
DATA
EXIT
ACTIVE FAULTS
LAST Supply Missing This menu lists the Active Faults of the relay if there are any.
FAULT
A Reset button will appear if the fault is no longer active and if
FAULT
PANEL RESET is Enabled in the Protection Function.
HISTORY The '∗' next to the fault means that the fault is still active.
The characters preceding the fault description denote the action taken, a ‘T’ denoting a TRIP, an ‘A’ denoting an
ALARM and an ‘I’ denotes an INHIBIT.
LAST Both Events would also appear with their time and date stamp at the top of the associated fault
FAULT history pages.
FAULT The Analogue data for the last historical event is recorded at the time of Trip or Alarm.
HISTORY
EXIT
Page 20 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
This screen displays the same as the LAST TRIP screen above except that it shows the LAST ALARM event
that occurred.
ACTIVE Fault History allows viewing of the last 32 TRIP events and the last 32 ALARM events, each
FAULTS
event is time and date stamped to the millisecond.
LAST
FAULT The two lists operates on a first-in first-out principle meaning any recent events will force the
earliest events from the register.
FAULT
HISTORY Single events can be deleted providing the password is known.
EXIT
TRIP
HISTORY UP VIEW Each occurrence in the Trip, Alarm histories and SER
Tr ip History Summary will be time and date stamped to an accuracy of 1
ALARM ARC SEQUENCE millisecond.
HISTORY 16 : 41 : 47 : 30 14 / 12 / 05
ARC SEQUENCE This can help to identify tripping and alarm trends of the
16 : 40 : 30 : 57 14 / 12 / 05
SER breaker and also to aid identification as to the cause of any
SUMMARY
32 date & time stamped ev ents cascade tripping sequences.
This screen displays the same as the TRIP HISTORY screen above except that it shows the previous alarm
events that have occurred.
Page 21 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
TRIP
HISTORY UP
DATA DISPLAY
MENU SCROLL
The BREAKER CONTROL page allows local PANEL control of the Circuit
FEEDER TAG
Breaker (CB).
I1:0A The breaker control page displays the control availability matrix which shows in a
I2:0A very effective format from which sources the CB can be Closed and Opened.
I3:0A
BREAKER SETTINGS
CONTROL MENU
Panel refers to any command issued via the face plate buttons.
Serial refers to any command issued via any of the serial ports.
Remote refers to any command issued via the digital inputs.
CLOSE
As well as the Close and Trip pushbuttons on the front fascia the CB can be
Breaker Control controlled via the local PANEL buttons.
L R Status LOCAL
Close Open The permissive and inhibit sources displayed here for the circuit breaker are
Panel Y es Y es dictated by the Remote Pushbutton on the front fascia.
Serial No No
Remote No No
Those settings transpose directly into this page producing the YES and NO
OPERATE
EXIT OPEN indications for each source.
Page 22 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
As the four software driven buttons change function depending upon what page (or equally what
type) of data is being changed, this section also details the use of; pop-up boxes, changing values
and timers, handling tick box applications and multiple choice settings.
CONTROL The CONTROL SETTINGS sub menu of the Settings Menu allows manipulation of the
SETTINGS necessary functions required to set-up the Circuit Breaker.
PROTECT The Digital Inputs, Relay Outputs and the Breaker Settings functions are all configured under
SETTINGS
this menu header.
SYSTEM
SETTINGS
EXIT
Page 23 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
UP SELECT If a digital input is already assigned to an input no. then it cannot be set to
Auto / Man another input no. it will still appear in the list and will be lined-out.
Digital
Loc Inputs
/ Rem
The digital input functions are described in more detail in section 9.
Input 1Cont. A Stop
Cont. B This pop-up format also applies to Relay Outputs selection or where a list of
Input 2 Start A
Test selectable options is available.
Input 3Authorise Test
Input 4 EXTERNAL Cont1 A
On exit from this screen Input 5 will be set to EXTERNAL 1.
Input 5 Not Used
DOWN EXIT
Page 24 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
CONTROL
SETTINGS UP SELECT
On selecting, this page displays all protective function available.
Protection Settings
A Cold Load Pickup Each function can be selected using the UP and DOWN keys,
PROTECT
SETTINGS T CLPU HS each function can then be configured.
T E/F CLPU At a glance the left-hand coloumn shows whether a function is
OFF E/F CLPU HS
SYSTEM active or not and what configuration or action it is set to.
T Ov ercurrent 1
SETTINGS
OFF Overcurrent 1 HS
In this example the configuration for the behaviour of Definite Time protection
UP SELECT can be controlled.
Ov ercurrent 1 There are four setting groups:
Function On T
Function: Set ON / OFF, Set ALARM, Set TRIP.
Reset Auto Reset: Auto / Panel / Serial or Remote or combination.
Indicator 1+3 NOTE:- When the unit is set to Reclose all resets are
Charcteristic automatically set as Auto.
Def inite Time
Trip Time 0.05s Indicator: Relay output indicators 1, 2, 3 or 4 or combination.
Characteristic: The User can select between Definite Time, Normal
DOWN EXIT Inverse, Very Inverse and Extremely Inverse curves.
Depending on the selected characteristic the settable
options may change. For further details see section 18
Trip Time: The settable trip time.
Each option moves a ‘pop-up box’ forward to select the desired operation.
Each protective function has specific settings associated with it. The settable options for each protective function
are explained in further detail in section 18.
Page 25 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
PROTECT
SETTINGS The System Settings menu provide access to a further sub set of menus:
SYSTEM Feeder settings, Serial Settings, Unit Settings and Smart Card settings.
SETTINGS
EXIT
FEEDER UP SELECT This screen allows the user to change the feeder settings of
SETTINGS the relay. The list of values to be changed can be scrolled
Feeder Settings
Ov ercurrent Poles
through by pressing the UP and DOWN buttons (top-left and
SERIAL bottom left). A value can be selected to have its value changed
3 Poles
SETTINGS
CT Primary 500A by pressing the SELECT button (top-right) when the value is
VT Prima ry 19920V highlighted. This then brings up the VALUE CHANGE
UNIT VT Secondary 120V
& SMT CARD Voltage 9960V
SCREEN
UP DISCARD The Value Change pop-up allows you to alter settings in specified steps within
Feeder Settings
the minimum and maximum values of the particular setting range. The pop-up
Ov ercurrent Poles over lays the main screen, the menu buttons operate the pop-up as normal. The
3 Poles Exit button becomes a Next function in this window to skip along to the next
CTVT Secondary
Primary 500A character. If an undesired value is inserted incorrectly use the Next button to skip
VT Prima ry 1 19920V
2 0
VT Secondary 120V
past the last character to the left the Select option button now operates as a
Voltage 9960V Discard to dump the new value without saving – reverting back to the original
value on initial selection.
DOWN NEXT
FEEDER
SETTINGS UP SELECT
This screen allows the user to change the communication port
Serial Settings
aspects of the relay.
SERIAL Serial Enabled
SETTINGS Driv e Number 1
RS485 Baud Rate 9600 Section 12 describes in detail the function of each of the
UNIT RS232 Baud Rate 9600 available serial settings.
& SMT CARD Serial Delay 5ms
Fastscan = 4 Words
Page 26 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
FEEDER UP SELECT
SETTINGS
Unit Settings
This screen allows the user to change
Ver 2.014 certain global characteristics of the relay.
SERIAL SMART
Unit ID 9999
SETTINGS CARD
Password Disabled Each setting is explained in detail in section
Engineer Passwo rd 16.
UNIT UNIT
Disabled
& SMT CARD SETTINGS
Change Password
UP SELECT
The Smart Card is a removable eeprom memory card which
can be supplied with VISIONr on request.
Smart Card Settings
SMART Card Setting Card
Card Not Inserted
The Smart Card can be used for parameter storage and for
CARD
Card Data Different cloning other relays or it can be formatted as an extended data
Write 00 : 00 : 00 card which will log and store events.
UNIT
00 / 00 / 00
SETTINGS Tra nsf er Data
Page 27 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
8 CONTROL OUTPUTS
The relay has 8 output relays 6 of which can be assigned to any of the following list except for:-
8.2.1 Close.
Once receiving a command to close the circuit breaker the output relay closes, thus sending a close signal to the
circuit breaker. This signal remains closed until the relay is informed that the breaker has changed state. The
relay determines the status of the breaker via the digital input that is assigned to "ACB Feedback". Once the
status of this digital input has changed the output relay opens. In the case where no change of breaker status is
detected, the output relay remains closed until the time specified in the Breaker Fail Protection Function has
elapsed.
8.2.2 Trip.
This output is used to trip the circuit breaker and follows the same pattern as above. i.e. when a trip command is
received the output relay closes and remains closed until the breaker is seen to open via the "ACB Feedback"
input or the time specified in the Breaker Fail Protection Function has elapsed.
This option switches off the use of that particular output relay.
8.2.4 Warn 1.
If an output relay is assigned as “Warn 1” then this relay will change state from de-energised
to energised when triggered by any protection function or external device connected to the relay that is
configured with Warn 1 enabled.
The relay will only be energised while the protection function or external device registers that a pickup setting or
fault status has been violated. When the pickup setting is no longer violated the output relay assigned as “Warn
1” will be de-energised.
“Warn 1” output relay will be energised as soon as a protection features pickup has been exceeded despite any
delays that may have been assigned.
Page 28 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
8.2.5 Warn 2.
If an output relay is assigned as “Warn 2” then this relay will change state from de-energised
to energised when triggered by any protection function or external device connected to the relay that is
configured with “Warn 2” enabled.
The relay will only be energised while the protection function or external device registers that a pickup setting or
fault status has been violated. When the pickup setting is no longer violated the output relay assigned as “Warn
2” will be de-energised.
“Warn 2” output relay will be energised as soon as a protection features pickup has been exceeded despite any
delays that may have been assigned.
8.2.6 Alarm.
If an output relay is assigned as “Alarm” then this relay will change state from de-energised to energised when
triggered by any protection function or external device connected to the relay that is configured to alarm.
The alarm operates after the expiry of the programmed time delay assigned to the protection feature.
If an output relay is assigned as any of the 4 available Indicators then this relay will change state from de-
energised to energised when triggered by any protection function or external device connected to the relay that
is configured to indicate on that same indicator channel.
Once activated the output relay will be latched and requires a reset before returning to its normal state. Unlike
Warn 1 and Warn 2 which are activated as soon as a protection feature pickup is exceeded, Indicators will only
be activated after the expiry of the time delay assigned to the protection feature.
If an output relay is assigned as “Alarm FS” then this relay will change state from energised to de-energised
when triggered by any protection function or external device connected to the relay that is configured to alarm.
The alarm operates after the expiry of the programmed time delay assigned to the protection feature.
If an output relay is assigned as any of the 4 available fail safe indicators then this relay will change state from
energised to the de-energised relay contact when triggered by any protection function or external device
connected to the relay that is configured to indicate on that same indicator channel.
Once activated the output relay will be latched and requires a reset before returning to its normal state. Unlike
Warn 1 and Warn 2 which are activated as soon as a protection feature pickup is exceeded, Indicators will only
be activated after the expiry of the time delay assigned to the protection feature.
If an output relay is assigned as ‘Serial Available’ this relay will be energised only when the breaker is available
to be closed through the serial port, via a serial command.
Page 29 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
If an output relay is assigned as “Panel Available” this relay will be energised only when the breaker is available
to be closed from the front panel of the relay.
If an output relay is assigned as ‘Remote Available’ this relay will be energised only when the breaker is
available to be closed from a remote station via a digital input.
If an output relay is assigned as “Trip & Lockout” then this relay will change state from the de-energised to the
energised relay contact when triggered by any protection function or external device connected to the relay that
is configured to trip the circuit breaker. Once “Tripped” the relay will not permit any further control of the circuit
breaker until the fault has been acknowledged by means of a reset. Trip and Lockout will provide a permanent
open signal to the circuit breaker thus preventing manual closure of the circuit breaker onto a possible fault
condition. The Trip and Lockout relay is a maintained relay action.
8.2.14 Follow A.
If an output relay is programmed as “Follow A” its state will mirror the state of output relay 1.
Output relay 1 is always set to CLOSE and is a pulse contact.
8.2.15 Follow B.
If an output relay is programmed as “Follow B” its state will mirror the state of output relay 2.
Output relay 2 is always set to TRIP and is a pulse contact.
If an output relay is programmed as “Gas Pressure Alarm” then this relay will change state from the energised to
the de-energised state if the gas pressure falls below a pre-set alarm level.
If an output relay is assigned as “Sequence Lockout” then this relay will change state from the de-energised to
the energised relay contact when triggered by any protection function that terminates the re-closing sequence or
the relay completes its programmed reclose sequence without reclaiming. Once “Locked Out” the relay will not
de-energise until the relay is re-closed.
If an output relay is programmed as “Protection Enabled” then this relay will energise when the relays Protection
Function is ENABLED and de-energise when the Protection Function is DISABLED.
Page 30 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
If an output relay is programmed as “E/F Protection Enabled” then this relay will energise when the relays E/F
Protection Function is ENABLED and de-energise when the E/F Protection Function is DISABLED.
If an output relay is programmed as “Live Line Enabled” then this relay will energise when the relays Live Line
Function is ENABLED and de-energise when the Live Line Function is DISABLED.
If an output relay is programmed as “Reclose Enabled” then this relay will energise when the relays is set to Auto
Reclose de-energise when the relay is set to Single Shot.
If an output relay is programmed as “Aux 1- 3 Enabled” then this relay will energise when that Auxiliary Function
(if programmed) is ENABLED and de-energise when that Auxiliary Function is DISABLED.
If an output relay is programmed as “Supply Missing FS” then this relay will change state from the energised to
the de-energised state if the relay supply is lost.
If an output relay is programmed as “Internal Error FS” then this relay will change state from the energised to the
de-energised state if the relay develops an internal fault.
Page 31 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
9 CONTROL INPUTS.
12 digital inputs are provided. The supply voltage range for these inputs is the same as the supply voltage range
for the relay. The condition of all these inputs can be viewed at any time via the Digital Inputs page of the Data
Menu.
Input 1 is always assigned as “ACB Feedback” and allows the relay to monitor the position of the circuit breaker.
The status of the switchgear is determined and shown via the front plate LED's and LCD display. An auxiliary
contact on the Circuit Breaker provides the signal for this digital input.
Input 2 is always assigned as “Close” and will close the circuit breaker provided that the close setup source
within the software has been configured to allow remote closing of the breaker.
For a close to occur there must be no inhibit conditions existing. Any fault condition must be cleared.
Note: A circuit breaker may only be closed provided all conditions that inhibit such an action are healthy including
password security.
Input 3 is always assigned as “Open” and will open the circuit breaker provided that the open setup source
within the software has been configured to allow remote opening of the breaker.
Only a momentary digital input signal is required for the “Close” and “Open” commands.
Reset Fault
Auto / Manual
Local / Remote
Test / Service
Authorise
Blocking Input.
External Fault 1-5
Protection
E/F Protection
Live Line
Reclose
Aux 1-3
This input enables the operator to reset Fault or Alarm conditions. Normally this input can only perform a reset if
the following conditions are met:
1. The Protection Settings for the specific fault or alarm are set to allow remote resets.
2. The condition that caused the Fault or Alarm to occur no longer exists.
However if the Authorise input is set (see later) then the Reset Fault input will work irrespective of condition 1.
These inputs are used to determine which of the Close and Open sources (front panel, serial, remote) are
enabled.
Page 32 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
This input allows the protection relay to enter Test Mode. In this mode selected protection functions can be
disabled to permit easier testing.
9.1.4 Authorise.
When this input is open it prevents unauthorised access to change settings. Any attempt to adjust settings will
result in a request for a password.
This input can block any protection function that has blocking enabled.
These inputs can be used to trigger Trip or Alarm conditions. These inputs can work with either normally close or
normally open contacts.
9.1.7 Protection.
This input is used to Enable or Disable the VISIONr Protection function when the unit is in REMOTE control.
This input is used to Enable or Disable the VISIONr Earth Fault Protection function when the unit is in REMOTE
control.
This input is used to Enable or Disable the VISIONr Live Line Protection function when the unit is in REMOTE
control.
9.1.10 Reclose.
This input is used to switch the VISIONr into Single Shot Protection or Auto Reclose Protection when the unit is
in REMOTE control.
These inputs Enable or Disable the VISIONr Aux1-3 function (if programmed) when the unit is in REMOTE
control.
Page 33 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
10 BREAKER SETTINGS
This allows the user to program a delay between a panel close command and the unit closing. This delay is
settable between 0-60s. This setting is to allow the operator to gain safe distance before the VISIONr closes the
breaker.
This allows the user to program a delay between a panel open command and the unit open. This delay is
settable between 0-60s. This setting is to allow the operator to gain safe distance before the VISIONr opens the
breaker.
This allows the user to program the overcurrent pickup level for the sequence and single shot overcurrent trips.
This allows the user to program the Earthfault pickup level for the sequence and single shot Earthfault trips.
THE FOLLOWING 3 SETTINGS (10.1.5 – 10.1.7) ARE ONLY AVAILABLE IF THE RELAY
IS FITTED WITH DIRECTIONAL EARTH FAULT SOFTWARE
This setting allows the configuration of the residual voltage pickup level. Ve is internally calculated from the
residual sum of the connected three phase voltages.
10.1.6 Ie Direction
This setting dictates the direction of earth fault the relay will call a trip. This setting provides the datum point for
the Ie Sector setting.
10.1.7 Ie Sector
The Ie Sector is the operational zone in which Earth Fault protection settings are inhibited. The sector is
effectively split evenly each side of the Ie Direction setting.
For a more detailed explanation of the directional earth operation see Appendix 5.
Page 34 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
This allows the user to enable or disable the cold load pickup function.
The cold load pickup (CLPU) feature is a 1 SHOT sequence intended for those applications where the start up
currents of a system, which occur when the breaker is closed, might cause the normal protection sequence
(whether it is RECLOSE or 1 SHOT) to trip.
This feature will cause the unit to only perform the last trip in the sequence if the enclose enabled function is set
or the last single shot trip if the unit is closed after lockout and the set sequence rest time (1-180s) has not
elapsed.
This allows the user to enable or disable the Sequence Co-ordination function.
The sequence co-ordination feature is intended for applications where two or more breakers are connected
inseries. It is used to automatically advance the sequence of an upstream breaker when it sees fault current
interrupted by a down stream breaker.
This allows the user to set the number of overcurrent trips from 1 to 4 in the trip sequence. The setting of these
trips can be configured in protection settings.
Note: To set all via overcurrent trips via the screen this value must be set to 4 else only the number selected can
be configured.
This allows the user to set the number of Earth Fault trips from 1 to 4 in the trip sequence. The setting of these
trips can be configured in protection settings.
Note: To set all via Earth Fault trips via the screen this value must be set to 4 else only the number selected can
be configured.
This allows the user to set the dead time interval (0.25s-180s) between the trips in the sequence.
This allows the user to set the time between a fault clearing before the unit has completed a sequence and the
relay resetting.
Page 35 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
11 FEEDER SETTINGS.
This specifies that the unit is set for 3 x phase current inputs.
11.1.2 CT Primary
This setting allows the user to program the primary current rating of the protection class current transformers on
the supply phases. It is assumed that all phase current transformers are of the same rating.
11.1.3 VT Primary
This setting allows the user to program the primary voltage rating of the three phase voltage transformers (if
used). If a VT is not used enter the rated voltage for the direct connection. This is limited to 415V.
Note: Each of the 3 phase Voltage Inputs should be connected between a phase and neutral only. The
Voltage Reference Input (check synch) may be connected between two phases or a phase and neutral.
11.1.4 VT Secondary
This setting allows the user to program the secondary voltage rating of the external voltage transformers (if
used).
11.1.5 Voltage
This should be set to the line voltage of the supply and is necessary for power calculations. The setting is also
used for the Under/Overvoltage.
As an example if the voltage input was connected between two phases on a 415V system this setting would be
415V. If however the voltage input was connected between a phase and neutral then this setting should be
240V.
This setting allows the user to program the Constant Current Rating of the feeder or transformer supplying the
load as a percentage of the CT Primary rating.
Since this setting is a percentage of the CT primary, any change in the CT Primary setting will alter the
CCR setting. As a result it is recommended that the CT Primary be set first.
Page 36 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
This setting allows the user to program the primary current rating of the protection class current transformer
used to measure the primary earth fault current.
NOTE:- This should be set to the same value as the phase CT Primary for residually connected earth
fault measurement.
This setting range 1 to 60 min in steps of 1min determines the period over which a measurement is taken to
integrate the Kilowatt Hours value.
Page 37 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
12 SERIAL SETTINGS
12.1.1 RS485
A 3 pin RS485 connector on the rear of the relay permits the control of the relay via a number of protocols.
VISIONr is compatible with DNP3, Modbus RTU and Modbus ASCII based systems. A Profibus version of
VISIONr is available but the physical interface changes to a 9-way D-type connector.
12.1.2 RS232
The 9-way D-type RS232 connector on the front of the rely permits programming of settings and retrieval of
historical data using the supplied Windows software.
This setting allows the user to enable the VISIONr serial communications port. This setting must be set to
“Enable” if communication with the relay through the serial link is required.
Drive Number.
This setting range 1 to 32 0r 1-125 with Profibus, with a default setting of 1, identifies the VISIONr unit to the
Xcell unit (or any Master device connected to the Data highway) to which the RS485 or Profibus port is
connected. When updating firmware the auto program mode requires the drive number to be 1.
This setting allows the user to configure the appropriate communications baud rate such that the VISIONr can
communicate effectively on the Data Highway to which it is connected.
This setting allows the user to configure the baud rate for the front mounted RS232 port.
Serial Delay.
The VISIONr may be configured to respond to a request for information from the serial port instantly or after a
designated delay.
A communications delay may be beneficial to ensure the Master device on the Data Highway receives all
information sent back by the VISIONr without enduring data collisions on the network.
A Fast Scan is a system used when operating in conjunction with the XCell Data Concentrator. As the XCell
polls relays attached on its network, the fastscan settings allows the user to select important data to be read
back faster.
The data on the communications link is broken into Fast Scan Data (or Process Critical Data) and Slow Scan or
Full Read Data (Electrical Engineering Data).
The amount of Fast Scan Data to be sent back to the XCell in response to a request is configurable. This setting
has the range 4, 6 or 8 Words. A setting of 4 Words will give 3 Fast Scans. The remaining Word is taken up by
the Total Power. A setting of 6 Words will give 5 configurable Fast Scans and a setting of 8 Words will allow 7
configurable Fast Scans.
Page 38 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The configuration of Fast Scan is not necessary unless the VISIONr in used in conjunction with the XCell unit.
Each Fastscan number can be programmed to export important data when requested. This number references
an internal address in FV2 and allows configurable data mapping between units. Typical data could be 3-Phase
Current, 3-Phase Voltage and so on. A table of the Fastscan reference numbers can be found in appendix 1
This setting need only be used in order to limit the amount of data traffic on a RS485 network. Dynamic data can
change rapidly, this setting allows the VISIONr to limit the number of updates it makes to its Fast Scan values.
The RS485 serial communications port may be configured to operate using a slave implementation of Modbus
RTU®, Modbus ASCII, DNP3 or P&B Engineering’s own protocol “P&B Standard” designed to remove some of
the speed issues associated with a function based protocol like Modbus.
Parity.
This setting allows the user to set the parity to match that of the host system on the serial link. The options are
“Odd”, “Even” and “None”.
This setting allows the user to configure the way the relay transmits the measurement data via the serial port. If
set too fixed the relay transmits this information without any scaling i.e. power is transmitted as KW. If set to
Auto the data will be transmitted with a scaling factor as part of the transmission allowing the measurement to be
displayed as a scaled value i.e. power will be transmitted as MW. The options are “Auto” and “Fixed”.
Gap in Message.
This is an additional delay period between the transmission of multiple byte data from the relay. The delay can
be set from 10ms to 1s in 10ms steps.
Page 39 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
13 DISTURBANCE RECORDING.
Disturbance and fault recording is a very effective tool for personnel to analyse the performance of the power
system and related equipment during and after a major disturbance.
Utilising the graphical display to full effect an onscreen Disturbance Recording facility is available.
The relay captures the 8 most recent oscillographic records. These can be weighted pre and post fault on
selectable triggering events.
All the currents and voltages are captured on a single recording (viewable separately) along with a specified
digital output and digital input.
The disturbance traces can also be extracted via the optional front mounted RS232 port in Comtrade format for
high resolution analysis.
The disturbance recording feature is accessed using the DATA MENU / MEASURED VALUES / DISTURB
VALUES buttons. This brings up the screen below.
UP SELECT
Disturbance Trace
Clear Traces
Tr igger On Tr ip
Tr igger Position 0 / 100%
Maximum Traces 8
Digital Input 1
Digital Output 1
Resolution Half
DOWN EXIT
View trace
Displays the oscillographic record appropriate to the ‘Trace Time’. A screen similar to that shown below is
presented.
SCROLL SCROLL
LEFT RIGHT
DO 1
0
DI 1
0
MORE
KEYS EXIT
In this screen the SCROLL LEFT / SCROLL RIGHT buttons move about the trace. The MORE KEYS button
changes the function of the SCROLL LEFT and SCROLL RIGHT buttons to ZOOM IN and ZOOM OUT.
Trace Time
Displays the time and date of the presently selected trace. SELECT this option to see a list of the times and
dates for the available oscillographic records. If desired, one of the alternative traces can then be selected.
Page 40 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Trace Input
Shows which analogue value will be displayed when the View Trace option is selected. SELECT this option to
see a list of the available analogue values. If desired, one of the alternative values can then be selected.
Enable Overwrite
Once the maximum traces have been recorded “trace full” will be displayed on screen. If Overwrite is enabled
then a new recording will overwrite the oldest recording.
Clear Traces
This clears and permanently deletes all oscillographic records from the buffer memory.
Trigger
Shows the trigger condition for oscillographic recording. SELECT this option to see a list of the available
triggering options. If desired, one of the alternative options can then be selected.
Trigger Position
Shows the trigger position as pre and post fault percentages. SELECT this option to see a list of the available
options. If desired, one of the alternative options can then be selected.
Resolution
The resolution can be set to half (allowing the full 9 seconds) or full, which allows a maximum of 4.5 seconds
recording.
Maximum Traces
Up to eight traces can be recorded. If set to the maximum with full resolution, then each trace length can only be
a maximum of 1.1seconds each.
Page 41 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
14 TRIP HISTORY.
This option provides detailed information about the 32 most recent protection sequences. This option is
accessed via the Data Menu / Fault Data / Fault History buttons. This brings up a screen similar to that shown
below: -
UP VIEW
FAULT SEQUENCE
Overcurrent 1
Sec:10ms 0:0
Dead time 1
Overcurrent 2
Sec:10ms
Dead time 2
Overcurrent 3
Sec:10ms
DOWN EXIT
The four most recent protection sequences are listed with their time and dates. The Up and Down buttons can
be used to step through the list of sequences. Pressing the View button shows more detail about the highlighted
sequence. The exact display content depends upon the sequence detail but an example is given below: -
UP VIEW
Overcurrent 1
I1 449.3A
I2 0.0A
I3 0.0A
I0 449.5A
V1 0.0V
V2 0.0V
V3 0.0V
DOWN EXIT
This screen typically lists the trip type, trip time and dead time for each trip in the sequence. It may be necessary
to use the Up and Down keys to view all of the data. As these keys are used the following / preceding trip will be
highlighted. Pressing the VIEW button will show more detail about a particular trip. A typical screen is shown
below: -
Page 42 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
TRIP
HISTORY UP RESET SER Triggering.
SER Summary
ALARM UnderFrequency *D The VISIONr relay triggers (or generates) a entry in the SER
HISTORY 18 : 03 : 28 : 88 17 / 11 / 05
UnderFrequency *R log for a change in state of any of the 121 binary inputs listed
18 : 03 : 28 : 81 17 / 11 / 05 in the SER Event Trigger Source list. The factory default is
SER UnderFrequency *A
SUMMARY
18 : 03 : 28 : 81
UnderFrequency
17 / 11 /
*P
05 that all inputs are active.
18 : 03 : 27 : 81 17 / 11 / 05
SER Monitoring.
The relay monitors each of the 121 binary inputs. If the input changes state, the relay time and date stamps the
change in the SER. If a protection element exceeds its pickup level, initiates a trip, resets or de-asserts the
element, the relay time and date stamps each change in the SER.
SER Log.
The relay logs the last 100 events but the user only has access to the 32 most recent events via the screen by
using the Up and Down scroll keys to scroll the events. The most recent event is located at the Top of the
rd
screen and after the 33 event the oldest record is not displayed. The user has got access to the last 100 events
st
via DNP3. After the 101 event the oldest record is erased.
The above screen shows an example of a Protection SER event. The sequence starts when the relay detects
the Frequency has fallen below its set limit and the element has picked up (*P). The next line in the sequence is
when the element trip time for that setting has elapsed and the unit has asserted a trip (*A). Almost at the same
time as the trip the relay see that the under-frequency has cleared as the breaker has tripped so resets (*R) then
finally the elements de-asserts (*D).
As the above screen show the pickup (*P) and reset (*R) are a pair and are used in the logging of Protection
events. If the relay then trips due to this pick then the elements asserts (*A) and then finally de-asserts (*D)
again are a pair. In logging of keypad changes, digital input or output changes then the later pair are used giving
an asserted (*A) when the change is activate and de-asserted (*D) when de-active.
A full listing of the events can be seen in Appendix 3. These can be selected or deselected via the VISION
Control II windows software.
Page 43 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
16 UNIT SETTINGS.
Software Version.
Displays the operating software (firmware) loaded on to the unit. This should be noted along with the serial
number when corresponding about this equipment
Password.
If the password is set to enabled the default password (6363) may be used to change setting and reset statistical
data. If the password has been changed the new password must be used.
If a digital input is set to Authorise, by energising this digital input you can change settings without being
prompted for a password.
Engineering Password
If enabled the Engineer Password will allow access using the standard password. Generally if a password is
requested a prompt will offer ‘AAAAA’, changing the second A to a B ‘ABAAA’ allows access.
The settings may only be modified when the correct password has been entered.
Change Password.
The VISIONr default password is '6363'. It is recommended for security purposes this password be changed.
The password may be up to 6 characters long and alphanumeric if desired.
If the User Password is lost and the Engineers Password has been disabled the only options are to either Read
the information via the serial Link or execute a Configuration Reset on the relay to restore all of the factory
defaults.
Page 44 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Calibration.
Each unit is calibrated prior to despatch and a signed test report is issued. The user may however access these
settings if required and re-calibrate the device if deemed necessary. In addition to the calibration of analogue
inputs the Calibration Sub Menu provides some useful diagnostic tools.
After entering the password the Calibration Sub Menu will be displayed and allows access to the following
settings:
It is very likely that altering any calibration value will directly affect the performance of the relay and may
compromise its ability to adequately function and protect.
Screen Saver
To help extend the life of the LCD we can power the display down if the application suits. The screen will power
down after the set time from the last key press. The VISIONr will still operate and can be remotely controlled via
digital inputs or the serial interface.
On any key press or active fault the display will reactivate.
Hours in Service
The hours in service is a counter which increments whilst the unit is in service or energised, this is used to help
determine MTBF figures.
Page 45 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Auto Reset- When the source of the alarm/indicator has cleared the relay contact will automatically reset.
Timed Reset- The alarm/Indicator relay contact will reset after the source of the alarm/indicator has cleared
and the pre-selected reset time has elapsed (See Alm & Indc Reset Time).
Manual Reset- The alarm/indicator relay contact will require a manual reset by the keys on the unit in the Active
Fault screen to reset the relay contact.
Page 46 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Settings Card
Password protected up to 6 characters (default AAAAA)
All parameter settings for a single relay can be saved on one card
Fast transfer time, typically 5 seconds
One card can be used to clone multiple relays with the same settings
Data transfer can be controlled without the need of external equipment
Data Card
Password protected up to 6 characters (default AAAAA)
Selectable events to record
64K of memory available for data logging (150-4500 events)
Time and date stamping of events to 1ms
Stored in text file format
Settings Card:
The Card detail is displayed on the first two lines, the card data indicates whether the parameter settings both on
the card and those programmed into the relay concur with each other. Any single setting change causes
Compare Fail to be displayed across the screen.
The time and date of the last setting transfer are recorded for that particular card.
The card can be locked against overwriting by means of the password or if set to auto lock the card will be
automatically password protected on removal. The password required to unlock and transfer the parameter
settings is the password which was set on initial formatting.
Parameters are transferred by selecting Transfer Data.
Page 47 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Data Card:
As with the Settings card the card detail is displayed on the first two lines in the menu.
The card options allow the user to set which of the conditions the data card is required to store, single or multiple
events can be set.
Trip Data:
Trip Event, Time & Date, All currents and Voltages, all other relevant measured data
Control Data:
Control Event (start / close, stop / open or reset), Time & Date, Origin (serial / panel / remote / auto / trip)
Power Down:
Time& Date
NOTES:-
1) Data will only be stored to the card whilst the card is inserted into the relay
2) SER Events are only available for download via serial communication.
We recommend that the device is isolated from the network during any smart card use.
Page 48 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
17 PROTECTION SETTINGS.
Each protection function is configurable independently of the others. The available action, the type of reset, the
various threshold levels and trip timers for each and every protection function can be found in section 5
This section describes in detail what each function does and how it operates.
Function. UP SELECT
Protection Settings
If a particular protective function is required for use it should be selected and set A Cold Load Pickup
to Function: Enabled. That function now operates as per its configuration. T CLPU HS
On exit the protective list will show to the left hand side of the name a tick if the T E/F CLPU
function is enabled, and A or T, or both if set, to operate an Alarm or a Trip. OFF E/F CLPU HS
T Ov ercurrent 1
If a particular function is not required it can be left disabled and it will display OFF OFF Overcurrent 1 HS
next to the function.
DOWN EXIT
Warn 1.
When set to Enabled this setting activates the Output Relay that is programmed to Warn 1 indicating that a trip
is imminent after the trip time has been exceeded. It is activated when the Trip Level has been exceeded.
Warn 2.
When set to Enabled this setting activates the Output Relay that is programmed to Warn 2 indicating that a trip
is imminent after the trip time has been exceeded. It is activated when the Trip Level has been exceeded
Alarm.
An Alarm is considered as a high level function. If enabled, an A will appear alongside the protection setting
description. If the function activates it will be recorded as part of the alarm history and cause VISIONr to enter an
alarm state; the fault will be displayed in the active faults. If an output relay is set as Alarm it will change state
with the fault.
Trip.
A Trip is considered as a high level function. If enabled, a T will appear alongside the protection setting
description. If the function activates it will be recorded as part of the trip history and cause VISIONr to enter a trip
state; the fault will be displayed in the active faults page and the unit will automatically display that page, the right
hand LED will turn RED if the unit goes to Lockout.
Inhibit.
An Inhibit is considered as a high level function. If enabled and the function activates it will display in the active
faults page with a letter ‘I’ to indicate the function is causing an inhibit. The feeder may continue to remained
closed but cannot be reclosed whilst the inhibit remains.
Active In Test.
When Enabled this will allow the Protection Function to be Enabled when the Test Digital Input is set to Test. It is
normal that when in the Test position certain Functions are disabled to allow easier testing. With this option the
user is able to choose which functions are disabled during test.
Page 49 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Blockable.
Enabling this function will allow the Protection Function to be blocked when the corresponding blocking digital
input is closed, thereby allowing the user to block certain Protection Functions from being active.
Reset.
The configuration of the reset allows that particular function to be cleared or reset to a healthy condition
providing the condition that caused the fault, alarm or inhibit has been removed.
If a fault remains active an asterix appears with the T, A or I and fault description in the active faults page.
Auto Reset.
This option, when enabled, automatically resets the Fault when the situation that caused the trip has been
removed.
NOTE:- The autoreclose settings are all set to auto and cannot be changed otherwise the unit would be
unable to sequence.
Panel-Reset.
This option, when Enabled, allows a reset of a fault to be carried out from the front panel of the relay. A reset
button will be displayed in the active fault page if any fault has been removed and is enabled for a panel reset.
Serial-Reset.
This option, when Enabled, allows a reset of a fault to be carried out through the serial link of the relay.
Remote-Reset.
This option, when Enabled, allows a reset of a fault to be carried out through the digital inputs to the relay. A
digital input must be set to Reset Faults and must be closed after the fault condition has been removed in order
for the reset to operate.
Indicators.
The indicators can be used for transparent signalling when a protective condition is active. There are 4 separate
indicators to choose from.
The indicators are considered as a low level function meaning no automated response arises from an active
condition, i.e the unit does not trip (unless activated to) or indicate via the LEDS.
The Indicators are used to drive output relays and can be used as a specific function output. For example, all
earth fault protection is configured to call Indicator 1, all phase overcurrent protection activates Indicator 2.
Indicator 1 and 2 can then be used to distinguish between phase and earth fault trips via a dedicated output
relay.
Indicators can also be used for hardwired interlocking control when driven from the External Fault based
protective functions.
The output relay must also be configured as an indicator to operate in this manner.
Page 50 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
17.1.1 Undervoltage.
The VISIONr may be configured to trip, alarm and/or indicate as a result of an Undervoltage condition on any
phase. Undervoltage may be due to large machines starting due to inrush currents creating voltage dips. As
such, Undervoltage protection should be set with the ability to ride-out some Undervoltage conditions to avoid
unnecessary tripping.
Trip Level.
The Undervoltage pickup is set as a percentage of the Voltage setting. If this should decrease and remains
below the threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an Undervoltage condition can persist before the configured action is
taken.
17.1.2 Overvoltage.
The VISIONr may be configured to trip, alarm and/or indicate as a result of an overvoltage condition on any
phase.
System overvoltages or swells may be as a result of capacitor bank switching for example, so care must be
exercised to avoid nuisance tripping. The overvoltage trip delay should be programmed to prevent nuisance
tripping during such transients whilst providing protection against longer swell conditions not typically seen or
that have adverse effects on equipment.
Trip Level.
The overvoltage pickup is set as a percentage of the Voltage setting. If this increases and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an overvoltage condition can persist before the configured action is
taken.
The VISIONr may be set to perform a 1 SHOT overcurrent sequence which permits just one trip to lockout. It
may be configured to trip, alarm and/or indicate as a result of an overcurrent condition. The relay uses the O/C
Pickup Level set in the Breaker Setting Menu for the Trip Level.
Deselecting the ‘Auto’ panel button of the VISIONr forces this protection to be active providing fault current is
detected.
Characteristic.
This corresponds to a set of time curves (Definite Time, Normal Inverse, Very Inverse and Extremely Inverse)
that dictate the time delay to trip depending on the phase current and the characteristic chosen. This is used
when co-ordinating and discriminating between faults on larger systems. See Section 18
Trip Time.
The trip time is set to determine how long an Single Shot Overcurrent condition can persist before the configured
action is taken.
Note: this setting is only available when the characteristic setting is set to Definite Time
Time Multiplier.
This setting is available when the Characteristic is set to Normal Inverse, Very Inverse and Extremely Inverse. It
refers to the value tI> used in the calculation of the Trip Time Curves in See Section 18.
Page 51 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The VISIONr also provides a high set instantaneous or definite time single shot overcurrent element. This
feature allows for faster tripping on high magnitude single shot overcurrent conditions than would otherwise be
provided by the IDMT curve.
Trip Level.
The HS Overcurrent pickup is set as a percentage of the CT Primary. If the current rises and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an HS Overcurrent condition can persist before the configured action
is taken.
The VISIONr may be set to perform a 1 SHOT Earth Fault sequence which permits just one trip to lockout. It
may be configured to trip, alarm and/or indicate as a result of an single shot Earth Fault condition. The relay
uses the E/F Pickup Level set in the Breaker Setting Menu for the Trip Level.
Deselecting the ‘Auto’ panel button of the VISIONr forces this protection to be active providing fault current is
detected.
Characteristic.
This corresponds to a set of time curves (Definite Time, Normal Inverse, Very Inverse and Extremely Inverse)
that dictate the time delay to trip depending on the phase current and the characteristic chosen. This is used
when co-ordinating and discriminating between faults on larger systems. See Section 18.
Trip Time.
The trip time is set to determine how long an Single Shot Overcurrent condition can persist before the configured
action is taken.
Note: this setting is only available when the characteristic setting is set to Definite Time
Time Multiplier.
This setting is available when the Characteristic is set to Normal Inverse, Very Inverse and Extremely Inverse. It
refers to the value tI> used in the calculation of the Trip Time Curves in See Section 18.
The VISIONr also provides a high set instantaneous or definite time single shot Earth Fault element. This feature
allows for faster tripping on high magnitude single shot Earth Fault conditions than would otherwise be provided
by the IDMT curve.
Trip Level.
The HS Overcurrent pickup is set as a percentage of the CT Primary. If the current rises and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an HS Overcurrent condition can persist before the configured action
is taken.
Page 52 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Trip Level.
The Earth Fault 1 HS pickup is set as a percentage of the EF CT Primary. If the current rises and remains above
the threshold level, action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an earth fault condition can persist before the configured action is
taken.
Active On Trip.
st nd rd th
The trip the setting becomes active on can be set to either the 1 , 2 , 3 or 4 reclose.
Trip Level.
The Earth Fault 1 HS pickup is set as a percentage of the EF CT Primary. If the current rises and remains above
the threshold level, action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an earth fault condition can persist before the configured action is
taken.
Active On Trip.
st nd rd th
The trip the setting becomes active on can be set to either the 1 , 2 , 3 or 4 reclose.
The VISIONr provides a overcurrent cold load pickup (CLPU) feature which is a 1 SHOT sequence intended for
those applications where the start up currents of a system, which occur when the breaker is closed, might cause
the normal protection sequence (whether it is RECLOSE or 1 SHOT) to trip. It may be configured to trip, alarm
and/or indicate as a result of a Cold load pickup condition.
Characteristic.
This corresponds to a set of time curves (Definite Time, Normal Inverse, Very Inverse and Extremely Inverse)
that dictate the time delay to trip depending on the phase current and the characteristic chosen. This is used
when co-ordinating and discriminating between faults on larger systems. See Section 18.
Trip Level.
The Overcurrent pickup is set as a percentage of the CT Primary If the current rises and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an Overcurrent condition can persist before the configured action is
taken.
Note: this setting is only available when the characteristic setting is set to Definite Time
Page 53 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Time Multiplier.
This setting is available when the Characteristic is set to Normal Inverse, Very Inverse and Extremely Inverse. It
refers to the value tI> used in the calculation of the Trip Time Curves in See Section 19.
The VISIONr also provides a high set instantaneous or definite time overcurrent cold load pickup. This feature
allows for faster tripping on high magnitude cold load pickup overcurrent conditions than would otherwise be
provided by the IDMT curve.
Trip Level.
The HS Overcurrent cold load pickup is set as a percentage of the CT Primary. If the current rises and remains
above the threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an HS Overcurrent cold load pickup condition can persist before the
configured action is taken.
The VISIONr provides a Earth Fault cold load pickup (CLPU) feature which is a 1 SHOT sequence intended for
those applications where the start up currents of a system, which occur when the breaker is closed, might cause
the normal protection sequence (whether it is RECLOSE or 1 SHOT) to trip. It may be configured to trip, alarm
and/or indicate as a result of a Cold load pickup condition.
Characteristic.
This corresponds to a set of time curves (Definite Time, Normal Inverse, Very Inverse and Extremely Inverse)
that dictate the time delay to trip depending on the phase current and the characteristic chosen. This is used
when co-ordinating and discriminating between faults on larger systems. See Section 19.
Trip Level.
The Overcurrent pickup is set as a percentage of the CT Primary If the current rises and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an Overcurrent condition can persist before the configured action is
taken.
Note: this setting is only available when the characteristic setting is set to Definite Time
Time Multiplier.
This setting is available when the Characteristic is set to Normal Inverse, Very Inverse and Extremely Inverse. It
refers to the value tI> used in the calculation of the Trip Time Curves in See Section 19.
The VISIONr also provides a high set instantaneous or definite time Earth Fault cold load pickup. This feature
allows for faster tripping on high magnitude cold load pickup overcurrent conditions than would otherwise be
provided by the IDMT curve.
Trip Level.
The HS Earth Fault cold load pickup is set as a percentage of the CT Primary. If the current rises and remains
above the threshold level action is taken after the trip time has elapsed.
Page 54 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Trip Time.
The trip time is set to determine how long an HS Earth Fault cold load pickup condition can persist before the
configured action is taken.
The VISIONr also provides an instantaneous or definite time live line overcurrent trip. It may be configured to
trip, alarm and/or indicate as a result of a Live Line overcurrent condition.
The VISIONr also provides an instantaneous or definite time live line Earth Fault trip. It may be configured to trip,
alarm and/or indicate as a result of a Live Line Earth Fault condition.
The VISIONr may be configured to trip, alarm and/or indicate as a result of a load (current based measurement)
increase condition.
Trip Level.
The load increase pickup is set as a percentage of the Constant Current Rating (CCR). Depending on the
application a load increase may be a frequent occurrence and care must be taken to prevent nuisance tripping.
Trip Time.
The trip time is set to determine how long an increased load condition can persist before the configured action is
taken.
The VISIONr may be configured to trip, alarm and/or indicate as a result of an Over Power condition.
Depending on the application an overpower condition may be a frequent occurrence and care must be
taken to prevent nuisance tripping.
Trip Level.
The Over Power pickup is selected under this option. If Over Power should rises and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long Over Power condition (above the pickup setting) can persist before the
configured action is taken.
The VISIONr may be configured to trip, alarm and/or indicate as a result of an over frequency condition.
Frequency is auto-sensing (50 or 60Hz) and is determined by the VT input (V1).
Trip Level
If the frequency increases and remains above the set level, action is taken after the trip time has elapsed.
Trip Time
The trip time is set to determine how long an over frequency condition can persist before the configured action is
taken.
Page 55 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
17.1.19 Breaker.
The VISIONr provides the facility to monitor the status of the circuit breaker. Auxiliary contacts on the circuit
breaker are used to provide the current state of the breaker to the VISIONr. The VISIONr then compares the
physical status of the circuit breaker with the state it should be in according to the VISIONr.
If the VISIONr detects the circuit breaker closed via the digital inputs after an open/trip command has been
issued the relay will display “Breaker Fail” on the screen and may be configured to re-attempt to open the
breaker, alarm and/or indicate.
Similarly if the VISIONr detects the circuit breaker open and has already executed a close command to the
circuit breaker “Breaker Fail” will be reported and action may be initiated.
Trip Time
The trip time is set to determine how long a delay is implemented for the VISIONr to receive a feeder back of the
breaker status that matches the VISIONr status via the digital inputs
The external faults are digital input based, configurable action inputs. Up to 5 are available and bring a flexible
PLC approach to the normal protective functionality. Each is independently configurable and can be used to
provide permissive interlocking or process commands.
Each External fault can be renamed to an eleven character user defined text string, Unit Settings > Edit Custom
Strings.
Function.
The function can be set to any combination of Alarm, Trip, Inhibit, Warn 1-2 or Blockable. The function can also
be set to Test option which allows the function to be active when in the test mode.
Reset.
Normal reset options apply, Auto or a combination of Panel, Serial and Remote.
Polarity.
This option determines the polarity of the digital input that activates this function. 'OFF=Fault' (typically fed from
a NC contact), means that when the digital input is Open the External Fault will action.
'ON=Fault' (typically fed from a NO contact), means that when the digital input is Closed the External Fault will
action.
Trip Time.
Determines the time an external input can remain in its fault state before any action is taken.
For a set period of inactivity on the rear communication port the unit can be configured to take some action in
the event.
It is worth noting that the VISIONr device is slave to any host system, the unit will not send information via the
serial port unless it has been requested by a master device.
Page 56 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The VISIONr incorporates an internal software and hardware watchdog feature to monitor the integrity of both on
board hardware and software systems. This feature may be configured to indicate as a result of any registered
problems. If a problem with the hardware or software is located during the error check routines the VISIONr will
generate an error code (or diagnostic status) which will be reported at the very bottom of the Analogue Values,
Measured Values screen.
17.1.23 Overcurrent 1 - 4.
The VISIONr provides the user with 4 independent Inverse Definite Minimum Time (IDMT) overcurrent elements
for increased flexibility when coordinating with other overcurrent devices. The relay may be configured to trip,
alarm and/or indicate as a result of an overcurrent condition. The relay uses the O/C Pickup Level set in the
Breaker Setting Menu for the Trip Level.
Characteristic.
This corresponds to a set of time curves (Definite Time, Normal Inverse, Very Inverse and Extremely Inverse)
that dictate the time delay to trip depending on the phase current and the characteristic chosen. This is used
when co-ordinating and discriminating between faults on larger systems. See Section 19.
Trip Time.
The trip time is set to determine how long an Overcurrent condition can persist before the configured action is
taken.
Note: this setting is only available when the characteristic setting is set to Definite Time
Time Multiplier.
This setting is available when the Characteristic is set to Normal Inverse, Very Inverse and Extremely Inverse. It
refers to the value tI> used in the calculation of the Trip Time Curves in See Section 19.
Added Delay.
This setting is a fixed time which can be added to the time multiplied curve. If this feature is not required the
added delay should be set to zero.
Page 57 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The VISIONr also provides a high set instantaneous or definite time overcurrent element. This feature allows for
faster tripping on high magnitude overcurrent conditions than would otherwise be provided by the IDMT curve.
The relay uses the O/C Pickup Level set in the Breaker Setting Menu for the Trip Level.
Trip Level.
The HS Overcurrent pickup is set as a percentage of the CT Primary. If the current rises and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an HS Overcurrent condition can persist before the configured action
is taken.
The VISIONr provides the user with 4 independent Inverse Definite Minimum Time (IDMT) Earth Fault elements
for increased flexibility when coordinating with other devices. The relay may be configured to trip, alarm and/or
indicate as a result of an Earth Fault condition. The relay uses the E/F Pickup Level set in the Breaker Setting
Menu for the Trip Level.
Characteristic.
This corresponds to a set of time curves (Definite Time, Normal Inverse, Very Inverse and Extremely Inverse)
that dictate the time delay to trip depending on the Earth Fault current and the characteristic chosen. This is
used when co-ordinating and discriminating between faults on larger systems. See Section 19.
Trip Time.
The trip time is set to determine how long an Earth Fault condition can persist before the configured action is
taken.
Note: this setting is only available when the characteristic setting is set to Definite Time
Time Multiplier.
This setting is available when the Characteristic is set to Normal Inverse, Very Inverse and Extremely Inverse. It
refers to the value tI> used in the calculation of the Trip Time Curves in See Section 19.
Added Delay.
This setting is a fixed time which can be added to the time multiplied curve. If this feature is not required the
added delay should be set to zero.
The VISIONr also provides a high set instantaneous or definite time Earth Fault element. This feature allows for
faster tripping on high magnitude Earth Fault conditions than would otherwise be provided by the IDMT curve.
The relay uses the E/F Pickup Level set in the Breaker Setting Menu for the Trip Level.
Trip Level.
The HS Earth Fault pickup is set as a percentage of the CT Primary. If the current rises and remains above the
threshold level action is taken after the trip time has elapsed.
Trip Time.
The trip time is set to determine how long an HS Earth Fault condition can persist before the configured action is
taken.
Page 58 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
I/I s
Page 59 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Page 60 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The following is an example of the SER event recorder with the VISIONr set to 2 Phase trips to Lockout, both
Overcurrent trips set to Normal Inverse 2X Multiplier, 1S dead time, 5S Sequence Reset Time and injecting 2 X
Overload giving each trip time of 20seconds.
# Due to the filtered inputs of the relay the Breaker Feedback input is delayed by 30-40mS from CB operation.
Page 61 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The following is list of the binary events that can be selected or deselected via the VISION Control II windows
software.
Page 62 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
Page 63 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
TB4 Actuator Relay Contacts Outputs (15KV) TB4 Actuator Relay Contacts Outputs (38KV)
TB4-1 Link to TB4-6 TB4-1 Close Actuator +VE Termination
TB4-2 Link to TB4-5 TB4-2 Close Actuator -VE Termination
TB4-3 Actuator +VE Termination TB4-3 Trip Actuator +VE Termination
TB4-4 Actuator -VE Termination TB4-4 Trip Actuator -VE Termination
TB4-5 Link from TB4-2 TB4-5 No Connection
TB4-6 Link from TB4-1 TB4-6 No Connection
Page 64 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
The VISIONr relay can be supplied with directional earth fault protection when required. The Earth Fault
protection behaves and is configured in the normal way.
There are three (3) additional settings required in order for directional E/F to operate, these are Ve Pickup Level,
Ie Direction and Ie Sector as described in sections 6 and 10.
The Ie Sector setting creates an Operational Zone within the phasor relationship either side of the direction
setting.
In order for Earth Fault current to trip the relay certain conditions must be met.
0
90
Operational Zone
Ie Direction
0
40
0
40
0
30
0 0
180 0
0
270
Page 65 of 66
22/JUNE/06
VISIONr TECHNICAL MANUAL Issue 3
In addition to standard Modbus RTU VISIONr is capable of communicating to host systems in Modbus ASCII. In
ASCII mode the relay is capable of behaving as a master device and can transmit pertinent data without being
requested by the host system.
RTU Mode
Each 8 bit byte in a message contains two 4-bit hexadecimal characters. Achieving greater character density
over ASCII hence improved throughput at the same baud rate. Transmitted in a continuous data stream.
Frame Format
ASCII Mode
Each 8-bit byte is sent as two ASCII characters. Main advantage is up to 1 sec between characters without error.
Frame Format
Modbus address mapping and application documents for the following are available on request.
Page 66 of 66
22/JUNE/06