Beruflich Dokumente
Kultur Dokumente
4.1 INTRODUCTION
The double angle web cleat connection consists of a pair The rotational capacity of the connection is governed
of angle cleats that are usually bolted to the supported principallyby the deformation capacity of the angles and,
beam web in the shop and the beam assembly is then to a lesser extent, by the slip between the connected
bolted to the supporting member (Beam, I column or parts, (see Figure 4.2).
RHS column) on site. Flowdrill or Hollo-Bolts are used for
connections to RHS columns, (see Figure 4.1). To minimise rotational resistance, the thickness of the
angle cleats should be kept to a minimum and the bolt
The connection requires no welding and permits minor cross-centres (or gauge) should be relatively large.
site adjustment when using untorqued bolts in clearance
holes. However, it lacks flexibility in accommodating The connection moment is indeterminate but small and
beam skews and there is difficulty in connecting into can be neglected.
shallow depth columns. It is also not as strong as an
equivalent end plate connection.
Figure 4.1 Double angle cleat. Beam-to-column Figure 4.2 Deformation of angle cleats
and beam-to-beamconnections
70
Double Angle Web Cleats - Recommended Geometry
Supporting
column
Supporting
beam
to clear bolts
-1
Cross-centres
7 0 Projection
50 50 50
(loo+ tw)mm
Beam-to-column Beam-to-beam
90 x 90x 10 Angle 1
150~90~10Angle 2
~ _ _ ~
72
Double Angle Web Cleats - Design
4.4 DESIGN
The full design procedure is presented in Section 4.5. Worked examples
Five worked examples are provided in Section 4.6 to
With a single vertical line of bolts in the beam web, the
illustrate the full set of design checks of Section 4.5.
best that can be achieved from a web cleat connection is
a connection shear capacity of around 50% of that of the
beam in shear. Two vertical lines of bolts will increase this
CONNECTION CAPACITY TABLES
value up to a maximum of 75%, although it will be found
that due to the increased eccentricity of the design load, Capacity tables for double angle web cleat connections
the benefit is disproportionate to the additional bolts using ordinary or Flowdrill bolts are given in Tables H.9 to
used. H.12 and inTables H.13 to H.16for Hollo-Boltconnections
in the yellow pages. The tables include connections with
For a configurationsuch as that shown in Figure 4.4, it will one or two lines of bolts, using both S275 or 5355 beams
be found that shear capacity in a connection with one and are detailed in accordancewith the standard geometry
vertical line of bolts is generally governed by bolt bearing presented in Figure 4.4 and Table H.7.
on the web of the supported beam (Check 4). Block shear
failure of the beam web may also be critical (Check 4). Values of the connection shear and tying capacities are
tabulated, together with simple aids to check the
Check 3, dealingwith the shear capacity of the angle cleat supporting member and the beam notch (if applicable).
leg, generally becomes the critical mode for larger size The tying capacities are based on the rigorous method
beams when a connection has to be made with two outlined in Appendix B.
vertical rows of bolts. If extra capacity is needed in these
cases, then 150 x 90 x 12mm thick cleats may be the
solution. This will increase the rotational stiffness of the
connection, but it will not be detrimental.
Structural integrity
All floor beam-to-columnconnections must be designed
to resist a tying force of a t least 75kN - a force which can
be carried by the simplest of cleats. (See Appendix A).
For certain tall, multi-storey buildings it will be necessary
to check the connectionfor large tying forces to satisfy the
structural integrity requirements of BS 5950-1 ['I.
73
Double Angle Web Cleats - Design Procedures
Recommended design model The design model assumes that the angles will deform as
Any simple equilibrium analysis is suitable for design. The the beam ends rotates and the eccentricity moment is
one used in this guide is in accordance with traditional UK resisted by the bolt group on the supported beam. The
design practice and does not imply any out of plane design procedure applies to beams connected to the
bending of the cleat legs. flange or web of a column, the wall of a RHS column or the
web of a supporting beam.
- , Supported beam
Single vertical line
Single vertical line rows
{!$
of bolts
of bolts
Supporting colum
(Ior RHS)
Supporting beam -
Assumed line of
shear transfer
(face of column)
FV
Assumed line of
shear transfer
(face of web) 4 FV
Supported beam
Supported beam Double vertical line
Double vertical line n rows of bolts
of bolts
Supporting colum
(Ior RHS)
4- 4
Assumed line of
shear transfer
4 I I
Assumed line of
shear transfer
(face of column) (face of web)
FV FV
Check 1 Recommended detailing practice
Check 2 Supported beam - Bolt group
Check 3 Supported beam - Connectingelements
Check 4 Supported beam - Capacity a t the connection
Check 5 Supported beam - Capacity a t a notch
Check 6 Supported beam - Local stability of notched beam
Check 7 Unrestrained supported beam - Overall stability of notched beam
Check 8 Supporting beam/column - Bolt group
Check 9 Supporting beam/column - Connecting elements
Check 10 Supporting beam/column - Local capacity
Check 11 Structural integrity - Connecting elements
Check 12 Structural integrity - Supported beam
Check 13 Structural integrity - Tension bolt group
Check 14 Structural integrity - Supporting column web (UC or UB)
Check 15 Structural integrity - Supporting column wall (RHS)
Check 16 Not applicable
74
Double Angle Web Cleats - Design Procedures
1r
End projection, t, approximately 1Omm
Length of cleat,
Min. 2.5 d
I20.6D
\ m Bolt diameter, d
. Hole diameter, Dh
D
Dh = d + 2mm for d I24mm
Dh = d + 3mm ford > 24mm
(for Hollo-Boltssee Table H.61)
50mm but
4
t
Supported beam
(Single notched)
1
Supporting beam /-
Notes
(1) The angle cleats are generally positioned close to the top flange of the beam to provide adequate
positional restraint.Cleat length of a t least 0.6D is usually adopted to give “nominal torsional restraint”
(BS 5950-1[’I Table 13 and clause 4.2.2).
(2) In addition, for connections to RHS columns, g should be a t least 0.3 x face width.
(3). Detail requirements for Flowdrill and Hollo-Bolt connections to RHS columns should also comply with
Tables H.60 and H.61 of the yellow pages.
(4) Bolt spacing and edge distances should comply with the recommendations of BS 5950-1: 2000.
In beam-to-I section column flange connections, where it is requiredto comply with structural integrity
requirements for a tie force of 75kN, the connection must have a t least 2 no. M20, 8.8 bolts in tension
with I 2 140mm, t, 2 8mm and g I 140mm.
For greater tie forces and other connections (e.g. to column webs and RHS), checks 11 to 15, as
appropriate, should be carried out.
75
Double Angle Web Cleats - Design Procedures
I or RHS
Assumed line of
shear transfer shear transfer
-F
Assumed line of
(a +x)
FV
Single Line of bolts Double -..re of bc ts
76
Double Angle Web Cleats - Design Procedures
n rows
of bolts
Block shear
pbs = bearing strength of cleat
p, = 0.6 py tc( 1 Ke(Lt - kDh ))
1 = el +(n-1)p e = end distance, and may
conservatively be taken
k = 0.5 and 4= e2 (for single line of bolts)
as smaller of el and e2
k = 2.5 and 4= e2 + gb (for double line of bolts)
F, is defined in CHECK 2
ji) For bearing:
Basic requirement:
Fs/2 'bs
77
Double Angle Web Cleats - Design Procedures
n rows
of bolts
/ 4 '
Block shear failure
tearing out of shaded portion
/ Fv' / FV'
n rows
of bolts
%.net = %-'"ht, .
78
Double Angle Web Cleats - Design Procedures
Note: If the notch length c is greater than (e, + gd, then shear and bending interaction should be checked
at the 2ndline of bolts. The beam at the end of the notch may also be critical - see Check 5.
n rows
of bolts
t FV
(ii) Shear and Bending interaction at the 2nd line of bolts, if the notch length c > (e3 + gb):
Basic requirement:
+ e3
Fv (tl + gb) MC
, where:
For single notched beam: Mcc = moment capacity of the notched
For low shear (Le. F, I 0.75P,.min) beam a t the connection in the
presence of shear.
Mcc = PyZ
Z = elastic section modulus of the
For high shear (i.e. F, > O.75Pv min)
gross tee section a t the bolt line.
112
Mcc = 1.5pyZ [l-(L)2)
Pvmin
79
Double Angle Web Cleats - Design Procedures
e3
i r
Basic requirement:
FS ' 'bs
20
Double Angle Web Cleats - Design Procedures
n rows
of bolts
beam flange
Shear and bending interaction at the notch:
Basic requirement:
(a) For single bolt line or for double bolt lines, if% 2 2d:
+ clI
Fv (tl McN
I where:
M,, for Single notched beam:
For low shear (i.e. F, I 0.75PV,) M
,, = moment capacity of the beam a t the
notch in the presence of shear
McN = PyzN P, = shear capacity a t the notch
= OS6 P y b N
For high shear (i.e. F, > O.75Pv,)
bN = (et+(n-l)p + eb)L
(for single notched beam)
M
,, = 1.5pYZ,
( -(-)
1
N: p = O.g(e, + (n - 1) p +
eb)L
(for double notch beam)
M,, for Double notched beam:
For low shear (i.e. F, I 0.75PV,) tl = end projection
c = length of notch
I For high shear (i.e. F, > 0.75PV,) Z, = elastic section modulus of the gross tee
section a t the notch
x, = +ve
e 3 , gb as per CHECK 4
(b) For double bolt lines, if X, < 2d:
M
,, = M
,, from CHECK4
27
Double Angle Web Cleats - Design Procedures
When the beam is restrained against lateral torsional buckling, no account need be taken of
notch stability provided the following conditions are met:
For one flange notched [141J51
Basic requirement:
11OOOOD
C I for D/t, > 48.0 (5355 steel)
(D/c.J3
where:
Where the notch length c exceeds these limits, either suitable stiffening should be provided or the notch
should be checked to references 14, 15 and 16.
22
Double Angle Web Cleats - Design Procedures
~ ~~
I $I
When a notched beam is unrestrained against lateral torsional buckling, the overall
stability of the beam should be checked.
Notes:
(1) This check is only applicable for beams with one flange notched. Guidance on double-notched
beams is given in Section 5.1 2 of Reference 1 7.
(2) If the notch length c and/or notch depth d, are different a t each end, then the larger values for
c and d, should be used.
(4) The solution below gives the modified effective length (LE) based on references 18,19 and 20.
It is only valid for C / L b < 0.15 and d,,/D < 0.2(beams with notches outside these limits should
be checked as tee sections, or stiffened).
K =
U v Lb
hb =
Y‘
where: x, v and ry are for the un-notched I beam section and are defined in BS 5950-1
U,
for hb 2 30 KO = go x but I , , ,K
C Kmax
-
Lb go UB uc
section section
I .025 5.56 260 70
.os0 5.88 280 80
.075 6.19 290 90
.loo 6.50 300 95
.125 6.81 305 95
.150 7.1 3 31 5 100
23
~ ~~
J - \
I
i
f e1
dpporting column
I I or RHS
--r-
Shear capacity of bolt group connecting cleats to supporting beam or column
Basic requirement:
* For Hollo-Bolts p, A, should be taken as the shear capacity given in Table H.56 of the yellow pages
24
Double Angle Web Cleats - Design Procedures
i
\
A
t e1
i
n rows
of bolts
L - A
Shear and bearing capacity of cleats conn - :ted to ipporting beam or column
(i) For shear: where:
Basic requirement: P = bolt pitch
Fv/2 ‘ Pvmin
d = diameter of bolt *
Pv,min = shear capacity of the leg of the angle cleat
= smaller of Plain shear capacity P,
Dh = diameter of hole *
and Block shear capacity P,
= thickness of cleat
Plain shear tC
25
Double Angle Web Cleats - Design Procedures
Supporting Column
I
Supporting Beam I Column RHS Column
Critical sections
Critical sections Top of column web
web thickness t
2 2 2 2 2 2
Fv
- 5 -
Fv 5
Local shear and bearing capacity of supporting beam web or column web or RHS wall
for one supported beam
where:
(i) For shear:
e, = smaller of et, and 5d
Basic requirement:
1
smallest of e, g/2 and 5d
F,/2 I P, (for supporting beam)
e b =
P, = local shear capacity of supporting beam web -
- smaller of g/2 and 5d
or I column web or RHS column wall (for supporting column)
Note: The above check (i) is for local shear only; the effects of any global shear forces must also be considered.
If the beam is connected to a rolled column flange, and the thickness of the column flange is less than
the thickness of the cleat then the bearing capacity of the flange should also be checked.
26
Double Angle Web Cleats - Design Procedures
clear bolts
4 - T
lt
Fv2 Fir1
FW+ Fa
2
+,,F,
2
Fa
lt
Fv2 Fv1
Lw
F+,
2
Fa Fa+ Fa
2
-ocal shear and bearing capacity of supporting beam web or column web for two supported beams
diameter of bolt
diameter of hole
% = (e, + (n2 - 1) P + eb> tw
thickness of supporting
%.net = $- n2Dh$v beam web or column web
N te: The above check (i)is for local shear only; the effects of any global shear forces must also -e considered.
27
Double Angle Web Cleats - Design Procedures
r-
g
e1
P
n rows
of bolts P
P
e1
Critical
sections
t
Tie force
Note: This check is only needed if it is necessary to comply with structural integrity requirements
P = bolt pitch
Limitations:
g I 140mm D, = diameter of hole *
tc 2 8mm
tC
= thickness of cleat
Note: Appendix B, gives a rigorous approach for calculating the tension capacity of double angle cleats.
The capacity tables on the yellow pages are based on the rigorous approach and not the simplified
approach given here.
Double Angle Web Cleats - Design Procedures
i e 3 t
n rows
of bolts
-;;I++;
n rows
of bolts
Note: This check is only needed if it is necessary to comply with structural integrity requirements
d = diameter of bolt
29
Double Angle Web Cleats - Design Procedures
Structural integrity -
CHECK 13 Tension bolt group
Tension
bolt Tie force
Note: This check is only needed if it is necessary to comply with structural integrity requirements
Basic requirement:
where:
Tension capacity of
Tie force 5 n = number of rows of bolts
tension bolt group
A, = tensile stress area of a bolt
Tension capacity of
tension bolt group
= 2nAt Ptr * reduced tension strength of a
Ptr =
bolt in presence of extreme prying
= 300N/mm2 for grade 8.8 bolts
(see Appendix 0)
Votes:
(1) The reduced tension strength, (ptr) is only used when double angle web cleat design for structural
integrity is based on Appendix B or CHECK 11.
(2) Where a beam is attached to one side of a column web without a beam on the opposite side, or to
RHS column, the bolt tensions have to be resisted by local bending of the web or RHS wall. UC webs
can resist 75kN but need to be checked if the tying force is higher. UB webs need to be checked for 75kN
and higher tying forces. CHECK 14 proposes a design model which could be used for this purpose.
CHECK 15 proposes a design model for checking the wall of RHS column.
(3) For Flowdrill or Hollo-Bolt connections the value At ptr is replaced by the Structural integrity Tensile
Capacity (Psi) taken from Tables H.55b and H.56 respectively, in the yellow pages.
30
Double Angle Web Cleats - Design Procedures
CHECK 14
Structural integrity -
Supporting column web (UC or UB) I
Angle cleats
(n-1 connecting to
column web
yield lines
Tie Force
Note: This check is only needed if it is necessary to comply with structural integrity requirements
Structural integrity -Tying capacity of rolled column web, in the presence of axial compression in
the column
Basic requirement:
where:
Tie force < Tying capacity of column web
17, =
Tying capacity 8 Mu
If column web
= - (ql + lS(1 - p1)0.5 (1 -y,)0.5) * =
1 -P, P1
Note: The check is required for either single-sided connections to the rolled column web
or unequally loaded double-sidedconnections to the rolled column web.
37
Double Angle Web Cleats - Design Procedures
Structural integrity -
CHECK 15 Supporting column wall (RHS) 0
B
m
Angle cleats
connecting to
P RHS column
yield lines
Ti6 Force
Note: This check is only needed if it is necessary to comply with structural integrity requirements
Structural integrity - Tying capacity of RHS wall, in the presence of axial compression in the
column
where:
Basic requirement:
Tie force 5 Tying capacity of RHS column wall rl, =
9
rying capacity
=
8 Mu
- (ql + 1.5(1 - p1)0.5 (1 - Y1)O.’) * PI =
(B - 3tw)
RHS column wall
1- p , Y, = Dh
(B -3L)
Mu -- moment capacity of RHS column
B = overall width of RHS column wall
wall per unit length
2
to which the connection is made
-- -Pu t w
4 thickness of RHS column
t w =
pu = design tensile strength of the RHS column D, = diameter of hole in RHS
= U, /1.25 (see inset box)
-
- bolt diameter
* Factor 1.5 in the equation includes an allowance for
for Flowdrill
P = bolt pitch
BS EN 10210 - 1:1994f3]
32
Double Angle Web Cleats - Worked Examples
The worked examples show design calculations for typical It should be noted that tie forces are ignored in checks for
standard connections. Each example demonstrates first vertical reactions and vertical reactions are ignored in
the use of the capacity tables (yellow pages) and then full checks for tie forces.
checks accordingto the procedures in Section 4.5. The full
checks will normally only need to be applied to non- Example 4
standard connections but their application to standard
connections demonstrates thevalidity of the much simpler Example 4 covers the same beam connections to an RHS
process when using standard details. column as in Example 3 but uses Hollo-Bolts to connect
double angle web cleats to the column wall.
When calculations must be made for non-standard
Example 5
connections, some design checks may be omitted where
it is obvious, from inspection of the detail, that a check is not Example 5 demonstrates the stability CHECK 7 for a
critical. In the case of Example 1, CHECK 3 and CHECK 9 laterally unrestrained beam with a single notch a t each
Block Shear calculation are not made since they are never end. Although this example is presented here, it is equally
a critical factor for well proportioned angle cleats with applicable to flexible end plates and fin plates.
bolts spaced a t reasonable centres in the cleat length.
However, if a connection design were made using a
long cleat with bolts concentrated a t one end of the
cleat, it is possible that Block Shear failure could occur
before Plain Shear failure and then the Block shear
checks should be made.
Example 1
Example 2
Example 3
33
Double Angle Web Cleats - Worked Example 7
job No Sheet
Joints in Steel Construction - Simple Connections 1 of 18
Title
Example 7 - Double Angle Cleats - Beam to Beam
CALCULATION Client
SHEET SCI/BCSA Connections Croup
Calcs by
RS
Checked by
AM
I May 2002
Date
REF.
DESIGN EXAMPLE 7
Check the following beam to beam connection for the design forces shown.
Yellow pages used for initial selection of Angle cleats.
N= 7 20
to clear bolts
2 - 1 5 0 ~ 9 10
0 ~ 10
2-90x90~
angle cleats (Type CB4) angle cleats (Type CA6, Yellow pages
Grade 5275 Crade 5275 Table H.2
Design Information:
34
Double Angle Web Cleats - Worked Example 7
533 x 27b x 92 UB
Grade 5275
6 7 0 x 2 2 9 ~140 UB
Grade 5275
Cleat type CB4 Grade 5275 Cleat type CA6 Grade 5275
From capacity table H.7 0 From capacity table H.9 Yellow pages
in Yellow pages in Yellow pages Tables
H.10 & H.9
Minimum support thickness = 5.5 + 4.3 = 9.8mm < 13.1mm .*. O.K.
Connection is adequate
35
Double Angle Web Cleats - Worked Example 7
I
~~
-
406UB (5275) 533UB (5275) 610UB (5275)
Sheet I I
I I I
CHECK
Nos
Yapacity
I Load I I
capacity Applied Capacity
Load I 1 Applied
Load
4 CHECK 1
- Recommended detailing practice
4 CHECK 2 (Capacity
184 64.9 184 91 Not Applicable
Supported beam per bolt, kN)
- Bolt group shear capacity
14
CHECK 6
Supported beam
Notch length
mm
412.8 I 770 1 153.7 I 170 Not Applicable
- Local stablity of notched beam Notch length (c) < Specified limits
(Beam restrained)
14 CHECK 7
L TB of Supported beam Not Applicable Not Applicable
(Beam restrained)
75 CHECK 8 (Capacity of
Supporting beam bolt group, kN) 735 300 1103 465 Not Applicable
- Bolt group shear capacity
76 & CHECK 9 Shear (kN) 400 150 589 233
77 Supporting beam - Connecting Bearing Not Applicable
368 750 552 233
elements (Strength of cleat) (Capacity per
bolt line, kN)
CHECK 10 Shear (kN)
18 Supporting beam - Capacity Bearing Not Applicable
(Local capacity of beam web) (Capacity
- Der bolt, kN)
36
Double Angle Web Cleats - Worked Example 7
For406x 1 7 8 x 7 4 UB
Ibg = c s2
= 4(252 + 1052) + 4 ( 2 9 + 352)
= 54000mm4
--j*+x)fookN
I
MX - 2 2 . 5 ~ 2 5103
~
FSmv = - - = 10.4kN
54000
Ibs Fastener
25 75
= ((37.5 + 1 0.4)2 + 43.82)'/2 = 64.9kN capacities
F,
yell0w pages
Double shear capacity of an M20 8.8 bolt, Table H.49
2P, = 184kN
n(n+l)p - 6 (6 + 1)70
'bg = - = 490mm-
6 6
M = Fv a = 465~0.05 = 23.3kNn
M 23.3 1 O3
FSrn =
- -
x
= 47.6kN
490 Fastener
'b
capacities
F, = (F,: + Fsm2 )'I2= (77S2 + 47.62)1'2 = 97kN yellow pages
Table H.49
2PS = 184kN
37
Double Angle Web Cleats - Worked Example 1
~
Tit'e
Example 7 - Double Angle Cleats - Beam to Beam
= 2610mm2
= A, - n D, tc
= 2610 - (4 x 2 2 x 1 0 ) = 1730mm2
0 . 6 ~ 2 7 5x2610
- = 431kN
103
.: P, = 400kN
LV
= el+(n-1)p = 40+210 = 250mm
= 400kN
38
Double Angle Web Cleats - Worked Example 1
Tit'e
Example 7 - Double Angle Cleats - Beam to Beam I 6 of 18
0 . 7 ~ 2 7 51 .~2 ~ 2 5 5 0
- = 589kN
103
.: Pv = 589kN
Lt e2 = 40mm
589kN
Block shear checks have been shown here, but they are never critical for well proportioned cleats.
However, if the bolt spacing is concentrated at one part of a cleat then these checks may be critical.
39
Double Angle Web Cleats - Worked Example 7
ks
(ii) Badc requirement for bearing: - ‘bs
2
e lesser of e, or e2 (conservatively)
e =SO
2
4 k - 40mm
20x 10x460 --
‘c pbs 92kN
103
&A J
e,=40
tc Pbs
0.5~40
1 03
10x460
~
-- 92kN
Pbr fmm
BS 5950- 1
Table 32
Fs
-
2
‘bs 92kN
64.9
- - 32.5kN Sheet 4
2
Pb,
= 92kN asabove
e, = 40
c -
- -
91
2
45.5kN Sheet 4
ez= 40
40
~~~~
where P,, is the smaller of the plain shear capacity, P, or the block shear capacity, P, of the supported beam
!L
Hole diameter (for Single notched beam)
1
1’ =210 = (40+210+ 113)x9.5 = 3 4 4 9 m d
1
Block shear capacity
0.7py ‘8 ,.net
.:
P,
=
=
0.7 x 275 x 7.2 x 2613
569kN
103
0.6 p, t,(L,
= 604kN
+ Ke(Lt- kDh ))
Bolt diameter
et= 40
d = 20mm
(n- 1 ) P L, = et + (n -1) P
Hole diameter,
=210 - 40+210
Dh = 22mm
= 250mm
t, = 9.5
--IP
II 0.6 x 275 x 9.5 (250 + 1.2( 90 - 55))
.: P, =
-R 103
= 458kN
47
Double Angle Web Cleats - Worked Example 7
Tit'e
Example 7 - Double Angle Cleats - Beam to Beam I 9 of 78
(ii) Shear and bending interaction at the second bolt line is required if c > e3 + gb
t, + = 700
- - I - 9.5
ir
258
-
7 05
300kN
Section gross section
Basic requirement:
'xx = I
104
( 1 7 ; ; ~ 1 6 ~+ (179.5 x 16 x 972))
+ ( 3 4 7 ~9.5 x 84S2))
= 8370cm4
42
Double Angle Web Cleats - Worked Example 1
Tit’e
Example 7 - Double Angle Cleats - Beam to Beam 1 700f 18
= (40x(6-1)70+93)xJ0.7
D, = 22mm
= 4878mm2
4
e b = 93
Netsheararea, = A, - n D, t,
t = 4878 - (6~22~70.1)
Shear plane
t w = 10.1 = 3545mm2
i
J 03
0 . 7 ~ 2 7 51 ~
.2~
3545
0.7~yKeA,.net -
- = 819kN
J 03
.’. P, = 805kN
e = 40
t = e, + (n-7)p
LV
Bolt diameter -
- 40 + 350 = 390mm
d = 2Omm (n - J)P
= 350 single line of bolts
Hole diameter, k = 0.5 and
D, = 22mm
kD, = 0 . S x 22 = IJmm
Block Shear
Failure
L,= e 3 .*. P, = 0 . 6 ~ 2 7 5 ~ 7 0(390+
.1 7.2(40-11))
= 40 J 03
= 708kN
.: Pv,min = P, = 708kN
43
~
I
~
(iii) Bearing
Basic requirement: F, I 'bs
20 x 9.5 x 460
twPbs = = 87.4kN
103
Pbs from
BS 5950-1
0.5 x 40 x 9.5 x 460
= 87.4kN Table 32
103
87.4kN
64.9kN Sheet 4
87.4 x 300
Note, the connection capacity is thus: = 404kN
64.9
Pbs from
BS 5950-1
For 533 x 2 7 0 x 92 UB Grade 5275 Table 32
'bs =
92.9kN
97kN Sheet 4
92.9kN .* O.K.
92.9 x 465
Note, the connection capacity is thus. 475kN
91
Double Angle Web Cleats - Worked €xample 7
c = 110
for 406 x 7 78 x 7 4 UB Grade 5275
M L,=lo
Double bolt line. Find whether:
XN < 2d or xN 2 2d
2d = 2 x 20 = 40mm
xN = 20mm
=2 since xN < 2d, requirement (b) applies
FV
I 0.75 P,
a c = 710
'VN =
=
0.6pYA,
(e, + (n - 7)
4878mm2
0.6 p, AVN
p + eb)tw
[ram
=
sheet 10
50 'VN
483 = 805kN
.'.
f,=
465kN t low shear criteria for bending applies
.'. Mc, = Py z,
45
Double Angle Web Cleats - Worked Example 7
Tit'e
Example 7 - Double Angle Cleats - Beam to Beam 1 Sheet
13 of 78
~~
= 151mm
Second moment of area about neutral axis:
-1 (20p;'x 75.63
t , = 10.1
1 04
+ (209.3 x 7 5 . 6 ~143.2')
1
ir + (467.4 x 10.7 98.3'))
7 9858cm4
I xx
-
ZN
Ymox
7 9858
- 598cm3
151 33.2
gross section
275 x 598
Momentcapacity, M,N = p,ZN = = 164kNm
7 O3
465x( 1 0 + 710)
Eccentric moment,F, (t, +c) -
103
- 55.8kNm < 764kNm .* O.K.
46
Double Angle Web Cleats - Worked Example 1
C -
- 7 1 Omm < 412.8mm .*. O.K.
c from
Sheet 12
47
Double Angle Web Cleats - Worked Example 7
\ \
6 1 0 x 229 x 740 UB
300kN
t Grade 52 75
I
p, from
Shear capacity of single bolt, P, = p, A, BS 5950- 7
Table 30.
1 . 0 ~ 4 10x460
0~ Pbs from
0.5 kb, el tc pbs = 0.5X BS 5950- 1
103 Table 32.
= 92kN .: use 91.9kN
For533 x 210 x 92 UB s 3 3 x 2 1 0 x 92
Y
e,= 40
6 1 0 Grade
x 229
6 1 0 x 229 x 140 UB
5275
I I
I I I
465kN
PS
= 72~91.9 = 7103kN
48
Double Angle Web Cleats - Worked Example 7
= 470kN
.*.Pv,min = min (P,, P,)
= 400kN I
Fv/2 = l5OkN < 400kN .,. O.K.
For533 x 210 x 92 UB
Plain shear P,
A, = 0.9(80 + 350)x 10 = 3870mm2
Fv = 465kN 275 x 10 ( 3 9 0
0.6~ + 1.2( 40 - 0.5 x 2 2 ) )
P, =
103
= 701kN
. =
Pv.mm min(P,, P, )
= 589kN
'v/2 = 233kN< 589kN .*. O.K.
NOTE: Block shear checks have been shown here, but they are never critical for well proportioned cleats.
However, if the bolt spacing is concentrated at one part of a cleat then these checks may be critical.
~
Tit'e
Example 7 - Double Angle Cleats - Beam to Beam 1 17of 18
1 . 0 ~ 2 01 ~
0x460
0.Skb5e7 tcPbs = = 92kN
103
For533 x270 x 92 UB
'
Bearing capacity as above-
'bs = 5 x92+92 = 552kN
FvlA
(i) Basic requirement for shear: - + -Fv2 < - pv
2 2
e, = 90
p = 70
nq ll == 6
P
P
P
+T
eb2 = 3 17.2 P
g = 110
465kN
1 03
= 779kN
.'. P, = 740kN
I
310 300
L A + & = -+ - = 305kN
2 2 2 2
305kN < 740kN
Note: The above check is for 1- shear only; the effects of any global shear forces must also be considered.
.: 0.K
57
Double Angle Web Cleats - Worked Example 2
CALCULATION Client
SHEET SCl/BCSA Connections Group
Calcs by Checked by Date
RS AM May 2002
DESIGN EXAMPLE 2
Check the following beam to column connections for the tie force shown.
50
-It-
-
370kN
Tie force
406x 178x74 U S
Crude 5275
533 x 21 0 x 92 UB
305 x 305 x 137 UC
Grade 5275
Crude 5275
2 - 1 5 0 ~ 9 700 ~
angle cleats (Type CB4)
Grade 5275
55
55 For cleat details
see Figure 4.4
2-90~90~10 nd yellow page:
angle cleats (Type CA6) Table H.2
Grade 5275
55 55
De5.,ln Information:
52
Double Angle Web Cleats - Worked Example 2
Tit'e Example 2 - Double Angle Cleats - Beam to UC Column - Structural Integrity 2of 8
-240kN
Tie force
-
370kN
Tie force
I Sx 1 7 8 x 7 4 UB
Grade 5275
5 3 3 x 2 1 0 ~ 9 2UB
Grade S275
305 x 305 x 7 37 UC
Grade 5275
Cleat type CB4 Grade 5275 Cleat type CA6 Grade 5275
Note:
(I) The tying capacity of the connectiongiven in the tables in the yellow pages is the least value
obtained from CHECKS 7 I , 12 and 13. The values for CHECK 1 1 are based upon the large
displacement analysis given in Appendix B.
(2) Beams connecting into a column web must also be checked for web bending as shown in
CHECK 14 on sheet 7.
In the case of the 406UB illustrated, CHECK 14 gives the critical tie capacity unless the web
is stiffened.
53
Double Angle Web Cleats - Worked Example 2
Applied
Load
Capacity
I
Applied
Load
Capacity
1 Applied
Load
I
CHECK 7 7 492 370
Structural lntegrity (448)* (662)*
- Connecting Elements - Tension capacity of 333 240
double angle cleats (kN) CRITICAL CHECK
BEAM SIDE
CHECK 13
Structural integrity 588 I 240 882 3 70
- Tension capacity of bolts (kN)
CHECK 14
Structural integrity Not Applicable 392 1 240
- Tying capacity of supporting column web (kN) CRITICAL CHECK
COLUMN SIDE
54
Double Angle Web Cleats - Worked Example 2
Tit'e Example 2 - Double Angle Cleats- Beam to UC Column - Structural Integrity 1 4of 8
Basic requirement: Tie force I Tying capacity of double angle web cleats
For406x 778x 74 U6
ez = 40
Tying capacity of double angle web cleats
= 0.6 Le t, p, (For 5275 steel)
e ! = 40 Effective net length of cleats is Le
i
p = 70
Le
= 2 ee + (n - I ) pe - n D,
70
- e ] but I e2 -- 40mm
70
pe = p but I 2e2 -- 70mm
e,= 40
T w
Critical sections
Le
Tying capacity
=
=
(2 x 40) + (3 x 70) - (4 x 22) =
0 . 6 ~ 2 0 210x275
103
~
-
202mm
333kN
For533x270x92UB
e2 = 40
e, = 40
U= 70
Tying capacity of double angle we6 cleats
70
= 0.6 Le tc pv (For S275Steel)
70
Le = 2 e, + (n - 1 ) pe - n D,
70
ee -
- el but I ez -
- 40mm
70
pe = p but I 2e2 - 70mm
= 40
(2 x 40) + (5 x 70) - (6 x 22) = 298mm
!1/'
Critical sections
Le
Tying capacity
=
=
0 . 6 ~ 2 9 870x275
103
~
- 492kN
55
Double Angle Web Cleats - Worked Example 2
Ti t'e Example 2 - Double Angle Cleats - Beam to UC Column - Structural Integrity I 5of 8
e,+ gb= 90
Effective net length, Le - 2 e, + (n - I ) pe - n Dh
-U-- ee
-
- (e3 + g b - D h ) but e,
e, = 90 68mm I 90
70 ++ nrows
of bolts Pe p but I 2(e3+gb-Dh)
70 ++
70mm I2(90-22)
70
Le (2 x 68) + (3 x70) - (4 x 22)
I : \ - 258mm
2 5 8 ~ 9 . 5 ~ 2 7 5= 674kN See note
Net tension capacity =
below
103
e, but I e,
-
e, =
i
n rows
of bolts 40mm I 90
p but I 2e
L
298mm
See note
298 x 10.7 x 275 below
Net tension capacity = 828kN
103
56
Double Angle Web Cleats - Worked Example 2
Tit'e ,%ample 2 - Double Angle Cleats - Beam to UC Column - Structural Integrity I 6of 8
57
Double Angle Web Cleats - Worked Example 2
Tit’e
Example 2 - Double Angle Cleats - Beam to UC Column - Structural Integrity I 7of 8
a
d,= 246.7
Grade 5275
I 1 t = 13.8
W
4
Tie Force
Tying capacity
of column web
dC
4
(4 -1) 70 -i 22
0.673
246.7
9
-
Pl
dC
110
- = 0.446
246.7
Dh
Yl
a;-
22
0.089
246.7
58
Double Angle Web Cleats - Worked Example 2
Tit'e
Example 2 - Double Angle Cleats - Beam to UC Column - Structural Integrity I 8of 8
If column web fails to satisfy the criteria shown on sheet 7 then sfiffeners fillet welded on one
side to the web and flanges would be required thus:
59
Double Angle Web Cleats - Worked Example 3
1 Sheet
joints in Steel Construction - Simple Connections 7 of 9
CALCULATION Client
SHEET SCI/BCSA Connections Croup
Calcs by Checked by Date
RS ASM May 2002
I I I
300kN
tie 1 4 O I
force
+
406 x 178 x 74 U S 40
Grade 5275
I
I 533 x 210 x 92 UB
! Grade5275
70
I
300kN 1 1 465kN
50
For cleat detail!
see Figure 4.4
2 - 1 5 0 x 9 0 10
~ 2 - 90 x 90 x 70
& Yellowpage!
angle cleats (Type CB4) angle cleats (Type CA6)
Grade 5275 Grade 5275 Table H.2
Design Information:
Flowdrill: M20 8.8
Ordinary bolts: M20 8.8
Column: 5355
Beams: 5275
Angle cleats: 5275
60
Double Angle Web Cleats - Worked Example 3
Tit'e
Example 3 - Double Angle Cleats - Beam to RHS column using Flowdrill I Sheet 2 o f 9
300kN I --
-PI+
\
force 465kN
-cl--(+ tie
++ force
406 x 178 x 74 Ut? A)- +
Grade S275 l- 533 x 2 1 0 x 92 UB
I
Grade 5275
I ,- I
300kN 1 t 465kN
Cleat type CBD Grade 5275 Cleat type CAS Grade 5275
The beam side of the connection The beam side of the connection
is adequate is adequate
Note:
(I) The tying capacity of the connectiongiven in the tables in the yellow pages is the least value
obtained from CHECKS 11, 12 and 13. The values for CHECK 1 1 are based upon the large
displacement analysis given in Appendix B.
(2) Beams connecting into a column web or RHS wall must also be checked for web bending as
shown in CHECK 15 on sheets 8 and 9.
67
Double Angle Web Cleats - Worked Example 3
Tit‘e Example 3 - Double Angle Cleats - Beam to RHS column using Flowdrill
Sheet
3of 9
capacivl I I
CHECK
Nos Applied Appb
Load Capacity Load
tI CHECK 1
- Recommended detailinq practice All recommendations adopted
I
92 32.5 Not Applicable
(Strength of cleat) (per bolt, kN)
92 45.5
CHECK 4 Supported Beam Shear (kN) 647 300 888 465
- Capacity at connection (plain (plain
See (ii) above shear) shear)
Not Applicable
Bearing 87.4 64.9 92.9 97
(per bolt,kN) CI TICAL C
FOf IERTlCA,
1 CHECKS 5 , 6 & 7 I Not Applicable Not Applicable
CHECK 8 Supporting Column Shear (bolt
735 300 1103 465 Not Applicable
- Bolt Croup shear capacity
P U P , kN)
J
CHECK 10 Supporting Column Shear (kN)
4 & 5 - Capacity Bearing (per Not Applicable 37.5 38.8
Local capacity of column web bolt, kN)
6
CHECK 1 7 Structural Integrity
-Connecting Elements
Tension capacity of of double
Tension
(kN)
333 I 1 1
300 492
anale cleats
CHECK 12 Structural integritp Tension(kN)
674 300 828 465
6 - Supported Beam
Not Applicable
Tension and bearing capacit] Bearing(kN) 874 300 558 465
of beam web
CHECK 7 3 Structural Integrity
- Tension bolt group Tension (kN) Not Applicable
I 1 1
~~
62
Double Angle Web Cleats - Worked Example 3
rit'e Example 3 - Double Angle Cleats - Beam to RHS column using Flowdrill I Sheet 4 o f 9
Critical sections __
et = 5d = 5x20 = 700mm
AV
= (7 00 + (4 - 1 ) 70 + 55) 12.5 = 4563mm2
63
Double Angle Web Cleats - Worked Example 3
Me Example 3 - Double Angle Cleats - Beam to RHS column using Flowdrill I Sheet 5 o f 9
For 5 3 3 ~ 2 1 0 ~ 9 2 U B s i d e
RHS Column Grade 5355
Critical sections -
AV
= (700 + (6 - I ) 70 + 55)x 72.5 = 6313mm2
- 0 . 6 355
~ x 6313
0.6 Py AV - = 7345kN
103
%.net = 6313 - ( 6 x 2 0 ~12.5) = 4813mm2
0. 7 x 355 x 1.2 x 481 3
0.7 P y Ke *v.net = = 1316kN
103
.: Pv = 1316kN
FV
- = 233kN c 1376kN .*. O.K.
Note: The above check is for&/ shear only; the effects of any global shear forces must also be considered.
F"
- - - 300 -
- 37.5kN c 138kN .*.O.K.
2n 2 x 4
For 5 3 3 ~ 2 7 0 ~ 9 2 U B s i d e
465
-
- -
2x 6
-
- 38.8kN c 138kN .'. O.K.
64
Double Angle Web Cleats - Worked Example 3
Tit'e
Example 3 - Double Angle Cleats - Beam to RHS column using Nowdrill I 6 of 9
Basic requirement: Tie force I tying capacity of double angle web cleats
For 406 x 178 x 74UB Side
:xample 2 DA(
Tying capacity of double angle cleats = 333kN
sheet 4 of 8
Tie Force = 300kN < 333kN .*.O.K.
For 533 x 2 10 x 92UB Side
!xample 2 DAC
Tying capacity of double angle cleats = 492kN sheet 4 of 8
65
Double Angle Web Cleats - Worked Example 3
rit'e Example 3 - Double Angle Cleats - Beam to RHS column using Flowdrill I Sheet 7of 9
Flowdrill
Psi = Flowdrill Structural integrity
Pull-out
Tensile Capacity Capacity
Tie Force
Tension
bolt group 4
-
- 73kN for a grade 8.8 bolt in a yellow pages
72.5mm RHS column wall Table H.55b
56
Double Angle Web Cleats - Worked Example 3
Tit'e Example 3 - Double Angle Cleats - Beam to RHS column using Flowdrill
I 8of9
L
@
t w = 12.5
c
P g = 110
t
J
Tie Force
P" t',
4
392x 12.52
= 75.3kNm/mm
4 x 103
2Omm (Bolt diameter for Flowdrill)
n
(n - I ) P -F Dh
B - 3t,
(4 - 1 ) 70 - 74 20
= 0.80
250 - 3 x 12.5
9
PI
B - 3tw
110
= 0.518
212.5
Dh
B - 3tw
20
= 0.094
212.5
67
Double Angle Web Cleats - Worked Example 3
rit'e
Example 3 - Double Angle Cleats - Beam to RHS column using Flowdrill
B - 3t,
6
(6-1) 7 0 - p 2 0
= 1.36
250 - 3 x 12.5
Tying capacity
of column wall
8 x 15.3
1 - 0.518
[ 7.36+ 7.5(7 - 0 . 5 1 8 ) o . 5 ~( I -0.094)o,5]
68
Double Angle Web Cleats - Worked Example 4
Job Sheet
Joints in Steel Construction - Simple Connections 7 of77
Title
Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt
CALCULATION
SHEET
~ B C S A ~Calcs by RS Checked by
ASM
Date
May 2002
REF.
DESIGN EXAMPLE 4
Check the following beam to RHS column connection for the design forces shown using Hollo-Bolt
connectors to the column.
In this example it is assumed that the tying force is equal to the end reaction. However, depending
on how the floor beams are arranged, the tying force given by the formula in BS 5950- 1 clause
2.4.5.3 can sometimes be less.
The yellow pages should be used for initial selection of angle cleats.
I + I
t I II I i
300kN
_I
40 ''
tie
force 70
+ 70
406x 178x74
Grade 5275
ut?
I
70
40
EBij
I I
I
I
I I! AI
/-
533 x 21 0 x 92 Ut?
Grade 5275
\
300kN 1 t
465kN
2 - 1 5 0 ~ 9 10
0 ~ 2 - 9 0 ~ 9 0 ~ 1 0
angle cleats (Type CD4) angle cleats (Type CC6)
grade 5275 . grade 5275
Design Information:
Hollo-bolts: M20
Ordinary bolts: M20 8.8
Column: 5355
Beams: 5275
Angle cleats: 5275
69
Double Angle Web Cleats - Worked Example 4
Tit'e Sheet
Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt 2of77
300kN 1 46SkN
Note:
(I) The tying capacity of the connection given in the tables in the yellow pages is the least value
obtained from CHECKS 7 I , 7 2 and 13. The values for CHECK 7 7 are based upon the large
displacement analysis given in Appendix B.
(2) Beams connecting into a column web or RHS wall must also be checked for web bending as
shown in CHECK 15 on sheets 10 and 1 7 .
70
Double Angle Web Cleats - Worked Example 4
Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt Isheet 30f1J
CHECK 7
All recommendations adopted
- Recommended detailing practice
CHECK 2 Supported Beam shear 184 64.9 184 91 Not Applicable
- Bolt Croup Shear Capacity (Per kN)
CHECK 3 Supported Beam Shear (kN) 400 750 589 233
- Connecting Elements Bearing
Not Applicable
(Strength of cleat) (per bolt kN) 92 32.5 92 45.5
CHECK 17structUrallntegrity
-Connecting Elements
Tension
W )
248
(393)*
1 1 1
300 363
(580)*
465
Not Applicable
Tension capacity of of double
CRITICAL CHECK FOR TIE FORCE
anale cleats
I I I
CHECK 72 Structural integrity ~~~~i~~(kN) 674
300 828 465
- Supported Beam
(kN) 874 300 558 465 Not Applicable
Tension and bearing capacity
70
of beam web
CHECK 7 3 Structural Integrity
- Tension bolt group Tension (kN) Not Applicable
1 I I I
584 300 876 465
Tit'e Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt I Sheet 4 of 1 1
406 x 178 x 74 UB
Basic requirement: FV I CP,
Shear capacity of single bolt, ps = PSAS
For M20 Hollo-bolts shear capacity Ps = 1 OOkN Yellowpages
Table H.56
But for top pair of bolts, ps = min (ps As O.5 kbs e1 tc pbs)
I
ps = 2x92+6~100 = 784kN
250 x 250 x 12.5 RHS
FV
= 300kN < 784kN .'. O.K.
300kN
533 x 2 7 0 x 92 UB
For533x270x92UB
A p, = 2 x 9 2 + 1 O x 100 = 1184kN
= 465kN < 1184kN .'. O.K.
f
el =40
FV
2 5 0 x 2 5 0 ~12. lHS
465kN
J
72
Double Angle Web Cleats - Worked Example 4
Tit'e Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt Sheet
5of 1 7
CHECK 9: Supportins Beam - Connectinq elements
Shear and bearing of cleats connected to supporting column
-
FV
2
= 150kN < 280kN .'. O.K.
For 533 x 210 x 92 U6
Plain shear,
AV = 0 . 9 ( 8 0 + 3 5 0 ) ~ 70 = 3870mm2
'".net = 3870 - ( 6 x 3 5 x10) = 7770mm2
Jel =40
0.6 x 275 x 3870
1
0.6 P y AV - = 639kN
(n- 7 ) P 7 O3
= 350 0.7~275
7 .~2 ~ 1 7 7 0
- = 409kN
0.7 py ' e A v.net - 7 O3
=40
.'.
7" P, = 409kN
0.6 275 70 (390 + 1.2(40 - 0.5 35))
Blockshear, P, =
FY = 465kN 7 O3
= 688kN
Pv.min = min ( P , , Pr) = 409kN
-
FV
2
= 233kN < 409kN .'. O.K.
73
Double Angle Web Cleats - Worked Example 4
~~~~
Tit'e Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt
I 6 of 7 7
-
FV
2
= lSOkN < 368kN .'. O.K.
for 533 x 210 x 92 UB
Bearing capacities are as above
'bs = 5 x 9 2 + 92 = 552kN
-
FV
2
= 233kN < 552kN .'. O.K.
Double Angle Web Cleats - Worked Example 4
Tit'e Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt I Sheet 7 of 7 7
Critical sections
Fv
t
Fv
-
2
= 7SOkN
e, = 5d = 5x20 = lOOmm
AV
= (100 + (4 - 1 ) 70 + 55)x 12.5 = 4563mm2
0. 7 355x 1.1 ~ 2 8 1 3
.*. 0.7 py K, A =
x
103
= 769kN
.: P, = 769kN
-
f"
2
= 1SOkN < 769kN .'. O.K.
Double Angle Web Cleats - Worked Example 4
Tit'e Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt
I 8 of 1 7
Critical sections
wall thickness
et = 5d - 5x20 = 100mm
AV = ( 1 0 0 + ( 6 - 1 ) 7 0 + 5 5 ) ~ 12.5 = 6313mm2
0.6~355~6313
.: 0.6p,Av - = 1345kN
103
-- P, = 1008kN
F"
-
2
= 233kN < 1008kN .'. O.K.
Note: The above check is for&/ shear only; the effects of any global shear forces must also be considered.
Bearing capacity of column wall per bolt fbs = kbs d tw pbs Pbs from
l.Ox2Ox12.5 x 550 BS 5950-1
- = 138kN Table 32
103
for 406 x 178 x 74 U6 side
300
F, -
- - = 37.5kN < 138kN .'. O.K.
2n 2x4
F, - 465
- = 38.8kN < 138kN .'. O.K.
2n 2x6
76
Double Angle Web Cleats - Worked Example 4
E!
el = 40 Effective net length of cleats is Le
p = 70 = 2 e, + (n - 1 ) pe - n Dh
Le
70 - e7 but I e2 - 40mm
ee
70 pe = p but I 2e2 -
- 70mm
el = 40
Le
= (2 x 40) + (3 x 70) - (4 x 35) = 150mm
sections 0 . 6 150x
~ 70x275
Tying capacity = - 248kN
Critical
703
Tie Force = 300kN 4: 248kN .: Fails
Yellow pages
However, using the rigorous approach of Appendix 6, the tying capacity is 393kN. Table H. 14
(For this standard connection, the value is given in the yellow pages)
Tie Force = 300kN < 393kN .*. O.K.
For533x210x92UB
Tying capacity of double angle web cleats
e2 = 40
= 0.6 Le t, py (For 5275Steel)
Le
= 2 e, + (n - 7) pe - n Dh
ee - e7 but I e2 = 40mm
0 . 6 ~ 2 2 70x275
0~
ing capacity = = 363kN
7 O3
Critical sections Tie force = 465kN 4: 363kN .: Fails
However, using the rigorous approach of Appendix 6, the tying capacity is 580kN. Yellow pages
Table H. 14
Tie Force = 465kN < 580kN .'.0.K.
Note: The tying capacity obtained by CHECK 7 1 is the same, for similar cleats, with a "single line
of bolts" or a "double line of bolts". The standard connection values, obtained from Table H. 14 of
the yellow pages,are CHECK 7 7 critical values (whereas the values tabulated in Table H. 13 are
CHECK 12(ii) values for these particular standard connections).
77
Double Angle Web Cleats - Worked Example 4
Tit'e Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt I Sheet
70 of 7 7
Tension
bolt group
-
Tension capacity
t,= 12.5
c
P
1
Tie Force
Title Example 4 - Double Angle Cleats - Beam to RHS column using Hollo-bolt 1 Sheet 7 7 of 7 7
M U
moment capacity of RHS column wall per unit length
4
(4 -7)x70 - 2 x 35
= 0.659
250 - 3 x 12.5
9
PI
B - 3tw
170
- = 0.518
212.5
Dh
B - 3tw
35
- = 0.16
212.5
B - 3tw
6
(6-1) 70- 2x35
= 1.152
250 - 3 x 12.5
Tying capacity -
of column wall -
8 x 15.3
7 - 0.518
[ I . 752 -+ 1.5(1 - 0.5 18)O.’ x ( I - 0.165)O.’ ]
- 253.9[ 1.752+(7.047 x 0.974)]= 534kN
CALCULATION Client
SHEET SCI/BCSA Connections Croup
Basic requirement: Beams should be checked for lateral torsional buckling to BS 5950- I
clause 4.3.6 with a modified effective length (LE) which takes account of notches.
The following approach is only valid for c/Lb < 0.1 5 and d,, / D < 0. 2 (beams with notches
outside these limits should be checked as tee sections, or stiffened)
c = 110 c = 110
b-4 k--cl
5 3 3 x 2 1 0 ~ 9 2UB
7 - L-d, I
=50
U
5355 steel
Lb =7000
4 rn
Check the beam shown, which was designed as unrestrained over the span with an effective length of
l.OL, when it has a single notch at each end, and a design moment of 2OOkNm due to UDL.
1
2360cm3
4.5 1cm properties obtained from published SCI - P202
36.4 tables or derived from BS 5950- 7 'Blue Book'
0.873
7
I consewative
110
-
7000
= 0.016 < 0.15 .'. OK
50
533.1
= 0.094 < 0.2 .'. OK
7
2c /2
Modified effective length, LE = Lb [I + -(K2 + 2K)]
Lb
K = Ko /'b
U v Lb
'Y
0.873 x 1 x 7000
= 135.5
45.1
80
-
Note: For values of c / ~ b< 0.025 use: go = 5.56 and K,, = 260
KO = 5 . 5 6 ~36.4 = 202.4 < K,,,,,
202.4
.. K - - 1.49
135.5
(2 x 110)
and LE = 7 0 0 0 [ 1 + 7ooo x ((1.492 + (2 x 1.49))]
BS 5950- 1
4.3.6.7
IyT
=
= 0.873
355N/mm2
x I x 167 = 146
I
PY
BS 5950- 1
pb = 74N/mm2 pb - Table I 6
M, - 4.3.6.4
Mb = pb 5, (for class 1 cross-section)
74 x 2360
- -- 175kNm
103
BS 5950- I
Basic requirement: M, -< -Mb and M, I M,, 4.3.6.2
mlt
Mcx = 838kNm
s a - P202
Page D-59