Beruflich Dokumente
Kultur Dokumente
INSTALLATION
3
OPERATING INSTRUCTIONS
4
TROUBLE-SHOOTING 5
MAINTENANCE
-CLEANING 6
OPTIONAL FEATURES &
ACCESSORIES 7
APPEDIXES & NOTES
8
Read Safety Section before installing or using equipment
INTRODUCTION
Turbo Refrigerating is a will help avoid injury to falling over vertical
supplier of fluid chillers, personnel and/or damage to stainless steel plates in a
icemaking, and ice storage the equipment. Both are thin falling film. Because of
equipment. TURBO® does valuable assets to your method of chilling the
not engineer or design fluid operation. Take the time to liquid heat exchangers are
chilling systems, ice protect them. often referred to as falling
systems, ice plants, or film chillers.
processing lines. TURBO Read the manual contents
can provide assistance in before you start your HTD Series
locating qualified installation or operation. HTD stands for High
companies familiar with the This will save time by Temperature Difference.
installation and operation of ensuring that all necessary Fluids are chilled or heated
TURBO chillers. Contact materials and tools are over large temperature
the factory at the address or available when the differences, ranging from
telephone numbers listed at equipment arrives. 5°F to 60°F in a single pass
the end of this section. using R-22, ammonia or
History glycol as the refrigerant
Information on safety, inside the plate. Systems are
installation, operation, TURBO has been available in direct
maintenance and trouble- producing a line of fluid expansion (DX), flooded
shooting is contained in this chillers since 1984 and recirculated models.
manual. If you have equipment as well as Flow rates are available
questions concerning any of icemakers and ice over a wide range but are
these phases, contact generators for the ice typical considered relatively
TURBO or one of its industry since 1960. The low. Higher flow rates can
distributors to ensure that chillers described in this be obtained with HF
you fully understand the manual are part of a family chillers.
instructions and guidelines. of products designed
specifically for the HF Chillers
You must read all of the industrial market for a HF stands for High Flow.
information carefully and variety of cooling needs. Fluids are chilled over
make sure that all personnel narrow temperature
involved in the installation Fluid Heat Exchangers differences, ranging from
have also read and HTD and HF series heat 1°F to 2°F. The plate’s long
understood the information exchangers are designed to narrow geometry enables
and safety instructions. This instantaneously chill fluids high fluid flow over the
plate. Ammonia, R-22 and and uniform fragmented the field (trailer mounted
glycol are all available for nuggets. TURBO has units) or in the processing
use in direct expansion, produced the C-line area
flooded and recirculated icemaker since 1964. This • Concrete icing
systems. product line uses a water • Ingredient icing
defrost to produce ice in (bakeries)
Applications capacities ranging from 1 • Fish icing
HTD/HF chillers are ton per dry to 200 tons per • Poultry icing
suitable for a variety of day in CAR and CAR-LR • Chemical and dye
applications including: (ammonia) and CF (R-22) processes
• Food models. • Emergency cooling
• Beverage loads
• Chemical TURBO® TIG/TIGAR • Ice slurries
• Manufacturing Ice Generators • Catering trucks
In industrial applications • Salad bars or display ice
Models where ice is being used for • Food processing
A number of standard and processing or for top icing,
special chiller plates are TURBO produces a series Ice Storage Systems
available in a variety of of wet ice generators called TURBO® rakes and storage
configurations to meet the TIG (R-22) and TIGAR bins were introduced in
many applications. Standard (NH3) series. These hot gas 1967. There are three basic
plate sizes include: defrost icemakers are built sizes in the hydraulic
• 48” x 60” with the same high quality version as well as two
• 72’ x 60” standards and engineering larger versions known as
as the TURBO® icemakers automatic ice rakes
• 96” x 60”
of the sixties. The only (described in this manual).
• 144” x 24”
difference is that the The smaller hydraulic
icemaking process produces models range in capacity
Refrigerants/Refrigerant
slightly wetter ices due to from 20 to 87 tons while the
Feed
the hot gas defrost, and the larger automatic ice rakes
Chillers are available in R-
standard system used to range from 100 to 300 tons
22, ammonia, and glycol
produce dry, uniform ice of ice storage.
with direct expansion (DX),
nuggets is eliminated. As a TURBO rakes have been
flooded, and recirculated
result, a random shaped used in USDA inspected
refrigerant feed. Chillers
piece of fragmented ice is installations.
can be furnished with their
produced at a lower cost per
own high side and
ton. USDA Design
condensing unit or
All TURBO® ice storage
connected to existing
In applications where systems are designed to
refrigeration systems.
totally dry, uniform ice is meet USDA guidelines and
not required; the meet rugged industrial
Associated Equipment
TIG/TIGAR series offers a standards which make them
low cost alternative. the most reliable in the
Icemakers/Ice Generators
industry. Each system is
TURBO® C-Line
Typical Applications designed to make the
Icemakers
• Produce (broccoli, loading and unloading of
Packaged ice applications
carrots, etc.) – top icing in the ice storage system as
require a dry sub-cooled ice
safe and simple as possible. Optional Rake Features TURBO® block press the
Regardless of size, all of the most reliable on the market.
ice storage systems operate Although TURBO designs
in basically the same simple and builds the ice storage Special Applications
yet reliable manner. system to be as flexible as
possible, the standard TURBO is in the business
system may not meet a of supplying equipment to
The entire load and unload particular application. meet the needs of the
sequence is automatic and TURBO can design a customer. If you have an
does not require the storage system to meet application or a need that is
operator to be in contact almost any need. not discussed here, contact:
with the ice or any moving
parts in the ice storage TURBO® Block Press Turbo Refrigerating, LLC
system. TURBO offers another Sales Department
feature to make optimum P.O. Box 396
The continuous presence of profits from your ice Denton, Texas 76202-0396
an operator is not required production. Instead of Phone: 940-387-4301
although it is recommended. throwing away the snow Fax: 940-382-0364
At the end of the day, the produced by the breaker Web Site:
bin is empty (on a design bar, ice sizer, screw WWW.vogtice.com
day). The bin refills conveyors, or other
overnight and is full when handling devices, install a Customer Service
personnel return to work. TURBO® block press. This
block press converts the The TURBO service
NOTE: All controls are snow into ten or fifty-five department provides
adjustable to allow the pound blocks of ice. assistance for all customer
load or unload rate to needs. TURBO conducts
match the customer’s Introduced in 1977, the training schools at the
production and/or block press is a completely factory and at various
delivery requirements. automatic, hydraulic locations throughout the
powered unit capable of world.
Rake Variations producing from 120 to an
CB and Automatic rakes are excess of 400 ten pound NOTE: The model and
available in a number of blocks per hour. serial number of your
standard sizes to The block press is available TURBO equipment is
accommodate bulk storage with a block bagger located on the data
capacities ranging from 20 attachment, which means: nameplate attached to the
tons to 400 tons. Models are electrical control panel.
available in standard 10’, • Eliminates handling Please refer to the model
12’-6”, 15’ and 20’ widths; until the block is in the bag and serial number when
20’ to 55’ length; heights • A better product making inquiries about
from 9’ to 25’ making it • Higher profits the equipment. This will
possible to produce a enable our personnel to
variety of standard Rugged industrial handle your questions
capacities. construction and stainless quickly and accurately.
steel or UHMW in all areas
of ice contact make the
High Values
TURBO highly values its friends and customers in the industry. Please remember to:
TERMS &
CONDITIONS
Turbo Refrigerating, LLC Company may be required upon delivery to
(the “Company”) agrees to to pay arising from the sale transporting carrier.
sell the Equipment or delivery of the
described herein upon the Equipment or the use 3. Delivery
following terms and thereof. Prepaid freight, if
conditions of sale which, applicable, will be added to (a) The Company will
accordingly, supersede any the purchase price and endeavor to make shipment
of Buyer’s additional or invoiced separately. Where of orders as scheduled.
inconsistent terms and price includes transportation However, all shipment dates
conditions of purchase. or other shipping charges, are approximate only, and
any increases in the Company reserves the
1. Terms and Prices transportation rates or other right to readjust shipment
shipping charges from date schedules.
(a) All orders are to be of quotation or purchase
accompanied by a twenty order shall be for the (b) Under no circumstances
percent (20%) down account of and paid by will the Company be
payment or an acceptable Buyer. responsible or incur any
irrevocable letter of credit liability for costs or
confirmed on a U.S. Bank (d) Contract prices are damages of any nature
acceptable to Turbo. No subject to adjustment to the (whether general,
orders are to be entered Company’s prices in effect consequential, as a penalty
without payment or L/C in at time of shipment unless or liquidated damages or
hand. otherwise specified in a otherwise) arising out of or
separate Price Adjustment owing to (i) any delays in
(b) All orders are subject to Policy attached to the delivery or (ii) failure to
the approval of the proposal or other contract make delivery at agreed or
Company’s home office. document of the Company. specified times due to
Unless otherwise stated, circumstances beyond its
standard terms of payment (e) If Buyer requests reasonable control.
are thirty (30) days net from changes in the Equipment
the earlier of date of or delays progress of the (c) If shipment is delayed or
shipment or readiness of the manufacture or shipment of suspended by Buyer, Buyer
Equipment for shipment. If the Equipment, the contract shall pay (i) Company’s
partial shipments are made, price shall be adjusted to invoice for the Equipment
payment shall become due reflect increases in selling as per payment terms, (ii)
and payable to the partial price caused thereby. Company’s handling and
shipment. storage charges then in
2. Shipment effect, and (iii) demurrage
(c) In addition to the charges if loaded on rail
purchase price, Buyer shall Shipment is F.O.B. cars.
pay any excise, sales, Company’s plant or place of
privilege, use or any other manufacture, unless 4. Limited Warranty:
taxes, Local, State or otherwise specified. Risk of Warranty Adjustment:
Federal, which the loss shall pass to Buyer
returning the Equipment or the Warranty and Warranty ANY OTHER CAUSE
any part or parts will not be Adjustment extended to the WHETHER BASED ON
reimbursed by the Company by the original WARRANTY (EXPRESS
Company. manufacturer of such parts, OR IMPLIED) OR TORT
in no event shall such other OR CONTRACT, and
(d) SPARE AND manufacturer’s warranty regardless of any advices or
REPLACEMENT PARTS create any more extensive recommendations that may
WARRANTY warranty obligation of the have been rendered
ADJUSTMENT Company to the Buyer for concerning the purchase,
such parts than the installation or use of the
The Company sells spare Company’s Warranty Equipment.
and replacement parts. This Adjustment covering parts
subparagraph (d) is the manufactured by the 5. Patents
Warranty Adjustment for Company as set forth in this
such parts. Buyer must subparagraph (d). Expenses (a) PATENT INDEMNITY
make claim of any breach incurred by the Buyer in AND CONDITIONS
of any spare or replacement replacing, repairing, or
parts warranty by written returning the spare or The Company agrees at its
notice to the Company’s replacements parts will not own expense to defend and
home office within thirty be reimbursed by the hold Buyer harmless in the
(30) days of the discovery Company. event of any suits instituted
of any alleged defect for all against Buyer for an alleged
such parts manufactured by (e) LIMITATION OF infringement of any claim
the Company. The LIABILITY of any United States Patent
Company agrees at its covering solely to the
option to repair or replace, The above Warranty structure of the Equipment
BUT NOT INSTALL, Adjustment sets forth as originally manufactured
F.O.B. Company’s plant, Buyer’s exclusive remedy by the Company per the
any part or parts of material and the extent of the Company’s specifications,
it manufactures which, Company’s liability for and without modification by
within one (1) year from the breach of implied (if any) the Buyer, provided buyer
date of shipment shall prove and express warranties, shall (i) have given the
to the Company’s representations, instructions Company immediate notice
satisfactory (including or defects from any cause in in writing of any such claim
return to the Company’s connection with the sale or or institution or threat of
plant, transportation use of the Equipment. THE such suit, and (ii) have
prepaid, for inspection, if COMPANY SHALL NOT permitted the Company to
required by the Company) BE LIABLE FOR ANY defend or settle the same,
to be defective within this SPECIAL, INDIRECT OR and have given all needed
Parts Warranty. The CONSEQUENTIAL information assistance and
Warranty and warranty DAMAGES OR FOR authority to enable the
period for spare and LOSS, DAMAGE OR Company to do so. Buyer
replacement parts not EXPENSE, DIRECTLY shall defend and indemnify
manufactured by the OR INDIRECTLY the Company against all
Company (purchased by the ARISING FROM THE expenses, costs and loss by
Company, from third party USE OF THE reason of any real or alleged
suppliers) shall be limited to EQUIPMENT OR FROM infringement by the
Section 2: SAFETY
Here are some safety points to Important • Follow directions and
keep in mind when creating an Indicates hazards or unsafe illustrations.
efficient yet safe working practices which could cause • Check to see that all
environment. minor personal injury or equipment meets
product or property damage. applicable installation
Safety Definitions codes for your area as well
Note as state and federal
Statements or labels in this Gives helpful information. requirements.
manual or on the product • Have sufficient safety
preceded by the following Machinery Is Dangerous warnings on all equipment.
words are of special • Make sure all safety
significance: Machinery can hurt you if you devices and guards are in
are not careful. Use caution place.
Warning during assembly and operation
Indicates severe personal of equipment. Note:
injury or death will result if Warning labels attached to the
instructions are not followed. ALWAYS: chiller, equipment installed
• Read the entire manual with the chiller, and on access
Caution first. panels should be followed.
Indicates a strong possibility of • Use common sense and be They are shown in Figures 2-1,
severe personal injury or death careful. and 2-2.
if instructions are not followed. • Have enough manpower.
• Have the proper tools.
2. When working with completed his own task, when it has actually been
electrical equipment and remove his own lock. turned back on.
where the accidental
starting of such C. If the equipment controls F. If a machine is locked out
equipment or release of are so located that only one and it is necessary to leave
stored energy would lock can be the area, recheck the lock
create a hazard, the accommodated, a special upon returning to make
employee must turn off attachment that sure that the machine is
all power to the unit or accommodates several still locked out. While
use energy isolating locks must be used. This supervision will make
devices and apply his attachment will be issued every attempt to avoid the
personal lock, and have to all designated removal of locks, there
the supervisor of that employees. may be situations when it
area apply his personal must be done. This recheck
lock. At all times when D. Should an employee be is for your protection.
maintenance is being required to work on
performed on our another piece of equipment G. It is sometimes necessary
equipment, that and need to leave his lock to operate equipment for
equipment will have 2 on the present equipment, purposes of testing or
locks on it, one by the another lock must be making adjustments prior
person performing the obtained from the plant to the actual completion of
maintenance plus the manager. the work. It is recognized
one of the supervisor. that electricians must work
E. Should it be necessary to on live circuits from time
3. In instances where operate a piece of to time, particularly when
multiple circuits are in equipment which is locked trouble-shooting, but
a circuit breaker box, out, every effort should be extreme caution must be
an attaching made by supervision to used under these
mechanism will be locate the employee whose circumstances. Never work
placed on the outside of lock is on the equipment. If alone when changing live
the box to allow that that employee cannot be wiring.
box to be locked out located, the supervisor may
and prevent the door obtain a master key for the VII. Outside Contractors
from being opened. lock. The supervisor must
personally assure himself Whenever outside servicing
B. Each employee who that it is safe to remove the personnel are to be engaged in
performs the duties lock. The lock should than activities covered by the scope
prescribed above will be be returned to the proper and application of this lockout
provided with an individual employee. and tag procedure, such
safety lock and one key. If personnel are to be informed of
more that one employee is This procedure must be used this procedure by the person
assigned to a task, each with extreme caution and good responsible for their work
employee is required to judgement. There is danger activity and are to direct them
place his own lock and tag that the employee involved to follow its requirements.
so the controls cannot be will return thinking that the Failure to do so shall require
operated, even though machine is still locked out, that they do not be permitted to
another person may have continue working in the plant.
Material Safety Data Sheets (MSDS) are provided for all refrigerants (ammonia, Freon, glycol, refrigerant
oils) typically used in chiller applications.
Toxicity Data
Effects of Exposure
Acute Overexposure: Concentrations of ammonia in air of 5,000 to 10,000 PPM are reportedly fatal.
Chronic Overexposure: Concentrations of ammonia in air of 2,500 to 6,000 PPM during 30 minute
exposure are considered dangerous to life.
Eyes: Flood immediately with copious quantities of clean water. Irrigation must continue for at least
15 minutes. Patient must receive prompt attention from a physician.
Skin: Flood with water for 15 minutes and remove any contaminated clothing. Do not use salves or
ointments during 24 hour period after injury. Subsequent treatment is as for thermal burns.
Inhalation: Remove to uncontaminated area and begin artificial respiration immediately if necessary. If
available, administer oxygen when breathing restored. Call physician.
Ingestion: If patient is conscious and able, have him drink large quantities of water. If vomiting begins,
place patient face down with head lower than hips.
Notes to Physician: If respiratory embarrassment is the result of pulmonary edema, provide appropriate
supportive treatment and drug therapy.
Conditions Contributing To Instability: Dissociation begins to occur at 429° – 498°C (804° – 930°F)
Incompatibility: Store separately from oxidizers, halogens and acids.
Hazardous Decomposition Products: Hydrogen and nitrogen.
Conditions Contributing To Hazardous Polymerization: Not applicable.
X. Special Precautions
Precautionary Statements:
WARNING! HAZARDOUS LIQUID AND VAPOR UNDER PRESSURE. LIQUID CAUSES
BURNS. VAPOR EXTREMELY IRRITATING. Do not breathe vapor. Do not get in eyes, on skin, or
clothing.
The information and recommendations contained herein are based upon data believed to be correct.
However, no guaranty or warranty of any kind expressed or implied is made by TURBO with respect
to the information contained herein. This data is provided solely for your consideration and
investigation.
Section I.
Special Fire Fighting Procedures: Wear self-contained breathing apparatus. Water spray is an unsuitable
extinguishing agent.
Unusual Fire and Explosion Hazards: None
Flash Point (Method Used): ASTM D-92 >300° F (>150° C)
Flammable Limits %: NA
Extinguishing Agents: n Dry Chemical n CO2 n Water fog
q Water spray n Foam n Sand/Earth
q Other:
Waste Disposal:
Dispose of in accordance with Local, State, and Federal government regulations.
Unregulated by D.O.T. n
Regulated by D.O.T. q
Transportation Emergency Information: CHEM TREC 1-800-424-9300
U.S. D.O.T. Proper Shipping Name: NA
U.S. D.O.T. Hazard Class: NA
I.D. Number: NA
RQ: NA
Label(s) Required: NA
Freight Classification: Petroleum Oil NOIBN
Special Transportation Notes: NA
CAS #64742-52-5
Signature: ____________________________________
Title: ________________________________________
Telephone:____________________________________
Date: ________________________________________
Revision Date:_________________________________
Sent To:______________________________________
Supersedes: ___________________________________
TURBO believes the statements, technical information and recommendations contained herein are
reliable, but they are given without warranty or guarantee of any kind, express or implied, and
TURBO assumes no responsibility for any loss, damage, or expense, direct or consequential, arising
out of their use.
Section I.
Special Fire Fighting Procedures: Wear self-contained breathing apparatus. Water spray is an unsuitable
extinguishing agent.
Unusual Fire and Explosion Hazards: None
Flash Point (Method Used): ASTM D-92 >300° F (>150° C)
Flammable Limits %: NA
Extinguishing Agents: n Dry Chemical n CO2 n Water fog
q Water spray n Foam n Sand/Earth
q Other:
Waste Disposal:
Dispose of in accordance with Local, State, and Federal government regulations.
Unregulated by D.O.T. n
Regulated by D.O.T. q
Transportation Emergency Information: CHEM TREC 1-800-424-9300
U.S. D.O.T. Proper Shipping Name: NA
U.S. D.O.T. Hazard Class: NA
I.D. Number: NA
RQ: NA
Label(s) Required: NA
Freight Classification: Petroleum Oil NOIBN
Special Transportation Notes: NA
CAS #64742-52-5
Signature: ____________________________________
Title: ________________________________________
Telephone: ___________________________________
Date: ________________________________________
Supersedes:___________________________________
TURBO believes the statements, technical information and recommendations contained herein are
reliable, but they are given without warranty or guarantee of any kind, express or implied, and
TURBO assumes no responsibility for any loss, damage, or expense, direct or consequential, arising
out of their use.
PRECAUTIONARY LABELLING
FLAMMABILITY - 1 SLIGHT
REACTIVITY - 1 SLIGHT
CONTACT - 2 MODERATE
HAZARD RATINGS ARE 0 TO 4 (0 = NO HAZARD; 4 = EXTREME HAZARD).
DISPOSAL PROCEDURE
DISPOSE IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE, AND
LOCAL ENVIRONMENTAL REGULATIONS.
8 - PROTECTIVE EQUIPMENT
VENTILATION:
USE ADEQUATE GENERAL OR LOCAL EXHAUST VENTILATION TO KEEP VAPOR
AND MIST LEVELS AS LOW AS POSSIBLE.IF AIRBORNE CONCENTRATION IS
HIGH, USE AN APPROPRIATE RESPIRATOR OR DUST MASK.
EYE/SKIN PROTECTION:
SAFETY GOGGLES, UNIFORM, APRON, PROPER GLOVES ARE RECOMMENDED.
Recommended Service and rotate the upper chiller • Wrenches and sockets (a full
Cleaning Clearances section 180° when placing it set up to 1 1/8")
on the chiller sump. • Phillips (not cross-point) and
Minimum recommended standard (slotted) screw
clearances for service and Tools Required for drivers
cleaning: Installation • Level (four feet long)
• 48" on all sides • Tape measure (thirty feet
• 36" above the chiller for To install the Chiller, you will long)
access to the water need two to three people whose • Pry bar
distribution pan(s) and skills include mechanical, • Lifting straps (2000#)
header(s) for cleaning. welding, and plumbing • Welder suitable for carbon-to-
capabilities as well as a stainless steel
Access doors are provided on qualified electrician. The • Framing square
the front, rear, and top of the following is a list of tools • Forklift or crane
chiller. required for safe erection and
assembly of the Chiller: Always remember –SAFETY
Note: To locate the FIRST!!!
connections on the opposite
1. DELIVERY INSPECTION
All Chillers and reservoirs (if Delivery Inspection Checklist
supplied) are inspected at the
factory to assure shipment of a 1. Inspect panels.
mechanically sound piece of
equipment. If provided 2. Open and inspect loose
electrical controls and options equipment and crate(s).
are also factory tested
3. Inspect evaporator plates.
TURBO® Chillers are shipped
on “air-ride” trailers to ensure 4. Inspect valves (if
that the equipment arrives in the applicable) and piping.
best possible condition.
5. Damage and missing parts
Inspect the Chiller and reservoir must be noted on bill of
thoroughly upon arrival at the lading at the time of receipt.
installation site to check for any
shipment damage. Report any
damage to the transportation
company immediately so that an
authorized agent can:
2. HOISTING OR MOVING
Equipment Rigging A spreader bar and blocks may
Instructions be required to protect the plates. Figure 3-2 shows the
The hinged roof panels and configuration with lifting slings
The Chiller should be lifted by front and rear doors should be around the plate bank and
the lifting straps (slings) around removed during the rigging reservoir (sump).
the plate bank inside the frame. operation.
HTD "X" -48-06-01 1,482 2,466 HTD "X" -48-12-07 2,540 4,634
HTD "X" -48-06-02 1,587 2,637 HTD "X" -48-12-08 2,645 4,805
HTD "X" -48-06-03 1,692 2,809 HTD "X" -48-12-09 2,750 4,977
HTD "X" -48-06-04 1,797 2,981 HTD "X" -48-12-10 2,855 5,149
HTD "X" -48-06-05 1,902 3,153 HTD "X" -48-12-11 2,960 5,320
HTD "X" -48-06-06 2,007 3,324 HTD "X" -48-12-12 3,065 5,492
HTD "X" -48-06-07 2,112 3,496 HTD "X" -48-12-13 3,170 5,664
DIMENSIONS (IN) L W DIMENSIONS (IN) L W
68 36 68 60
HTD "X" -72-06-01 1,856 3,227 HTD "X" -72-12-07 3,347 6,296
HTD "X" -72-06-02 2,014 3,488 HTD "X" -72-12-08 3,505 6,557
HTD "X" -72-06-03 2,172 3,749 HTD "X" -72-12-09 3,663 6,818
HTD "X" -72-06-04 2,330 4,011 HTD "X" -72-12-10 3,821 7,079
HTD "X" -72-06-05 2,488 4,272 HTD "X" -72-12-11 3,979 7,340
HTD "X" -72-06-06 2,646 4,533 HTD "X" -72-12-12 4,137 7,601
HTD "X" -72-06-07 2,804 4,794 HTD "X" -72-12-13 4,295 7,862
DIMENSIONS (IN) L W DIMENSIONS (IN) L W
92 36 92 60
uChiller
MODEL SHIP OPERATING
WT. WEIGHT
(LBS) (LBS)
3. SITE PREPARATION
Install the Chiller in an area outdoor installations are the data sheet provided with the
where the ambient temperature not recommended. chiller.
does not fall below 40°F or rise • A cover over the roof
above 100°F. The chiller and panels to prevent debris, Raised Curbing
reservoir (sump) on all HTD/HF rain, snow, and other
chillers are insulated against outdoor contaminates A raised curbing around the
excessive heat infiltration. Most from collecting on the outside of the Chiller is
Reservoirs are optional on HF roof and preventing recommended to contain any
series chillers are provided normal opening of the condensate, leakage, or cleaning
without reservoirs. uHTD roof panel for cleaning fluid during maintenance from
chiller cabinets are not without contaminating the unit. A curbing height of
insulated. the interior of the two (2) to three (3) inches is
chiller. Optional roof typically sufficient. Refer to
Provide adequate working space vinyl covers are Figure 3-6.
on all sides and the top of the available.
Chiller for easy access to Elevated Installation
service and clean. IMPORTANT
Normal freeze-up precautions Some installations require
Outdoor Installation should be taken when pump mounting the Chiller at an
or drain lines must be exposed elevation above grade. In these
Insulated chillers are suitable to freezing temperatures. cases, a structural steel platform
for outdoor installation. For (capable of supporting the
ease of maintenance and Concrete Slab dynamic and static load) must
cleaning as well as access under be provided.
all weather conditions indoor If the Chiller is to be mounted
installations are preferred. on a concrete slab, the surface Due to variations in local and
Outside installation typically of the slab must be level or state codes, a local firm
require additional installation shimming must be provided specializing in structural steel
considerations including but not under the unit to ensure that it is should be consulted to
limited to: level to ensure proper water determine the requirements of
flow over the evaporator plates. the steel to be erected. Contact
• Provisions for chiller Leveling legs are provided on TURBO for information
operation in conditions all chiller reservoirs for final required by the firm that is
where the ambient is leveling after the providing the steel platform
below 40°F to prevent chiller/reservoir are set in place. including weight, dimensions,
freeze up. Operation for connection locations, and access
short intervals (less than IMPORTANT requirements for service. The
8 hours per day) is Failure to follow these steel supporting the unit must
possible without guidelines could result in be level or shimmed to obtain a
problems. For uneven water distribution satisfactory level. The same
operations requiring over the evaporator plates. guidelines for supported and
24/7 (24 hours per day; unsupported sections apply as
seven days a week) Location of all leveling feet on for concrete slabs. Refer to
the chiller reservoir is shown on Figure 3-4.
5. WATER SYSTEM
General Chiller Requirements temperature can not be Water Temperature
obtained. Refer to the
Water temperature and flow are maintenance section for Entering water temperatures on
used to determine the number of cleaning procedures. typical chiller installations can
evaporator plates required for range from 90°F down to 35°F.
the chilling service to be Free chlorine is released from For entering water temperatures
provided. All chiller capacities the water as it is discharged over 90°F consult the factory.
are based on the entering water from the distribution header. As Leaving water temperatures to
temperature, leaving water the chlorine level of the water within 0.5°F of the fluid freeze
temperature, specific heat of the increases or if the water is super point are obtainable.
fluid, and the flow rate over the chlorinated, the free chlorine
chiller plates. The number of level can concentrate and cause The fluid to be cooled is
plates is determined by the load corrosion of even stainless steel brought into the chiller through
calculated from the data above surfaces that are not wetted the water inlets located at the
and the saturated evaporator during operation. These top of the chiller. Entering fluid
temperature which is typically surfaces include the chiller is discharged from the PVC
between 26°F and 30°F for frame, parts of the water fluid distribution system located
applications using water as the distribution pan, exterior panel inside the chiller into the
fluid being chilled. surfaces, and refrigerant stainless steel water distribution
headers. The free chlorine must pan to ensure optimum
The holes sizes in the water be vented to reduce the distribution to all plates in the
distribution pan and the water concentration level. Venting can system. From the water
distribution header are also be obtained by installing distribution pan, the fluid flows
based on the water flow over optional vents or typically by over the exterior of the chiller
the plates. To minimize fouling weekly cleaning procedures to plates and is discharged into the
of the holes in the header and remove the stagnant water that reservoir located below the
pan, the maximum diameter collects on the non-wetted chiller. Pump, drain, and
size allowable without surfaces and vent free chlorine. overflow connections are
impacting water distribution is Cleaning procedures are located in the reservoir.
used. described in the maintenance
section. Opening the cabinet High flow (HF) chillers for
Water Quality doors releases trapped chlorine. some application do not use a
If followed by a fresh water reservoir below the chiller
When the fluid to be cooled is wash down of all the surfaces plates. For these applications
water, the water quality can on a weekly basis the system the chilled fluid is discharged
affect the performance and will typically remain in a directly into the process, over a
corrosion resistance of the passive state and corrosion free. processing conveyor carrying
system if proper corrective Weekly cleaning also eliminates the product, or directly into a
action is not taken. scale build that requires more chilled fluid tank.
aggressive cleaning methods to
Minerals in the water can cause remove. Reference the Maintenance
a scale build up on the surface Section for additional
of the heat transfer surface. If information on cleaning, and
this fouling is not removed from the “Handling and Post
the plates the leaving water Installation” section of the
Installation & Assembly Requirements 3/04 Turbo Refrigerating, LLC 3-15
WARNING! Read safety section before this section. Failure to carefully follow these instructions could
result in permanent injury or loss of life.
Installation Instructions for Water Distribution Pan in the water distribution pan.
additional steps to follow to For USDA applications a
ensure the long term integrity of A stainless steel water perforated PVC sheet is used in
the chiller. If you are uncertain distribution pan is located on the bottom of the water
about the quality of the water or top of the chiller plates to distribution pan to filter the
fluid to be used in the chiller uniformly distribute the fluid water before it plugs the holes
consult the factory for over all the plates. The size and in the water distribution pan.
assistance. number of holes in the pans are The PVC filter requires more
Water Distribution Header selected to match the flow frequent cleaning to ensure
requirements specified by the proper water distribution at all
A PVC water distribution customer. At design rate rates times.
header is located inside the unit. the water level in the pans is at
This is designed for easy approximately the 50% full Insulation
disassembly for cleaning. The level. All pans are designed to
laterals that branch off of the maintain proper flow over a 2:1 Fluid lines connected to the
main lines can be removed from flow range that covers a water chiller should be insulated to
the fittings into which they are level from approximately 1” reduce heat infiltration and
inserted for cleaning. Plastic minimum to 4” maximum in the condensation. Insulation of
caps are located on the end of pan. these lines is by others.
the laterals to permit full access
to the lateral interior from both NOTE: Water levels below 1”
ends. These parts are not glued in the water distribution pan
together to allow for will result in water wicking
disassembly for cleaning. (separation of the fluid flow
over the plates) and will result
Holes in the water distribution in freeze ups due to erratic
header are sized for even fluid flow to t he plates.
distribution of the fluid into the
pan and large enough to pass Water levels above 4” can
solids in the fluid stream. result in excessive splashing
Reference “Water Distribution and also result in freeze-ups
Pan Filter” below for removal due to the splashing freezing
of solids and debris from the on the refrigerant headers or
fluid stream. other surfaces that are
normally not wetted.
Larger chillers normally use
multiple water distribution Larger chillers normally use
headers to make them easier to multiple water distribution pans
remove for cleaning. to make them easier to remove
for cleaning.
Stainless steel water distribution
headers with sanitary fittings for Water Distribution Pan Filter
easy disconnect and removal of
the complete water distribution A filter pad is located in the
system are available as an bottom of the water distribution
option. pan for all non-USDA
applications to filter debris that
is large enough to plug the holes
3-16 Turbo Refrigerating, LLC 3/04 Installation & Assembly Requirements
WARNING! Read safety section before this section. Failure to carefully follow these instructions could
result in permanent injury or loss of life.
6. ELECTRICAL CONNECTIONS
Standard chillers consist of the and are furnished with each disconnects/circuit breakers to
upper evaporator section and operating manual. Consult the terminal blocks in the
lower reservoir. No electrical these diagrams before making chiller. All field wiring is
components are required for electrical service connections. provided by others.
these components. Control of
the chiller and/or water system Electrical Service Connections Checking Pump Rotation
is an option or typically
supplied by others and Chillers can be furnished with The water pump (by other
integrated into the control optional features factory wired. unless otherwise specified)
systems for other parts of the Electrical service connections to rotation is typically indicated on
processing plant. the following is required by the pump housing. Pump
others: rotation can be verified by
The options section can be observing the fan rotation on
referenced for optional kits • L1, L2, L3 motor starter the pump motor or by
required for a complete system connectors (three phase) measuring the amp draw of the
and the electrical requirements motor. The correct motor amp
for each. • L1, L2 control circuit draw will be higher than the
connections (single phase) amp draw in the reverse
WARNING rotation. Rotation can be
All electrical work should be All of these connections are changed by reversing two of the
done only by a qualified made on the terminal blocks phases on the motor starter; i.e.
electrician. Do NOT turn located inside the optional reverse the wiring connections
power on at this time. Failure Chiller control panel if to L2 and L3 if the rotation is
to carefully follow these supplied. Installation of not correct.
instructions could result in disconnect switches or circuit
permanent injury or loss of breakers is by others in the Note:
life. incoming power lines ahead of When checking rotation, only
the control panel on the chiller. the power to the pump should
IMPORTANT Field wiring is required from be on. Turn the three phase
Electrical wiring diagrams for the electrical source to power to the other
optional control systems are disconnects and/or circuit components in the system off.
located in each control panel breakers, and from
7. WATER CONNECTIONS
Water Pump Connection cleaning. The shut off valve on 3 GPM/ton of refrigeration.*
should be closed during normal The actual flow rate is wholly
A MPT connection is provided operation. Installation of the contingent on the water
at the bottom of the reservoir valve and piping are by others. temperature and evaporator load
for connection to a water pump but will not exceed the design
to be used to pump the chilled IMPORTANT flow.
water to the process or final Normal freeze-up precautions
distribution point. should be taken when pump * Tons of refrigeration = Total
or drain lines must be exposed Heat Rejection @ 10°F
This connection is typically to freezing temperatures. SET/105°F SDT ÷ 15,000
located at the same end as the BTU/ton
overflow and drain connection. Connection Size and Location
Optional Water Regulating
Multiple pump connections or Refer to the Data Sheet supplied Valve (SC Models Only)
connections in different with the manual for connection
locations including the bottom sizes and locations. The A water regulating valve can be
of the reservoir are available as locations shown in Figure 3-1 furnished in the Chiller high
options. are typical. Locations for side and must be field installed
special chillers may vary. external of the unit in the outlet
Water Overflow Connection water line. A 1/4" SAE flare
Optional Components type valve is provided on the
A connection for water Water Requirements water cooled condenser for the
overflow is located on the front (Optional Condensing Unit) water regulator high pressure
of the chiller above the pump Water Cooled Condensers gas connection. The regulator
connection. This is piped to an modulates in response to
overflow drain for disposal if Water-cooled condensers increases and decreases in the
the pump fail, water flow to the supplied on chiller high sides discharge pressure to maintain a
chiller exceeds design flow, or are the conventional constant pressure under all
the lines become plugged. condenser/receiver combination operating conditions.
Piping to a safe discharge type. They feature shell and
location is by others. tube type construction, Evaporative-Cooled
cleanable with removable Condensers
Drain Connection heads. The water in and out
connections are sized to permit Evaporative-cooled condensers
A female coupling is factory maximum water flow at peak can also be supplied with
installed in the bottom of the requirements. optional high side system to be
pump connection. The reservoir used with TURBO chillers.
is shipped from the factory with Condenser water requirements
a plug installed in the are based on 85°F water to the The same basic requirements
connection. The plug may be condenser, 95°F water off the for water quality and
removed and replaced by a shut condenser, and 105°F temperature apply to
off (isolation) valve for draining condensing. The condenser’s evaporative-cooled systems
the reservoir for service or design water flow rate is based except evaporative-cooled
3-18 Turbo Refrigerating, LLC 3/04 Installation & Assembly Requirements
WARNING! Read safety section before this section. Failure to carefully follow these instructions could
result in permanent injury or loss of life.
condensers like cooling towers other devices used to feed liquid Optional Features &
sizing is based on the design to the recirculation vessel or Accessories for Winterizing.
wet bulb temperature for the surge drum.
installation location. Standard Optional evaporative-cooled
selections are based on a design When contemplating the use of condensers also require
wet bulb temperature of 78°F city or well water for discharge pressure controls to
and a saturated condensing condensing, a careful check maintain the discharge under all
temperature of 95°F. For other should be made of the seasonal operating conditions. Discharge
design conditions consult the variation in the water pressure controls include a
factory. temperatures and the quality of variety of methods. Air
the water. discharge dampers that
Discharge Pressure Controls modulate in response to the
Water flow lines should be discharge pressure are the most
When optional cooling towers sized large enough for the economical. Flood back
are used and no other positive required flow at the maximum controls and variable frequency
means of regulating head water temperature to be drives (VFD) may be required
pressure are provided (i.e., fan encountered. for applications that operate in a
and pump pressure switches), a wide range of ambient
water regulating valve will be For applications requiring conditions including low
required. Adequate head condenser water above 85°F, ambient conditions where
pressure is important to provide consult TURBO. When Chillers dampers alone may not be
proper refrigerant flow to are installed in an area where sufficient. Consult factory for
refrigerant control valves such the ambient falls below additional information.
as hand expansion valves or freezing, refer to section 8 –
8. REFRIGERANT PIPING
All piping in the chiller is 304L Steel Pipe Joints compound may be used. Use
stainless steel. Optional 316L thread filling compound
piping is also available. As indicated all piping inside sparingly and on the pipe only.
Refrigerant connections are the chiller is stainless steel. It is; Do not put any thread filling
stubbed out on the right side of however, acceptable to connect compound on the first two
the chiller for standard carbon steel pipe to the inlet and threads, this prevents any of the
installation. These connections outlet connections. compound from entering the
can be easily reversed by system.
rotating the chiller on the IMPORTANT: When welding
reservoir during installation. carbon steel to stainless steel, Refer to the Data Sheet in the
the chiller should be covered manual for the refrigerant
NOTE: Although the during all grinding, welding connection sizes and location.
connections can be reversed in and deburring operations to The locations shown in Figure
the field please specify the avoid contamination of the 3-1 are typical. Locations for
side the refrigerant headers stainless steel surfaces. special chillers may vary.
should exit when the chiller is Failures to follow these
ordered to ensure the package instructions could result in
along with any options pitting or corrosion of the Steel Pipe
provided can be properly stainless steel. Reference
assembled in the field. additional information on Carbon steel or stainless steel
post-installation clean up in pipe can be used for refrigerant
Piping in a refrigerant system this section. lines but must be either
has two functions: sandblasted or pickled to ensure
Clean threads on the pipe and complete removal of wax, oil,
1. To carry the refrigerant fittings to remove all traces of or other processing films.
through the system as a grease or oil. Wipe the threads
liquid, a gas, or a liquid/gas dry with a lintless wiping cloth. Pipe Line Hangers
mixture with a minimum
pressure drop. Threaded Joints Hangers and supports for coils
and pipe lines should receive
2. To return any oil entrained Standard refrigerant careful attention. Hangers must
in the refrigerant to the connections are butt weld. have ample strength and be
compressor. Threaded connections are not securely anchored to withstand
recommended but can be any vibration from the
Avoid trapping the lines except supplied if specified. For compressor and adequately
for specific purposes. If traps threaded connections on piping support the pipe lines.
are used, the horizontal for refrigerants, use Teflon
dimension should be as short as thread sealing tape. Wrap the Storage / Inactive Systems
possible to avoid excessive tape around the threaded male
trapping of oil. Suction mains portion of the joint about two If the equipment is not installed
should be pitched toward the full turns, thread into the female upon receipt or is installed but
compressor. portion, and tighten. If thread not put in service, the interior
sealing tape is not available, must be maintained in a clean
conventional thread filling dry environment. All units are
3-20 Turbo Refrigerating, LLC 3/04 Installation & Assembly Requirements
WARNING! Read safety section before this section. Failure to carefully follow these instructions could
result in permanent injury or loss of life.
evacuated and charged with installation, the system should water and air dried or wiped off
nitrogen or an ammonia holding be properly evacuated and an with clean dry cloth. The
charge to protect the system. ammonia holding charge integrity of the system should
During installation the dry established. All external be checked on a regular basis to
holding charge will be lost. If surfaced should also be avoid damage during the
the system is not started after thoroughly washed with clean extended off period.
3. Stop the pump and isolate 2. Allow the pump to operate 2. Allow the pump to operate
the system. for two (2) or three (3) an additional six (6) hours.
hours.
4. Allow it to stand at this 3. Stop the system and allow it
vacuum for another five (5) 3. Stop the pump and allow the to stand for approximately
to six (6) hours. system to stand with this twelve (12) hours at the low
vacuum for a minimum of pressure.
5. Break the vacuum. three (3) hours.
4. Break the vacuum with the
6. Raise the system pressure 4. Break the vacuum with the oil free dry nitrogen.
up to zero (0) with oil free oil pumped dry nitrogen.
dry nitrogen. 5. Allow the pressure in the
5. Raise the pressure in the system to come up to
Second Evacuation system to zero (0). slightly above zero (0)
pounds (drier cartridges and
1. Start the second evacuation, Third Evacuation moisture indicators may be
again allowing the pump to installed in the system).
operate, and reduce the 1. Operate the pump until the
pressure to less than 500 system pressure is reduced 6. Evacuate the system below
microns. below the 500 micron the 500 micron figure and
figure. charge with the refrigerant
being used for the system.
Remote Air or Evaporative the system dry during shipment (condensers, receivers, etc.) to
Cooled Units (Optional) or storage. prevent excessive pressure
build-up in the system. These
Optional condensing units Refrigerant Recirculation safety relief valves should be
furnished for use with remote Systems (Optional) vented to a safe discharge point.
air cooled condensers (SCAR) Field piping will be required to
or remote evaporative cooled Optional refrigerant vent the valve outside for
condensers (SCER) are shipped recirculation vessels are shipped indoor installations or to a
without the operating charge without a refrigerant charge. location away from exposure to
and will require refrigerant gas. personnel for indoor or outdoor
Follow the procedure set forth Relief Devices installations. Refer to Figure 3-
under “Adding Refrigerant” on 9, Figure 3-10, and Figure 3-11.
this page. Each unit is shipped Relief valves should be installed
with a holding charge to keep on all pressure vessels
Figure 3-9 Typical Optional Air Cooled Condenser Relief Valve Field Piping
Figure 3-10 Typical Indoor Installation Relief Valve Piping of Optional Condensing
Unit
where:
L = maximum length of relief valve discharge piping (ft)
P2 = Absolute pressure at relief valve outlet (PSIA)
Po = Absolute back pressure at relief valve outlet (PSIA)
d = Internal diameter of discharge piping (inches)
Cr = Rated capacity of relief valve (lbs. of air per minute)
f = Moody friction factor in full turbulent flow (see list below for factors)
Ln = Natural logarithm
C = f DL1
Where:
C = minimum required discharge capacity of relief valve (lbs. of air per minute)
f = 0.5 for NH3
D = outside diameter of vessel (ft)
L1 = length of vessel (ft)
Example:
A Chiller with a water cooled condensing unit using a 12-3/4" diameter x 48" receiver.
Where:
P2 = 14.7 PSIA
Therefore P22 = 216.09
Po = (0.15*300) +14.7 = 59.7 PSIA
Therefore Po2 = 3,564.09
d = 1.049" (1-1/4" SCH40 pipe)
d5 = 1.2702
Ln Po / P2 = Ln(59.7/14.7) = 1.401
Then:
Therefore, a 1" SCH40 pipe is adequate for installations with relief valve discharge piping less than 86 feet
long. If longer piping is required, a larger pipe size may be required. In the example above a 1-1/4” line could
be used for relief discharge lines up to 394 feet.
For other applications the tables and formulas above should be used to calculate the relief valve size and the
maximum piping distance. For convenience Table 3-11 below shows typical valve selections and piping
distances for the relief valves used on standard TURBO models.
3-30 Turbo Refrigerating, LLC 3/04 Installation & Assembly Requirements
WARNING! Read safety section before this section. Failure to carefully follow these instructions could
result in permanent injury or loss of life.
13.PRE-START-UP CHECKLIST
A. AMMONIA (NH3) SYSTEMS
Customer ________________________________________
Date ____________________________________________
Serial No ________________________________________
Model __________________________________________
Check off the following items prior to start-up of the unit (recirculated or flooded):
□1. Verify that all loose components shipped for field installation are at the jobsite and have been installed
per the manufacturer’s instructions.
Note: The Chiller is a low side evaporator only. Field connection to a condensing unit and
refrigerant recirculation unit or surge vessel are required to complete the system. Field
connections may include water piping, refrigerant piping, electrical controls and power, and
insulation of vessels and piping. Refer to the wiring and piping diagrams provided with the unit
for field connection requirements.
□2. Familiarize yourself with the installation site: the location of safety equipment, eye wash and showers
for exposure to ammonia (NH3), and evacuation plans in the event of an NH3 release.
□3. Review the operating and maintenance manual provided with the equipment. Read the safety section
before starting the installation of the equipment.
□4. Complete the checklist provided with the condensing unit (if applicable).
□5. Complete the checklist provided with the refrigerant recirculation unit or surge drum (if applicable).
□6. Verify that all field electrical connections to the evaporator have been completed per the wiring diagram
provided with the equipment and per the instructions in the operating and maintenance manual. Circuit
breakers and/or electrical disconnects are not supplied by TURBO but are required by code in most
locations. Supply and proper installation of the circuit breakers and/or disconnects to meet all applicable
codes is the responsibility of others.
□7. Verify that all field refrigerant piping connections to the evaporator have been completed per the piping
diagram provided with the equipment and per the instructions in the operating and maintenance manual.
Supply and proper installation of field refrigerant piping to meet all applicable codes is the responsibility
of others.
□8. If the unit is to be connected to an existing central system, verify the interface requirements for the
evaporator to the central system.
□9. Verify that all relief valves have been piped to a safe discharge location (refer to the operating and
maintenance manual for guidelines).
3-34 Turbo Refrigerating, LLC 3/04 Installation & Assembly Requirements
WARNING! Read safety section before this section. Failure to carefully follow these instructions could
result in permanent injury or loss of life.
□10. Verify that all field water piping connections to the evaporator have been completed per the piping
diagram provided with the equipment and per the instructions in the operating and maintenance manual.
Supply and proper installation of field water piping to meet all applicable codes is the responsibility of
others. Flush and drain all water piping and water tanks.
Note: Water piping may include the make-up water to condensers, oil coolers, or components
supplied by others with the condensing unit and/or refrigerant recirculation unit, and the make-
up water connection to the evaporator. Water drain and overflow piping is required from the
evaporator to the proper disposal points (provided by others).
□11. Verify that the complete system has been properly evacuated, leak checked, and charged with the
proper refrigerant (refrigerant grade ammonia - NH3).
Note: Each of the above functions is the responsibility of others. Refrigerant is not supplied with
the equipment.
□12. Note all leaks found and repaired during step number 11.
If you have any questions concerning the above checklist or any other aspect of equipment installation in
preparation for start-up, contact:
Check off the following items prior to start-up of the unit (recirculated or flooded):
□1. Verify that all loose components shipped for field installation are at the jobsite and have been installed
per the manufacturer’s instructions.
Note: The Chiller is a low side evaporator only. Field connection to a condensing unit and
refrigerant recirculation unit or surge vessel are required to complete the system. Field
connections may include water piping, refrigerant piping, electrical controls and power, and
insulation of vessels and piping. Refer to the wiring and piping diagrams provided with the unit
for field connection requirements.
□2. Familiarize yourself with the installation site: the location of safety equipment, and evacuation plans in
the event of a fire or other hazardous situations.
□3. Review the operating and maintenance manual provided with the equipment. Read the safety section
before starting the installation of the equipment.
□4. Complete the checklist provided with the condensing unit (if applicable).
□5. Complete the checklist provided with the high side and condenser (if applicable).
□6. Verify that all field electrical connections to the evaporator have been completed per the wiring diagram
provided with the equipment and per the instructions in the operating and maintenance manual. Circuit
breakers and/or electrical disconnects are not supplied by TURBO but are required by code in most
locations. Supply and proper installation of the circuit breakers and/or disconnects to meet all applicable
codes is the responsibility of others.
□7. Verify that all field refrigerant piping connections to the evaporator have been completed per the piping
diagram provided with the equipment and per the instructions in the operating and maintenance manual.
Supply and proper installation of field refrigerant piping to meet all applicable codes is the responsibility
of others.
□8. Verify the interface requirements for the evaporator to the high side and condenser.
□9. Verify that all relief valves have been piped to a safe discharge location (refer to the operating and
maintenance manual for guidelines).
□10. Verify that all field water piping connections to the evaporator have been completed per the piping
diagram provided with the equipment and per the instructions in the operating and maintenance manual.
Note: Water piping may include the make-up water to chiller, condensers, oil coolers, or other
components supplied by others with the condensing unit, and the make-up water connection to the
evaporator. Water drain and overflow piping is required from the evaporator to the proper
disposal points (provided by others).
□11. Verify that the complete system has been properly evacuated, leak checked, and charged with the
proper refrigerant.
Note: Each of the above functions is the responsibility of others. Refrigerant is not supplied with
the equipment.
□12. Note all leaks found and repaired during step number 11.
If you have any questions concerning the above checklist or any other aspect of equipment installation in
preparation for start-up, contact:
C. GLYCOL SYSTEMS
Customer ________________________________________
Date ____________________________________________
Serial No ________________________________________
Model __________________________________________
Check off the following items prior to start-up of the unit (recirculated or flooded):
□1. Verify that all loose components shipped for field installation are at the jobsite and have been installed
per the manufacturer’s instructions.
Note: The Chiller is a low side evaporator only. Field connection to a glycol system are required
to complete the system. Field connections may include water piping, glycol piping, electrical
controls and power, and insulation of vessels and piping. Refer to the wiring and piping diagrams
provided with the unit for field connection requirements.
□2. Familiarize yourself with the installation site: the location of safety equipment, and evacuation plans in
the event of a fire or other hazardous situations.
□3. Review the operating and maintenance manual provided with the equipment. Read the safety section
before starting the installation of the equipment.
□4. Complete the checklist provided with the glycol unit (if applicable).
□6. Verify that all field electrical connections to the evaporator have been completed per the wiring diagram
provided with the equipment and per the instructions in the operating and maintenance manual. Circuit
breakers and/or electrical disconnects are not supplied by TURBO but are required by code in most
locations. Supply and proper installation of the circuit breakers and/or disconnects to meet all applicable
codes is the responsibility of others.
□7. Verify that all field glycol piping connections to the evaporator have been completed per the piping
diagram provided with the equipment and per the instructions in the operating and maintenance manual.
Supply and proper installation of field glycol piping to meet all applicable codes is the responsibility of
others.
□8. Verify the interface requirements for the evaporator to the glycol system.
□9. Verify that all relief valves have been piped to a safe discharge location (refer to the operating and
maintenance manual with equipment supplied by others for guidelines).
□10. Verify that all field water piping connections to the evaporator have been completed per the piping
diagram provided with the equipment and per the instructions in the operating and maintenance manual.
Supply and proper installation of field water piping to meet all applicable codes is the responsibility of
others. Flush and drain all water piping and water tanks.
□11. Verify that the complete system has been properly evacuated, and leak checked.
Note: Each of the above functions is the responsibility of others. Glycol is not supplied with the
equipment.
□12. Note all leaks found and repaired during step number 11.
If you have any questions concerning the above checklist or any other aspect of equipment installation in
preparation for start-up, contact:
14.START-UP CHECKLIST
The checklist below is a reduction of the actual checklist. Contact TURBO for a full sized checklist.
oil pot vent, and oil drain valve. The end of the hose Note:
connections. A pipe plug should be placed in a SET (saturated evaporator
is provided for the oil bucket of water to absorb temperature) for the
drain valve in case of the NH3 removed with the chilling mode is noted
leakage through the valve oil. above. For condenser
or accidental opening of selection use a SET 10°F
the oil drain valve. Once the oil is removed, above Chilling mode SET
close the oil drain valve for calculating the Total
During normal operation, and replace the plug. Heat of Rejection (THR)
the oil inlet valve and oil Open the oil vent line used for selecting the
pot vent valve will always first, then the oil drain condenser. This ensures
be open. The oil drain inlet valve. adequate sizing for start-
valve is closed. As the up and pull down loads.
liquid refrigerant and oil WARNING
flows down the liquid leg, Never leave the oil THR (total heat rejection)
the velocity is very low, accumulator isolated for is evaporator load plus
allowing the heavier oil to extended periods of compressor input for open
separate and go to the time. Excessive pressure compressor at selected
bottom of the liquid leg will develop in the SET. For example:
along with the liquid isolated drum. A relief Chiller SET is 26°F,
refrigerant where it is valve is provided as a therefore select condenser
drained into the oil safety device. Failure to based on 26°F + 10°F =
accumulator. Oil will carefully follow these 36°F
continue to displace the instructions could result THR = Evaporator load
liquid in the oil in permanent injury of (BTU/HR) @ 36°F +
accumulator until it loss of life. compressor BHP @ 36°F
reaches a level requiring it x 2,545
to be removed. Isolation of the drum for
extended periods of time Fluid Temperature
To drain the oil from the means that the small oil Water “on” chiller plates:
oil accumulator, isolate pot built into the bottom Specified by customer.
the oil accumulator by of the liquid leg may not For entering water
closing the oil inlet valve hold all of the oil temperatures above 90°F
and the oil pot vent valve. accumulated. The excess consult the factory
After the oil accumulator oil would then go to the
warms up, check the oil evaporator, resulting in Water “off” chiller plates:
drain valve to make sure poor or erratic operation Minimum 32.5°F for
it is tightly closed and including failure to water; consult factory for
then carefully remove the harvest properly. other fluids
pipe plug from the valve
outlet. Remove the plug Flooded System Fluid Flow Rates
slowly because gas or Operating Parameters Reference Table 4-1
small amounts of liquid
could be trapped in the Saturated Evaporator Surge Drum Location
valve outlet. Next, 26°F Minimum (40 PSIG Minimum 42" for
connect a hose or some for ammonia; 50 PSIG for ammonia; 72” for R-22
other means of draining R-22).
the oil to the outlet of the
4-10 Turbo Refrigerating, LLC 3/04 Operating Instructions
WARNING! Read the Safety Section before this section. Failure to carefully follow these
instructions could result in permanent injury or loss of life.
This distance is from the
top of the evaporator plate Relief Valve Setting
to the bottom of the drum. 250 PSIG
RECIRCULATED OPERATION
valve will always be open. The A relief valve is provided as a the chiller operation). For
oil drain valve is closed. As the safety device. Failure to evaporators connected to a
liquid refrigerant and oil flows carefully follow these central system, the dry contacts
down the liquid leg, the instructions could result in can be used to indicate the
velocity is very low, allowing permanent injury of loss of status of the chiller (ON/OFF)
the heavier oil to separate and life. at a remote control panel such
go to the bottom of the liquid as the central equipment room.
leg along with the liquid Isolation of the drum for
refrigerant where it is drained extended periods of time means Additional relay contacts or an
into the oil accumulator. Oil that the small oil pot built into interlock of the NH3 pump
will continue to displace the the bottom of the liquid leg should be used to start the
liquid in the oil accumulator may not hold all of the oil compressor/condensing unit as
until it reaches a level requiring accumulated. The excess oil well as to open and close the
it to be removed. would then go to the high pressure liquid solenoid
evaporator, resulting in poor or supplying liquid refrigerant to
To drain the oil from the oil erratic operation. the recirculating unit.
accumulator, isolate the oil
accumulator by closing the oil Control Devices The following sequence may be
inlet valve and the oil pot vent used to control the compressor,
valve. After the oil accumulator Compressor/NH3 NH3 pump, and liquid solenoid:
warms up, check the oil drain Pump/Liquid Solenoid
valve to make sure it is tightly Control Relay 1. The Control Relay (-1)
closed and then carefully contact closes to turn the
remove the pipe plug from the A control relay is provided in NH3 pump on.
valve outlet. Remove the plug the control panel to control the
slowly because gas or small operation of remote 2. An interlock of the NH3
amounts of liquid could be components including the pump (by others) is used to
trapped in the valve outlet. compressor/condensing unit, input a signal to the
Next, connect a hose or some NH3 pump, and high pressure compressor (condensing
other means of draining the oil liquid solenoid. All of these unit) control circuit to
to the outlet of the valve. The components are supplied by initiate start-up of the
end of the hose should be others or as an option by compressor and to energize
placed in a bucket of water to TURBO. Through the logic of the high pressure liquid
absorb the NH3 removed with the PLC, the Control Relay is solenoid valve.
the oil. energized via an output of the
PLC. When the relay is 3. An interlock of the
Once the oil is removed, close energized, a normally open compressor starter is used
the oil drain valve and replace (N.O.) dry contact of the to input a signal to the
the plug. Open the oil vent line Control Relay (-1) closes. The chiller PLC indicating the
first, then the oil drain inlet control circuit of the compressor has started. The
valve. recirculation unit should be interlock of the compressor
connected to these dry contacts would be connected as a dry
WARNING to initiate the start and stop of contact in series with the
Never leave the oil the NH3 pump (i.e., the NH3 pump interlock (AP-1)
accumulator isolated for evaporator and NH3 pump and would provide the same
extended periods of time. should be turned on before the control as the AP-1
Excessive pressure will compressor is started and interlock.
develop in the isolated drum. turned off upon termination of
4-20 Turbo Refrigerating, LLC 3/04 Operating Instructions
WARNING! Read the Safety Section before this section. Failure to carefully follow these instructions
could result in permanent injury or loss of life.
Note: energize the liquid solenoid
For central plant operations Field wiring by others is valve to feed liquid refrigerant
only, the NH3 pump interlock required for all installations. A to the vessel. When the liquid
input is required to the PLC. jumper is not installed between level reaches the proper
the terminal strip connections operating level, the sensor
NH3 Pump Interlock (AP-1) - when the evaporator is shipped. contacts open, and the high
Recirculating Units Only pressure liquid solenoid valve
Refrigerant Level Float closes.
An interlock of the NH3 Switches (FSHL) - Electronic
recirculating pump magnetic Level Probe The third sensor is used to
starter (AP-1) is required as an terminate operation of the NH3
input to the programmable Although the recirculation recirculating pump if the
controller. The normally open unit/liquid level assembly is refrigerant level in the
(N.O.) dry contact must be field supplied only as an option from recirculation vessel is not
installed by others. The chiller TURBO, it is required for the adequate (too low) to supply
will not operate without this system to function properly. liquid to the NH3 pump. The
input present. Refer to the Inputs from the electronic level liquid level is continuously
wiring diagram provided with probe and the FSHL switch are monitored by the electronic
the Chiller for the terminal strip required to control the level controls during operation.
numbers which the contacts are operating, low, and high liquid
connected to. The NH3 level in the recirculation drum. Pump and Water Distributor
recirculating pump can be If the level reaches the high Circuit
provided by TURBO as an refrigerant level sensor of the
option. electronic level indicator, The water is drawn from the
operation of the recirculator, reservoir and pumped to the
The AP interlock is a proof of condensing unit, and evaporator process or to the water
operation for the supply of NH3 are terminated immediately. distribution header in the
refrigerant to the evaporator The FSHL is a mechanical float Chiller.
plates by the remote switch used as a maximum
recirculating unit. This signal liquid level control and is wired Overflow Drain Circuit
must be received by the PLC in parallel to the electronic
logic for the evaporator to level probe as a secondary An overflow drain box is
operate. If the signal is not switch to terminate operation if provided in the reservoir to
received, the PLC logic will the electronic switch should allow for overflow incase of
terminate operation of the fail. surges in the water flow.
evaporator after a preset time
delay (typically 2 seconds). The electronic probe has a The overflow drain box is piped
probe column installed in the to the outside of the unit for
A red pilot light is located on liquid column. This column has field connection to a drain line.
the control panel door to three (3) sensors. One sensor is
indicate an NH3 pump failure. for the high level cut-out. The Shutting Equipment Off For
The PLC requires a reset signal second sensor is used to control an Extended Period of Time
after such a failure. Turn the the high pressure liquid
MCS to the OFF position and solenoid valve that supplies An extended period of time is
then back to the AUTO position refrigerant to the surge drum. more than forty-eight (48)
to reset. After resetting, When the liquid level drops hours.
operation should be monitored below the setting of the
to determine the cause of the operating level sensor, the Close the isolation “king” valve
failure. contacts of the sensor close to on the outlet of the optional
Operating Instructions 3/04 Turbo Refrigerating, LLC 4-21
WARNING! Read the Safety Section before this section. Failure to carefully follow these instructions
could result in permanent injury or loss of life.
receiver or optional Do not turn off the single phase be turned on for a minimum
combination control circuit power. This may of twenty-four (24) hours
condenser/receiver. turn off power to the prior to use to ensure that
compressor crankcase heater in any liquid refrigerant that
Turn off the three phase the optional high side package migrated to the compressor
electrical power to the and optional winterizing crankcase (by others) is
compressor, NH3 pumps, water equipment and/or the PLC eliminated prior to start-up.
pump(s), and other motors power supply. Failure to follow these
(disconnect or circuit breakers instructions could result in
furnished by others). IMPORTANT failure or damage to the
If the control circuit power compressor.
has been turned off, it should
Evaporator Plates
304 Stainless Steel
Hydraulically blown to inflate
to proper rise.
304L available as option.
Burst Pressure
1,500 PSIG
Optional Features
Condenser Discharge maintain receiver pressure units are provided with flood-
Pressure Control during “cold” start-up. Factory back controls as standard.
installed on SCE models; Variable speed drives are also
Water Cooled supplied for field installation on available.
Optional pressure actuated SCER models.
water regulating valve(s) are Reservoir Water Level
field installed. Optional cooling A variable speed fan motor Controls
tower and cooling tower pumps control (optional) adjusts the
are available. RPM of the condenser fan Refer to the chiller manual
motor to maintain a desired Options Section for the
Evaporative Cooled discharge pressure. operation of the water level
An upstream pressure regulator controls (Option #1) for the
is in the discharge line entering Air Cooled chillers. The operation of the
the condenser. A hot gas bypass Fan cycling can be used in water level controls is the same
through a downstream pressure place of flood-back controls in for both the DX and flooded
regulator is provided to some installations. Air cooled chillers.
Section 5: TROUBLE-SHOOTING
This section lists common problems and suggests solutions with various chillers and chiller systems. Some of the problems and solutions
apply to optional equipment o r equipment supplied by others and may vary. Many problems are easy to solve if you know what caused
them. If your problem is not covered in this section, contact Turbo Refrigerating at: 1-940-387-4301 Ask for the Service Department.
The following pages describe problems you might encounter and provide diagnostic instructions and solutions.
Chiller MCS turned off. Turn switch to “ON” position. For dedicated system the
icemaker should be on before the compressor starts.
Emergency stop button depressed. Determine reason emergency stop button was used and correct
before resetting.
Overload relay on magnetic starter Determine cause of motor overload. Depress manual reset
tripped. button.
Unit drawing high amps Loose terminal connections. Tighten connections (qualified electrician).
(compressor or water pump
motors).
Defective motor bearings or motor. Replace. Check compressor/motor alignment and mounting
bolts before restarting.
Chiller evaporator temperature too High discharge pressure: Check pressure sensing connection to regulator. Replace if
high; leaving water temperature too - Defective water regulating valve necessary.
high (water cooled).
- Fouling at condenser (water cooled). Clean condenser by brushing and/or acid treatment. Consult
. manufacturer for water treatment recommendations.
- Faulty water pump (water or Replace pump. Check pump suction and discharge for
evaporative cooled). obstructions.
- Fouling at condenser (air cooled). Clean with air, water hose, or brushing. Remove debris from
condenser inlet.
- Fan turning too slow (air cooled). Change sheave to increase speed up to FLA of motor. Consult
factory before restarting. Check for restrictions.
Low on NH3. Search for leak and repair. Add refrigerant to maintain proper
. level in recirculator or surge drum (flooded) and high pressure
receiver
Hand expansion valve improperly Balance all hand expansion valves to maintain adequate
adjusted. refrigerant to all sections. Open the valve(s) if necessary until
proper evaporator temperature is obtained. Note: It may be
necessary to close the hand TXV to other sections/chillers to
increase flow to chiller that is not operating properly. Adjust
hand expansion valve to maintain 40-45 PSIG in each chiller.
Reference chiller specifications for evaporator temperature.
Plugged or restricted liquid line Clean strainer. Restrictions can be observed by temperature
strainer. drop across the strainer resulting in lower temperature at outlet.
If temperature can not be measured isolate the strainer and
remove it for visual inspection.
Air or other non-condensable in Bleed air from condenser. Replace refrigerant charge if
refrigerant system. contamination can not be removed.
Restriction in piping. Check all isolation valves for proper position – open or closed.
Except for the hand expansion valves all other valves should be
fully open or closed and should not be used for throttling or
flow control.
Power off to condensing unit. Check power, circuit breaker, and disconnects to all motors,
starters, and control switches.
- Strainer plugged. Check water pump impeller for wear – replace impeller or
-Float valve defective (make-up water pump if necessary.
line to cooling tower).
-Pump impeller worn
Condenser pump prime lost – low Add water to cooling tower. Determine cause of water loss.
water level in sump. - leak in sump or piping
. - water line broken
- isolation valve in water line closed
Condenser water make-up valve closed Clean, repair, open, or replace valve.
or restricted.
Recirculating water pump off: Check pump for restrictions. Reset starter overload relay.
-Motor overloads tripped. Locate water feed restriction. Add water to tank.
-Water recirculating pump prime lost. Remove and clean.
Low water level in reservoir. Remove and clean.
-Strainer plugged. Clean, repair, or replace valve. This check is installed and
-Check valve stuck closed. normally located outside the unit at the liquid line connection to
-water connection broken or water the ice generator
supply lost
-water level sensor switch defective Verify connection to the water solenoid valve and check the
upstream water piping and valves outside unit.
Evaporator plates oil logged. Drain oil from NH3 recirculation unit oil reservoir. Raise
evaporator plate temperature by placing manual defrost switch
(MDS) in manual position or by spraying plates with warm
water (not to exceed 90°F).
High suction pressure. Water temperature too high. Water temperature above 60°F (based on incoming city water).
Improperly adjusted hand expansion Check expansion valve adjustment (close to reduce refrigerant
valve (overfeeding refrigerant). flow). Set to maintain 15 PSIG in all sections.
High discharge pressure. Refrigerant system overcharged. Verify actual charge. Reduce charge as required.
Note: Optional condensing unit
supplied by others or Dirty condenser. Clean.
separately, consult supplier’s
data for additional information. Non-condensable in refrigerant. Air in system. Remove by purging.
Readjust to correct setting.
Head pressure controls improperly set. Normally 190–220 PSIG for water cooled; 170–190 PSIG for
evaporative cooled; 210–250 PSIG for air cooled.
Low oil pressure. Oil reservoir full indicating need for Drain oil reservoir and add new oil to compressor.
Note: Optional condensing unit maintenance.
supplied by others or
separately, consult supplier’s Plugged or stopped up oil strainer. Clean. Purge line.
data for additional information.
Low oil level in crankcase. Consult supplier’s data.
Defective compressor oil pump. Check rotation and wear. Replace as required.
Oil leak Check all areas around system for signs of oil leakage. Repair
leak and recharge system with oil.
Excessive vibration of motor Misalignment. Realign to within specifications.
and compressor.
Note: Optional condensing unit Loose motor/compressor hold down Tighten. Check alignment.
supplied by others or bolts.
separately, consult supplier’s
data for additional information. Flooding of compressor. Adjust high pressure liquid line hand expansion valve setting.
Check refrigerant level controls on NH3 recirculation unit to
Excessive motor temperature. Defective or worn bearing. ensure high refrigerant level switch is operative.
Note: Optional condensing unit
supplied by others or Structural support under unit Remove coupling and check bearing.
separately, consult supplier’s insufficient.
data for additional information. Reinforce structural support. Shim as required. Consult factory
for guidelines.
Section 6: MAINTENANCE
To help you get the best Weekly Inspections (Includes • General neat
performance from your Chiller accessory equipment used housekeeping
system, follow the maintenance with the Chiller System)
instructions listed below. If you Clean the chiller weekly:
have questions concerning the Check the oil level in the • Clean the water
maintenance or upkeep of your compressor. distribution pan and
equipment, contact: header. The
Check for signs of oil leakage. distribution header
Turbo Refrigerating can be easily
Service Department Check the refrigerant liquid disassembled to
P.O. Box 396 level in the receiver (if remove debris inside
Denton, Texas 76202 applicable) or during pump- the header or clear
Phone: 940-387-4301 down to ensure that the level is plugged holes.
Fax: 940-382-0364 proper and has not changed • If necessary remove
the water distribution
Daily Inspections Check the receiver. Inspect header from the water
valve packings and relief valve distribution pan and
Inspect the chiller daily to for indications of refrigerant wipe out all loose
determine that the unit is loss. debris in the pans.
operating properly. Observe t he Unplug holes in the
fluid flow over the plates to Check for 20-30% refrigerant pans as required to
ensure the water distribution level in the receiver (or the ensure complete flow
system is free of debris. Check supplier’s recommendation) over the entire plate.
as required. while operating. • Check for indications
of discoloration on
When starting, observe that the Check unit at least once a week. the frame, water,
discharge and suction pressures A visual inspection includes and pans, panels, and
are correct on the gauges and is not limited to: headers. If necessary
are stable to ensure the proper • Leaks use citric acid to
refrigerant feed to the chiller. • Vibration of piping clean the areas using
on other components a non-abrasive
• Capillary tubes cleaning pad. Follow
rubbing the cleaning with a
• Unusual noises fresh water rinse.
• Tight bolts, nuts,
screws
Maintenance 03/04 Turbo Refrigerating, LLC 6-1
WARNING! Read the Safety Section before this section. Failure to carefully follow these instructions
could result in permanent injury or loss of life.
After Initial Ten Hours of • Solids build-up on the unit, contact a local reputable
Operation interior of water cooled supplier of chemical and
condenser (if so equipped) cleaning sanitizing products.
Check for indications of Based on the knowledge of the
discoloration on the frame, To avoid these problems, local water conditions, the
water, pans, panels, and consult a local water treatment material to be cleaned (304
headers. If necessary use consultant and follow these and/or 304L stainless steel), and
citric acid to clean the areas guidelines below. the operating conditions of the
using a non-abrasive equipment, they can
cleaning pad. Follow the Goldenrod water treatment recommend a cleaning and
cleaning with a fresh water systems are also available from sanitizing product to meet your
rinse. Vogt Ice. The Goldenrod can specific needs.
eliminate scaling problems in
After Initial Fifty Hours of most cases. Consult the factory Helpful Hints
Operation for additional information.
1. Chlorine will attack
Check for indications of Plates Forming Scale stainless steel. Most water
discoloration on the frame, supplies contain chlorine in
water, pans, panels, and Flush plates with an acceptable levels too low to cause
headers. If necessary use icemaker cleaner – typically concern. Some cleaning
citric acid to clean the areas citric acid. Have water agents contain high levels of
using a non-abrasive analyzed. chlorine and should be
cleaning pad. Follow the avoided unless the cleaning
cleaning with a fresh water Stainless Steel Surface process can be closely
rinse. Cleaning controlled and a thorough
rinsing of the plates and any
Have a qualified electrician Scale on the chiller plates other parts coming in
check the control panel for resulting from mineral deposits contact with the cleaning
loose connections or loose lugs in the water and other sources agent can be ensured every
on the magnetic starter. of contamination can reduce the time.
efficiency of the plate. If left
Every Six Weeks untreated, it may result in 2. Water scale can be removed
deterioration of the metal using dilute nitric acid under
Grease all greasable fittings on surface thus reducing the life of 1% or phosphoric acid
the shaft bearings. the plates. under 5% at temperatures no
higher than 105°F. These
Water Scale Build-Up The life and efficiency of the solutions must be free of
plates are dependent on proper salt and thoroughly flushed
One of the main concerns with care and cleaning of the surface. from all surfaces
any system using water is scale Since conditions and immediately after use with a
build-up resulting from: installation of equipment vary 1/4% caustic and plain
from location to location, it is water flush.
• Solids forming the plates difficult to provide a simple
• Solids build-up in the water solution to selecting a cleaning Citric acid cleaning agents
distribution pan and headers and sanitizing method. To are also recommended for
obtain the best care for your frequent cleaning. Regular
03/04 Turbo Refrigerating, LLC 6-2 Maintenance
WARNING! Read the Safety Section before this section. Failure to carefully follow these instructions
could result in permanent injury or loss of life.
Water flow across all plates providing complete wetting of plate surface
First Shift Start First Shift End
Second Shift Start Second Shift End
Third Shift Start Third Shift End
Chiller High Side Head (discharge) Pressure within normal range (Reference
manual for various refrigerants and condensing types)
First Shift Start First Shift End
Second Shift Start Second Shift End
Third Shift Start Third Shift End
Ambient Temperature
First Shift Start First Shift End
Second Shift Start Second Shift End
Third Shift Start Third Shift End
Operators
First Shift
Second Shift
Third Shift
Remarks
First Shift
Second Shift
Third Shift
Option #3
Oil Drum (Ammonia) exposure
to ammonia in the
In flooded ammonia event of an accident
systems, the refrigerant Failure to carefully
oil contained in the liquid follow these
ammonia must be re- instructions
moved from the system could result in
before it enters the chiller permanent injury or
plates. The liquid leg loss of life.
from the surge drum
to the chiller is not
provided with any of the
option kits. When the
liquid leg is field in-
stalled, it should be
provided with an oil pot
lower than the horizontal
portion of the liquid
leg. This allows the oil to
collect in the bottom of
the liquid leg before it
reaches the chiller
refrigerant inlet.
To remove the
refrigerant oil, an oil
drain drum with an
isolating valve is
provided. This
drum is also provided
with a 150 # relief
valve.
The isolating valve,
located between the oil
pot on the liquid leg and
the drum inlet, is
closed.
A drain valve is located
on the bottom of the oil
drum to remove the oil.
Reference
Refer to the compressor manufacturer alignment procedure in the Installation, Start-Up and Service
Instructions in the Appendix & Notes Section
.
Table 3-1 Compressor Alignment Tolerances