Sie sind auf Seite 1von 1

Specification

2.9 COMMUNICATION PORTS

NOTE: All communication ports can be used at the same time.

Description Specification
Type B USB 2.0
USB Slave Port For connection to PC running DSE Configuration Suite
Max distance 6 m (20 feet)
Type A USB 2.0
USB Host Port Capability to add a maximum of 16 GB USB storage device for data
recording only
Non – isolated
Max Baud rate 115 k baud subject to configuration
RS232 Serial Port TX, RX, RTS, CTS, DSR, DTR, DCD
Male 9 way D type connector
Max distance 15 m (50 feet)
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
2 x RS485 Serial Ports
Max Baud Rate 115 k baud subject to configuration
External termination required (120 Ω)
Max common mode offset 70 V (on board protection transorb)
Max distance 1.2 km (¾ mile)
Ethernet Auto detecting 10/100 Mbit Ethernet port.

NOTE: For additional length, the DSE124 CAN & MSC Extender
is available. For more information, refer to DSE Publication: 057-116
DSE124 Operator Manual
MSC (Multi Set
Communication) and Standard implementation of ‘Slow mode’, up to 250K bits/s
CAN Port Data connection 2 wire + common
Isolated
External termination required (120 Ω)
Max common mode offset 70 V (on board protection transorb)
Max distance 250 M using Belden 9841 Cable or equivalent
Non-isolated
Data connection 2 wire + common
Half Duplex
DSENet® Data direction control for Transmit (by s/w protocol)
(Expansion Comms) Port Baud Rate of 115 k baud
Internal termination fitted (120 Ω)
Max common mode offset ±5 V
Max distance 1.2 km (¾ mile)

057-259 ISSUE: 1 Page 18 of 146