AMF Controller (Model: SPC-100)

Microcontroller Based Automatic


Mains Failure controller unit is most
versatile and ragged. It is immune to
industrial noise and fluctuation in the
supply voltages.

It operate [starts, stops] the DG and


monitor for faults, speed [RPM],
frequency, Voltage, Current, running
duration [hour meter] and battery
voltage. It switches the load on Mains or
on DG.

SALIENT FEATURES:
1. Works in 3 modes like AUTO, MANUAL and BY PASS.
2. 16 X 2 line LCD (with back light) for status indication.
3. Nine inputs monitoring (inputs are +ve or –ve active).
4. Five output controllers. Three out puts are +ve drives.
5. Two nonpotential relays for switching Load on Mains or
Load on DG.
6. Inputs are optically isolated for signals.
7. Working auxiliary power is 9vdc to 36vdc.
8. Seven functional keys: Acknowledge, Reset, Test & Emergency stop,
Para, Start and Stop.
9. Parameters setting provision.
10. Monitoring of DG’s frequency, RPM, Voltage & Current.
11. Panel mounting type cabinet (size: 96x96 x85 mm).

Connection diagram:
PARAMETER SETTING:
The SPC-100 has the following settings and monitoring provisions by using 5 front panel Keys.
PARA: Select the different parameters to be set or monitor.
RESET: Unit RESET button.
UP/TEST: Multi functional key, for increment/change the PARA or Run the DG TEST function.
DOWN/E.STOP: Multi functional key, for decrement/ change the PARA or Emergency STOP of DG.
ENTER/ACK: Multi functional key, for Enter the change PARA and come out of settings, and
Acknowledge The HOOTER to Stop.
START: MANUL START. STOP: MANUAL STOP
Para Parameter Settings Default Description
No.
1 MANUAL/ AUTO MANUAL MANUAL DG start and stop is set for Manual or
OR Auto mode. Displays ‘M’ for manual
AUTO and ‘A’ auto mode on left corner.
2 MAIN DELAY XXs 1 to 99 sec. 5 sec. Load on Mains Relay will be ON
after the set delay
3 DG DELAY XXs 1 to 99 sec. 7 sec. Load on DG Relay will be ON after
the set delay
4 WAIT DELAY XXs 1 to 99 sec. 20 sec. Before starting the DG wait for
Mains for set delay
5 DG COOLING XXXs 1 to 255 sec. 50 sec. The DG Cooling period. DG runs
with out load before stopping for set
delay
6 FUEL SOLENOID: Energize to Energize The DG stop type can be set
stop / to stop selecting the type of fuel solenoid
Energize to
run
7 START Attempts X 1 to 9 times 3 Number of START kicks given to
DG
8 CRANK Period Xs 1 to 9 sec. 2 sec. The ON period of the START kick

9 CRANK Pause XXs 1 to 99 sec 7 sec. The OFF period of the START kick

10 FREQUENY/ RPM Displays the frequency of the AC and


RPM of the Engine
11 BATTERY = XX.X Displays the battery volts.
LOW BAT.= XX.X 8 to 22V 18V Displays the low battery setting.

12 OVER FREQUENCY:XX 45 to 65 Hz 55Hz Displays the Over frequency.

13 UNDER FREQUENCY:XX 40 to 55 Hz 45Hz Displays the Under frequency.

14 CT RATIO :XXX:05 005:05 to 100:05 The DG current CT Ratio.


900:05