1. General:
1.1. The systems have to be highly reliable.
1.2. It must be safe and exceed the requirements of all national and international
standards of safety.
1.3. Must be easy to operate.
1.4. Mean time to rectify should be minimal.
1.5. Operating costs must be low.
2. Site conditions:
2.1. The sites are having electrostatic and electromagnetic fields due to charged
equipment at 400kV level. The equipment supplied shall have inbuilt protection
against voltages developed by these fields.
2.2. The equipment shall work in ambient temperature range -10°C to +50°C and
relative humidity up to 95%.
Page 1 of 2
Technical specification for Intruder alert system
4. Power supply:
4.1. The system shall work on AC voltage 230V (±10%) and frequency 50Hz (±5%).
4.2. The system should have battery backup of minimum 10 hours, so that in case
of power failure the system should remain in service.
4.3. If the power supply for slave units has to be taken from other point available
along the boundary wall instead of power supply for main unit, separate battery
backup for both the supplies shall be provided.
4.4. The connection between slave units has to be provided through PVC insulated
10C x 1.5sqmm copper armored cables.
4.5. The scope of work shall include excavation, preparation of sand bedding, soil
cover, supply and installation of brick or concrete protective covers, back filling
and ramming. Cables shall be buried in the ground at a depth of 300mm below
finish formation level