Sie sind auf Seite 1von 4

FEATURE | OPERATIONS

WATER OPERATIONS:
SECURITY OF SUPPLY – MONITORING
POWER STATUS OF REMOTE
WATER FACILITIES BY KEVIN STEWART AND GRAHAM NASBY

C
ontrary to what your parents said,
electricity and water do mix! In
fact, for any water utility, a reli-
able electricity supply is essen-
tial to keeping the water on and ensuring
regulatory compliance. Pumps require
electricity to operate, and the SCADA
(supervisory control and data acquisition)
system needs electricity to monitor/control
process equipment and log critical compli-
ance data. However, effectively monitoring
the electricity supply to water facilities is
challenging. For example, Guelph Water
has 30 remote facilities, all unstaffed, with
each having its own individual power feeds.
Thus, when there is a storm, or there are
problems in the hydro utility’s power lines, it
is imperative that operators know which sites
have power and which do not. Furthermore
remote monitoring is needed to check on
the status of generators, automatic trans-
fer switches, and uninterruptable power
supplies (UPSs). Using this power status
information, the operations team can then
effectively determine when, and in what
order, to check on facilities – or make process
adjustments – during power outages.
At Guelph Water, each of the 35 SCADA
programmable logic controllers (PLCs) that
are distributed through our water facili-
ties is equipped with a UPS. The UPSs keep
the PLCs online during power outages, so
the SCADA system can continue logging
ALL IMAGES COURTESY CITY OF GUELPH

process data and providing monitoring/


control connectivity to the centralized
SCADA system. The UPS units are sized to
provide at least 30 minutes of runtime for
the PLC, which is enough time to cover
over 95 per cent of power outages. As part
of this setup, the PLCs also look after shut-
ting off process equipment at the start of
Figure 1 – UPS (interruptible power supplies) are used to keep PLC panels online during
short power interruptions and to keep PLC panels online while on-site generators are a power outage, and re-starting facilities
starting up. Notice the communications network card in the back of the UPS. once stable power returns.

18 | O N T A R I O P I P E L I N E | SPRING 2018
Monitoring Power Statuses network management cards. This selection
To ensure security of supply, Guelph was made based on our count of existing
Water embarked on a project in 2017 to UPS units plus available technical features.
enhance the monitoring of electrical power It should be noted that other UPS vendors
at all of its sites. This included the addition of also have similar configurations available
power status relays to PLC panels, improved in their product lines. For our larger facility
generator status monitoring, monitoring of UPS units we installed the corresponding
(electrical) Automatic Transfer Switches, and Ethernet network cards for those units.
adding communication cards to monitor the We avoided the use of serial protocols and
status of UPS units. Monitoring both small relay-based UPS interfaces as we wanted to
PLC panel UPSs and large facility UPSs was ensure that each UPS would have a built-in
also included in the project. diagnostic webpage accessible for trouble-
Starting in 2013, Guelph Water had shooting via the SCADA network.
already started on a project to standard- Connecting the UPSs to the SCADA
ize the typical UPS units it uses. For PLC system did involve some challenges. We
panels, a standardized 1500 VA UPS from originally wanted to connect using the
a reputable manufacturer was selected, so Modbus TCP protocol, as we already had a
that only one set of spare units and spare Modbus driver installed in our SCADA soft-
batteries had to be stocked. For larger UPS ware. However, we discovered the Modbus
units, a process of selecting units closely interface of the UPS network cards did not
matched to individual site requirements include all the status monitoring points we
was used, while ensuring the appropriate wanted. Instead, we elected to use SNMP
vendor support agreements were in place. (simple network management protocol),
which is a communications protocol widely
UPS Communications used in the IT sector. All of our UPS units,
Part of the UPS selection process was to go including both the PLC panel UPSs and
with enterprise grade UPS units. This meant the large facility UPSs, also supported the
ensuring that each UPS would have certain SNMP protocol.
core technical features and the capability Since SCADA systems do not read-
of having a network communications card ily speak SNMP, we used a centralized
added. In our case, we went with an Ethernet Ethernet-to-Ethernet protocol converter
UPS network card so we could leverage the module. For our system we used a device
existing SCADA network, use standardized called a “Babel Buster” for this role, though
Ethernet-based protocols, and have access it should be noted there are a several mod-
to a diagnostic webpage for each UPS. ules available from variety of vendors that
For our PLC panel UPSs, we selected could be used. We used the Babel Buster
APC Smart UPS 1500 units with AP9630 to convert the SNMP protocol’s OID (object
Identifiers) into Modbus holding registers
that the SCADA system could read. The
Babel Buster also provided a web-based
setup utility that used XML configuration
files that can be readily uploaded/down-
loaded via its web interface.

Using the UPS Data


Once we could read the UPS status data
into the SCADA system, the next step was
to put it into a format that could be used
by the Operations Team. This was accom-
plished by designing a power status screen
that provided the power feed, generator,
ATS and UPS statuses for all sites on one
HMI (human-machine interface) screen.
Figure 2 – Protocol Converter Module
which was used to interface the SCADA The intent was to have a single HMI screen
system to the UPSs network cards that operators could use to get an overview
via Ethernet. view of the power status across the entire

O N T A R I O P1 I P E L I N E
904064_Myron.indd | SPRING 2018 | 19
2/10/18 5:40 PM
Browse our
upcoming
training
schedule: GRAB & GO
CORDLESS POWER PIPE BEVELER
wcwc.ca/registration RBIT2 • Rechargeable tool deburrs
and bevels plastic pipe quickly.
• Lightweight and cordless.
Great for field work.
• Adjustable and creates 15°
external bevel, up to 5/8” long.
• Long-lasting carbide router bit
uses 22,000 RPM, 18V cordless
CPBKIT
die grinder for smooth cuts.

Add the optional RBIT2 router bit with bevel length of


7/16” – 1” for larger plastic pipe and longer bevel.

Reed Manufacturing • Erie, PA USA • reedsales@reedmfgco.com • www.reedmfgco.com

901119_Reed.indd 1 22/01/18 8:27 pm

1,500 km
of
underground
watermain
restored

Not a single
tree uprooted
The green choice
e
Our industry-leading trenchless
watermain solutions provide a
green alternative to open-cut. On
average,
FER-PAL
saves

Don’t see your


BEFORE AFTER
18,9 50 + tons
location? of greenhouse
Contact us to gases annually
bring training to you!
S t ay a h
e ad of the
c u r ve w i
training@wcwc.ca t h F E R- PA L

866-515-0550 e: info@ferpalinfrastructure.com ferpalinfrastructure.com

20 | O N T A1 R I O
899068_Walkerton.indd P I P E L I N E |01/02/18
SPRING7:26
2018
823720_FerPal.indd
PM 1 7/21/16 11:15 PM
Figure 3 – A single status screen was added to the SCADA system so operators could see power status of all water facilities at a glance.

water utility at a glance. Part of this screen Using the new Power Status screen in the Ontario. He recently completed a SCADA
is shown in Figure 3. SCADA system, operators now can quickly developer co-op placement at Guelph Water
The screen features a standardized status achieve situational awareness of the power Services. Kevin, originally from Kingston
row for each site. Each status row consists status of Guelph Water’s facilities at any Ontario, is enrolled in the UofG’s B.Sc.(Eng.)
of: the site’s overall power status; if there time. This screen is available at all SCADA Engineering Systems and Computing pro-
is an ATS or MTS fitted (automatic or man- terminals, and is now used extensively gram. kstewa11@uoguelph.ca
ual transfer switch); the type and status of whenever storms or hydro utility problems
onsite generator if there is one; the status are affecting the power feeds to Guelph Graham Nasby, P.Eng, PMP, CAP holds
of power feeding the PLC panel; and the Water’s 30 remote facilities. Armed with this the position of Water SCADA & Security
status of any UPSs on site. The percent of knowledge, the operation team can now Specialist at City of Guelph Water Services,
battery left and remaining runtime for UPS make better decisions based on real-time a publicly-owned water utility located in
is also shown. An on-screen legend is pro- data as to which sites to visit, including Guelph, Ontario, Canada. He is a member
vided for reading the compactly arranged when and in what order, during a power of both OWWA and WEAO, and currently
UPS status indicators. Also, if there is histori- interruption event. sits on the OWWA Automation Committee.
cal equipment (e.g. older standalone ATS Graham is also co-chair of the ISA112
units) that are not yet monitored by SCADA Kevin Stewart is a third-year engineering stu- SCADA Systems Standards committee.
this information is provided to operators. dent at the University of Guelph in Guelph, graham.nasby@guelph.ca

WE DO IT ALL
CORROSION PROTECTION & SEALING SYSTEMS YOU CAN DEPEND ON

Extend Structure Life,


Reduce Maintenance & Repair Costs
• for industrial steelwork, pipework & road surfaces
• above & below ground pipe, valves, fittings & steel
www.densona.com
Toronto • Edmonton
• offshore marine piling protection
Denso North America Inc.
• road, bridge, airport & asphalt applications
90 Ironside Cres. Unit 12 Toronto, ON M1X 1M3
A member of Winn & Coales International. Tel: 416.291.3435 Fax: 416.291.0898

596337_Denso.indd 1 O N T A R I O P I P E L I N E | SPRING
7/13/12 2018 | PM
12:55:57 21

Das könnte Ihnen auch gefallen