Determine the safe span that 100 mm x 150 mm purlins would have if it has a spacing of 800 mm
on centers to carry a roofing load of 60 Pa and wind load of 1.4 kPa of vertical surface. Allowable bending
stress is 10 MPa. Weight of purlins is 5000 N/m³. Use nominal dimensions only. The roof truss has a pitch
of ¼.
Solution:
1
Tan Ѳ = 2
Ѳ = 26.6°
Wind load:
2𝑃 𝑆𝑖𝑛 26.6°
Pn = 1+𝑆𝑖𝑛² 26.6°
2 (1400)𝑆𝑖𝑛 26.6°
Pn = 1+𝑆𝑖𝑛² 26.6°
Pn = 1044 Pa
W2 = 835.2 L
W1 = 75 L + 43 L
W1 = 118 L
W1 = W2 + W1 Cos 26.6°
Wn = 940.7 L
Wt = 52.8 L
𝑊𝑛 𝐿
Mn = 8
940.7 𝐿(𝐿)(1000)
Mn = 8
Mn = 117587.5L²
𝑊𝑡 𝐿
Mt = 8
52.8𝐿² (1000)
Mt = 8
Mt = 6600 L²
6𝑀𝑛
fn =
𝑑𝑏²
6(117587.5)𝐿²
fn = 100(150)²
fn = 0.314 L²
6𝑀
ft = 𝑑𝑏²𝑡
6(6600)𝐿²
ft = 150(100)²
ft = 0.026 L²
ft = 𝑓𝑛 + 𝑓𝑡
10 = 0.314 L² + 0.026 L²
10 = 0.340 L²
L = 5.42 m
PROBLEM:
Determine the maximum safe rather spacing whose dimension are 75 mm x 300 mm x 5m. as
shown, with allowance flexural stress of 15.9 MPa. Consider live load = 770 N/m² , roof and purlin loads =
280 N/m² and weight of rafter is 8 x 10³ N/m³.
Solution:
W1 = 5843.7 S + 900
W2 = W1 Cos 25°
W2 (5)(1000)N.mm
M = 8
6𝑀
M = 𝑏𝑑²
6𝑀
15.9 = 75 (300)²
M = 17.9 x 106
(5000)
17.9 x 106 = W2 8
W2 =28640
S = 5.25 m. (spacing)
TENSION WITH BENDING
Fa 𝐹𝑏
+ 𝑓𝑏 = 1
fa
𝑇
Fa = 𝐴𝑛 (actual tensile stress)
3
An = 5 A (net area, to allow for notching, bolt holes)
6𝑀
Fb = 𝑏𝑑² (actual bending stress)